The Verafix-VKE is an lockshield valve for compact radiators
with connection centres of 50 mm. It is used on two-pipe
systems with radiators which have integral valves to regulate
and shut-off individual radiators.
Verafix-VKE is suitable for hot water heating systems.
Verafix-VKE with 1/2" internal threads are suitable for radiators
which include the following makes:
BemmFinimètalNorthorSuperia
ConceptFerroliPurmoThor
Dia-NormHenradRadsonVEHA
Dia-thermKoradoSchäferVogel & Noot
DuraManautStelrad
Design
The Verafix-VKE consists of:
• Straight valve body for floor connection or angle valve body
for wall connection
• Ball valve insert
• Radiator connection nuts
• Universal externally threaded connections (Eurotaper
connections) suitable for copper, precision steel tube,
plastics and composite tube (see accessories for external
thread fittings)
Materials
• Hot-forged brass body
• Brass nickel ball valve insert
• EPDM O-ring sealings
• Brass union connections
• Brass radiator connection nuts
• Seat sealings PTFE
• EPDM seals
Verafix-VKE with 3/4" external threads are suitable for radiators
which include the following makes:
BaufaBuderusKermiRibe
BrötjeDe LonghiReuschRIOPanel
Brugman
Features
• Optional flow direction. Performance values apply for
both directions of flow
• Robust brass housing
• Connection on pipework side 3/4" external thread for
copper, soft steel, plastic and composite pipes
• Connectors on radiator side 1/2" internal or 3/4" external
thread
Specifications
MediumWater
ph-value8...9.5
Operating temperaturemax. 120°C (248°F)
Operating pressuremax. 10.0bar (145psi)
kv(cv)-value
Straight
Angle
3.5
1.8
Honeywell y Subject to changeEN0H-2208GE25 R0807
Page 2
V2496 VERAFIX-VKE
Function
The supply and return of the radiator can be shut-off by turning the ball valve inserts of the Verafix-VKE to the horizontal position
with a screwdriver. The valves are supplied set fully open.
Dimensions
Fig. 1. Dimensions Verafix-VKE angle
with flat seal and cone
Fig. 3. Dimensions Verafix-VKE straight
with flat seal and cone
NOTE: All dimensions in mm unless stated otherwise.
Ordering Information
Table. 1. Dimensions and OS-Nos (OS=Ordering System)
TypePipe connectionRadiator
connection
Angle (wall connection) flat seal
and cone
Angle (wall connection) flat seal
and double nippel
Straight (floor connection) flat seal
and cone
Straight (floor connection) flat seal
and double nippel
3
/4” external
3
/4” external
3
/4” external
3
/4” external
3
/4” external151.8V2496EX020A
1
/2” internal151.8V2496EY015A
3
/4” external153.5V2496DX020
1
/2” internal153.5V2496DY015
Fig. 2. Dimensions Verafix-VKE angle
with flat seal and double nippel
Fig. 4. Dimensions Verafix-VKE straight
with flat seal and double nippel
DNkvs(cv)-
OS-No.
value
Honeywell y Subject to change2EN0H-2208GE25 R0807
Page 3
V2496 VERAFIX-VKE
Accessories
Connections for copper and soft steel pipe (2 pcs.)
3/4" x 10 mmVA7200A010
3/4" x 12 mmVA7200A012
3/4" x 14 mmVA7200A014
3/4" x 15 mmVA7200A015
3/4" x 16 mmVA7200A016
3/4" x 18 mmVA7200A018
Connection for copper pipe (2 pcs.)
3/4" x 10 mmOT114M-3/4B
3/4" x 12 mmOT114M-3/4C
3/4" x 14 mmOT114M-3/4D
3/4" x 15 mmOT114M-3/4E
3/4" x 16 mmOT114M-3/4F
3/4" x 18 mmOT114M-3/4H
Connection for PE-X pipe (2 pcs.)
3/4" x 14 x 2 mmOT112M-3/4D
3/4" x 16 x 2 mmOT112M-3/4F
3/4" x 16 x 2,2 mmOT112M-3/4F2
3/4" x 17 x 2 mmOT112M-3/4G
3/4" x 18 x 2 mmOT112M-3/4H
Connection for composite pipe (2 pcs.)
3/4" x 14 x 2 mmOT113M-3/4D
3/4" x 16 x 2 mmOT113M-3/4F
3/4" x 18 x 2 mmOT113M-3/4H
Installation Example
Double nippel (2 pcs.)
for all V2496VS3296A015
Flat seal
for all V2496VA5096A015
Flat seal and cone (2 pcs.)
for all V2496VA5096B015
Fig. 5. Two-pipe system with distribution manifold and Verafix-VKE
Please Note:
• To avoid stone deposit and corrosion the composition of the
medium should conform with VDI-Guideline 2035
• Additives have to be suitable for EPDM sealings
• System has to be flushed thoroughly before initial operation
with all valves fully open
• Any complaints or costs resulting from non-compliance with
above rules will not be accepted by Honeywell
• Please contact us if you should have any special requirements or needs