Honeywell V2440, V2430 PRODUCT DATA

V2430, V2440 Veramax

PRE-SETTABLE HIGH FLOW LOCKSHIELD VALVES

PRODUCT DATA

Compact Angle

Angle

Straight

Design

The lockshield valve consists of:

Valve housing PN10, DN15, 20 or 25 with

internal thread connection to DIN2999 (ISO7) on inlet

external thread connection to DIN/ISO228 with union-nut and radiator tailpiece on outlet

Valve insert

Protection cap

Materials

Valve housing made of nickel-plated red bronze

Valve insert made of brass with EPDM seals

Cover cap made of brass with PTFE sealing ring

Union-nut and tailpiece made of nickel-plated brass

Application

The Verafix is a pre-settable radiator lockshield valve for the supply or return of radiators or heat exchangers. It is used

in gravity heating systems

in two-pipe systems with high flow rates

in one-pipe heating systems

for shutoff and regulation of individual radiators or heat exchangers.

The Veramax is suitable for hot water or low pressure steam heating systems and cold water cooling systems.

Features

For high flow rates

Retainable pre-setting, independent of shutoff process

Pre-setting and shutoff with one valve

Pre-settable by stroke limitation

Optional flow direction. Performance values apply for both directions

Piston externally O-ring sealed

Robust corrosion-resistant red bronze housing

Connection to all types of DN15...DN20 pipework and to DN25 threaded pipework

Specifications

Medium

Water, water-glycol mixture

 

Low pressure steam

 

Quality to VDI2035

Operating temperature

Water:

2...130°C (36...266°F)

 

Steam:

max. 110°C (230°F)

Operating pressure

Water:

max. 10.0 bar (145 psi)

 

Steam:

max. 0.5 bar (7.3 psi)

kvs(cv)-values

Compact angle 5.0 (5.85)

 

Angle

7.0 (8.19)

 

Straight

5.0 (5.85)

Honeywell y Subject to change

EN0H-2203GE25 R1106

Honeywell V2440, V2430 PRODUCT DATA

V2430, V2440 - VERAMAX

Function

The Verafix connects the return of a radiator or heat exchanger to the water loop and has the functions regulation and shutoff.

Regulation:

The flow can be regulated by pre-setting the Verafix to a certain value derived from the flow diagrams. By pre-setting, the opening between valve insert and valve seat is reduced. In this way the flow is throttled.

The Verafix is supplied set fully open. Shutoff:

The return of the radiator can be shutoff by closing the valve insert.

Identification

Compact angle (V2430): Red bronze coloured body with hexagon cap..

Angle and Straight (V2440); Red bronze coloured body with collar and cap with hexagon cap.

Please Note:

To avoid stone deposit and corrosion the composition of the medium should conform with VDI-Guideline 2035

Additives have to be suitable for EPDM sealings

System has to be flushed thoroughly before initial operation with all valves fully open

Any complaints or costs resulting from non-compliance with above rules will not be accepted by Honeywell

Please contact us if you should have any special requirements or needs

Dimensions and Ordering Information

l

L

Fig. 1. Compact angle (V2430)

Fig. 2. Angle (V2440E)

 

Fig. 3. Straight (V2440D)

 

Table 1. Available versions and OS-Nos (OS=Ordering System)

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

DN

Pipe connection

kvs(cv)-value

 

Dimensions in mm

 

OS-No.

 

L

I

H

 

h

 

 

 

 

 

 

 

Compact angle (Fig.1)

15

Rp 1/2"

 

5.0 (5.85)

58

29

30

 

26

V2430E0015

Angle (Fig.2)

15

Rp 1/2"

 

7.0 (8.19)

60

32

38

 

30

V2440E0015

 

20

Rp 3/4"

 

7.0 (8.19)

67

36

38

 

34

V2440E0020

 

25

Rp 1”

 

7.0 (8.19)

74

42

39

 

38

V2440E0025

Straight (Fig.3)

15

Rp 1/2"

 

5.0 (5.85)

96

68

46

 

V2440D0015

 

20

Rp 3/4"

 

5.0 (5.85)

105

74

46

 

V2440D0020

 

25

Rp 1”

 

5.0 (5.85)

122

90

47

 

V2440D0025

NOTE: All dimensions in mm unless stated otherwise.

Installation Examples

Fig. 4. Installation example heating system

Fig. 5. Installation example radiator

EN0H-2203GE25 R1106

2

Honeywell y Subject to change

Loading...