Honeywell
VE4000 & VE5000 SERIES
CLASS "A" GAS VALVES
INSTRUCTION SHEET
APPLICATION
These series class A gas valves are used for control and
regulation of gaseous fluids in gas power burners, atmospheric
gas boilers, melting furnaces, incinerators and other gas
consuming appliances
GENERAL
DESCRIPTION
VE4000 Series Gas Valve
The VE series gas valves offer a series of functionalities:
Gas valves, Normally Closed.
CPI switch optional
Gas valves for use with Honeywell V4055, V4062 and
V9055 fluid power actuators.
Relief valves Normally Open.
Adjustable opening characteristics optional
FEATURES
The VExxxxX1xxx series gas valves have a wrench boss
as well on inlet side as on outlet side for pipe fitting
incorporated in the valve housing.
The VExxxxX3xxx and VE5xxxX3xxx series gas valves
are equipped at both sides with mounting holes to adapt a
pilot solenoid valve combination, to allow either internal or
external pilot gas. Furthermore these valves are equipped
with two M6 mounting holes to adapt an A4020A
electronic leak test The VExxxxB series gas valves have
an adjustable flow rate regulator on top of the coil.
For the VE series gas valves a series of field replaceable
connection boxes (including circuits) are available
The VExxxxC series gas valves have adjustments for step
pressure flow rate and opening speed in hydraulic damper
unit on top of the coil.
The VExxxxS series gas valves normally open relief
valves have no option for mounting a CPI switch
The VE5xxxX3xxx series gas valves can be equipped with
a wide range of Honeywell fluid power actuators. These
fluid power actuators are field replaceable.
Subject to change without notice. All rights reserved.
ISTR0018 1602RA-NE
1

MODEL CHART
Options 1000/2000 series internal thread 3000
DN10 / 3/8” VExx10
DN15 / 1/2” VExx15
DN20 / 3/4” VExx20
DN25 / 1” VExx25
DN32 / 1 1/4” VExx32
DN40 / 1 1/2” VExx40
DN50 / 2” VExx50
DN65 / 2 1/2” VExx65 VExx65
DN80 / 3” VExx80 VExx80
DN100 / 4” VEx100
Non regulated ON/OFF (VExxxxAxxxx) Standard Standard
Flow regulator (VExxxxBxxxx) Optional Optional 2)
Adjustable opening and flow regulator
(VExxxxCxxxx)
Motorized opening: ON/OFF
(VE5xxxAxxxx)
Motorized opening: characterized
(VE5xxxCxxxx)
Safety relief valve, ON/OFF, Normally
Open, with or without position
indication switch (VExxxxSxxxx)
1) Except VExx65/VExx80
2) Except VE4100
Optional 1) Not available
Not available VE5065A3xxx
Not available VE5065C3xxx
Optional for:
VE..20
VE..25
4000 series flange connection
VE5085A3xxx
VE5085C3xxx
Not available
Honeywell
2
ISTR0018 1602RA-NE

TECHNICAL
SPECIFICATIONS
VE series solenoid gas valves
VExx10 (DN 10)
VExx15 (DN 15)
VExx20 (DN 20)
VExx25 (DN 25)
VExx32 (DN 32)
VExx40 (DN 40)
VExx50 (DN 50)
VExx65 (DN 65)
VExx80 (DN 80)
VEx100 (DN 100)
VE series suitable for fluid power actuators
VE5065 (DN 65)
VE5080 (DN 80)
VE5100 (DN 100)
Pipe sizes 1000/2000 series
Inlet and outlet G3/8" up to G21/2" internal parallel pipe
thread according ISO 7-1
Pipe sizes 3000/4000 series
Flanged connection DN 65, DN 80 and DN100 according to
DN 16 UNI 2223.
Torsion and bending stress
Pipe connections meet Group 2 according EN 161
requirements.
Ambient temperature
-15 °C ... 60 °C
Supply voltage
24 V, 50/60 Hz 1)*
100-120 V, 50/60 Hz
200-240 V, 50/60 Hz
The applicable voltage is led to the solenoid coil via a
rectified circuit.
1): only for DN10 up to DN50
Operational voltage range
The gas valve will function between 85% and 110% of the
rated voltage
Electrical connection VE4xxx/VE6xxx/VE8xxx
Option 1: Wiring on terminal block on circuit cables entering
box via PG Cable Gland
Option 2: Connection by means of DIN plug on DIN faced
connection located on front cover according to
ISO4400 / DIN EN 175301-803
Electrical connection VE5xxx series
See product literature fluid power actuators
Enclosure VE4xxx/VE6xxx/ VE8xxx
IP 65 when using supplied PG gland and cable
diameter 7 – 13 mm for PG version or using suitable DIN
plug with gasket.
Honeywell
Capacity
See page 7 and 8
Maximum operating pressure
Inlet Maximum operating pressure (mbar)
VE4010/VE6010
VE8010
VE4015/VE6015
VE8015
VE4020/VE6020
VE8020
VE4025/VE6025
VE8025
VE4032/VE6032
VE8032
VE4040/VE6040
VE8040
VE4050/VE6050
VE8050
VE4065/VE6065
VE8065
VE5065
VE4080/VE6080
VE8080
VE5080
VE4100/VE6100
VE5100
200 or 500
200
200 or 500
200
200 or 500
200
200 or 500
200
200 or 500
200
200 or 500
200
200 or 500
200
200 or 500
200
200 or 360
200 or 500
200
200 or 360
200 or 500
200 or 500
3
ISTR0018 1602RA-NE