Honeywell V2250, V2260, V2240, V2230 PRODUCT DATA

M
N
G
G
E
R
Y
M
N
A
Internal threads
V2230, V2240, V2250, V2260
Thermostatic Distribution Valves
THERMOSTATIC VALVES FOR DISTRIBUTION SYSTEMS
PRODUCT DATA
Application
Together with a radiator thermostat Thermostatic Distribution Valves are used to control temperature in one- or two-pipe distribution systems. They are used in combination with an F type Distribution Valve and/or a Verafix lockshield valve.
M
N
G
W
G
E
R
Y
M
N
A
The valve can be shutoff with the protection cap, or later with the radiator thermostat (not supplied with the valve).
By using distribution valves connections under the floor or in the wall are avoided.
Internal threads with
M
N
G
G
E
R
Y
M
N
A
External threads
injection lance
M
N
G
W
G
E
R
Y
M
N
A
External threads with injection lance
Design
The flowshare valve consists of:
• Valve housing PN10, DN15
• with external threads, or
• with internal threads to DIN2999 (ISO7) for threaded pipe or copper/precision steel pipe 10...18 mm using compres­sion pipe fittings (see ‘Accessories’)
• Thermostatic valve insert
• Union-nut and radiator tailpiece
• Colour protection cap
Materials
• Valve housing made of nickel-plated brass
• Valve insert made of brass with EPDM O-rings and soft seals and stainless steel spindle
• Union-nut and tailpiece made of brass, union-nut nickel­plated
• Protection cap made of plastic
Features
• No connections under the floor necessary
• Shutoff does not affect other radiators in the loop
• Installation in supply or return (observe flow direction)
• Valve seat can be cleaned and/or valve insert replaced without draining the system
• Available with R 1/2" internal or G 3/4" external threads
Specifications
Medium Heating water, water quality to
VDI2035
pH-value 8...9.5
Operating temperature max. 130°C (266°F)
Operating pressure max. 10 bar (145 psi)
Differential pressure max. 1 bar (14.5 psi) –
max. 0.2 bar (2.9 psi) recommended for quiet operation
kvs-values* two-pipe 0.14 (0.16)
0.36 (0.42)
0.62 (0.73)
0.80 (0.94)
one-pipe 1.70 (1.99)
Radiator proportion 50 % (one pipe)
Thermostat connection M30 x 1.5
Closing dimension 11.5 mm
Stroke 2.5 mm
NOTE: Protection cap is colour-coded for easy identification
Honeywell y Subject to change EN0H-2402GE25 R1206
V2230, V2240, V2250, V2260 THERMOSTATIC DISTRIBUTION VALVES
Function
Thermostatic radiator valves enable individual control of room temperature and thus save energy.
The TRV body is controlled by the radiator thermostat. Air from the room passing over the sensor of the radiator thermostat causes the sensor to expand when the temperature rises. The sensor acts onto the valve spindle and this causes the TRV
body to close. When the temperature falls the sensor contracts and the spring-loaded valve spindle is opened. The TRV opens in proportion to the temperature of the sensor. Only the amount of water required to maintain the room temperature set on the radiator thermostat can flow into the radiator.
Dimensions and Ordering Information
Fig. 1. External threads version Fig. 2. External threads version with injection lance
Fig. 3. Internal threads version Fig. 4. Internal threads version with injection lance
NOTE: All dimensions in mm unless stated otherwise.
Please Note:
• To avoid stone deposit and corrosion the composition of the medium should conform with VDI-Guideline 2035
• Additives have to be suitable for EPDM sealings
• System has to be flushed thoroughly before initial operation with all valves fully open
• Any complaints or costs resulting from non-compliance with above rules will not be accepted by Honeywell
• Please contact us if you should have any special require­ments or needs
EN0H-2402GE25 R1206 2 Honeywell y Subject to change
Loading...
+ 2 hidden pages