V2480 - Verafix Design
Thera Design Edition - Lockshield Valve
WITH HIGH QUALITY SURFACE FOR DESIGN RADIATORS
PRODUCT DATA
Application
The new Thera Design Edition is particularly styled for use with
design radiators. With their high class appearance they perfectly fit to all kinds of ambients.
Verafix Design lockshield valves are used to connect radiators
and other heat exchangers to heating circuits of hydronic heating systems. They are installed at the return port of the radiator
and offer a shutoff function to separate the radiator from the
Angle
Straight
heating circuit, for example for renovating.
Features
• Perfect finishing with high quality surface in chrome or
white (RAL9016)
• Varius versions in angle, straight and double angle
available to fit a visual appealing installation
• Including a chromed tail piece with integrated O-ring
•Pre-settable
• Connection to all types of pipework
Double angle right
Double angle left
Design
The Verafix design tlockshield valve consists of:
• Valve housing PN10, DN15 with
• external thread connection on inlet
• external thread connection with union-nut and radiator tailpiece on outlet
• Pre-settable valve insert
• Protection cap
Materials
• Valve housing made of brass with chrome or white (RAL
9016) surface
• Valve insert made of brass with EPDM O-rings and soft seals
and stainless steel spindle
• Protection cap made of brass with chrome or white (RAL
9016) surface
• Union-nut and tailpiece made of chrome plated brass with
EPDM O-ring
Specifications
Medium Water or water-glycol mixture,
quality to VDI 2035
pH-value 8…9,5
Operating temperature 2...130°C (36...266°F)
Operating pressure PN10
Differential pressure max. 1 bar (14.5 psi) –
max. 0.2 bar (2.9 psi) recommended
for quiet operation
kv(cv)-value 1.18 (1.38)
Honeywell y Subject to change EN0H-2109GE25 R0408
THERA DESIGN EDITION - LOCKSHIELD VALVE
Function
The Verafix Design connects the return of a radiator or heat exchanger to the heating loop and has the functions regulation
and shutoff.
Regulation:
The flow can be regulated by pre-setting the valve to a certain
value derived from the flow diagrams.
Application Examples
Please Note:
• To avoid stone deposit and corrosion the composition of the
medium should conform with VDI-Guideline 2035
• Additives have to be suitable for EPDM sealings
• System has to be flushed thoroughly before initial operation
with all valves fully open
• Any complaints or costs resulting from non-compliance with
above rules will not be accepted by Honeywell
• Please contact us if you should have any special requirements or needs
Fig. 1. Angle version Fig. 2. Straight version Fig. 3. Double angle version
EN0H-2109GE25 R0408 2 Honeywell y Subject to change