TC500A-N Commercial Thermostat
CONNECTED DEVICE FOR COMMERCIAL BUILDINGS
Disclaimer
All images used in this document are for illustrative purposes only and may not match the actual product.
APPLICATION
TC500A-N/TC500A-W Thermostat is an advanced, configurable, connected device for commercial buildings. ItcontrolsandmonitorsRTU,AHU,HeatPumpequipment, and their configurations. This device communicates over Wi-Fi,Bluetooth,BACnetIP,Sylk,easilyintegrates withthe building automation system.
The built-in intelligent control algorithms of the device help to achieve the perfect balance between Energy Efficiency and Comfort. The device is packaged with numerous presets suitable for most commercial building requirements that enable the easy and quick initial setup.
The firmware of the device can be upgraded via Wi-Fi network. The device has four universal terminals and a pair of Sylk terminals to connect with sensors or other accessories. It also has a built-in temperature sensor, humidity sensor, and proximity sensor.
PRODUCT DATA
FEATURES
•The device can be easily commissioned through the Honeywell Connect Mobile app.
•Easily customizable and intuitive UI.
•Supports BACnet system schedule and holiday configuration.
•Multiple, configurable, levels of user privilege access for features such as Reminders, Occupancy set points, Date/Time, Schedules, Calendars of special events, remote and local Manual Override, remote and local OccupancyOverride,Choiceoflanguageandunits,and screen lockouts to prevent unauthorized settings changes.
•HighlevelcontrolalgorithmssuchasAuto Changeover, Adaptive Intelligent Recovery, Pre-occupancy Purge, Power up disable time, Freeze protection, and Demand limit controls are supported.
•Settings to switch Fahrenheit to Celsius and vice-versa.
•Allsetpoints arelimited automatically between 40°F to 120°F.
•Auto display sleep to save energy when there is no user action for configured time out.
•A LED indicator to show the operational status of the thermostat when the display goes to sleep mode.
•Real-Time Clock time keeping accuracy with 72 hour retention during power loss.
Equipment Control Features
•5H/3C Heat Pump, 3H/3C Conventional and modulating heat system
•Constant speed Fan, 2-speed Fan, and Variable Speed Fan
•Packaged Economizer Coordination Output
•Multiple Dehumidification and Humidification options
•Servicemodetomanuallycommandtheoutputs totest the operation of the mechanical equipment
•Auto mode to switch between heating and cooling according to the current space temperature
•Staging control, PID Tuning, CPH, OAT Lockout, DAT Lockout, Modulating control
•Demand Limit Control to save energy
•System Switch Options
•Smoke Monitor
TC500A-N COMMERCIAL THERMOSTAT
TECHNICAL SPECIFICATIONS
Power Characteristics
Table 1. Power Characteristics
Power Supply |
Rated voltage: 24VAC |
|
50/60Hz, |
|
Working voltage range: |
|
20-30VAC, UL listed |
|
class-2transformerorIEC |
|
61558 listed transformer. |
Power Consumption |
Max. 8.5VA @ 24VAC |
(Display ON) |
(355mA @ 24VAC) |
Min. Load |
4VA (all BOs OFF, No Sylk |
|
sensor) |
Max. Load |
96VA (all BOs ON) |
Display
|
Table 2. Display |
Display Type |
24 BPP TFT display with |
|
CTP |
Resolutions |
480x480 pixel |
Active Display Area |
4” diagonally |
Backlight |
LCD (Dimmable) |
IO Characteristics
Table 3. IO Characteristics
UIO x 2 |
• |
Resistive Input |
|
|
|
— |
For 10K NTC type II, C7021 |
|
|
|
series |
|
|
— For 10K NTC type III,C7023 |
|
|
|
|
series |
|
|
— For 20K NTC, TR21 and |
|
|
|
|
C7041 series. |
|
• ±0.5°C (±1°F) at 10 – 32°C (50 – |
||
|
|
90°F) |
|
|
• ±1.1°C (±2°F) at -1.1 – 50°C (30 – |
||
|
|
122°F) |
|
|
• |
Voltage Input, SELV |
|
|
|
— 0-10V, ±5% of full scale |
|
|
• |
Digital Input |
|
|
|
— |
Dry contact closure |
|
|
— Open circuit (≥ 100Kohms) |
|
|
|
— |
Closed circuit (≤100ohms) |
|
• |
Voltage Output |
|
|
|
— 0-10V, ±3% of full scale @2K |
|
|
|
|
ohms |
Table 3. IO Characteristics(Continued)
UI x 2 |
• |
Resistive Input |
|
|
|
— |
for 10K NTC type II, C7021 |
|
|
|
series |
|
|
— |
for 10K NTC type III,C7023 |
|
|
|
series |
|
|
— for20KNTC,TR21 andC7041 |
|
|
|
|
series |
|
• ±0.5°C (±1°F) at 10 – 32°C (50 – |
||
|
|
90°F) |
|
|
• ±1.1°C (±2°F) at -1.1 – 50°C (30 – |
||
|
|
122°F) |
|
|
• |
Voltage Input, SELV |
|
|
|
— 0-10V, ±5% of full scale |
|
|
• |
Digital Input |
|
|
|
— |
Dry contact closure |
|
|
— Open circuit (≥ 100Kohms) |
|
|
|
— |
Closed circuit (≤100ohms) |
DO (G, |
• |
Relay Output |
|
Y1,Y2,Y3,W1,W2 |
|
— |
1 Amps Max. at 24VAC |
,W3) |
|
|
|
DO (AUX) |
• |
Relay Dry Contact |
|
|
|
— |
1 Amps Max. at 24VAC/DC |
Operating Environment
Table 4. Operating Environment |
|
Ambient |
32 to 122 °F (0 to +50°C) |
Operating |
|
Temperature |
|
Ambient |
10 to 90% relative humidity (non- |
Operating |
condensing) |
Humidity |
|
Storage |
-40 to 150 °F(-40 to 65.5°C) |
Temperature |
|
Protection |
IP20 |
Class |
|
31-00398M-01 | Rev. 10-20 |
2 |