Honeywell V2467 PRODUCT DATA

V2467
Verafix-EK-MES
LOCKSHIELD VALVE-SETS FOR COMPACT RADIATORS
PRODUCT DATA
Application
The Verafix-EK-MES is a set of one control valve and one measuring valve. They are used to connect compact radiators and universal radiators to heating loops in two-pipe heating systems.
The Verafix-EK-MES offers shutoff, pre-setting, measuring, draining and filling function. With Verafix-EK-MES it is possi­ble to measure the flow on the measuring valve and at the same time to throttle the flow on the control valve or a possi­ble pre-settable radiator TRV insert.
It doesn’t matter which valve is installed in the supply or re­turn as both valves have optional flow direction. If the meas­uring valve is installed in the supply the measuring ins t rument has to be connected inversely, though.
One Verafix-EK-MES is required to connect a radiator to the heating loop.
Design
The sets are made up of:
Valve housing PN10, DN15, valve inlet with external
Valve insert
Cap
Union-nut, partly with tailpiece. Suitable for radiators with
G 3/4” external threads or R 1/2” internal threads
Materials
Valve housing made of nickel-plated red bronze RG5
according to DIN 1705
Valve insert made of brass with EPDM O-rings
Cap made of nickel-plated brass with PTFE sealing
Union-nut and tailpiece made of brass, union-nut addition-
ally nickel-plated
Features
• Offers pre-setting, measuring, shutoff, draining and
filling function
• Measuring and pre-setting at the same time
• Draining and filling by means of draining adapter with
3/4" hose connection
• Optional flow direction
• Valve housing made of corrosion-resistant red bronze
• Available with various radiator connections
Specifications
Medium pH-value Operating temperature Operating pressure
-values
k
vs
Heating water
8...9,5 max. 130°C (266°F) max. 10 bar (145 P.S.I)) 1,7 (pre-setting valve, angle) 1,45 (pre-setting valve, straight) 0,2/1,0 (measuring valve, angle) 0,2/0,9 (measuring valve, straight)
Copyright © 2001 Honeywell AG • All rights reserved EN0H-190GE25 R0101
VERAFIX-EK-MES
Function
The flow through the radiator is throttled by pre-setting the flow rate. Pre-setting can either be done at the control valve or at a possible pre-settable radiator TRV insert.
To pre-set the control valve proceed as follows:
Shutoff valve with 4 mm Allan key.
Turn limiting ring clockwise to stop with screwdriver.
Turn limiting ring anti-clockwise number of turns as per
flow diagram on page 4.
Open valve as far as possible with 4 mm Allan key.
The valve is now pre-set. Pre-setting is retained even when valve is shutoff, e.g. to remove the radiator.
Dimensions
Optionally a measuring device can be connec ted to the measuring valve to control the flow or pre-set the control valve according to actual flow. Measuring is done when sys­tem is operating. The Verafix-MES-adapter is required to connect a measuring device to the valve – see ‘Accessories’ further below.
The radiator is shutoff from the heating loop by turning the valve inserts of both valves clockwise as far as possible. The radiator can be drained or filled over the Verafix-EK-MES by using the draining adapter (accessory).
Verafix-EK-MES are supplied set fully open.
Fig. 1. Angle 3/4” to 1/2” external thread Fig. 2. Angle 3/4” external to 3/4” internal thread
Fig. 3. Straight 3/4” to 1/2” external thread Fig. 4. Straight 3/4” external to 3/4” internal thread
NOTE: All dimensions in mm unless stated otherwise.
Ordering Information
Table 1. Ordering information and OS-Nos. (OS = Ordering System)
Type DN valve inlet valve outlet kvs-value OS-No.
Angle 15 3/4" external 1/2" external 1,70 V2467EX020 Angle 15 3/4" external 3/4" internal 0,2/1,0 V2467DY015 Straight 15 3/4" external 1/2" external 1,45 V2467DX020 Straight 15 3/4" external 3/4" internal 0,2/0,9 V2467DY015
EN0H-190GE25 R0101 2 Honeywell AG • All rights reserved