The V4062 Gas Valve Actuator in combination with a V5055
or V5097 Gas Valve provides three-position control of the
gas supply to commercial and industrial burners.
FEATURES
• When energized, the V4062 Actuator opens the V5055/
V5097 Gas Valve to the low-fire position. The actuator
opens the valve to the fully open position when the
line voltage contacts are made.
• When used with the V5055, V5097 or VE5000 Gas
Valve, the combination is rated for final safety shutoff
service.
• Although the V4062 can be used with all V5055 or
V5097 Valve models, the V5055/V5097B with
characterized guide is recommended for optimum
control and low-fire repeatability
V4062A,B,D
HI-LO-OFF Fluid Power
Gas Valve Actuator
PRODUCT DATA
• The standard model has an opening time of
26 seconds at 60 Hz, or 32 seconds at 50 Hz. A fastopening model is available, with timings of
13 seconds at 60 Hz, or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets
code, standard, insurer requirements.
• Damper shaft models are available with or without
spring return; shaft extends out both sides and rides
in Delrin bushings; used with standard damper crank
arm (part no. 7616BR).
• Red OPEN indicator attached to the actuator stem
shows when the valve is even slightly open; yellow
SHUT indicator on the valve stem shows only when
the gas valve is fully closed.
• Ambient temperature range is -40° to 150°F (-40° to
66°C) for 60 Hz models; -10° to 158°F (23° to 70°C) for
50 Hz and 50/60 Hz models.
• Models available with factory adjusted, fieldadjustable, single-pole-double throw (spdt) auxiliary
switch rated at 1/2 hp (0.37 kW). Auxiliary switch can
be added in the field.
• Low-fire position is adjustable with adjusting wrench,
part no. 135796 (included with the actuator).
• Standard enclosure meets NEMA 1 (IP30) general
purpose requirements.
• V4062/V5055C,E and V4062/V5097C,E combinations
available with a proof-of-closure switch and double
valve seal (valve seal overtravel interlock) to meet
specific code/standard/insurer requirements.
• Model available to be used with series 60 floating
type controller.
• Model available with adjustable maximum flow
switch.
V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR
SPECIFICATIONS
IMPORTANT:
Models:
Electrical Ratings:
120V /60 Hz59.512919.028.0
100V
50/60 Hz
200V
50/60 Hz
The specifications given in this publication do not
include normal manufacturing tolerances.
Therefore, this unit may not exactly match the listed
specifications. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be
expected if those conditions are changed.
V4062A HI-LO-OFF Gas Valve Actuator.
V4062B HI-LO-OFF Gas Valve Actuator, high pressure.
V4062D HI-LO-OFF Gas Valve Actuator with proof-of-
closure switch. Use with V5055/V5097C,E (double
seal) gas valves for valve seal overtravel interlock. Do
not use V4062 with V5034 Valve body.
Standard V4062A,D Actuators (Table 1):
60 Hz, 26 second opening.
50 Hz, 32 second opening.
230V, 50 Hz power supply.
230V, 60 Hz power supply..
74.5143.513.724.8
61.911211.220.5
Fast-opening V4062B Actuators (Table 3):
60 Hz, 13 second opening.
50 Hz, 16 second opening.
Table 3. Fast-opening V4062B Actuators.
Voltage
Frequency
220-240V /50/60 Hz
220-240V /50/60 Hz
a
230V, 50 Hz power supply.
b
230V, 60 Hz power supply.
a
b
OpeningHolding
WVaW Va
76.5150.613.328.8
64.4118.21123.2
Pressure Ratings Of Valve-Actuator Combinations:
See Table 4.
Fast-opening V4062A,D Actuators (Table 2):
60 Hz, 13 second opening.
50 Hz, 16 second opening.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1.Your local Home and Building Control Sales Office (check white pages of your phone directory).
2.Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2099—82
V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR
Table 4. Pressure Ratings of Valve-Actuators Combinations.