Honeywell V8944L, V8944B, V8944N, V8943C, V8944C, V8943CN, V4944 User Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
V4943/V8943B,C,N;
V4944/V8944B,C,L,N
Regulating Diaphragm Gas Valves
PRODUCT DATA
FEATURES
• Models are available for natural or liquid petroleum
(LP) gases.
• Valve models L, N are rapid opening (less than six
seconds) and fast closing, and are available for LP and
natural gases, respectively.
• Line voltage with two-wire thermostat or controller is
used with V4943; V8943 is used with 24V thermostat or
controller.
• V4944 is used with line voltage dual-stage thermostat
or controller; V8944 is used with 24V dual-stage
thermostat or controller.
• Slow opening B,C valve models are available for
natural and LP gases respectively.
• Valve closes on power failure; recommended for final
shutoff service.
APPLICATION
The V4943/V8943B and N (single stage) and V4944/V8944B
and N (two stage) are solenoid-operated diaphragm valves
suitable for natural gas only. The V4943/V8943C and
V4944/V8944C and L are solenoid-operated diaphragm
valves suitable for Liquefied Petroleum (LP) gas only. These
valves are used on boilers, unit heaters, duct furnaces,
makeup air and rooftop heaters.
• Valve closing time: 2 seconds maximum at 7 inches wc
inlet pressure.
• Valves rated for 0.5 pound per square inch (psi) (3.4
kPa).
• Leadwires and cover for electrical conduit connections
are provided.
Checkout and Troubleshooting ......................................... 10
Service Information .......................................................... 12
65-0214-08
V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES
SPECIFICATIONS
Models:
All models are solenoid-operated regulating diaphragm gas
valves. Details are shown in Table 1.
Table 1. Model Availability.
Power
Volt ag e
and
Model
V4943B 120V
V4943N1, 1-1/4,
V8943B 24V,(+10%,
V8943C1, 1-1/4LP
V8943N1, 1-1/4,
V4944B 120V
V4944CLP
V4944L1-1/4<6
V4944N1, 1-1/4,
V8944B 24V
V8944C1, 1-1/4,
V8944L1, 1-1/4<6
V8944N1, 1-1/4,
a
Includes natural gas, mixed air-natural gas, LP gas-air.
Frequency
(+10%,
-15%),
60 Hz
-15%)
50/60 Hz
(+10%,
-15%)
60 Hz
(+10%,
-15%)
50/60 hz
Maximum
Current
0.055A6.61, 1-1/4,
0.363A9.01, 1-1/4,
0.077A9.03 to 25Two stage3
0.470A11.33 to 25
Consumption
(VA
Maximum)
Pipe Size
(in.)
1-1/2, 2
1-1/2
1-1/2, 2
1-1/2
1-1/2, 2
1-1/2
1-1/2, 2
Thread
Typ e
NPT0.53.43 to 25Single
Maximum
Operating
Pressure
Opening
Time
(sec.)
<6
3 to 25
<6
Pressure
Regulation
stage
Type of
Gas
Natural
Natural
Natural
LP
Natural
Number
of Lead-
wirespsikPa
a
2
a
a
a
Flow Capacity: See Table 2.
Table 2. V4/8943 and V4/8944 Flow Capacity.
CSA
Certified
1.0 in. pd
Pipe Size
(in.)
11,0001,000,0001,000300
1-1/41,6001,600,0001,600480
1-1/22,3002,300,0002,300780
23,0003,000,0003,000870
Natural
Gas cfh
Btuh per
1000 cfh
Natural
gas
Regulation Capacities
0.64 sp gr Natural Gas
Maximum
cfh
Minimum
cfh
Valve Pattern:Straight-through, non offset.
Valve Body Material:Die-cast aluminum.
Electrical Terminations:1/4 in. (6 mm) spade terminals
(quick connects). Leadwires and cover for electrical conduit
connections are provided.
Valve Closing Time: On power failure, a maximum of
2 seconds at 7 in. wc inlet pressure.
Ambient Temperature Ratings: -40°F to +150°F (-40°C to
+66°C).
Maximum Fluid Temperatures: 150°F (66°C).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
65-0214—082
V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES
CAUTION
Pressure Reference Port Vent: 5/16–24 UNF internal
tapping.
Standard Factory Settings: See Table 3.
Weight:
1 in., 1-1/4 in. valves: 4 lb (1.8 kg).
1-1/2 in., 2 in. valves: 5 lb (2.3 kg).
Dimensions: See Fig. 1.
Table 3. Factory Settings and Regulation Ranges.
Natural Gas (i.e. B, N models)LP Gas (i.e. C, L models)
Firing stages
a
Factory SettingAdj. Range
b
Factory SettingAdj. Range
Low Fire:
Standard Models0.8” wc0.8” to 2” wc1.4” wc1.4” to 4.2” wc
Special Models (Group 1)1.6” wc1.6” to 4.2” wc
Special Models (Group 2)0.8” wc0.8” to 2” wc
Special Models (Group 3)0.8” wc0.8” to 2” wc
High Fire:
Standard Models3.5” wc3” to 4.5” wc10” wc8.8” to 11.5” wc
Special Models (Group 1)3.5” wc3” to 4.5” wc
Special Models (Group 2)3.5” wc1.4” to 4.2” wc
b
Special Models (Group 3)5” wc4.0” to 7” wc
a
V4943 is a single-stage valve, please refer to “High Fire” for spring specifications.
b
Do not adjust or operate valve outside of the specified ranges.
DO NOT adjust or operate valve outside of the
specified ranges. Valve will not regulate or work
properly.
Special Models (Group 3): V4944B1117, V4944B1133, V4944B1158; V4943B1092, V4943B1100, V4943B1118
Approvals:
Underwriters Laboratories Listed: File Number MH1639
CSA Certified: Report Number C2030020 (except those listed as Special Models Group 2 and Special Models Group 3)
Commonwealth of Massachusetts Product Certification Number: G1-12-05-22
Mounting Position:
Standard Position: Upright (horizontal).
NOTE: V4944B1059, V4944N1052 and V4944N1060 can
Accessories:
AT72D Transformer (40 VA) for all 24 Vac models.
204480 Vent Pipe Adapter
be mounted upright to 90 degrees from the
upright on the horizontal axis with respect to the
inlet connection.
365-0214—08
V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES
6-9/16 (167)
FOR 1, 1-1/4
OR
7-3/8 (187)
FOR 1-1/2, 2
SIDE VIEW
6 (152)
6
(152)
TOP VIEW
M23375
ATMOSPHERIC
PRESSURE
REFERENCE
PORT WITH
INTERNAL
VENT LIMITER
OUTLET
PRESSURE
TAP
INLET
PRESSURE
TAP
PRESSURE
REGULATOR
ADJUSTMENT
CAPS
M23376
1 INCH V4/8944B/N REGULATION AREA
0.1
1
10
100
FLOW NATURAL GAS (CFH)
PRESSURE DROP (IN. WC)
100
1000
10000
PO < 2.5 IN.
ANY PO
PO > 2 IN.
Fig. 1. V4943/44 and V8943/44 dimensions in in. (mm).
Gas Valve Sizing
1. Check the burner nameplate for:
a. the type of gas used, and
b. the gas flow capacity. The capacity will be listed in
2. Contact the local gas utility for information regarding:
a. the specific gravity (sp gr) and
b. the Btu per cubic foot (Btucf) for the type of gas used.
3. Find the capacity in cf/h. If the capacity is listed in Btu,
convert to cf/h using the following formula:
4. For gases with specific gravities other than 0.64, multiply
the burner cf/h using the proper conversion factor in
Table 4.
Type of Gassp gr (average)Multiply cfh by
Manufactured0.600.968
Mixed0.701.046
LP-Propane1.531.546
LP-Butane1.981.759
5. Use the corrected burner capacity in cfh when determining the gas valve size in Figs. 2–9.
6. Determine the maximum pressure drop across the valve
and draw a vertical line at this pressure in Figs. 2–9.
British thermal units per hour (Btuh) or in cubic feet
per hour (cfh).
Capacity in cfh = Btuh (burner nameplate)
Btu/cf (gas utility)
Table 4. Gas Conversion Factors.
7. At the point of intersection of the vertical line and the
curve, draw a horizontal line to intersect the flow
(capacity) scale. The point of intersection indicates the
capacity that can be obtained with the maximum
pressure drop.
8. If the capacity at the maximum pressure drop is
insufficient, use the capacity vs. pressure drop curve for
the next larger valve size and repeat steps 6 and 7.
Fig. 2. Capacity vs. pressure drop of Natural Gas
curves for 1 in. valve.
65-0214—084