Honeywell V4297A, V4297A1005, V4297A1013 Product Data

Solenoid Safety Shut-Off Valve

APPLICATION

The V4297A controls gas flow to commercial and industrial burners. The valve is part of the Honeywell Integrated Valve Train System that allows gas train components to be directly bolted together.
V4297A
PRODUCT DATA

FEATURES

• Used with natural or liquefied petroleum (LP) gases.
• V4297A normally closed valves are rated for final shutoff service (safety shutoff).
• One valve body (small) applicable to five pipe sizes:
• 3/4 in. (19 mm), 1 in. (25 mm), 1-1/4 in. (32 mm), 1-1/2 in. (38 mm) and 2 in. (51 mm) pipes.
• Two valves with different capacities:
• V4297A1005: 1 in. (25 mm) internal opening (small capacity).
• V4297A1013: 2 in. (51 mm) internal opening (high capacity).
• Two 1/4 in. NPT upstream and one 1/4 in. NPT downstream pressure taps and plugs.
• Accepts C6097 Pressure Switch mounted directly to flange (upstream pressure tap only).
• NEMA 1 enclosure standard.
• Optional Visual Position Indicator available.
• Unpainted aluminum body.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 6
Wiring ............................................................................... 6
Operation And Checkout .................................................. 7
Troubleshooting ................................................................ 8
Service Information ............................................ ...... ...... .. 8
65-0246-1
SOLENOID SAFETY SHUT-OFF VALVE

SPECIFICATIONS

IMPORTANT
The specifications in this publication do not include normal manufacturing tolerances; therefore, an individual unit may not exactly match the specifications listed. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.
Models:
V4297A1005: small body, 1 in. (25 mm) internal opening
(small capacity).
V4297A1013: small body, 2 in. (51 mm) internal opening
(high capacity).
T yp es of Gas: Gas Train Pipe Size:
1-1/4 in. (32 mm), 1-1/ 2 in. (38 mm), 2 in. (51 mm).
Operating Pressure Rating: Valve Capacities:
Valve Type
Small Flange
Safety Shut-Off (large flow) V4297A1013
Safety Shut-Off (small flow) V4297A1005
a
Ratings at 1 in. (.025 kPa) pressure drop for gas with
0.64 sp gr.
Flow Curves:
Natural, manufactured, mixed or LP only.
3/4 in. (19 mm), 1 in. (25 mm),
Maximum: 5 psi.
See Table 1.
Table 1. Valve Flow Capacities.
Pipe Diameter
(in.)
Flow Capacity
(cfh)
3/4 1190 1 1460 1-1/4 2260 1-1/2 2735 23060 3/4 650 1700 1-1/4 780
See Table 1 and Fig. 1 through 8.
a
100
10
1
PRESSURE DROP (IN. WC)
0.1 100 1,000 10,000 30,000
LEGEND:
FLOW CAPACITY (cfh)
Propane, sp. gr = 1.53. Natural Gas, sp. gr = 0.64.
M16531
Fig. 1. Flow curves for V4297A1005 SSOV
with 3/4 in. (19 mm) pipe adapter.
100
10
1
PRESSURE DROP (IN. WC)
0.1 100 1,000 10,000 30,000
LEGEND:
FLOW CAPACITY (cfh) Propane, sp. gr = 1.53. Natural Gas, sp. gr = 0.64.
M16533
Fig. 2. Flow curves for V4297A1005 SSOV
with 1 in. (25 mm) pipe adapter.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1.
Your local Home and Building Control Sales Office (check white pages of your phone directory).
2.
Home and Building Control Customer Relations Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (800) 328-5111 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0246—1 2
100
100
100 1,000 10,000 30,000
10
1
0.1
PRESSURE DROP (IN. WC)
FLOW CAPACITY (cfh)
M16536
Propane, sp. gr = 1.53. Natural Gas, sp. gr = 0.64.
LEGEND:
100
100 1,000 10,000 30,000
10
1
0.1
PRESSURE DROP (IN. WC)
FLOW CAPACITY (cfh)
M16537
Propane, sp. gr = 1.53. Natural Gas, sp. gr = 0.64.
LEGEND:
10
1
PRESSURE DROP (IN. WC)
0.1 100 1,000 10,000 30,000
LEGEND:
FLOW CAPACITY (cfh)
Propane, sp. gr = 1.53. Natural Gas, sp. gr = 0.64.
M16534
SOLENOID SAFETY SHUT-OFF VALVE
Fig. 3. Flow curves for V4297A1005 SSOV
with 1-1/4 in. (32 mm) pipe adapter
100
10
1
PRESSURE DROP (IN. WC)
0.1 100 1,000 10,000 30,000
LEGEND:
FLOW CAPACITY (cfh)
Propane, sp. gr = 1.53. Natural Gas, sp. gr = 0.64.
M16535
Fig. 4. Flow curves for V4297A1013 SSOV
with 3/4 in. (19mm) pipe adapter.
Fig. 5. Flow curves for V4297A1013 SSOV
with 1 in. (25 mm) pipe adapter.
Fig. 6. Flow curves for V4297A1013 SSOV
with 1-1/4 in. (32 mm) pipe adapter.
3 65-0246—1