Motorized Zone Valves
Flare Connection Sweat Connection
NPT Connection
V4043 Line Voltage Zone Valves
Two way on-off line voltage valves consist of an actuator motor
and valve assembly for controlling the flow of hot or chilled water.
• Manual opener (on all models, except straight-through, normally
open valves) for valve operation on power failure; valve returns to
automatic position when power is restored.
• All models may be installed without disassembling the valve.
• Compact construction for easy installation.
• Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
• Motor may be replaced without removing the valve body or draining
the system.
• Suitable for heating and cooling applications.
Application: Hydronic Control
Typ e: Two position
Body Pattern: Two-way, Straight-through
Frequency: 60 Hz
Power Consumption: 9.6 VA
Nominal Timing (sec, min): De-energized Position: Normally Closed
Electrical Connections: 18 in. leads (457 mm leads)
Fluid Temperature Range: 40 F to 200 F (5 C to 93 C)
Maximum Ambient Temperature: 125 F (52 C)
Materials
(Body): Brass
(Stem): Stainless Steel
(Seat): Brass
(Packing O-Ring): EPDM rubber
(Ball Plug): Buna-N (NBR) Rubber Ball
Capacity Pipe Size
Product Number
V4043A1002/U 3.5 Cv 3 Kv 1/2 in. DN15 Flare 20 psi 138 kPa Normally
V4043A1010/U 3.5 Cv 3 Kv 1/2 in. DN15 Sweat 20 psi 138 kPa Normally
V4043A1028/U 3.5 Cv 3 Kv 1/2 in. DN15 Flare 20 psi 138 kPa Normally
V4043A1044/U 3.5 Cv 3 Kv 1/2 in. DN15 Flare 20 psi 138 kPa Normally
V4043A1051/U 3.5 Cv 3 Kv 1/2 in. DN15 Sweat 20 psi 138 kPa Normally
V4043A1184/U 1 Cv 0.9 Kv 1/2 in. DN15 Sweat 50 psi 345 kPa Normally
V4043A1259/U 8 Cv 6.9 Kv 3/4 in. DN20 Sweat 8 psi 55 kPa Normally
V4043A1317/U 8 Cv 6.9 Kv 1 in. DN25 Sweat 8 psi 55 kPa Normally
V4043A1689/U 3.5 Cv 3 Kv 1/2 in. DN15 NPT 20 psi 138 kPa Normally
V4043A1697/U 10 Cv 8.6 Kv 1 in. DN25 NPT 6.5 psi 45 kPa Normally
V4043A1705/U 3.5 Cv 3 Kv 3/4 in. DN20 NPT 20 psi 138 kPa Normally
V4043B1000/U 3.5 Cv 3 Kv 1/2 in. DN15 Flare 20 psi 138 kPa Normally Open Spring return to open 120 Vac 0.08A No
V4043B1018/U 3.5 Cv 3 Kv 1/2 in. DN15 Sweat 20 psi 138 kPa Normally Open Spring return to open 120 Vac 0.08A No
V4043B1059/U 3.5 Cv 3 Kv 1/2 in. DN15 Sweat 20 psi 138 kPa Normally Open Spring return to open 240 Vac 0.04A No
Connection
Type
Maximum Closeoff Pressure
Comments: Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water.
Valve designed for cycling (not constantly powered on) applications.
Approvals
Underwriters Laboratories, Inc: UL Listed: File MH11826
Replacement Parts:
802360LA-120V, 60 Hz Replacement motor for V4043, V4044 Zone
Val ves
802360MA-208V, 60 Hz Replacement motor for V4043, V4044 Zone
Val ves
802360NA-220V/50 Hz; 240V/60 Hz Replacement motor for V4043,
V4044 Zone Valves
De-energized
Position Valve Action Voltage
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Spring return to close 120 Vac 0.08A Yes
Spring return to close 120 Vac 0.08A Yes
Spring return to close 208 Vac 0.04A Yes
Spring return to close 240 Vac 0.04A Yes
Spring return to close 240 Vac 0.04A Yes
Spring return to close 120 Vac 0.08A Yes
Spring return to close 120 Vac 0.08A Yes
Spring return to close 120 Vac 0.08A Yes
Spring return to close 120 Vac 0.08A Yes
Spring return to close 120 Vac 0.08A Yes
Spring return to close 120 Vac 0.08A Yes
Current
Draw
(A)
Manual
Opener(Cv) (Kv) inch DN (psi) (kPa)
202 customer.honeywell.com 70-6910