V4295A,S; V8295A,S
Solenoid Gas Valves
APPLICATION
The electrically operated V4295A, S and V8295A, S Solenoid
Gas Valves control the flow of natural and LP (liquefied
petroleum) gases.
INSTALLATION INSTRUCTIONS
FEATURES
• V4295A,S are used with 120 Vac controllers;
V8295A,S are used with 24 Vac controllers.
• Models available in Normally Closed and Normally
Open configurations.
• Normally Closed models, for safety shut-off
applications, consist of a direct on/off operator for
opening and closing of the valve.
• Normally Open models, for vent (double block and
bleed) valve applications, consist of a direct electric
on/off operator for closing and opening of the valve.
• Models are suitable for the control of gaseous fluids in
gas consuming appliances according to international
standards.
• Models have 1/4 inch NPT inlet and outlet pressure
taps.
• Models have inlet screen to protect the valve from the
entry of dirt.
These valves are used on atmospheric boilers, commercial
water heaters, roof-top make-up air burners, power burners
and boilers.
SPECIFICATIONS
Models
V4295A Normally Closed (N.C.) Safety shut-off Valve, 120V
V4295S Normally Open (N.O.) Vent Valve, 120V
V8295A Normally Closed (N.C.) Safety shut-off Valve, 24V
V8295S Normally Open (N.O.) Vent Valve, 24V
Type of gas
Air, Natural, Manufactured, Mixed and LP gas.
Valve capacities
Refer to Figures 1 and 2
Valve pattern
Straight through, non-offset
Body Material
Die cast aluminum
Electrical terminations
Screw terminal connections
Valve opening time
Less than 1 second
65-0194-04

V4295A,S; V8295A,S SOLENOID GAS VALVES
Valve closing time
Current draw
Less than 1 second
Maximum operating pressure
3/8 in. through 3 in. pipe sizes: 2 psi
3/8 in. through 2 in. pipe sizes: 5 psi
Normally Closed (N.C.)
Pipe size (inch)
V4295A V8295A
120 Vac 24 Vac
2 psi 5 psi 2 psi
3/8 and 1/2 0.160 A 0.160 A 0.80 A
3/4 and 1 0.160 A 0.200 A 0.80 A
1-1/4 0.340 A 0.550 A 1.60 A
1-1/2 0.300 A 0.550 A 1.70 A
2 0.525 A 0.540 A 2.80 A
2-1/2 0.575 A n/a n/a
3 0.675 A n/a n/a
Normally Open (N.O.)
Pipe size (inch)
V4295A V8295A
120 Vac 24 Vac
2 psi
3/4 and 1 0.160 A 0.80 A
1-1/4 0.340 A 2.40 A
Table 1. Models Available.
Model Voltage/Frequency
Maximum Pressure
Pipe size (inch)
Thread
typepsi mbar
V4295A (N.C.) 110/120 Vac, 50/60 Hz 2.0 140 3/8, 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3 NPT
V4295A (N.C.) 110/120 Vac, 50/60 Hz 5.0 350 3/8, 1/2, 3/4, 1, 1-1/4, 1-1/2, 2 NPT
V4295S (N.O.) 110/120 Vac, 50/60 Hz 2.0 140 3/4, 1, 1-1/4 NPT
V8295A (N.C.) 24 Vac, 50/60 Hz 2.0 140 3/8, 1/2, 3/4, 1, 1-1/4, 1-1/2, 2 NPT
V8295S (N.O.) 24 Vac, 50/60 Hz 2.0 140 3/4, 1, 1-1/4 NPT
Table 2. Capacity in CFH at Pressure Drop of 1-Inch Water Column sp. gr. = 0.64 for V4295A, V8295A (N.C.).
3/8 in. 1/2 in. 3/4 in. 1 in. 1-1/4 in. 1-1/2 in. 2 in. 2-1/2 in.* 3 in.*
2 psi 230 250 645 790 1,450 2,190 3,465 5,070 6,100
5 psi 210 290 610 825 1,950 2,270 3,740 n.a. n.a.
* V4295A only
Table 3. Capacity in CFH at Pressure Drop of 1-Inch
Water Column sp. gr. = 0.64 for V4295S, V8295S (N.O.).
3/4 in. 1 in. 1-1/4 in.
350 420 1,100
65-0194—04 2

6
24
520
4
16
3
12
V4295A,S; V8295A,S SOLENOID GAS VALVES
3 IN.
2-1/2 IN.
2 IN.
28
1
4
0.8
3.2
∆ P (KPA)
∆ P (IN. W.C.)
0.6
2.4
0.5
0.4
0.3
0.2
0.1
2.0
1.6
1.2
1.0
0.8
0.4
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400
3/8 IN.
1/2 IN.
3/4 IN.
1 IN.
1-1/4 IN.
X 100Vg (NATURAL GAS SG 0.64) (CFH) =
1-1/2 IN.
M28666
Fig. 1. Capacity curves for V4295A and V8295A, 2 psi versions.
6
24
520
4
16
3
12
28
1
4
0.8
3.2
∆ P (KPA)
∆ P (IN. W.C.)
0.6
2.4
0.5
0.4
0.3
0.2
0.1
2.0
1.6
1.2
1.0
0.8
0.4
3/8 IN.
1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400
1/2 IN.
3/4 IN.
1 IN.
1-1/4 IN.
X 100Vg (NATURAL GAS SG 0.64) (CFH) =
1-1/2 IN.
2 IN.
M28667
Fig. 2. Capacity curves for V4295A, 5 psi versions.
3 65-0194—04