Together with a radiator thermostat Thermostatic Distribution
Valves are used to control temperature in one- or two-pipe
distribution systems. They are used in combination with an F
type Distribution Valve and/or a Verafix lockshield valve.
M
N
G
W
G
E
R
Y
M
N
A
The valve can be shutoff with the protection cap, or later with
the radiator thermostat (not supplied with the valve).
By using distribution valves connections under the floor or in
the wall are avoided.
Internal threads with
M
N
G
W
G
E
R
Y
M
N
A
External threads
injection lance
M
N
G
W
G
E
R
Y
M
N
A
External threads with
injection lance
Design
The flowshare valve consists of:
• Valve housing PN10, DN15
• with external threads, or
• with internal threads to DIN2999 (ISO7) for threaded pipe
or copper/precision steel pipe 10...18 mm using compression pipe fittings (see ‘Accessories’)
• Thermostatic valve insert
• Union-nut and radiator tailpiece
• Colour protection cap
Materials
• Valve housing made of nickel-plated brass
• Valve insert made of brass with EPDM O-rings and soft seals
and stainless steel spindle
• Union-nut and tailpiece made of brass, union-nut nickelplated
• Protection cap made of plastic
Features
• No connections under the floor necessary
• Shutoff does not affect other radiators in the loop
• Installation in supply or return (observe flow direction)
• Valve seat can be cleaned and/or valve insert replaced
without draining the system
• Available with R 1/2" internal or G 3/4" external threads
Specifications
MediumHeating water, water quality to
VDI2035
pH-value8...9.5
Operating temperature max. 130°C (266°F)
Operating pressuremax. 10 bar (145 psi)
Differential pressuremax. 1 bar (14.5 psi) –
max. 0.2 bar (2.9 psi) recommended
for quiet operation
kvs-values*two-pipe0.14 (0.16)
0.36 (0.42)
0.62 (0.73)
0.80 (0.94)
one-pipe1.70 (1.99)
Radiator proportion50 % (one pipe)
Thermostat connection M30 x 1.5
Closing dimension11.5 mm
Stroke2.5 mm
NOTE: Protection cap is colour-coded for easy identification
Honeywell y Subject to changeEN0H-2402GE25 R1206
V2230, V2240, V2250, V2260 THERMOSTATIC DISTRIBUTION VALVES
Function
Thermostatic radiator valves enable individual control of room
temperature and thus save energy.
The TRV body is controlled by the radiator thermostat. Air from
the room passing over the sensor of the radiator thermostat
causes the sensor to expand when the temperature rises. The
sensor acts onto the valve spindle and this causes the TRV
body to close. When the temperature falls the sensor contracts
and the spring-loaded valve spindle is opened. The TRV opens
in proportion to the temperature of the sensor. Only the amount
of water required to maintain the room temperature set on the
radiator thermostat can flow into the radiator.
Dimensions and Ordering Information
Fig. 1. External threads versionFig. 2. External threads version with injection lance
Fig. 3. Internal threads versionFig. 4. Internal threads version with injection lance
NOTE: All dimensions in mm unless stated otherwise.
Please Note:
• To avoid stone deposit and corrosion the composition of the
medium should conform with VDI-Guideline 2035
• Additives have to be suitable for EPDM sealings
• System has to be flushed thoroughly before initial operation
with all valves fully open
• Any complaints or costs resulting from non-compliance with
above rules will not be accepted by Honeywell
• Please contact us if you should have any special requirements or needs
EN0H-2402GE25 R12062Honeywell y Subject to change
V2230, V2240, V2250, V2260 THERMOSTATIC DISTRIBUTION VALVES
Table 1. Available versions and OS-Nos (OS=Ordering Specification)
Body typeDNkvs(cv)-valuesProtection capOS-No.
Thermostatic Distribution Valves for two-pipe systems
External threads with injection lance150.14redV2260XK315
External threads with injection lance150.36blueV2260XK415
External threads with injection lance150.62blackV2260XBB15
External threads with injection lance150.80greenV2260XK515
Internal threads with injection lance150.14redV2260YK315
Internal threads with injection lance150.36blueV2260YK415
Internal threads with injection lance150.62blackV2260YBB15
Internal threads with injection lance150.80greenV2260YK515
Thermostatic Distribution Valves for one-pipe systems
External threads151.70whiteV2230X0015
Internal threads151.70whiteV2230Y0015
External threads with injection lance151.70whiteV2250X0015
Internal threads with injection lance151.70whiteV2250Y0015
Honeywell y Subject to change3EN0H-2402GE25 R1206
V2230, V2240, V2250, V2260 THERMOSTATIC DISTRIBUTION VALVES
Accessories
Connections for valves with external threads
2 Connections for copper and soft steel pipe
3/4" x 10 mmVA7200A010
3/4" x 12 mmVA7200A012
3/4" x 14 mmVA7200A014
3/4" x 15 mmVA7200A015
3/4" x 16 mmVA7200A016
3/4" x 18 mmVA7200A018
2 External connections for plastic pipe
3/4" x 12 x 2 mmVA7210A012
3/4" x 14 x 2 mmVA7210A014
3/4" x 16 x 2 mmVA7210A016
3/4" x 17 x 2 mmVA7210A017
3/4" x 18 x 2 mmVA7210A018
2 External connections for composite pipe, alpex-therm
3/4" x 14 x 2 mmVA7220A014
3/4" x 16 x 2 mmVA7220A016
3/4" x 18 x 2 mmVA7220A018
NOTE: Processing after technical documentation of the
several companies
Connections for valves with internal threads
Compression ring and nut with support insert (2 pcs each)
1/2" x 10 mmVA621A1510
1/2" x 12 mmVA621A1512
1/2" x 14 mmVA621A1514
1/2" x 15 mmVA621A1515
1/2" x 16 mmVA621A1516
1/2" x 18 mmVA621A1518
NOTE: Support inserts have to be used for copper or soft
steel pipe with 1,0 mm wall thickness
NOTE:
NOTE:
1
without support inserts
2
with 2 adapters
Compression ring and nut with support insert for composite pipe (2 pcs each)
1/2" x 14 mmVA622B1514
1/2" x 16 mmVA622B1516
1
1
2
Manual handwheel cap
Pre-settable, with integrated
VA2200D001
locking device
Floor cover for Ø15, 16 and 18 mm pipe
whiteVA2201B015
Service tool to replace valve insert
for all sizesVA8200A001
Replacement valve insert
KV3 typeVS1200K301
KV4 typeVS1200K401
KV5 typeVS1200K501
Replacement valve insert
BB typeVS1200BB01
Replacement valve insert
UBG typeVS1200UB01
Special tool for assembly of thermostat
VA8210A001
Pressure cap – for shutting off valves on radiator outlet