Honeywell V4120 DATASHEET

NW-6130AS2114
Alwa-KFR
with external threads
Alwa-F-KFR with
flanges
Construction
The Alwa-KFR consists of:
• Y-pattern valve housing with test cock. Available pipe connections see Dimensions and Ordering Information
• Valve insert with backflow preventer
• Handwheel
• Pipe connection (accessory)
• Draining facility (optional)
Materials
• Red bronze housing
•Valve insert made of red bronze and brass
• Cone made of red bronze and plastic
• Closing spring made of stainless spring steel
• Handwheel made of sheet steel, painted red
• O-rings and soft seals made of EPDM
• EPDM seat sealing
• Optional draining facility made of red bronze, brass and
EN0H-1806GE23 R0607 • Subject to change
plastic (VA3401A).
V4120
Alwa-KFR
Shutoff valve with backflow preventer
Product specification sheet
Application
The Alwa-KFR is used as shut-off valve with backflow preventer in potable water installations. The downstream installation is isolated by shutting off the valve with the handwheel. The inte­grated backflow preventer with an opening pressure of ≤ 10 mbar (to DN50) stops water from flowing back through the valve. The valve insert with integrated backflow preventer is avail-able as spare part and fits into all valve housings with dimensions according to DVGW so that normal shutoff valves can be upgraded to shutoff valves with backflow preventer.
Alwa-KFR valves are available with various pipe connections. Alwa-K-KFR valves are equipped with larger external threads specially suitable for connections of various plastic pipes.
Alwa-valves are low noise to DVGW and noise protection regula­tions.
Valves with draining facility allow draining of the system over the valve.
Alwa-KFR are DVGW-certified under certification-no.
NW-6130AS2114.
Special Features
• All parts with contact to the flow made of corrosionresistant materials
• Opening pressure 10 mbar (up to DN 50)
• Permanent easy operation due to isolated spindle
• Maintenance-free spindle sealing with additional back sealing
• Low installation height for sizes DN25 and larger with non­rising spindle
• Cavity-free valve insert
• Draining facility optionally available
Technical Data
Medium Water Operating
temperature Operating pressure max. 16 bar (232 psi) Opening pressure 10 mbar ( up to DN 50)
kv(cv)-value Alwa-KFR Alwa-F-KFR
max. 90°C (194°F)
150 mbar (DN 65 - DN 100)
DN15 5.1 5.1 DN20 10.6 10.6 DN25 17.1 17.1 DN32 29.0 29.0 DN40 35.1 35.1 DN50 64.5 64.5 DN65 88.5 132.0 DN80 129.0 193.0
DN100 251.0
www.honeywell.com 1
V4120 Alwa-KFR
Dimensions
All dimensions in mm umless otherwise
Fig. 1 Alwa-KFR with internal threads to DIN 3502
Fig. 2 Alwa-KFR with external threads Table 2 Dimensions Alwa-KFR with external threads
DN kvs D1 D2 H L SW t
1
15 5.1 R 20 10.6 R
/2"5090652715.0
3
/4"5095753216.3
25 17.1 R 1" 80 125 90 41 19.1
1
32 29.0 R 1 40 35.1 R 1
/4" 80 130 110 50 21.4
1
/2" 80 140 120 55 21.4
50 64.5 R 2" 80 160 150 70 25.7
Table 1 Dimensions Alwa-KFR with internal threads
DN kvs D1 D2 H L
15 5.1 G 3/4"509070 20 10.6 G 1" 50 95 81
1
25 17.1 G 1
/4" 80 125 98
32 29.0 G 1 1/2" 80 130 117
3
40 35.1 G 1 50 64.5 G 2
/4" 80 140 130
3
/8" 80 160 152
65 88.5 G 3" 120 240 205
1
80 129 G 3
/2" 120 265 234
Fig. 3 Alwa-KFR with internal thread on inlet and external thread
on outlet
Fig. 4 Alwa-K-KFR with external threads for plastic pipe
DN kvs D1 D2 D3 H L SW
15 5.1 R 1/2"50G 3/4" 90 71.5 27
3
20 10.6 R 25 17.1 R 1" 80 G 1
/4" 50 G 1" 95 84.5 32
1
/4" 125 102 41
32 29.0 R 1 1/4"80G 1 1/2" 130 122 50
1
40 35.1 R 1 50 64.5 R 2" 80 G 2
/2"80G 1 3/4" 145 134 55
3
/8" 160 160 70
Table 3 Dimensions Alwa-KFR with internal thread on inlet and
external thread on outlet
DN kvs D1 D2 H L
15 5.1 G 1" 50 90 70
1
20 10.6 G 1 25 17.1 G 1
/4"509581
1
/2" 80 125 98
32 29.0 G 2" 80 130 117
1
40 35.1 G 2 50 64.5 G 2
/4" 80 140 130
3
/4" 80 160 152
Table 4 Dimensions Alwa-K-KFR for plastic pipe
2 www.honeywell.com
EN0H-1806GE23 R0607 • Subject to change
Loading...