TB7600 Series Communicating
TB7600 Series
Thermostat
TB7600 Series
Thermostat with
Occupancy Sensor
RTU/Heat Pump Thermostats
FOR COMMERCIAL HVAC APPLICATIONS
SPECIFICATION DATA
advantageous energy savings during occupied hours without
sacrificing occupant comfort. All thermostats are PIR ready
and can be ordered with or without Honeywell occupancy
sensor. The occupancy sensor cover is available to order
separately if a PIR is needed at a later time.
FEATURES
• Available in BACnet MS/TP and ZigBee wireless
protocols
• Backlit LCD display with dedicated function menu
keys for simple operation
• Built in default profile set-up for easier start up and
commissioning
• Fully integrated advanced occupancy functionality
with a PIR accessory cover on some models
• Non-volatile EEPROM memory prevents loss of
parameters during power outage
APPLICATION
The TB7600 Series PI thermostat family is specifically
designed for single stage and multi-stage control of heating/
cooling equipment such as rooftop and self-contained units.
The TB7600 Series are communicating thermostats with
models available in BACnet® MS/TP and ZigBee® wireless
mesh protocols and can be easily integrated into a WEBs-AX
building automation system based on the NiagaraAX®
platform. The product features an intuitive, menu-driven, backlit LCD display, which walks users through the programming
steps, making the process extremely simple. Accurate
temperature control is achieved due to the product’s PI time
proportional control algorithm, which virtually eliminates
temperature offset associated with traditional, differentialbased thermostats.
Depending on the model, up to three remote sensor inputs are
available. All models contain a SPST auxiliary switch, which
can be used to control lighting or disable the economizer
function and a discharge air sensor input. For more advanced
applications, economizer control logic has been integrated
into the thermostat for use with proportional damper
economizer actuators.
Thermostats equipped with an occupancy sensor cover
provide advanced active occupancy logic, which will
automatically switch occupancy levels from Occupied to
Unoccupied as required by local activity being present or not.
This advanced occupancy functionality provides
• Programmable smart fan operation can provide energy
savings during night mode
• Password protection to minimize parameter tampering
• Three levels of keypad lockout to limit access to
change user parameters such as setpoints, system
mode, etc.
• Gas/oil or electric system compatibility for all type of
applications
• SPST auxiliary output can be used for lighting and/or
economizer override
• 0 to 10 Vdc economizer output for more retrofit
opportunities
— Built in dry bulb economizer logic using outdoor tem-
perature sensor
— Input for supply/mixed air temperature sensor
• Support single and two stages heat pump with one
auxiliary heat stage
• Remote indoor averaging sensing with 2, 3, 4, 9 or 16
sensors
• Remote discharge air sensor input
• Automatic frost protection to prevents costly freeze
damage
• Anti short cycle and minimum on/off run time
protection to reduce wear and maximizes life span of
mechanical equipment
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS
• Two programmable digital inputs for added flexibility
can be use to monitor filter status, activate a remote
temporary occupancy switch, and/or used as a general
purpose service indicator
• 7 day programmable models, 2 or 4 events for use in
non-networked applications*
• Six hour reserve prevents the need to reprogram day/
time on programmable models after a power outage on
programmable models
Heat Pump Model Specific Features
• Selectable single or dual stage compressor stages
• High balance point locks out auxiliary heating when
outside air temperature is above set value, low balance
point locks out heat pump compressor operation when
outside air temperature is below the set value
• Comfort/economy mode maximizes heat pump use
before turning on auxiliary heating
• Compressor/auxiliary interlock adds flexibility by
locking out heat pump operation during auxiliary
heating to prevent high pressure trip when the coil is
downstream of the auxiliary heat source
* Use programmable models only when installing as stand-
alone thermostats that may eventually be added to a
WEBs-AX network. When a programmable thermostat is
added to a network, schedules should be applied through
the WEBStation-AX.
More Information
To learn about additional products in this family visit
http://customer.honeywell.com.
• TB7300 Series Communicating Fan Coil Unit Thermostats
Specification Data (Form No. 63-2709).
• TB7200 Communicating Zoning Thermostats Specification
Data (Form No. 63-2708).
• Sensors Product Overview Brochure (Form No. 63-9285)
for a complete listing of compatible sensors.
TB7600 Series Model Selection
Product Number Description Outputs Scheduling
BACnet Models
TB7600A5014B Single Stage RTU 1H/1C No
TB7600A5514B Single Stage RTU 1H/1C No X
TB7600B5014B Multi-stage RTU 2H/2C No
TB7600B5514B Multi-stage RTU 2H/2C No X
TB7600H5014B Heat Pump 3H/2C No
TB7600H5514B Heat Pump 3H/2C No X
TB7605B5014B Economizer RTU 2H/2C No
TB7605B5514B Economizer RTU 2H/2C No X
TB7652A5014B Single Stage RTU 1H/1C Yes
TB7652A5514B Single Stage RTU 1H/1C Yes X
TB7652B5014B Multi-stage RTU 2H/2C Yes
TB7652B5514B Multi-stage RTU 2H/2C Yes X
TB7652H5014B Heat Pump 3H/2C Yes
TB7652H5514B Heat Pump 3H/2C Yes X
TB7656B5014B Economizer RTU 2H/2C Yes
TB7656B5514B Economizer RTU 2H/2C Yes X
Wireless Models
TB7600A5014W Single Stage RTU 1H/1C No
TB7600A5514W Single Stage RTU 1H/1C No X
TB7600B5014W Multi-stage RTU 2H/2C No
TB7600B5514W Multi-stage RTU 2H/2C No X
TB7600H5014W Heat Pump 3H/2C No
TB7600H5514W Heat Pump 3H/2C No X
TB7605B5014W Economizer RTU 2H/2C No
TB7605B5514W Economizer RTU 2H/2C No X
TB7652A5014W Single Stage RTU 1H/1C Yes
TB7652A5514W Single Stage RTU 1H/1C Yes X
TB7652B5014W Multi-stage RTU 2H/2C Yes
1
Occupancy
Sensor
2
63-2706—04 2