Honeywell Vertex M Technical Handbook

Page 1
Vertex M Continuous Gas Monitor
Technical Handbook
Table of Contents
Introduction
Installation
Startup
Operation
Maintenance
Installation Drawings
Specifications
Detectable Gases
Replacement and Consumable
Items
Optional Relay Specifications
Network Interface and Options
4-20mA Analog Output Option
Line Integrity Test Option
Warranty Statement
Page 2
Vertex MTM 24-Point Continuous Monitor
N OT I C E
WARNING
DANGER
!
Vertex M Continuous Monitor Symbols
Symbol Description
Power on
Power off
Potential damage to the device or other property, maintenance procedures, and “refer to manual” instructions.
Lifting instructions, low clearances, slipping/tripping hazards,
!
CAUTION
!
minor corrosive dangers. Also used when defining personal protective equipment (gloves, dust masks, etc.)
Personal injury risk: machinery hazards around guarded equipment, moving parts, crush/pinch hazards, flying debris, and arc flash hazards.
Vertex M TM Technical Handbook
The most dangerous or potentially lethal hazards: unguarded equipment, confined space entrances, and lockout labels.
Caution: possibility of electric shock
Caution: hot surface
Protective conductor terminal (ground terminal)
i
Page 3
Vertex MTM 24-Point Continuous Monitor
EMC Considerations
Your Honeywell Analytics monitor has been designed to comply with applicable Electromagnetic Compatibility (EMC) standards at the time of manufacture. The design includes filtering, shielding and bypassing techniques. At the time of certification, simulated customer Input/ Output (I/O) schemes were tested.
All methods used in your equipment for emission suppression and reduction of susceptibility are interactive. Modifications to the instrument could result in increased emissions and higher vulnerability to other radiated fields.
Following the guidelines in this EMC Considerations section will ensure your instrument maintains the highest degree of EMC integrity. The guidelines listed apply only to I/O emissions and do not apply to A.C. and D.C. instrument power connections.
Cabling
At a very minimum, all cables should include a braided shield. Ideal results have been obtained with twisted pair cabling which has a foil shield surrounding each pair plus foil and 90% braid shielding around the b undle. In addition, ensure local electrical code requirements are met.
The following cable parameters must be considered:
Braid Foil Twisted Pair
Stranded Pair
Shield Termination
Must have a minimum 90% coverage When used with braid, provides 100% coverage
Do not use foil alone. It has a tendency to break. Provides for cancelling of magnetic fields Provides the greatest surface area
Continuation of the shield to the cabinet earth ground is most important. For discrete wire terminations, pigtails to the cabinet (connector) ground should be extremely short (absolutely no greater than three inches). For multiconductor connector terminations, only 360° shielded shells should be used.
Vertex M TM Technical Handbook
Note:
Honeywell Analytics product testing uses >90% braid with foil (around the bundle); twisted pair; stranded 24 AWG (minimum wiring for all qualification and certifi­cation testing.)
Connectors
All qualification and certification of Honeywell Analytics products were achieved with high quality connectors, providing 360° shield coverage. These connectors generally had metal shells.
Failure to properly secure the connector to the equipment will result in high emission levels. Also, poorly constructed or improperly assembled connectors can be a high source of radiated noise and provide a path for external signals into the monitor.
ii
Page 4
Vertex MTM 24-Point Continuous Monitor
Table of Contents
Symbols Used on Your Instrument ..................................i
EMC Considerations Cabling Connectors
..........................................................................ii
....................................................................ii
.......................................................i
Introduction ................................................... 1-1
System Overview ........................................................1-2
Manufacturer General Safety
System Components
Vertex M Front Vertex M Back Sample Tubing, Exhaust and Wiring Ports Analyzer Side Panel Analyzer Front System Controls Data Acquisition Computer (rear) Back of Chemcassette Main PLC
4-20mA Analog Output Option PLC Menu Map Analyzer Modules Sampling System Chemcassette
Detector Optics
Stain Pattern
Chemcassette
Optional ChemCam
Sample Filters Pyrolyzer Module Detection System
Pyrolyzer Fan Vacuum Pumps Multiple Gas Monitoring Control System
Data Acquisition Computer
Programmable Logic Controller
............................................................1-2
.........................................................1-2
..................................................1-2
.........................................................1-3
..........................................................1-4
...............1-5
................................................1-6
.........................................................1-7
......................................................1-7
............................1-8
®
Module ..............................1-9
...............................................................1-10
......................1-11
.................................................................1-12
.....................................................1-13
......................................................1-13
®
Detection System ............................1-14
......................................................1-14
..........................................................1-14
®
Tapes ............................................1-15
...............................................1-15
........................................................1-15
.........................1-16
.........................................................1-16
........................................................1-16
............................................1-16
.........................................................1-17
....................................1-17
.............................1-17
Installation ..................................................... 2-1
Introduction .................................................................2-2
Surveying the Installation Site
Placement of the Vertex M System Exposure to Dust and Humidity Sample Transport Time Instrument Dimensions Sample Locations
Sample Line Particulate Filter Use Optional Floor Mounting Installing Sample Lines/Filters
Sample Line Installation Requirements
Sample Line Connections
Installing Sample Line Particulate Filters Installing Pump Exhaust Line
Exhaust Line Installation Requirements
Exhaust Line Connection Electrical Power
Connecting AC Power
Power On/Off Data Acquisition System
Printer
External Network Connection
Network Computer Security Wiring Alarm Relays
Relay Contacts
Wiring Guidelines
......................................................................2-7
....................................................2-2
..........................................................2-5
...........................................................2-6
...................................................2-8
........................................................2-8
....................................................2-9
....................................2-2
..........................2-2
...............................2-2
............................................2-2
............................................2-2
..........................2-3
.............................................2-3
....................................2-3
...................2-3
........................................2-4
.................2-4
.....................................2-4
..................2-5
.........................................2-5
..............................................2-5
.............................................2-6
..................................2-7
.....................................2-8
Startup ........................................................... 3-1
Startup ........................................................................3-2
Initial Startup............................................................3-2
Factory Configuration Getting Started Verify Installation Power Up Start Program
...........................................................3-2
........................................................3-2
....................................................................3-2
.............................................................3-4
..............................................3-2
Table of Contents
iii
Page 5
Vertex MTM 24-Point Continuous Monitor
Configuration Utility ....................................................3-6
Define Gas Location Configure Analyzers and Points Set Analyzer Window Configure Point Define and Assign Relays Configure PLC Set Alarm Relays Set Fault Relays
..............................................3-17
............................3-19
.............................................3-20
......................................................3-21
......................................3-28
.......................................................3-29
...................................................3-30
.....................................................3-32
Profile Management-File Menu..............................3-34
Other Menu
Load Tape Verify Flow Rates and Supply Vacuum
Verify Flow Rates
Leak Checking Sample Lines Reconfigure Moving to a New Site System Shut Down
............................................................3-34
.................................................................3-34
.....................3-35
...................................................3-35
...................................3-39
..............................................................3-39
................................................3-40
...................................................3-41
Operation ....................................................... 4-1
Introduction .................................................................4-2
Monitoring Mode Overview Main Screen
...............................................................4-3
System Display Area Point Detail Display Area Function Buttons
Project Functions
....................................................4-10
......................................................4-10
Log In and Log Out Changing Password
Updating Program..................................................4-12
Restore OnScreen Keyboard Stopping Project
Review Functions
Event History Data Trend
....................................................4-12
.....................................................4-12
.........................................................4-13
.............................................................4-20
Optional ChemCam Event List
Menu Buttons
...............................................................4-24
...........................................................4-26
.........................................4-2
...............................................4-4
.........................................4-8
................................................4-11
...............................................4-11
.................................4-12
...............................................4-22
Run Time Options ..................................................4-26
Flow Calibration Maintenance Diagnostics Service
...................................................................4-44
Security Access Configuration
OnScreen Keyboard
Restore OnScreen Keyboard
....................................................4-32
..........................................................4-40
............................................................4-41
.....................................................4-47
.........................................................4-48
.................................................4-48
.................................4-48
Maintenance .................................................. 5-1
Introduction .................................................................5-2
Maintenance Schedules Chemcassette
®
Analyzer Maintenance.......................5-3
Remove and Replace Analyzer Particulate Filters Remove Filters Replace Filters
.........................................................5-4
.........................................................5-4
Change Chemcassette
Replacing an Analyzer
Disconnecting Cables Remove Analyzer
Install Analyzers.......................................................5-7
Remove and Replace Pyrolyzer Filters
Remove Filters Replace Filters
.........................................................5-8
.........................................................5-8
Remove and Install Pumps
Remove Pump
.......................................................5-11
Install New Pump
Remove and Install Power Supplies
Remove Supply Replace Supply
.....................................................5-12
.....................................................5-12
Clean the Touch Screen PLC Module Battery Backup Check File Maintenance Optics Cleaning
......................................................5-14
........................................................5-15
.............................................5-2
..5-3
®
Tape ..................................5-5
................................................5-6
..............................................5-6
....................................................5-7
......................5-7
.........................................5-9
...................................................5-11
.........................5-12
...........................................5-12
.........................5-13
Table of Contents
iv
Page 6
Vertex MTM 24-Point Continuous Monitor
Troubleshooting ........................................... 6-1
Introduction .................................................................6-2
General System Problems Maintenance Faults Instrument Faults Information Events
LIT-Related Informational Events
Manual Analyzer Override
....................................................6-5
......................................................6-10
....................................................6-16
..........................................6-2
...........................6-19
........................................6-20
Installation Drawings ...................................A-1
Introduction ................................................................A-2
Floor Space Requirements General Considerations and Cooling General Wiring 4-Port Manifold Option Floor Mounting Option
...........................................................A-5
........................................A-3
.........................A-4
...............................................A-7
...............................................A-8
Specifications ...............................................B-1
Introduction ................................................................B-2
Filter Compatibility
Physical Dimensions..................................................B-3
Nominal Transport Times
.....................................................B-2
...........................................B-4
Detectable Gases..........................................C-1
Detectable Gases ......................................................C-2
Replacement and Consumable Items .........D-1
Consumables .............................................................D-2
Chemcassettes End of Line Particulate Sample Filters Analyzer Filters Pyrolyzer Filters Rack Filters
Printed Circuit Boards
Pyrolyzers All Analyzers Power Distribution Module
Components
All Analyzers
®
.....................................................D-2
..................D-2
.......................................................D-2
......................................................D-2
.............................................................D-2
................................................D-2
...............................................................D-2
...........................................................D-2
......................................D-2
..............................................................D-2
...........................................................D-2
Pyrolyzers ...............................................................D-3
Rack Systems
Power Distribution Module
Pump Modules
.........................................................D-3
...................................D-3
........................................................D-3
Optional Relay Specifications .....................E-1
Relay Output Contacts...............................................E-2
Relay Contact Ratings Default Relay Assignments
Introduction Main PLC Terminal Assignment of 1746-OW16 Relay Module Terminal Assignment of 1746-OX8 Relay Module
.............................................................E-3
................................................................E-3
...............................................E-2
........................................E-3
E-3
.E-4
Network Interface and Options ...................F-1
Network Interface and Options ..................................F-2
OLE for Process Control (OPC) Interface
Setting Up an OPC Client Application
Data Values Common to Fieldbus Networks
Alarms and Faults Concentrations
Heartbeat Data Map Profibus Option (P/N 1295-275)
Termination
Profibus Module Configuration DeviceNet Interface (P/N 1295-0329)
ControlNet Interface ............................................... F-14
DF1 Interface (P/N1295-0343) Modbus Plus Interface (P/N 1295-0330) LonWorks Interface (P/N 1295-0329) Modbus/TCP (P/N1295-0520)
Configuring the IP Address Ethernet/CIP (P/N1295-0519)
Configuring the IP Address Vertex M Remote Display Setup
Checking Remote Session Count
Determining the IP Address
.............................................................. F-10
................................................................. F-11
........................................................... F-12
................................................... F-9
....................................................... F-9
.............................. F-12
............................. F-12
................................ F-15
................................. F-17
................................... F-17
................................. F-20
................................... F-21
.............................. F-21
.................................. F-22
.................. F-3
.................... F-3
............. F-9
...................... F-14
................. F-16
...................... F-16
......................... F-21
Table of Contents
v
Page 7
Vertex MTM 24-Point Continuous Monitor
Basic Desktop Station Setup ................................ F-22
Installing Java Runtime Environment Software Install Adobe Reader Software Create HMI account Starting the Niagara Remote Display
Full Desktop Station Setup
Add Honeywell software to Desktop Create a “Honeywell Analytics” account Create Group “VertexDCOMUsers” Disable Windows Firewall Configure DCOM Windows Firewall Create matching Windows Accounts
Demonstrating Remote OPC Communication
Setup Procedure Demonstration with Matrikon OPC Explorer Demonstration with DAClient
.......................................... F-22
............................................... F-27
............................................... F-32
................................................... F-34
.......................... F-22
................ F-22
................................... F-25
.................. F-25
............ F-25
................... F-25
.................................. F-27
................. F-33
................................ F-38
4-20mA Analog Output Option ....................G-1
Overview ....................................................................G-2
Hardware Requirements Configuration Requirements Operational Description
............................................G-2
......................................G-2
.............................................G-3
. F-22
........ F-34
......... F-35
Line Integrity Test Option ............................H-1
Warranty Statement....................................... I-1
Chemcassette® Device Warranty Statement................I-2
Chemcassette
Table of Contents
®
Warranty .............................................I-3
vi
Page 8
Vertex MTM 24-Point Continuous Monitor
1 Introduction
Vertex M TM Technical Handbook
1-1
Page 9
Vertex MTM 24-Point Continuous Monitor
1.1 System Overview
The Honeywell Analytics Vertex M™ System continuously monitors up to 24 remote locations for toxic gases. It responds to gases that exceed programmed levels by:
Triggering alarms and opening event windows to warn operators of high or low concentrations
Triggering relays to external devices
Displaying the location, gas type and gas concentration
Storing the alarm information in a database
The Vertex M System provides fast response to a wide range of gases. Each location may be up to 400 ft (122 m) from the Vertex M System. The system uses one or more of Honeywell Analytics’ Chemcassette® analyzers, with or without pyrolyzer, to provide a monitoring system tailored to meet the requirements of the facility.
The V ertex M System incorporates a range of redundant and protective features for maximum uptime:
Filters, Chemcassettes® and major components in one of the analyzers can be replaced while the remaining analyzers continue to function
Operation can be through an LCD touch screen or through a local area network (LAN).
Chemcassette® is a registered trademark of Honeywell Analytics, Inc.
1.1.1 Manufacturer
The Vertex M System is manufactured by:
Honeywell Analytics Inc.
405 Barclay Boulevard
Lincolnshire, IL 60069 USA
www.honeywellanalytics.com
1.1.2 General Safety
Follow all installation and operational instructions to ensure the safe and reliable operation of this unit.
If this monitor is used in a manner not specified by Honeywell Analytics Inc., the protection provided by the equipment may be impaired.
Intelligent analyzer modules allow one to stop monitoring with no effect on the remaining modules
Power supplies are redundant
Pumps are redundant
The system powers up in the same state as when powered down
Section 1 - Introduction 1-2
1.2 System Components
The following photos illustrate Vertex M System components, ports, connections and controls. From the main front and back photos, click on the labels to see the detail photos.
Page 10
Vertex MTM 24-Point Continuous Monitor
1.2.1 Vertex M Front
Sample Tubing, Exhaust and Wiring Ports
Relay PLC (behind monitor)
See Relay Options or Network Interface Options
Touch Screen
System Controls
Pyrolyzer Analyzer
Analyzer Side Panel
Universal Chemcassette Analyzer
Analyzer Front
®
Section 1 - Introduction 1-3
Page 11
Vertex MTM 24-Point Continuous Monitor
1.2.2 Vertex M Back
Back of Pyrolyzing Chemcassette Analyzer
Data Acquisition
Computer (rear)
Pyrolyzer step-up/Isolation transformer
Section 1 - Introduction 1-4
4-20mA Option PLC
Page 12
Vertex MTM 24-Point Continuous Monitor
1.2.3 Sample Tubing, Exhaust and Wiring Ports
AC Input
0.75 in pipe thread
System Exhaust
0.5 in (12.7mm) tubing Analyzer 3 Sample Ports
Alarm Wiring Conduit Plate
2 in (50.8mm)
Power Connection
Access Panel
3-Port Manifold for multiple gas sampling
See Section A.4 Nominal T r ansport Times for tubing
length limitations
Note:
The Alarm wiring conduit plate must remain in place if not used.
Analyzer 2 Sample Ports
Analyzer 1 Sample Ports
Points 1 thru 8 (Left to Right)
Section 1 - Introduction 1-5
Page 13
Vertex MTM 24-Point Continuous Monitor
1.2.4 Analyzer Side Panel
Exterior View
Slide Latch
Access Screws
Internal View
Analyzer CPU
ChemCam Option
Proportional Valv e Filters
Section 1 - Introduction 1-6
Sample Pressure Transducers
Sample Flow Transducers
Sensor Interface PCB
Page 14
Vertex MTM 24-Point Continuous Monitor
1.2.5 Analyzer Front
1.2.6 System Controls
Rack Power Switch and Circuit Breaker
Power Distribution Module
Analyzer Status LED
Pyrolyzer Analyzer
Data Acquisition Computer (DAq)
Hot Swap
Hard Drives
Section 1 - Introduction 1-7
24VDC Power Supplies
2
Analyzer DC and Pyrolyzer AC Power Switches with Indicators
3
Slot
CD-RW Drive
Page 15
Vertex MTM 24-Point Continuous Monitor
1.2.7 Data Acquisition Computer (rear)
Power
Mouse
Keyboard
Serial Com2
(not used)
Serial interface
for touchscreen
(COM 1)
USB (3)
Touchscreen
LCD
video
video
USB,
Chemcam
(3 ports)
USB Host Device
Internal Ethernet
External Ethernet
USB (Com8)
to PLC
(this port only)
Caution:
Restrict access to the USB port to reduce the risk of malicious software being introduced.
Note:
Speakers
(not used)
Microphone
(not used)
This photograph shows a typical port configuration. Port and slot locations vary from model to model.
Section 1 - Introduction 1-8
Page 16
Vertex MTM 24-Point Continuous Monitor
1.2.8 Back of Chemcassette® Module
ChemCam USB Connection (Optional)
Analyzer Communications (Ethernet)
Analyzer 24V Power Supply
Multi-Function Connector
Note:
Connection secured by slide latch. Push up to open. Push down to close.
Section 1 - Introduction 1-9
Circular Tubing Harness
Cable Carrier
Page 17
Vertex MTM 24-Point Continuous Monitor
1.2.9 Main PLC
PLC Processor
Module
DH485/RS232 Interface Module
Expansion slot for optional Communications Interface
DH485 Link Coupler
PLC Power Supply
Section 1 - Introduction 1-10
Advanced Interface
Converter
Optional Relay Modules
Page 18
Vertex MTM 24-Point Continuous Monitor
1.2.10 4-20mA Analog Output Option PLC
Power Supply
4-20mA Output Modules (6X)
Section 1 - Introduction 1-11
Page 19
Vertex MTM 24-Point Continuous Monitor
Review
Functions
Event History
Data Trend
ChemCam
(Optional)
Event List
Main Screen
System
Display Area
Point Detail
Display Area
Menu Buttons
Run Time
Options
Flow
Calibration
Maintenance
Analyzer
Operation/Maintenance
Remove and Replace
Chemcassette Analyzer
Particulate Filters
Change Chemcassette
Tape
Diagnostics
Service
Alarm Test
Fault Test
4-20 mA Test
Authorized
Service
Security
Access
Configuration
Utility
Project
Functions
Define Gas
Location
Configure
Analyzers and
Points
Set Analyzer
Window
Configure
Point
Define and
Assign Relays
Profile
Management-
File Menu
Other Menu
Log In
and Log Out
Changing Password
Updating
Program
Restore
OnScreen
Keyboard
Stopping
Project
1.3 Menu Map
Section 1 - Introduction 1-12
Page 20
Vertex MTM 24-Point Continuous Monitor
1.4 Analyzer Modules
The Vertex M System is populated with one or more types of analyzer modules. Each system may contain Chemcassette® modules or Pyrolyzer modules. Modules are installed in slots.
Tier 1
Table 1-1. Module Tier Structure
Chemcassette® modules occupy one slot each. Howev er , Pyrolyzer Chemcassette® modules are to be installed in slots 1 and 2. Pyrolyzer configuration and status information will appear in slot 2.
Chemcassette Pyrolyzer 8 1 and 2 Only 1
Examples of possible combinations in a Vertex M System:
One, Two or Three Chemcassette® modules
One Pyrolyzer Chemcassette® module
One pyrolyzer Chemcassette® module, one Chemcassette® module
Your monitor will include only those modules specified at time of ordering.
CC CC
PYRO
Slot 1 Slot 2 Slot 3
Number
of Points
®
8 1, 2 or 3 3
Table 1-2. Required Slots
Installed
into Slots
CC
Total
Possible
per Vertex
M System
1.5 Sampling System
Each Analyzer module is a monitoring center for sampling lines from sample locations. As they apply to the Vertex M System, the words point, line and location require definition:
A location is a place to be monitored
Sample atmosphere runs from the location to the Vertex M System via a line
Each of the 24 sample tubing connections on the Vertex M System corresponds to a point. A sample line can be connected directly to a single point or multiple points via a 4-port manifold
The system draws air simultaneously from all l ocations. Two different types of flow are:
Transport flow: high-velocity, large-volume air movement through the lines
Sample flow: air admitted to the Chemcassette® detection system
The high speed of transport flow allows rapid monitoring and response time when using long lines from monitored locations to the Vertex M System. A small portion of the transport flow (sample flow) is analyzed to determine concentration levels.
The complete sampling and monitoring system consists of the following components:
Sample lines to all monitored locations
Flow connections through quick-connect ports in bulkheads on top of unit
Section 1 - Introduction 1-13
Moving cable and connectors
Vacuum pumps
Analyzers incorporating manifolds,
®
Chemcassette
and filters
Flow controlling proportional valve
Page 21
Vertex MTM 24-Point Continuous Monitor
Top exhaust port
There are 24 inlets, one for each monitored location. One exhaust port is also located on top of the Vertex M cabinet.
1.6 Chemcassette® Detection System
The Chemcassette® Analyzer module is a self­contained, microprocessor controlled analyzer that occupies one slot in a Vertex M. Sample lines and the vacuum source are connected to the Chemcassette® via a single 10-tube connector.
The system powers up in the same state as when powered down. Data is stored in the module’ s memory until the data acquisition computer retrieves it.
The Vertex M Analyzer modules use the Honeywell Analytics’ Chemcassette® optical detection system. Analyzer modules sample and detect a specific gas or family of gases.
Each eight-point Analyzer module:
detection system that measures a stain that develops
®
on the Chemcassette target gas. Each eight-point Analyzer module has two detection heads, each with four individual detectors.
tape in the presence of a
1.6.2 Stain Pattern
The following chart shows the stain pattern of sample
®
detection on the Chemcassette
tape.
Manages Chemcassette® tape transport
Provides optical detection of stain
Directs sample flow through the Chemcassette
®
Stores data for retrieval by the data acquisition computer
Components of the detection system include:
Chemcassette® detection tape
Optics and electronics for the detection system
Chemcassette® tape transport mechanism
Self adjusting proportional valves
1.6.1 Detector Optics
The heart of the Chemcassette® module is an optical
Section 1 - Introduction 1-14
When monitoring a location, the system detects and measures a specific gas or a family of gases in the sample. The microprocessor in the analyzer module interprets the data and responds appropriately.
In the legacy detection system, the sample enters the inlet and passes through the Chemcassette tape to the sample outlet. The target gas in the sample flow reacts with the tape and produces a stain density proportional to the gas concentration. An LED in the detector head illuminates the sample stain and the detector then optically measures the stain.
Page 22
Vertex MTM 24-Point Continuous Monitor
Surface mount LED
1.6.3 Chemcassette® Tapes
Chemcassette® tapes are tagged with a radio frequency identification (RFID) tag to automatically identify the following:
Serial number
Gas family/ tape type
Revision level
Expiration date of the tape
Chemcassette® leader parameters
The module uses a leader on the Chemcassette
to allow calibration of the optics e very time a new tape
Legacy Detection System
is installed. This feature can be bypassed.
®
tape
Chemcassette tape
Sample outlet
CLO Detection System
Reference detector
Light pipe
Detector
Flow
Inlet
In the Closed Loop Optics (CLO) detection system, a reference detector monitors and controls the intensity of the LED.
The microprocessor in the Chemcassette analyzer module interprets the stain. It then calculates and stores a precise concentration level in the module’s memory. Gas concentrations are reported in parts-per-million (ppm), parts-per-billion (ppb) or milligrams-per-cubic-meter (mg/m3).
1.6.4 Optional ChemCam
The ChemCam is a small video camera located between the take-up reel and the optic head on the module. It provides a means to observe alarm level stains.
1.6.5 Sample Filters
The Chemcassette® module includes three types of filters in the sample flow system. Particulate filters protect the internal precision orifice from dust particles. An acid filter is used on the common line to the pumps. Both types of filters are located in a removable filter block on the side of the Chemcassette® module. An internal particulate filter protects each proportional valve.
Section 1 - Introduction 1-15
Page 23
Vertex MTM 24-Point Continuous Monitor
1.7 Pyrolyzer Module Detection System
The pyrolyzer module is similar to the standard Chemcassette trifluoride (NF temperature heater (pyrolyzer) which converts the NF
to hydrogen fluoride (HF). The hydrogen fluoride
3
is then detected with a standard or XPV mineral acids Chemcassette® tape. Detection is identical to the Chemcassette
The correlation algorithm between HF and NF3 is programmed into the module so the monitor displays the NF
concentration.
3
The Vertex M pyrolyzer module detects NF3 only and cannot be bypassed to detect mineral acids.
The right filter compartment houses eight par ticulate filters and one acid scrubber, which are identical to the standard Chemcassette compartment houses eight charcoal filters which remove the following compounds:
Freon® is a registered trademark of E.I. du Pont de Nemours & Company (DuPont).
The charcoal filters may also remov e other compounds. Contact Honeywell Analytics for a complete list. Charcoal filters have a part number (P/N 1874-0139) unique to the pyrolyzer module.
The Vertex M Pyrolyzer requires two adjacent slots on one tier and always occupies Slot 1 and 2. The bottom rail and latch must be removed from slot 1 to install pyrolyzer.
®
module except that it detects nitrogen
). The sample passes through a high
3
®
module.
®
filters. The left filter
Freon 12 Freon 113 HF Freon 13 Freon 114 HCl Freon 21 Freon 116 Cl
2
1.7.1 Pyrolyzer Fan
The Pyrolyzer has a fan that provides cooling to the pyrolyzer.
1.8 Vacuum Pumps
Two field-replaceable pumps provide a redundant vacuum source for the transport and sample flow system. One pump in the system dra ws v acuum while the other is idle. The pump exhaust connects to the manufacturing facility central toxic exhaust system.
Note:
The exhaust line from the Vertex M should not ex­ceed 50 feet.
The pumps are located in the bottom of the Vertex M System cabinet inside a sound-deadening enclosure to reduce noise. Three cooling fans circulate air over the pumps.
The Vertex M System draws cooling air in through a filter mounted on the pump module access door.
Pump Status Indicator
See Pump Status Indicator under Section 4.3.1 System
Display Area.
1.9 Multiple Gas Monitoring
A Vertex M System equipped with two or more types of Analyzer modules can monitor more than one gas (or groups of gases such as hydrides or mineral acids) at a location.
Each Vertex M Analyzer module can monitor only one gas family (such as hydrides or mineral acids).
Section 1 - Introduction 1-16
Page 24
Vertex MTM 24-Point Continuous Monitor
Communications
Above is a simplified block diagram of the communications path of the control system. The analyzer modules and PLC are microprocessor controlled and contain non­volatile memory.
1.10.1 Data Acquisition Computer
The data acquisition computer (DAq) is the central processor for the Vertex M System. It configures the analyzers, stores data and provides a netw ork interface for data transfer to other computers. System display and operator control is through an LCD touchscreen w/ on-screen keyboard or included external keyboard.
Optional manifold for multiple-gas monitoring.
CAUTION
1.10 Control System
The Vertex M control system is a redundant system consisting of a central data acquisition computer (DAq), a programmable logic controller (PLC) and one or more analyzer modules.
PLC
Primary Communications Alarms and Faults
Secondary
Az
Data Communications Prgramming and Display
AzAz
Alarms and Faults Should Primary Fail
OPC on TCP/IP via Ethernet not recommend­ed for alarm annunciation.
1.10.2 Programmable Logic Controller
The Programmable Logic Controller (PLC) is the control system path between the DAq and the individual analyzers. The PLC polls the analyzers for current information, activates relays which may be connected to external alarms and provides external communications.
DAq
Figure 1-1. Communications Path
Section 1 - Introduction 1-17
Page 25
Vertex MTM 24-Point Continuous Monitor
Section 1 - Introduction 1-18
Page 26
Vertex MTM 24-Point Continuous Monitor
2 Installation
Vertex M TM Technical Handbook
2-1
Page 27
Vertex MTM 24-Point Continuous Monitor
2.1 Introduction
The installation and initial start-up procedure for the Ver tex M System consists of seven steps, described in this and the following sections:
2.2 Surveying the Installation Site
2.3 Optional Floor Mounting
2.4 Installing Sample Lines/Filters
2.5 Installing Pump Exhaust Line
2.6 Electrical Power
2.7 Data Acquisition System
2.8 Wiring Alarm Relays
2.2 Surveying the Installation Site
A survey of the site helps you mak e important decisions before installing your Ver tex M System. Topics in this section assist you with appropriate placement of the V ertex M System and in determining if you have special filtering needs at the sampling location.
The site should:
• Be remote from the monitored location, not sharing the atmosphere
• Have sufficient ventilation for cabinet cooling
• Have power available
• Be indoors in an area that is not subject to wide variations in temperature and humidity.
Note:
The specified humidity is 20–65% RH and a temper­ature between 59°F to 95°F (15°C to 35°C).
2.2.1 Placement of the Vertex M System
Install the Vertex M System in an environmentally­protected setting remote from the manufacturing or storage locations that it monitors.
Note:
Refer to the installation drawing in Appendix A Installation
Drawings for lifting/mounting information.
Section 2 - Installation 2-2
You can place the V ertex M System up to 400 ft. (122 m) from sample locations.
2.2.2 Exposure to Dust and Humidity
Exposure to corrosive gases or materials, excess moisture, dust and other unusual environmental conditions could seriously hamper the Vertex M’s monitoring ability and could damage the monitor.
Allow room around the V ertex M System f or ventilation and servicing.
2.2.3 Sample Transport Time
Install the Vertex M System central to all 24 sample locations to achieve equal sample transport times during monitoring. The shorter the sample line, the shorter the response time. If monitoring a critical location, it may be desirab le to place the monitor near that critical area to reduce sample transport time for that location. See Appendix B Specifications for transport times.
2.2.4 Monitor Dimensions
Monitor dimensions are important factors in monitor placement. The Vertex M System is 24. in. (61 cm) wide, 36 in. (91.4 cm) deep and 57 in. (144.8 cm) in height. The system with 3 analyzers weighs about 550 pounds (249 kg). Allow f or 24 in. (61 cm) door s wing; 5 in. (12.3 cm) at rear and 5 in. (12.3 cm) on sides. Allo w clearance above monitor for installing sample lines.
2.2.5 Sample Locations
Before installing the Vertex M System, evaluate the sampling locations to determine if excessive dust or moisture are present. An external filter must be used in all locations. Make sure you use the correct filter. Dust may be a result of construction as well as manufacturing activities. Moisture ma y occur from rain entering a line at an outdoor sampling location or from
Page 28
Vertex MTM 24-Point Continuous Monitor
condensation caused by temperature fluctuations. Water condensation in the sample lines could cause false alarms.
Note:
Variables such as airflow, the molecular weight and temperature of the sample gas, and the physical conditions of the areas being monitored influence the placement of the sampling locations. You may need to consult your company’s industrial hygien­ist or safety officer before installing sample lines to determine your company’s policy related to sampling locations and monitoring of the desired sample gas.
2.2.6 Sample Line Particulate Filter Use
See Appendix B Specifications to determine which filter type should be used at the location.
2.3 Optional Floor Mounting
For added protection with optional floor mounts, prepare floor anchors to secure the base of the cabinet and prevent tipping. See Appendix A Installation Drawings for floor mounting instructions.
2.4 Installing Sample Lines/Filters
Use only FEP Teflon® tubing to assure proper sample transport. Other types of tubing are not sufficiently inert. See Appendix B Specifications for tube specifications. FEP tubing can be ordered from Honeywell Analytics. This tubing is manufactured to our own strict specifications, and has been purged of all by-products of the manufacturing process. On occasion, users have supplied their own FEP type tubing. Should y ou choose to use y our own tubing, be advised that some brands of FEP tubing off-gas small amounts of HF, which can be detected on start up by monitors configured for detecting mineral acids gases (HBr, HCl, HF, NF3). Before enabling building alarm systems, make certain that 1) you have installed the
correct Chemcassette® and 2) your monitor reads zero . Install sample lines from each location to the top of the
Vertex M System. This procedure involves:
2.4.1 Sample Line Installation Requirements
2.4.2 Sample Line Connections
2.4.3 Installing Sample Line Particulate Filters
Teflon® is a registered trademark of E.I. du Pont de Nemours & Company (DuPont).
2.4.1 Sample Line Installation Requirements
Follow the general requirements listed below when installing sample lines.
Sample lines should not exceed 400 ft. (122 m) in length.
Route all lines as direct as possible to improve transport time. See Appendix B Specifications for transport times.
Avoid running sample lines through areas of great temperature extremes, such as adjacent to steam or chiller lines.
Sample lines should not be crimped, bent to less than a 12 in. (30.5 cm) radius, or placed in an area where weight could collapse the tubing. Sample lines should be easily accessible for periodic inspection.
Where possible, leave as many bends exposed for periodic visual inspection of the line for kinked or damaged tubing.
Check each sample line installation for seal integrity after completing installation of the Vertex M System. See Section 3.8 Leak
Checking Sample Lines for the leak check
procedure. Also use this procedure to detect leaking or severed tubing after events, such as construction, which may have affected the
Section 2 - Installation 2-3
Page 29
Vertex MTM 24-Point Continuous Monitor
Correct - Fully Inserted Incorrect - Not Fully Inserted
Tubing Stop
integrity of the tubing.
Unused sample line ports may be blocked by the user with a plug, or a particulate filter may be installed to keep the system clean. If using a plug, make sure the system vacuum level is adjusted.
If an analyzer is installed in the Vertex with a Chemcassette tape, the optics may need cleaning before activating a previously unused point.
2.4.2 Sample Line Connections
O-Ring
Grey Locking Insert
install a tube into a sample line inlet, insert the tube far enough into the fitting to ensure that the tube has passed through both the external grab ring and the internal O-ring and is firmly seated against the stop. The insertion depth for a correctly installed sampling line is 1/2 in. to 5/8 in. (12 mm–16 mm). Verify the inser tion depth by holding the tube and marking with your thumb where it emerges from the fitting. Remove the tube to measure the insertion depth.
CAUTION
Improper installation of the tube into the con­nector results in dilution of the sample.
2.4.3 Installing Sample Line Particulate Filters
Attach a sample line filter to the sampling end of the line for all locations.
Figure 2-1. Sample Line Inlet Connections
To prepare for installation of sample lines, remo ve the FEP Teflon tubing from the installation kit. The top of the unit includes 25 connections:
24 Sample Inlets
Exhaust Outlet (See Section 2.5 Installing
Note:
Always perform a leak check after installing sample lines. See Section 3.8 Leak Checking Sample Lines for the leak check procedure.
Pump Exhaust Line for connection.)
Each inlet has a quick connect/disconnect fitting with an internal O-ring and an external grab ring. To
Section 2 - Installation 2-4
CAUTION
Keep in mind that excess amounts of dirt in
the lters reduces the sample ow, raises
sample vacuum and may affect concentration readings of the analyzer.
See Appendix A Specifications to determine the proper filter type to use with each target gas.
2.5 Installing Pump Exhaust Line
This section describes exhaust connections and installation. The Vertex M System is equipped with a vacuum pump that is located in the bottom of the V ertex M System cabinet. The pump exhaust line connects to the manufacturing facility central toxic exhaust system.
Page 30
Vertex MTM 24-Point Continuous Monitor
2.5.1 Exhaust Line Installation Require­ments
Follow the general requirements listed below when installing exhaust lines.
The length of the line should not exceed 50 ft. (15 m). If longer distances are required, contact Honeywell Analytics.
Do not crimp exhaust lines, or place them in an area where weight could collapse the tubing, or bend them to less than a 12 in. (30.5 cm) radius.
Where possible, leave as many bends exposed for periodic visual inspection of the line for kinked or damaged tubing.
Var ying exhaust pressure can induce pump failure or flow faults.
2.5.2 Exhaust Line Connection
The monitor includes 20 ft. (6m) of 3/8 in. (10 mm) I.D . x 1/2 in. (13 mm) O.D. Teflon tubing. Insert the tubing into the exhaust port on the top of the unit to the depth of 0.9 in. (23 mm).
System Exhaust
0.5 in (12.7mm) tubing
To ensure a leak-free installation:
Use a polypropolene tube with outside diameter 0.375 in. (9.525mm) +/-.005 in. (0.127mm).
Verify that the external surface of the tube is free of score marks and scratches that could compromise the O-ring seal used in the fitting over the insertion depth.
Cut the tube end perpendicular to its length
0.062 inches (1.5 mm) from its end.
Insert the tube in the fitting to a depth of 0.95 in. (24.13mm) ±0.05 inches (1.27mm)
With the system running, verifty the leak integrity with a small amount of leak test fluid.
2.6 Electrical Power
The Vertex M System requires a connection to a source of electrical power . An easil y accessible service disconnect/power switch must be installed near the instrument, and the switch must be marked as the main disconnect for the V ertex M unit. The f ollowing warning must be displayed at the switch:
CAUTION
Leaks in the exhaust tubing connection can cause exposure to toxic gases from remote sample areas.
Section 2 - Installation 2-5
WARNING
Hazardous voltages may exist at the Alarm
Contacts in this unit with the power switch turned off. Ensure power is disconnected at
the source prior to servicing alarm contacts.
Page 31
Vertex MTM 24-Point Continuous Monitor
2.6.1 Connecting AC Power
AC Source Requirements:
Operating Voltage: 110 or 230 VAC ± 10% (under load) @ 50/60 Hz; 15 Amps maximum, single phase.
The Vertex M System requires a dedicated AC circuit rated at either 110 or 230 volts , 50/60 Hz, 15 Amp single phase. Line voltage should fluctuate no more than ± 10%. The e xternal switch must be clearly labeled and installed in accordance with local electrical codes. Input power cable should be #14 A WG minimum. The saf ety ground wire must be the same or larger gauge as the line wires. Connect A C pow er connection to the three­position terminal block in the side panel of the rack.
See Figure 2-2.
AC Input
2.6.2 Power On/Off
An internal rack power switch is located behind the door.
After performing self-diagnostics, the V ertex M System main screen opens and the system returns to the same state it was in prior to power down.
Analyzer / Pyrolyzer
Power Switches and Indicators
Rack Power Switch
Line
Figure 2-2. AC Power Connection
Section 2 - Installation 2-6
Neutral
Ground
Figure 2-3. Rack Power Switch
WARNING
Hazardous voltages may exist at the Alarm
Contacts in this unit with the power switch turned off. Insure power is disconnected at
the source prior to servicing alarm contacts.
2.7 Data Acquisition System
The data acquisition computer or DAq is the main computer in the Vertex M System. System displa y and operator control are through an LCD touch screen with on-screen keyboard or the exter nal keyboard on top of the unit.
Page 32
Vertex MTM 24-Point Continuous Monitor
The on-screen keyboard operates similar to a standard keyboard e xcept when using modifier keys (CTRL, ALT, or SHIFT).
To use modifier keys:
1. Touch the modifier key. The key changes to show the modifier key is locked down.
2. Press the second key of the key combination.
Figure 2-4. On-screen Keyboard
2.7.1 Printer
The Vertex M System software can be programmed to print to either a network or local printer. To install a local printer, connect it to the parallel printer port as shown. You may also use the USB port. The correct printer driver must also be installed.
2.7.2 External Network Connection
The Vertex M System can be connected to an external Ethernet network at the port shown.
External Ethernet Connection
Figure 2-6.
CAUTION
Do not connect an external network to the
Vertex M Ethernet hub. Use only the external
Ethernet connection (as shown in Figure 2-6) on the back of the data acquisition computer. Connecting an external network to the hub will impair monitoring capability.
Parallel Printer Port
Figure 2-5. Printer Connection
Section 2 - Installation 2-7
USB Port
Figure 2-7. Ethernet cable
1. When using an Ethernet output, the conduit must be connected to Earth ground.
2. The Vertex M comes with a Ferrite. Four wraps of the Ethernet cable is needed as close to the Vertex M as possible.
Page 33
Vertex MTM 24-Point Continuous Monitor
2.7.3 Network Computer Security
The Vertex M relies on the HMI system of accounts and passwords to prevent unauthorized tampering as described in Section 4.6.6 Security Access of this manual. Microsoft® Windows® provides its own system of accounts and passwords. However RSView32 requires that Windows be run in an account with administrator privileges. Attempting to run the V ertex M RSView32 application in a Windows® account without administrator privileges will cause error messages to be displayed. The Vertex M should be treated and secured as any other networked PC by maintaining the appropriate virus protection. Contact your local Honeywell Analytics field service representative prior to installing Microsoft updates or Service Packs
Use an external hardware firew all to isolate the monitor from malicious Ethernet traffic.
2.8 Wiring Alarm Relays
This section describes relay:
Contacts
Ratings
2.8.1 Relay Contacts
The Vertex M System has form-A, single-pole, single­throw relays that activate external alarm devices. Contacts are availab le for each circuit to accommodate installation of external devices.
Relay panels are located behind the Vertex M LCD screen. See Appendix A Optional Relay Specifications for more information.
Wiring guidelines
WARNING
Use caution when servicing the PLC terminal blocks. Power to contacts is supplied exter-
nally. See Appendix A Optional Relay Speci-
cations for alarm relay voltage and contact
rating guidelines.
Section 2 - Installation 2-8
Page 34
Vertex MTM 24-Point Continuous Monitor
2.8.2 Wiring Guidelines
To wire the alarm relays:
Use agency approved wire (such as NRTL in the U.S.) with 300 volt insulation.
CAUTION
Make sure there is proper separation be­tween the mains power supply and alarm wiring.
Route relay wiring through raceway and out through the top of the cabinet.
Use shielded cable or conduit.
Conduit must be earth grounded.
CAUTION
Failure to replace and retighten hardware
after servicing can adversely affect monitor
performance and EMC compliance. Make certain all fasteners are reinstalled and rmly tightened. This will ensure a proper ground.
Use a single, solid or stranded wire (not exceeding 14 gauge or 2.5 mm2) per terminal block connection.
Do not switch DC current with the relay contact unless you are using counter electromotive force (CEMF) protection such as a suppression diode.
Do not use the Vertex M System power supply for external alarm power.
Note:
Make sure all connections comply with applicable RFI/EMI standards.
Alarm Wiring Conduit Plate
2 in (50.8mm)
Note:
The Alarm wiring conduit plate must remain in place if not used.
Validating the System
The Vertex M and Chemcassette products’ design, manufacture, and recommended maintenance ensure the correct operation of the system. For validation or commissioning after installation by gas exposure, these Technical Notes are available upon request from Honeywell Analytics:
1998-0837 1998-0219
Calibration and Verification Detector Testing Protocols
Section 2 - Installation 2-9
Page 35
Vertex MTM 24-Point Continuous Monitor
Section 2 - Installation 2-10
Page 36
Vertex MTM 24-Point Continuous Monitor
3 Startup
Vertex M TM Technical Handbook
3-1
Page 37
Vertex MTM 24-Point Continuous Monitor
3.1 Startup
This section describes the Vertex M System startup sequence.
Sample lines
Exhaust line
AC power connection
3.1.1 Initial Startup
Use this section to turn on your Vertex M System and to configure the analyzer modules f or specific gas locations. There are six parts to this startup procedure:
3.3 V erify Installation
3.4 Power Up
3.5 Start Program
3.6 Configuration Utility
3.7 Load T ape
3.8 Leak Checking Sample Lines
3.9 Verify Flow Rates and Supply Vacuum
3.1.2 Factory Conguration
Honeywell Analytics loads all software on the DAq at
®
the factory . The Univ ersal Chemcassette configured for the mineral acid f amily of gases and the Pyrolyzer Analyzers f or NF each point for the target gases at your facility.
. You will need to configure
3
Analyzers are
Relay wiring
See Section 2 Installation for connection details.
3.4 Power Up
Use the rack power switch behind the front door to power up the Vertex M System.
1. Open front door.
2. Turn on rack power switch.
3. Turn on power switch to appropriate analyzers.
4. Close and latch front door.
After 15 seconds, the analyzer status LEDs sequence four times through all colors.
Analyzer / Pyrolyzer
Power Switches and Indicators
Rack Power Switch
3.2 Getting Started
Before startup and configuration, gather the following information:
The location to which each point is connected
Target gas at each location
Alarm levels
Relay configuration
3.3 Verify Installation
Ahead of the startup sequence, make sure that the following installation steps have been completed:
Section 3 - Startup 3-2
Page 38
Vertex MTM 24-Point Continuous Monitor
Mon State Alarm State Fault State
none black green
500 400 100
time in millesconds
idle
pyrolyzer
warmup
monitoring
0
1 any red black
2 any red black
0
1 any green black red
0
1
2 red green
primary program invalid amber black amber black amber black amber black amber black
unpowered black
lockup
maintenance amber black
instrument amber black
none green black
m or i green black amber
none green black
maintenance amber green
instrument amber green
red green
any
green
amber
Table 3-1. Analyzer Status LEDs
Section 3 - Startup 3-3
red
Page 39
Vertex MTM 24-Point Continuous Monitor
3.5 Start Program
Upon power-up , the DAq automatically starts Windows and loads the V ertex M progr am. After the two-to-three minute startup sequence, the Vertex M main screen opens.
Note:
Any time the Vertex M System is powered up, loss of communications may cause maintenance faults.
See Section 4.5.4 Event List for instructions to clear faults.
Note:
Use the Windows Date/Time Properties dialog box to change the time zone, time and date on your Vertex M System. Stop project if adjusting time and time zone. Once complete restart project. See Sec-
tion 4.4.5 Stopping Project on how to stop the project.
CAUTION
Do not change language in Windows setup.
Section 3 - Startup 3-4
Page 40
Vertex MTM 24-Point Continuous Monitor
Figure 3-1. Vertex M Main Screen
Section 3 - Startup 3-5
Page 41
Vertex MTM 24-Point Continuous Monitor
3.6 Conguration Utility
Before the Vertex M System can begin monitoring, you must create a configuration profile. The configuration profile stores all of the monitor settings in a single file on the hard drive. Configuration profi les include system level information, point settings and analyzer information. Use the Configur ation menu to create a new configur ation profile or modify an existing profile.
To open the Configuration Menu, touch Main Screen, Menu and then Configuration.
Set Initial Conguration
Enter information and set parameters common to all points and modules.
Congure Analyzer / Points
Defines the type of analyzer module installed in each slot. Designates the target gas. Sets alarm levels for each point.
Dene Gas Location Names
Enter the short and long names for each monitored location.
Section 3 - Startup 3-6
Page 42
Vertex MTM 24-Point Continuous Monitor
Dene and Assign PLCs
Associate relays with software alarms and faults.
Information and Options
A display of key parameters about the Vertex M system.
See Summary Information
A tabular listing of the configuration profile
Section 3 - Startup 3-7
Options
Select a tab to enter information and set parameters common to all points and modules.
Page 43
Vertex MTM 24-Point Continuous Monitor
Install Profile Status
During the installation process, a dialog box will be shown indicating the status and final result of the installation.
Open Profile...
Opens a previously saved profile.
File Save/Save As...
Saves current profile on disk.
Vertex M will prompt you to save
changes when closing the
Configuration window.
Install Current Profile
Not active while creating configuration profiles on a computer other than the one running the Vertex M system. Loads the current configuration settings into the appropriate analyzers and PLCs. If the Vertex M System is in a monitoring state, the program will open a dialog box to verify that it is okay to take the Vertex M System out of monitor during the profile installation.
Close Window/Done
Exits Configuration setup
Section 3 - Startup 3-8
Page 44
Vertex MTM 24-Point Continuous Monitor
All events require User Ack
When selected, non-latching alarm
events will not be removed from the
event list until an authorized user
acknowledges the event. Fault and
latching alarm events are not affected
by this option, since an authorized
user must reset these events and a
reset also serves as an acknowledgement.
Inverted Gas Alarm Relays
Vertex M alarm relays, by default, are normally open (de-energized) when no alarm condition exists. If this option is checked, the alarm relays will be normally closed (energized) when there is no alarm. Fault relays are not affected by this option and are always normally closed (energized) unless a fault condition exists.
Non-Latching Gas Alarm Relays
A latching gas alarm relay activates when a gas concentration reaches a level 1 or level 2 alarm setting. The relay remains activated until an authorized operator resets the alarm. Non-latching gas alarm events clear themselves as soon as the gas concentration drops below the alarm setting.
Section 3 - Startup 3-9
Page 45
Vertex MTM 24-Point Continuous Monitor
response to the event. When utilizing data output options, it is highly
Disabled Alarm Action - Gas Relays Disabled or Full (No Gas Events)
This setting effects the operation when alarms are disabled using the Runtime Options screen. If “Full” is selected, Vertex M will not generate an alarm event for the affected point(s) and none of the associated actions such as relay actuation will occur. Otherwise, the alarm events will be generated normally when using data output options but, the alarm relays ONLY will not be activated in
Ignore Low ChemC. Alert
Vertex M software tracks the amount of Chemcassette the supply reel and triggers a low tape event when less than 24 hours of tape remain. Choosing “Ignore Low ChemC. Alert” disables the low tape event.
®
tape remaining on
Section 3 - Startup 3-10
Page 46
Vertex MTM 24-Point Continuous Monitor
Set the number of days the filters will last
before they need to be replaced. When the
target is reached, this setting will trigger a
Internal Filter Life (in Days)
maintenance fault to replace filter.
Set Timeout Values
Authorized users may temporarily disable
alarms from activating and points from
monitoring. A point or alarm that is disabled
longer than the timeout limit will cause a
maintenance fault which will call attention to
locations excluded from monitoring. Enter a
period of time up to displayed minutes or 0
to disable the maintenance fault.
User Specified Auto Logout
Users remain logged in until the auto logout period lapses. The auto logout period ranges from 30 minutes to 24 hours. A warning displays prior to auto logout.
Section 3 - Startup 3-11
Page 47
Vertex MTM 24-Point Continuous Monitor
1st TWA Time
Use to set times for the beginning and end of each 8-hour, Time Weighted Average (TWA) period. Use this option to associate the TWA periods with shifts or any other regular event. The system calculates and displays the TWA after each 8-hour TWA cycle.
The default setting is 04:00 indicating that the Vertex M will run three successive TWA periods from 04:00 to 11:59, 12:00 to 19:59, 20:00 to 03:59. Remember, the Vertex M System uses a 24-hour clock. For example, to set the first TWA to 3:00 P.M., enter 15:00. If you view the profile information for this example, you will see the TWA End At Time is 07:00/15:00/23:00. The system automatically sets the beginning times of the second and third TWA periods at 8-hour intervals from the time entered for the first TWA period.
Section 3 - Startup 3-12
Page 48
Vertex MTM 24-Point Continuous Monitor
Sets the time period to maintain historical
event and concentration data before purging.
Set the purge period in Database Management
to prevent a large number of records to accumulate.
Logging Rate
The Logging Rate option sets the
frequency that Vertex M enters gas
concentration data into the
database. The system logs data at
a slow rate unless a gas concentration
rises above the threshold set in the
point configuration window. Once the
concentration reaches the threshold,
Vertex M logs at a faster rate. Logging
period options are 5, 10, 30, 60, or 120
seconds for the slow rate and 5, 10, 15,
20, 30, or 45 seconds for the fast rate.
(See Section 3.5.4, Configure Point, for
instructions to set logging frequency.)
Note:
DB Management
Setting the Vertex M System to continuously log concentration data on a 3-analyzer system requires approximate­ly 15 megabytes of disk storage per day at the fastest logging rate of once every 5 seconds. Purge data often to avoid filling available disk space.
Section 3 - Startup 3-13
Page 49
Vertex MTM 24-Point Continuous Monitor
Database Management-Retention Periods
Retention periods are selected as either days or weeks. Valid entries for the period are positive numbers from 1-99. Vertex M will not recalculate the values when the unit is changed. For example, if the purge period is 14 days and you change “da ys” to “weeks”, V ertex M will set the period to 14 weeks. Vertex M performs the record purge as the data acquisition computer clock passes midnight.
Event Record Retention Period
When selected, Vertex M automatically purges
events from the database after the designated
period.
Logged Data Record Retention Period
When selected, Vertex M automatically purges concentration records from the database after the designated period.
Section 3 - Startup 3-14
Page 50
Vertex MTM 24-Point Continuous Monitor
Leave this box UN-checked regardless of whether a 4-20mA PLC is installed.
See Appendix G for Analog Output option configuration.
20 mA PLC Installed
Fieldbus
Use this setting to select the PLC network interface that is installed.
Section 3 - Startup 3-15
Fieldbus Parameters
These settings allow the user to change network specific parameters such as address and baud rate.
Page 51
Vertex MTM 24-Point Continuous Monitor
Use mg/m3 units
Select to display concentrations in milligrams
per cubic meter. If this option is not selected,
Vertex M displays concentrations in
parts-per-million (ppm) or parts-per-billion (ppb).
User File Rev
Allows the user to assign a revision number
to a configuration profile. The profile revision
number is not associated with software
version numbers.
Profile Description
Enter a descriptive name for the configuration profile. You may use up to 32 characters.
Section 3 - Startup 3-16
Page 52
Vertex MTM 24-Point Continuous Monitor
3.6.1 Dene Gas Location
Use Define Gas Location to edit the list of locations. Assign a long and a short name for each location.
Clear All Entries
Clears every entry in the list.
Short names
Enter up to 12 characters. Vertex M
displays the short name where space
does not permit the display of the
long name.
Add New Entry
Creates a new entry in the gas location list using the entered short and long names.
Long names
Enter up to 35 characters.
Replace Selected Item
Replaces the selected line in the gas location list with the information in the short and long name text boxes.
Delete Selected Item
Removes the selected line from the location list.
Map Location To Point
Brings up Location Map window.
Section 3 - Startup 3-17
Page 53
Vertex MTM 24-Point Continuous Monitor
Gas Location List
Select desired gas location from this list. For points with no assigned location, select (default). Points assigned to default location will automatically be given location names based on the point’s position in the Vertex M.
Point Map
Select point to add or remove it from the selected location. Up to 3 points can be assigned to each location.
Section 3 - Startup 3-18
Page 54
Vertex MTM 24-Point Continuous Monitor
3.6.2 Congure Analyzers and Points
Press “Configure Analyzer/P oints” to change the right side of the Configuration window to a display representing physical layout of the Vertex M System. Each slot is represented by a two-part button.
When you have configured an analyzer, the top of the button displays the type of analyzer and the gas family. The bottom of the button is a second button for configuring each point within the analyzer.
Note:
Only analyzers on tier one should be configured. Configuring analyzers on tiers 2 or 3 will result in errors and faults.
Two-part Button
Section 3 - Startup 3-19
Page 55
Vertex MTM 24-Point Continuous Monitor
3.6.3 Set Analyzer Window
To configure the type of analyzer slot, press the top of the button representing the slot. The Set Analyz er Window opens.
Options
When you choose a family of gases, Vertex M enters default settings into the profile. Selecting “Override Defaults” allows you to change the target gas type, alarm levels and the location assignment.
Analyzer Type
Choose the model of analyzer populating the slot. A pyrolyzer takes up slots 1 and 2. If pyrolyzer is selected, slot 1 automatically
becomes unavailable.
Any analyzer that is physically installed but
configured on this screen to “None” should
be de-energized.
Family/Chemcassette
Choose the family of target gases.
Target gases for all eight points in
the analyzer must be in the same
family of gases.
ChemCam AutoPicture
If the optional ChemCams are installed, select under what condition
a picture of the Chemcassette
®
stain will be automatically taken.
ChemCam AutoPicture
When either ChemCam for Level 1 or Level 2 gas is selected, a gas alarm signals the Vertex M System to store a picture of the stain the next time it advances the Chemcassette® tape. When the tape advances, the tape stops with the stain under the camera, the ChemCam takes a picture and then advance continues. The ChemCam field of view is only wide enough to capture four points on one picture. See Section 4.5.3 Optional
ChemCam for additional information on ChemCam features and functions.
Note:
This activity will consume additional tape. Some faint stains may not be visible via the camera
Section 3 - Startup 3-20
Page 56
Vertex MTM 24-Point Continuous Monitor
3.6.4 Congure Point
The Configure Point window provides the following options for each point:
Select the specific target gas Configure concentration logging
Designate the location of the target gas Configure point-specific event help
Set alarm levels Set PLC full-scale concentration
Enable/disable point
When all of the entries are correct for the point, use either the point selection buttons or choose Next Point/ Last Point to scroll to the next point in the analyzer. Press Done when all settings are entered.
Gas Calibration
Select the target gas from the dropdown list. Only the gases valid for the family of gases chosen for the designated tape will appear.
Warning
Select Warning to create an alarm when a gas concentration exceeds the Lower Detection Limit (LDL).
See Appendix A Detectable Gases for a complete list of LDLs. Warnings appear as a “W” on the main screen with no relay actions.
Last Point / Done / Next Point Buttons
Section 3 - Startup 3-21
Page 57
Vertex MTM 24-Point Continuous Monitor
Alarm Level 1 and Alarm Level 2
Ver tex M loads default alarm levels when you choose a target gas. See Appendix A Detectable Gases for a list of default alarm levels. You may enter new levels only within the range of the Vertex M detection system.
Make the gas assignments before changing alarm levels. Changing the gas automatically resets alarm level settings to the factory defaults.
The Vertex M System will not allow you to make invalid or inappropriate entries while setting alar m levels. Following are three examples of invalid attempts the Vertex M System will reject:
The alarm setting for Alarm Level 1 is greater than the setting for Alarm Level 2
An alarm setting is less than the lowest alarm level for that target gas
An alarm setting is greater than the full scale for that target gas
Alarm Level 1 Alarm Level 2
Section 3 - Startup 3-22
Page 58
Vertex MTM 24-Point Continuous Monitor
Log never/Log always/Log if
This option sets the frequency that Vertex M enters data into the data log.
PLC F/S Conc. (Data Output)
Calibrates the Vertex M current loop output or data concentration bits to correlate to the customer-specified output range (i.e.; milliamp output scaling or data output scaling to external PLC). Factory default value sets the 20 mA point to two times the TLV which is typically lower than the full scale value of the gas calibration (i.e.; F/S)
Log Always Log if >= Log Never
If concentration is below configured threshold
If concentration is equal to or greater than configured threshold
Note:
logs at slow rate
logs at fast rate
not logged not logged
logs at fast rate
not logged
Setting the Vertex M System to continuously log concentration data on a 3-analyzer system requires approximate­ly 15 megabytes of disk storage per day. Purge data often to avoid filling available disk space.
Section 3 - Startup 3-23
Page 59
Vertex MTM 24-Point Continuous Monitor
Units
Selects the unit of measure to display target gas concentrations. This selection applies to this screen only and does not effect displays during normal operation or events.
Unit choices are:
PPx
Parts-per-million or parts-ber-billion.
See Appendix A Detectable Gases
for definition.
Displays target gas as a percentage
of the threshold limit value. See
Appendix A Detectable Gases for a
list of the TLV for each target gas.
Displays target gas concentration
as a percentage of the full-scale
concentration.
See Appendix A Detectable
Gases for a list of the full scale
concentration for each target gas.
Displays gas concentration
in milligrams per cubic meter.
%TLV
%F/S
mg/m3
Section 3 - Startup 3-24
Page 60
Vertex MTM 24-Point Continuous Monitor
Check this box to perform a sample line integrity test.
P
erform Optional Line Integrity Test
See Appendix A Line Integrity Test Option.
Disable Point
No Monitoring
Select “Disable Point”
for points not needed.
Associated (*.HTM) File
You may link a user-generated HTML file
to this point. Either type in the file name
or touch the browse (…) button to bring
up a file selection window.
Gas Locations
Use this field to label the location the
point is monitoring. You may assign a
name by one of three methods:
* Choose a name from the location list.
See “Define Gas Location” for entering
names in the list.
* Edit the selected location.
Create a new location.
*
Section 3 - Startup 3-25
Page 61
Vertex MTM 24-Point Continuous Monitor
Generate Window Zero Reset Faults
Window Zero Reset events are generated when un­usual optics readings occur. Usually these are one-time events and present no long term issues. By default, these events generate an informational event. Howev­er, these events can some­time indicate conditions that could lead to a false concentration readings. For that reason, this option is provided. If selected, a maintenance fault will be generated when a Window Zero Reset event occurs.
Generate Accelerated CC Usage Faults
If a low background level of gas is present that is below the lower detectable limit, a stain can develop on the tape while the Vertex re­ports zero concentration. This can cause the Chem­cassette to be used up faster than expected. If the option is enabled, a main­tenance fault will be gener­ated if this condition exists.
PLC Network
Use to set communication parameters for the optional PLC Network interface.
F.8 DF1 Interface (P/N1295-0343) F.9 Modbus Plus Interface (P/N1295-0330)
Generate Sub-LDL
Events Generates a
warning alarm with 0 ppb/ppm concentration that may indicate the presence of gas below LDL.
Virtual Reference
Function See the
following page.
Line Integrity Test
Displays the optional Line Integrity Test configuration utility. See Appendix H -
Line Integrity Option.
Section 3 - Startup 3-26
Page 62
Vertex MTM 24-Point Continuous Monitor
Virtual Reference Function
The Virtual Reference option reduces the possibility that a non-gas event will result in a concentration or alarm. When enabled, it maintains a record of spe­cific monitor operation and, in the event of a reading ¼ TLV or above, executes a confirmation before the concentration or alarm is issued. Once confirmed, measurements for the same event will not be affect­ed. See software 1.25.5 release technote for further information.
The Virtual Reference function is user configurable by rack (it is disabled by default). See the following table for the number of windows used and the time to confirm an event. The function reduces the possibility that a non-gas event will result in a concentration or alarm.
Note:
The Virtual Reference function is not used on CLO analyzers, even if enabled.
Hydrides 3 15-25 XP Hydrides 3 15-25 Mineral Acids 6 30-40 Cl2/Oxidizers (NO2) 6 30-40 Mineral Acids (Pyro) 6 30-40 Phosgene 6 30-40 XP Phosgene 6 30-40 Aliphatic Amines 3 15-25 Cl2/Oxidizers-III 6 30-40 Hydrogen Cyanide 3 15-25 Hydrogen Sulfide 3 15-25 XPVChlorine 6 30-40 Fluorine/Oxidizers 3 15-25 XP Ammonia 3 15-25 XP Mineral Acids 6 30-40 XPVMineral Acids (Pyro) 6 30-40 LL Sulfur Dioxide 3 15-25 XP4 Hydrides 3 15-25 XP4 Mineral Acids 6 30-40 XP4 Mineral Acids (Pyro) 6 30-40 XP4 Chlorine 6 30-40 XP4 Ammonia 3 15-25 XP4 Phosgene 6 30-40
Chemcassette
Number of
Windows
Pulled
Time to
conrm
(sec)
Section 3 - Startup 3-27
Page 63
Vertex MTM 24-Point Continuous Monitor
3.6.5 Dene and Assign Relays
The Vertex M System includes multiple programmab le relays. You may associate relays with one or more alarms or faults to trigger external alarm devices or emergency equipment. Relays are located on relay cards; either 8 or 16 relays populate each card.
Note:
Relays are NOT factory configured.
Vertex M uses a two-part display to configure rela ys . The Configure PLC window displa ys the a v ailab le rela y cards and contacts. In a second windo w, Vertex M also displays a representation of the analyzers installed in the system.
See Appendix A Optional Relay Specifications for a complete listing of alarm relay specifications.
Section 3 - Startup 3-28
Page 64
Vertex MTM 24-Point Continuous Monitor
3.6.6 Congure PLC
Use Configure PLC to enter the following:
The number of relay cards installed
The number of contacts per card
The number of relays designated as fault relays.
PLC Relay Cards
Up to 4 relay cards populate the V ertex M System. The cards are numbered 3-6.
Relays per Card
Relays are located on rela y cards; either 8 or 16 rela ys populate each card.
Cards with 16 relays share a common connection among groups of eight contacts.
Cards with 8 relays have 8 isolated pairs of contacts.
Clear All
Erases the alarm and fault relay definitions
Set Default
Sets all relays to the initial default mappings
Section 3 - Startup 3-29
Fault Relay Count
You ma y allocate from 2 to 16 rela ys for fault indicators.
Note:
Set the number of fault relays before setting alarm relay definitions. If you change the number of fault re­lays, the current relay definitions become invalid and must be redefined.
When you change the number of f ault relays, Vertex M opens the Fault Relay Definition Change dialog box. Choosing Yes shifts the alarm definitions, choosing No pads the alarm definitions. Choose Cancel to return
Page 65
Vertex MTM 24-Point Continuous Monitor
to the PLC configuration without changing the relay assignments.
Changing the number of fault relays from 14 to 12 will result in two additional (and undefined) alarm relays being available at card 3 relays 12 and 13. Existing relay definitions are not moved.
3.6.7 Set Alarm Relays
A relay configured f or a Level 1 trigger will activate for both Level 1 and Level 2 alarms. A Level 2 trigger will only activate for Level 2 alarms.
Shift
Alarm relay definitions move down to fill the space created by fe wer fault relays or mov e up to accommodate the additional fault relays.
Changing the number of fault relays from 14 to 16 will cause the alarm relay assignments to move two rela ys up. Card 5, relay 2 definition moves to card 5, relay 4; card 5, relay 3 mov es to card 5 rela y 5; card 5 rela y 15 moves to card 6, relay 1, etc.
Changing the number of fault relays from 16 to 14 moves relay assignment down by 2 positions. Card 5, relay 4 definition moves to card 5, relay 2; card 5, relay 5 moves to card 5 relay 3; card 6, relay 1 moves to card 5, relay 15, etc.
Pad
Padding lea ves most alarm relay definitions unchanged. Some existing alarm definitions may be ov erwritten or undefined relays may become available.
Changing the number of fault relays from 14 to 16 will cause the alarm definitions on card 3, relay 14 and card 3, relay 15 to be overwritten by the fault relay assignments.
None of the relays are defined as general or point specific alarms until they are programmed or associated with one or more points in an analyzer.
Note:
Set the number of fault relays before setting alarm relay definitions. If you change the number of fault re­lays, the current alarm relay definitions may change and must be redefined. See Section 3.6.6 Configure
PLC.
Defining a point for association with a relay is a four­step process:
1. Choose the relays to which you want to associate with a point.
2. Choose L1 Alarm or L2 in the Change To... area.
3. Click the square representing the point or points to associate with the relay. The point changes color to indicate the change.
4. Choose Accept make the change the change to the configuration profile. Choosing cancel leaves the alarm definition unchanged.
Repeat the steps for all contacts. To verify a contacts association to analyzer points,
choose the contact. The associated point display changes color.
Section 3 - Startup 3-30
Page 66
Vertex MTM 24-Point Continuous Monitor
definitions from relays
Clear all alarm
Squares that represent the point or
points to associate with the relay
Selected relay in the relay block
Section 3 - Startup 3-31
Set type of alarm
Page 67
Vertex MTM 24-Point Continuous Monitor
3.6.8 Set Fault Relays
Fault relay contacts activate for instrument or maintenance faults. F aults are associated with an entire analyzer and not individual points.
Instrument faults indicate a loss of monitoring on one or more points.
Maintenance faults indicate the Vertex M System requires attention but is continuing to monitor.
Note:
The number of relays used for fault indication is con­figurable. See Section 3.6.6 Configure PLC.
Defining an analyzer for association with a relay is a four-step process:
1. Choose the relays to which you want to associate with an analyzer.
2. Choose Instrument, Maintenance, Both or None in the Change To... area.
3. Click the square representing the analyzer or analyzers to associate with the relay. The square changes color to indicate the association.
4. Choose Accept to modify to the configuration profile. Choosing Cancel leaves the alarm definition unchanged.
Repeat for all relays. T o v erify a relay’ s assignment to analyzers, choose the
contact. The associated analyzer changes color.
Section 3 - Startup 3-32
Page 68
Vertex MTM 24-Point Continuous Monitor
Clears all fault definitions
from all relays
Selected relay in
the relay block
Square that represents the
analyzer or analyzers to
associate with the relay
Section 3 - Startup 3-33
Set type of fault
Page 69
Vertex MTM 24-Point Continuous Monitor
3.6.9 Prole Management-File Menu
Use the file menu to open, create, save or close a configuration file. Configuration files may be stored in
3.6.10 Other Menu
The Other Menu offers several shortcuts to speed configuring the Vertex M System.
any directory on the Vertex M System hard disk. When you make any changes to the configuration
profile, Vertex M will always prompt you to save the change before closing the Configuration window.
Copy Az definition
Copies the configuration of one analyzer to any other analyzer in the system. There are two options when copying an analyzer configuration:
Copy Gas Location Name
Copies the location from the first analyzer to the second analyzer.
Copy *.htm File Name
Assigns the instruction file for the first analyzer to the second analyzer.
Alarm Defaults
Sets the level 1 and level 2 alarms of all analyzers not yet configured to the following values:
* One-half TLV and TL V * TLV and two times TLV * One-half TLV and two times TLV
Section 3 - Startup 3-34
3.7 Load Tape
After configuring the analyzers, load each analyzer with the proper Chemcassette® tape required for the target gas. See Section 5.3.4 Change Chemcassette® Tape for loading procedure. See Detectable Gases, for a list of target gases and Chemcassette® tape part numbers.
After installing Chemcassettes® for initial configuration, keep the analyzer in IDLE mode. Do not move to monitor mode until you have:
Performed a leak check on sample lines . See Section
3.8 Leak Checking Sample Lines.
Verified flow rates See Section 3.9.1 Verify Flow Rates.
Page 70
Vertex MTM 24-Point Continuous Monitor
3.8 Verify Flow Rates and Supply Vacuum
After you have configured all analyzers, loaded Chemcassettes verify flow rates in the Flow Diagnostics Window . F rom Main Screen, touch Menu, Service, Authorized Service. The Authorized Service window opens.
Note:
At higher altitudes with many analyzers installed, the system (50 Hz. mains) may not be able to achieve 13” Hg.
®
and performed leak check, you will
3.8.1 Verify Flow Rates
The Authorized Service window displays the flo w range in bar graph form f or each point of the selected analyzer.
Choose the analyzer from the selection pad in the upper right-hand corner. Press the pump on button. The eight points display their flow.
Section 3 - Startup 3-35
Page 71
Vertex MTM 24-Point Continuous Monitor
Flow (cc/min)
The real-time sample
flow to the point.
Point Vacuum (in Hg)
Point Vacuum indicates the restriction from sample line
length and the pressure
developed by shared lines.
Supply Vacuum
Typical supply vacuum is
9-12 in. Hg
Selection Pad
Section 3 - Startup 3-36
Optional Line Integrity Test Option
See Appendix A Line Integrity Test Option
Page 72
Vertex MTM 24-Point Continuous Monitor
Target Flow
A horizontal red line indicates the target flow rate required by the Vertex M System for correct analysis. The target flow rate is 180 cc/min. +/-5% (171-189 cc/min.)
Section 3 - Startup 3-37
Flow Rate
A floating white box indicates the actual flow rate. The position of the box graphs the flow; the numerical value of the flow is displayed in the box.
Page 73
Vertex MTM 24-Point Continuous Monitor
Minimum Flow
The minimum flow possible with the attached sample line and orifice.
Proportional Value Range
A vertical green bar displays the dynamic range over which the proportional valve can adjust the flow rate. Indicated numerically by Minimum Flow and Maximum Flow.
Maximum Flow
The maximum flow possible with the attached sample line and orifice.
See Section 4.6.2 Flow Calibration for
instructions on adjusting flow rates.
Section 3 - Startup 3-38
Auto Balance
Page 74
Vertex MTM 24-Point Continuous Monitor
3.9 Leak Checking Sample Lines
Perform a leak check of the sample lines following installation and also whenever a line is changed or moved. The leak check procedure involves plugging the end of the sample line and verifying that there is no flow through the line. To perform a leak check:
1. Put the affected Analyzer in Idle mode.
2. Choose Main Screen, Menu, Service, Authorized Service.
3. Select Analyzer.
4. Press pump on.
5. Securely plug the end of the sample line being tested.
6. Verify that the flow rate for the test line drops to zero. See Flow (cc/min) on page 3-36.
7. Verify that the sample Point Vacuum equals the Supply Vacuum within a tolerance of +/-0.5 inches Hg (see Point Vacuum (in Hg)) on page 3-36.
8. “Verify that the sample flow is less than 20cc.” “See Flow (cc/min)” and “(see Point Vacuum (in Hg)) are links.
9. After testing all points on the selected analyzer, press Pump Off.
If the sample point passes the test with the top port plugged, the leak is somewhere in the sample line and the line must be replaced. If the sample point fails the leak check procedure with the top inlet port plugged, contact Honeywell Analytics for assistance.
3.10 Recongure
The modular design of the Vertex M allows limited reconfiguration. All wiring and tubing is in place behind unpopulated slots. To add modules:
1. Remove filler panel.
2. Install new analyzer. See Section 5.4
3. Configure new analyzer. See Section 3.6
4. Load tape. See Section 3.7 Load Tape.
5. Leak check sample lines. See Section 3.9 Leak
6. Verify flow rates. See Section 3.8 Verify Flow
Note:
Replacing an Analyzer.
Configuration Utility.
Checking Sample Lines.
Rates and Supply Vacuum.
Any analyzers which are physically installed but not included in the configuration should be de-energized.
Note:
You must touch the Pumps On button even if the pumps are operating. Touching Pumps On turns on the solenoid valve to provide vacuum to the analyzer.
A sample point failing to meet both the flow and v acuum conditions of step 7 indicates either a leak in the sample line or a faulty sample inlet connection.
To troubleshoot the condition, disconnect the sample line at the inlet port at the top of the Vertex M cabinet. Securely plug the inlet port and repeat the above leak check procedure.
Section 3 - Startup 3-39
Page 75
Vertex MTM 24-Point Continuous Monitor
3.11 Moving to a New Site
Before moving the Ver tex M to a new site, use the following procedures to pre vent loss of data or damage to the monitor.
1. Remove all Chemcassette® tapes and store as required by local policies.
2. Exit the Vertex M program. Touch Project and then Stop Project.
3. Back up data and configuration files. See
Section 5.10 File Maintenance.
4. Open the front door and set all power switches to “Off”.
5. Disconnect electrical supply at the source and then disconnect from the power terminal in the side of the cabinet.
6. Disconnect sample lines and cap lines as required by local policies also cap Vertex M inlet points.
7. Disconnect exhaust line and cap line as required by local policies.
CAUTION
Leaks in the exhaust tubing connection can cause exposure to toxic gases from remote sample areas. For leak-tight connections, follow the instructions in the
Installing Pump Exhaust Line Pump
integrity with a small amount of leak test fluid.
section. With the system running, verify the leak
section and the
Remove
8. Disconnect alarm relays.
WARNING
Hazardous voltages may exist at the Alarm
Contacts in this unit with the power switch turned off. Insure power is disconnected at
the source prior to servicing alarm contacts.
Crate and pad the V ertex M to prevent damage during transport. If unsure of packing requirements , contact the Honeywell Analytics Service department.
Section 3 - Startup 3-40
Page 76
Vertex MTM 24-Point Continuous Monitor
System Shutdown
CAUTION
Failure to properly shut down the Vertex M could result in system le corruption.
1. Exit the Vertex program. Touch Project and then Stop Project.
2. In the Windows taskbar touch Start and then Shut Down.
3. Open touch screen and set all switches and the rack power switch to “Off”.
Section 3 - Startup 3-41
Stop Project
Project
Page 77
Vertex MTM 24-Point Continuous Monitor
4 Operation
Vertex M TM Technical Handbook
4-1
Page 78
Vertex MTM 24-Point Continuous Monitor
4.1 Introduction
This chapter describes Vertex M operation including monitoring, system control and data viewing.
This chapter includes the following sections:
4.2 Monitoring Mode Overview
4.3 Main Screen
4.4 Project Functions
4.5 Review Functions
4.6 Menu Buttons
4.7 OnScreen Keyboard
See Section 3 Startup if the analyzers in the Vertex M System have not yet been configured.
4.2 Monitoring Mode Overview
Monitor mode is the Vertex M System’s standard operating state. Upon power up, the monitor perf orms initialization routines and returns to the same state as when powered down. During monitoring, the Vertex M System will calculate concentrations ev ery second for each of the enabled points. Concentrations are used for:
Triggering alarm relays
Viewing in the main screen
Entries in the event list
Viewing in point detail screen
Concentration information is available through the:
Point detail screen
OPC
Optional fieldbuses
Optional 4-20 mA output
Data logger
Section 4 - Operation 4-2
Page 79
Vertex MTM 24-Point Continuous Monitor
4.3 Main Screen
The Vertex M System opens the main screen after power up. Vertex M divides the main screen into three areas:
System display
Point detail
Function buttons
Point Detail
System Display
Section 4 - Operation 4-3
Function Buttons
Page 80
Vertex MTM 24-Point Continuous Monitor
4.3.1 System Display Area
The System Display Area displays information about all of the points in the Ver tex System. Each of the 72 blocks in the System Displa y Area represents one point. A group of eight blocks represents an analyz er b lock. The analyzer block has the status bar indicator at the top of the block. A pyrolyzer displays as a blue block in slot 1 and points detail in slot 2.
The System Display Area positions the modules in the same order in which they are ph ysically located in monitor. The currently selected point displays a green border. If more than one point has the same gas location as the selected point, all points in same location display with green border.
Universal Chemcassette Analyzer
Section 4 - Operation 4-4
System Display
Page 81
Vertex MTM 24-Point Continuous Monitor
Status Indicators
The indicator displays brief information about analyzer status such as faults, warnings or maintenance functions in process.
Point 1
Point 2
Point 3
Point 4
Point 5
Point 6
Point 7
Point 8
Status indicators include:
IDLE - the analyzer is not monitoring or performing maintenance
MONT - the analyzer is monitoring
LD CC - Load Chemcassette® routine is in progress
PROG - a new application program is being loaded into the analyzer
CONF - a new configuration is being loaded into the analyzer
COMF - a communications failure between the DAq and the analyzer
PYRO-W - a pyrolyzer analyzer is warming up. When pyrolyzer has reached stable temperature, it will automatically go into monitor
The Vertex System displays only the short names of the location and target gases within each point block. During normal monitoring, the background color of each block is white. Vertex will change the background color of a point as conditions change.
White Normal operation.
Blue
Grey
Red
Alarms for the point are disabled in
the runtime options menu.
Point is disabled in the runtime menu
or is disabled due to a fault.
Gas concentration exceeded an
alarm level.
Purple Disable configuration alarm
Black
Point is not configured for
monitoring.
Table 4-1.
Alarm Indicators
When the target gas concentration for a point reaches a preset alarm level, Vertex will display a W, 1 or 2 in the point block to indicate the severity of the alarm.
Alarm
Indicator
W (if enabled) Lower Detectable Limit (LDL)
1 Alarm Level 1 2 Alarm Level 2
Concentration Threshold
See Section 3.6.4 Configure Point for information on setting Alarm Level 1 and Alarm Level 2.
See Section 3.6.10 Other Menu for information on alarm default values.
FLOW - a flow Auto Balance procedure is in process on the analyzer
Section 4 - Operation 4-5
Page 82
Vertex MTM 24-Point Continuous Monitor
Pump Status Indicator
The Vertex Display includes pump status indicators in the top right corner. The bottom row indicates which of the pumps is currently operating. The indicator will display “ON” with a green background if the pump is operating and “OFF” on a white background if the pump is not running.
The top row indicates what is known about pump health. The indicator will display “GOOD” with a green background if the pump has successfully provided proper levels of system vacuum. If the Indicator displays “BAD” on a red backg round, this indicates that pump related faults 112 or 219 have been generated. The indicator may display “UNKNOWN” on a white background after software is installed or after analyz ers are added or moved into a different location.
Pumps in the “UNKNOWN” or “BAD” state change to the “GOOD” state only when successfully used during gas monitoring. After a f ailed pump has been repaired or replaced, it can be exercised by pressing “PUMP ALTERNATE” button while monitoring. See Section
4.6.2 Flow Calibration. If successful, the pump state
will change to “GOOD”. Honeywell Analytics recommends that pumps be
alternated periodically to insure availability according to your facility’s schedule.
Pump Health
Indication
Pump Status Indicator
Pump Operation
Indication
Section 4 - Operation 4-6
Page 83
Vertex MTM 24-Point Continuous Monitor
Fault Indicators
In addition to changing color, an event window opens indicating a new event. A yellow square inside the status bar in the analyzer block indicates an analyzer-specific fault. A yellow square inside of the point block indicates a point-specific fault.
See Section 6.3 Maintenance Faults
See Section 6.5 Information Events
M - Indicates a maintenance fault
F - Indicates an instrument fault
Section 4 - Operation 4-7
Page 84
Vertex MTM 24-Point Continuous Monitor
4.3.2 Point Detail Display Area
The Point Detail Area (see Figure 4-1) displays comprehensive information about each location. Touching a block in the System Display Area displays the current information about a location.
Cong File
User ID
Location
Tier-Slot­Point
Point. Points not needed for monitoring may
The configuration profile file name The name of the current, logged in
user The short name of the sampled
location Points are identified by the tier, slot
and their point number in which the analyzer is installed
be disabled. A disabled point does not trigger alarms
See Section 4.5.4 Event List
See Section 4.5.2 Data Trend
See Section 4.5.1 Event History
Section 4 - Operation 4-8
Figure 4-1.
Page 85
Vertex MTM 24-Point Continuous Monitor
Figure 4-2 is an image of the P oint Detail section of the main Vertex display screen snapshot
Analyzer Points /
Alarms Gas Data
Point Color Legend
The analyzer type
A point may be enabled but the alarm may be disabled
Name of the gas or gases, up to three gases per location
Current concentration for each gas Alarms, if any, for that point and gas. This
field shows “on” or blank. This legend defines the background
colors in the system display area
Note:
A Vertex System equipped with two or more analyzer modules can monitor up to three different gases per location. However, you may not program an analyzer for more than one gas family at a time. When you configure the Vertex System for multiple gases per location, touching a point on the system display area will also change the border on other points monitor­ing the same location. The information for a location displayed in the point detail area will be identical regardless of which point is selected in the system display area.
Section 4 - Operation 4-9
Figure 4-2.
Page 86
Vertex MTM 24-Point Continuous Monitor
4.3.3 Function Buttons
Use the function buttons located under the point detail area to access the following areas.
Menu - Perform runtime changes, flow calibration, maintenance, diagnostics and service functions, edit security settings and configure the system.
Review - View stored historical gas concentration data or events and access ChemCam.
Project - Log in, log out, change passwords, update programs and stop the project (exit Vertex M).
Help - Opens a window to explain the functions of the main screen.
4.4 Project Functions
Use Project functions to log in, log out, change passwords, update programs, restore the keyboard and stop the project (exit Vertex M).
Section 4 - Operation 4-10
Page 87
Vertex MTM 24-Point Continuous Monitor
4.4.1 Log In and Log Out
T o protect the integrity of the system, the V ertex System classifies menus as either open or protected functions. If you require access to a protected menu, you must log in under a user account with permission to use that menu. The V ertex System administrator assigns access to protected functions by setting up user accounts.
See Section 4.6.6 Security Access for more information.
Logging In
Figure 4-3. Login
To log in, choose Main Screen, Project and then Log In. The Login window opens. Enter your user account name and password followed by Enter.
The Vertex System will automatically log out any user after a period of inactivity. The default timeout period is 8 hours. Authorized users may change the timeout setting in the Configuration Menu.
Thirty seconds prior to the end of the timeout per iod, Vertex will warn before logging out a user.
4.4.2 Changing Password
You ma y change your passw ord at anytime. To change your password:
1. Login with old password.
2. Touch Project and then Change Password.
3. Enter old password.
4. Enter new password in both text boxes.
5. Touch Enter.
If both new passw ords are identical, Vertex will accept your new password.
After you log in, the system checks your access privileges. As you use Vertex men us, only the buttons to which you have access will be active. The buttons associated with functions to which you are denied access are dimmed.
A user can choose Logout to select the default user account.
Logging Out
To log out, choose Main screen, Project and then Logout. A Log Out confirmation window appears. Simply click OK to close the window.
Section 4 - Operation 4-11
Figure 4-4. Password Change
Page 88
Vertex MTM 24-Point Continuous Monitor
4.4.3 Updating Program
Contact Honeywell Analytics for details.
4.4.4 Restore OnScreen Keyboard
Use the OnScreen Keyboard button to restore the keyboard if it becomes hidden.
OnScreen
Keyboard
Button
4.4.5 Stopping Project
Use Stop Project to exit the Vertex M program. Touch Project and then Stop Project.
Even though the Vertex M program is not running, individual analyzers continue to monitor and store data in their internal memory.
4.5 Review Functions
Section 4 - Operation 4-12
Use Review functions to view information stored in the Vertex M System database. Available for viewing through the Review menu are:
View currently active events using Event List.
View historical events using Event History.
View historical or real time concentration data through the Data Trend window.
Access ChemCam functionality.
Page 89
Vertex MTM 24-Point Continuous Monitor
4.5.1 Event History
An event is an y action that the V ertex System is required to enter into the database. As events occur , the Vertex System stores the events in a database on the DAq PC. The default database format is Microsoft Access.
Use the Event History Window to sort and filter data in the event log.
Figure 4-5. Event History
Events include but are not limited to:
Alarms and faults
User log in and log outs
Configuration changes
System maintenance
Security changes
Time and date of power up
User comments
The peak concentration during an alarm is reported in the Conc/Data field of the reset event. This supplements the concentration reported in the Alarm event, which is the first concentration reported by the Vertex after an alarm threshold is first exceeded.
Section 4 - Operation 4-13
Each event record contains the following minimum information:
Date and time of the event
Module name
An event message which may include alarm status, user login state or a comment.
Logging station computer name
To view the event log, choose Main Screen, Review and then Event History.
Unless sorted, Ver tex displays events in descending order with the most recent event at the top of the displa y .
Page 90
Vertex MTM 24-Point Continuous Monitor
Sort Options
Sorting arranges data according to the values in one of the sort lists. The default sorting of events is chronologically with the most recent events first.
If the data base is large, the sort may take a while.
Filter Options
Apply filters to find a subset of events in the log. A filtered list displays only the rows that meet the criteria you specify.
Note:
Changes to sort and filter options will not take effect until you press Apply/Refresh.
Section 4 - Operation 4-14
<< >>
Horizontal scroll to show additional fields.
Figure 4-6. Event History
Apply/Refresh
Touch to apply the selected sort or filter or filter options.
Page Up/Page Down
Vertical scroll to show additional records.
Page 91
Vertex MTM 24-Point Continuous Monitor
Print
Display All
Removes filtering.
Figure 4-7. Event History
Section 4 - Operation 4-15
Prints current query. Before printing, note that Event History can be quite long. The “total” figure shows the number of events.
Save
Saves current query to an Access database.
Page 92
Vertex MTM 24-Point Continuous Monitor
Date elds
Defaults to current date. The default range is current date and the previous two weeks.
Maximum Records
Use to limit the number of records to display . V ertex will display up to 10,000 records. The default setting is 500. Use the up and down arrow buttons to increment the value by 100.
Figure 4-8. Event History
Advanced Filter Options-Events
Use to filter on specific alarms, faults or other events.
Section 4 - Operation 4-16
Advance Filter Options
Use the Advance Filter Option buttons located to refine the sort.
Page 93
Vertex MTM 24-Point Continuous Monitor
Figure 4-9. Filter Options
Section 4 - Operation 4-17
Page 94
Select Filter Options-Modules Use to filter events based on specific points, analyzers or other hardware modules.
Figure 4-10. Filter Options
Page 95
Select User ID or Logging station
Use to select a specific Vertex station or operator.
Figure 4-11. Selecting Station or ID
Page 96
Vertex MTM 24-Point Continuous Monitor
4.5.2 Data Trend
Vertex plots gas concentration in the Data Trend window. You may choose multiple points to plot each point a different colored line on the graph. Data displayed in the graph can be either Stored data from the data log or Live (a continuous, real-time display, scrolling right to left).
Data can only be stored if datalogging was selected in the Profile Management Utility screen. A maximum of one year of data can be stored, however faster datalogging rates may require more frequent purging. Stored data shows only concentration (not location names)
Drag a finger across the
TIP
screen to zoom into the area selected
Information for each point appears in the table to the left of the graph.
Figure 4-12. Data Trend
Section 4 - Operation 4-20
Page 97
Vertex MTM 24-Point Continuous Monitor
Use the Properties window (bottom right) to select locations and data to include in the Data Trend. Selection options include the
Y axis data: points to display (to a maximum of 8), the data to display (live or stored) and the time span; and the
X axis data: one, some or all detection values.
Touch Help for additional
TIP
information on using the Properties dialog.
Section 4 - Operation 4-21
Page 98
Vertex MTM 24-Point Continuous Monitor
4.5.3 Optional ChemCam
The Vertex ChemCam option provides a means to observe the stains on the last window of a Chemcassette®
®
tape. It consists of a small video camera located between the Chemcassette The Vertex System records images of the stains in either AutoPicture mode or by a ChemCam Live capture. See Section 3.6.3 Set Analyzer Window for more information.
Note:
Some faint stains may not be visible via the camera.
To use the ChemCam window, touch Main Screen, Review and then ChemCam.
ChemCam Live
Use the ChemCam Live tab to manually save an image to the ChemCam database.
1. Touch the image you have selected for capture. The border around the image will turn green.
2. Enter comments about the image in the Comment text box.
3. Touch Capture. The border on the image will turn red.
4. When the border returns to green, the capture is complete. Choose an additional image to capture or touch Close.
take up reel and the optic head.
Figure 4-13. ChemCam Window
Section 4 - Operation 4-22
Page 99
Vertex MTM 24-Point Continuous Monitor
ChemCam Database
Use the ChemCam Database tab to review, print or delete records in the ChemCam database. The Refresh button updates the window with records stored since the window was opened.
Every record in the database includes the following:
Time and date of capture
Type of capture (manual or automatic)
Analyzer associated with the database entry
Chemcassette® serial number
Computer name
Additional information for records stored by ChemCam AutoPicture includes
Point number which triggered the alarm
Gas concentration at the time of alarm
Unit of measure for the concentration
The alarm level the concentration reached
The location ID
Figure 4-14. ChemCam Database
Section 4 - Operation 4-23
Page 100
Vertex MTM 24-Point Continuous Monitor
4.5.4 Event List
With the Event List, view and ac kno wledge activ e alarms and faults . Vertex M displays the new est e v ent at the top of the list. Scroll through the events with
the Back and More buttons. To select an event as the current event, touch the event. The current event will have a green border.
Reset Current
Clears the active event from the list. If the problem has not been resolved, events will continue to occur.
Ack Current
Acknowledges an operator has seen the current event
Section 4 - Operation 4-24
Reset All
Clears all events from the list. Reset All is not instantaneous. V ertex M may not remove events from the list for several seconds.
Ack All
Acknowledges an operator has seen all of the events
Loading...