Honeywell V4062A, V4062D User Manual

V4062A,B,D
HI-LO-OFF Fluid Power
Gas Valve Actuator
PRODUCT DATA

APPLICATION

a
or V5097 Gas Valve provides three-position control

FEATURES

• When energized, the V4062 Actuator opens the V5055/VE5000/V5097 Gas Valve to the low-fire position. The actuator opens the valve to the fully open position when the line voltage contacts are made.
a
VE5000 is a European manufactured and approved valve for
European use only.
• When used with the V5055, V5097 or VE5000 Valve, the combination is rated for final safety shutoff service.Although the V4062 can be used with all V5055 or V5097 Valve models, the V5055/V5097B with characterized guide is recommended for optimum control and low-fire repeatability.
• The standard model has an opening time of 26 seconds at 60 Hz, or 32 seconds at 50 Hz. A fast-opening model is available, with timings of 13 seconds at 60 Hz, or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets code, standard, insurer requirements.
• Damper shaft models are available with or without spring return; shaft extends out both sides and rides in Delrin bushings; used with standard damper crank arm (part no. 7616BR).
• Red OPEN indicator attached to the actuator stem shows when the valve is even slightly open; yellow SHUT indicator on the valve stem shows only when the gas valve is fully closed.
• Ambient temperature range is -40° to 150°F (-40° to 66°C) for 60 Hz models; -10° to 158°F (23° to 70°C) for 50 Hz and 50/60 Hz models.
• Models available with factory adjusted, field­adjustable, single-pole-double throw (spdt) auxiliary switch rated at 1/2 hp (0.37 kW). Auxiliary switch can be added in the field.
• Low-fire position is adjustable with adjusting wrench, part no. 135796 (included with the actuator).
• Standard enclosure meets NEMA 1 (IP30) general purpose requirements.
• V4062/V5055C,E and V4062/V5097C,E combinations available with a proof-of-closure switch and double valve seal (valve seal overtravel interlock) to meet specific code/standard/insurer requirements.
• Model available to be used with series 60 floating type controller.
• Model available with adjustable maximum flow switch.
a
Gas
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Wiring ............................................................................... 6
Adjustments ...................................................................... 7
Operation .......................................................................... 8
Service and Checkout ...................................................... 8
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
60- 2099- 9
V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

SPECIFICATIONS

IMPORTANT:
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.
Models:
V4062A HI-LO-OFF Gas Valve Actuator. V4062B HI-LO-OFF Gas Valve Actuator, high pressure. V4062D HI-LO-OFF Gas Valve Actuator with proof-of-closure
switch. Use with V5055/V5097C,E (double seal) gas valves for valve seal overtravel interlock. Do not use V4062 with V5034 Valve body.
Electrical Ratings:
Standard V4062A,D Actuators (Table 1):
60 Hz, 26 second opening. 50 Hz, 32 second opening.
Table 1. Standard V4062A,D Actuators.
Vol tage/
Frequency
Opening Holding
WVAWVA
120V/60 Hz 59.5 129 19.0 28.0
100V/50-60 Hz 53.0/42.7 105/80 20.0/17.2 33/29
200V/50-60 Hz 72.01/52.5 160/110 18.4/16.2 28/24
Fast-opening V4062A,D Actuators (Table 2):
60 Hz, 13 second opening. 50 Hz, 16 second opening.
Table 2. Fast-opening V4062A,D Actuators.
Voltage/
Frequency
Opening Holding
WVAWVA
120V/60 Hz 59.5 129 19.0 28.0
220V/50 Hz 84.0 196 17.0 27.0
220V/50 Hz 82.0 180 16.5 26.4
220V-240V; 50-
a
60 Hz
220V-240V; 50-
b
60 Hz
a
230V, 50 Hz power supply.
b
230V, 60 Hz power supply.
74.5 143.5 13.7 24.8
61.9 112 11.2 20.5
Fast-opening V4062B Actuators (Table 3):
60 Hz, 13 second opening. 50 Hz, 16 second opening.
Table 3. Fast-opening V4062B Actuators.
Opening Holding
Voltage/Frequency
220V-240V; 50-60 Hz
220V-240V; 50-60 Hz
a
230V, 50 Hz power supply.
b
230V, 60 Hz power supply.
WVAWVA
a
76.5 150.6 13.3 28.8
b
64.4 118.2 11 23.2
Pressure Ratings Of Valve-Actuator Combinations:
See Table 4.
Auxiliary Switch And Proof-Of-Closure Switch Ratings:
See Table 5.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (800) 328-5111 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2099—9 2
V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR
Table 4. Pressure Ratings of Valve-Actuators Combinations.
a
Closeoff
V4062B Actuator
c
Differential
b
Closeoff
c
Valve
V4062A,D Actuator
Differential
b
psi mbar psi bar psi mbar psi bar
V5055A,C; V5097A,C 3/4 to 3 in. 5 340 15 1 15 1000 15 1
V5055A,C 4 in. 3 200 15 1 5 340 15 1
V5055B, V5097B 3/4 to 3 in. 5 340 15 1 15 1000 15 1
V5055B 4 in. 3 200 5 1 5 340 15 1
V5055D,E, 3/4, 1, 1-1/4, 1-1/2;
5 340 75 5 25 1700 75 5
V5097D 3/4 in. to 2 in.
V5055D,E; V5097D,E 2, 2-1/2, 3 in. 5 340 45 3 15 1000 45 3
a
Use a V4062D (with proof-of-closure switch) with a V5055/V5097C or E (with double seal) for valve seal overtravel interlock.
b
Maximum operating pressure differential.
c
Maximum closeoff pressure without seal leakage. This is the maximum allowable pressure drop to which a valve may be
subjected when fully closed, and is independent of the valve body rating.
Table 5. Auxiliary Switch and Proof-of-Closure
Switch Ratings (1/2 hp [0.37 kW]
a
).
Load 120/v 240V
Full Load 9.8A 4.9A
Locked Rotor 58.8A 29.4A
a
Maximum total connected power to both switches (if used) is 1800 VA.
Mounting:
Mounts directly to V5055/V5097 Valve with two setscrews
positioned 90 degrees apart.
Valve and actuator can be mounted in any position
(multipoise).
NOTE: 220 to 240 Vac, 50/60 Hz models must be mounted
vertically.
Mounting Dimensions: See Fig. 1 and Table 7.
Low-Fire Adjustment: 0.17 inch to 0.64 inch (with respect
to V5055/V5097B Valve) valve stem travel.
NOTE: The low-fire position of the V5055/V5097A,C,D and
E Valves differ from the V5055/V5097B. Check the valve flow curves and match the low-fire position to the burner design and valve application.
Nominal Opening Time:
Standard Models: 26 sec at 60 Hz; 32 sec at 50 Hz. Fast-opening Models: 13 sec at 60 Hz; 16 sec at 50 Hz.
Closing Time: 1 sec maximum
Damper Shaft: 3/8 in. sq (9.5 mm) for use with 7616BR
Damper Crank Arm (not included). Models available with or without damper shaft return spring.
Maximum Damper Shaft Rotation: 52 angular degrees.
Maximum Force: At 2-11/16 in. (68.3 mm) radius for 7616BR
Damper Crank Arm (ordered separately).
NOTE: Damper shaft drives damper crank arm in one
direction only; optional return spring is available on damper shaft to turn damper crank arm in opposite direction. See Table 6.
Table 6. Actuator Torque (With
and Without Return Spring).
V4062 Model
-40°F to +20°F (-40°C to -7°C)
lb N lb N
20°F to 150°F
(-7°C to +66°C)
Without return spring 5 22.2 20 89.0
With return spring 5 22.2 10 44.5
Ambient Operating Temperature Rating:
-40° to 150°F (-40° to 66°C) for 60 Hz models;
-10° to 158°F (-23° to 70°C) for 50 Hz and 50/60 Hz models.
Approvals:
Underwriters Laboratories Inc. Listed: File No. MH1639,
Guide No. YIOZ. Factory Mutual: Approved. International Approval Services (Joint Venture of the
American Gas Association [AGA] and the Canadian Gas
Association [CGA]): Certified 60 Hz models only. Industrial Risk Insurers Acceptable. Some V4062 Actuators are approved as Class A valves in
accordance with EN161: When used with V5055 Valves: Pin: CE-0063AR1359. When used with VE5000 Series Valves: Pin:
CE-0063AP3075.
Accessories:
133568 Auxiliary Switch Bag Assembly. 133569 Proof-of-Closure Switch Bag Assembly. (Must be
used with a V5055/V5097C or E with double seal). 135796 Wrench (included with the actuator). 7616BR Damper Crank Arm (damper arm and clip).
3 60-2099—9