Honeywell T834C Installation Instructions Manual

Page 1
T834C Heating and
F S
T
T
0
Cooling Thermostat
INSTALLATION INSTRUCTIONS

APPLICATION

The T834C Thermostat (see Fig. 1) controls 24 to 30 Vac single-stage heating-cooling systems. See Table 1 for application information. An spdt mercury switch makes R to W on a temperature fall for heating, and R to Y on a temperature rise for cooling.
Table 1. T834C Specifications.
Model No. Application Heat Anticipation
T834C For use in standard heating-
AN WITCH
cooling systems.
.18
.9
.7
.2
.5
L
O
N
G
R
E
.3
.25
TEMPERATURE SETTING LEVER
MOUNTING HOLE (THERMOSTAT TO WALL OR OUTLET BOX)
BIMETAL ELEMEN BEHIND SCALE
ADJUSTABLE HEA ANTICIPATOR INDICATOR
SYSTEM SWITCH
MOUNTING HOLE
Fig. 1. T834C internal view.
0.18A to 1.0A, adjustable.
M2118

INSTALLATION

When Installing This Product . . .

1. Read these instructions carefully. Failure to follow
2. Check the ratings given in the instructions and on
3. Installer must be a trained, experienced service
4. After installation is complete, check out the product
Switching
Heat-Off­Cool
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.
them could damage the product or cause a hazard­ous condition.
the product to make sure the product is suitable for your application.
On-Auto 2
technician.
operation as provided in these instructions.
See Fig.
No.System Fan
® U.S. Registered Trademark Copyright © 2003 Honeywell International Inc. • • All Rights Reserved
69-1688
Page 2
T834C HEATING AND COOLING THERMOSTAT
T)
FAN

Location

Locate the thermostat about 5 ft (1.5m) above the floor on an inside wall in an area with good air circulation at average temperature.
Do not mount the thermostat where it can be affected by: — drafts or dead spots behind doors or in corner. — hot or cold air from ducts. — radiant heat from the sun, fireplaces or appliances. — unheated (uncooled) areas such as outside walls
behind the thermostats. This thermostat is a precision instrument and was carefully adjusted at the factory. Handle it carefully.

Wiring and Mounting

CAUTION
Electrical Shock Hazard. Can cause personal electrical shock and equipment damage.
Disconnect power supply before beginning installation.
IMPORTANT
All wiring must comply with local codes and ordinances.
The T834C can be mounted directly on a wall or vertical outlet box:
Use the 209649A (taupe) or 209650A (white)
Universal Cover Plate (ordered separately) to mount
on outlet box or to cover wall marks left by old
thermostat.
If the cover plate is used, review the instructions pro-
vided with it before wiring and mounting the
thermostat.
To wire and mount the thermostat:
1. In replacement applications, check the existing thermostat wires for cracked or frayed insulation. Replace any wires in poor condition. If the wire is plastered into the wall, make a hole next to the wires and loosen the wires so they can be pushed back into the wall later.
2. In new installations, run wiring (if necessary) to the thermostat location.
3. Set the adjustable heat anticipator indicator to match the current draw of the primary heating control or as recommended by the equipment manufacturer (see Heat Anticipator Setting).
4. Connect the wires to the terminals on the back of the thermostat. See Fig. 2 for internal schematic and typical hookup diagram.
5. Remove thermostat cover by pulling outward on right edge of cover until it snaps free of the thermostat base. Carefully remove and discard the foam plastic shipping insert that protects the switch and bimetal assembly during shipping.
6. Push excess wire back through the hole and plug any opening with insulation to prevent drafts that can affect thermostat performance.
7. Loosely fasten the thermostat (with wallplate, if applicable) to the wall or outlet box with a screw through the top mounting hole. Adjust the thermostat so it is approximately level and fasten the second screw through the bottom mounting hole. Do not tighten.
8. For optimum performance, level the thermostat using a spirit level or plumb line. Tighten the mounting screws.
9. Adjust temperature setting lever so mercury bulb is in horizontal position as shown in Fig. 1.
10. Carefully replace the thermostat cover.
IMPORTANT
An incorrectly leveled thermostat causes the temperature control to deviate from setpoint.
SWITCH
H1
69-1688 2
C1
TEMP. FALL
C1 ANTICIPATOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 2. Internal schematic and typical hookup for T834C in standard heating-cooling system.
ON
AUTO
SYSTEM SWITCH
COOL
OFF
HEAT
HEAT OFF COOL
R G
Y
W
FAN RELAY
COOL RELAY
HEAT RELAY
L1 (HO
L2
1
M21181
Page 3

SETTINGS AND ADJUSTMENTS

T834C HEATING AND COOLING THERMOSTAT

Temperature Setting

Push the temperature setting lever to the desired control point on the temperature scale. The same lever controls the temperature setting for either heating or cooling.

System and Fan Switching

The T834C has System and Fan switches to control the heating-cooling systems and fan.
The System switch controls system operation:
Heat: Operates only heating system. Off: Both heating and cooling systems are
disconnected.
Cool: Operates only cooling system.
The Fan switch controls fan operation:
Auto: For gas-or oil-fired systems; the fan operates in
response to the thermostat in cooling and in response to the plenum fan control in heating.
On: The fan runs continuously.
To switch positions, use thumb and index finger to slide lever to desired position. Stop switch lever in detent directly over desired position. Stop switch lever in detent directly over desired function indicator mark for correct circuit operation.

Heat Anticipator Setting

IMPORTANT
The T834C Thermostat has an adjustable heat anticipator and operates correctly only if the anticipator is adjusted to match the current draw of the primary control. Use this thermostat only on systems with current draw that falls within the range of the heat anticipator. Do not use this device on Powerpile® Systems (millivolt).
Look for the current rating stamped on the nameplate of the primary control. Set the adjustable heat anticipator indicator to match the value shown on the nameplate.
If the current rating is not available, proceed as follows to determine the rating:
1. Turn off the power.
2. Wire the thermostat, but do not mount it on the
wall.
3. Connect the ammeter between the W wire and the W terminal on the thermostat (in series with the primary control).
4. Prepare the system for operation.
5. Turn on the power.
6. Turn the System switch to Heat.
7. Increase the thermostat setpoint, as necessary, to
begin operating the system.
8. With the system operating through the ammeter, wait one minute, then read the ammeter.
9. Turn the System switch to Off and turn off the power.
10. Adjust the heat anticipator to match the ammeter reading.
11. Disconnect the ammeter, reconnect the W wire, and mount the thermostat.
NOTE: For best performance, the heat anticipator may
require further adjustment. To lengthen burner­on time, move the indicator in the direction of the longer arrows but not more than one-half scale marking at one time. To shorten burner-on time, move the indicator in the opposite direction.

CHECKOUT

CAUTION
Equipment Damage Hazard. Heat anticipator can be damaged.
Do not check operation by shorting across system control terminals.
IMPORTANT
To assure accurate temperature control, do not touch or breathe on bimetal or thermometer.

Heating

With System switch set at Heat, and Fan switch set at Auto, move the temperature setting lever about 10°F (6°C) above room temperature:
Gas or oil-fired systems: heating should start; fan
should start after a short delay.
Move the temperature setting lever about 10°F (6°C) below room temperature:
Gas or oil-fired systems: heating should shut off and
fan should shut off after a short delay.
3 69-1688
Page 4
T834C HEATING AND COOLING THERMOSTAT
T

Cooling

CAUTION
Equipment Damage Hazard. Air conditioning equipment (compressor) can be damaged.
Do not operate cooling when outdoor temperature is below 50°F (10°C). Refer to manufacturer’s recommendations.
IMPORTANT
To prevent compressor short cycling, some manufacturer’s equipment includes a minimum­off timer to provide a five-minute time delay from when the thermostat last turned off the compressor, or from when the system first received power. This delay protects the com­pressor.
WIth the System switch set at Cool and the Fan switch set to Auto, move the temperature setting lever about 10°F (6°C) below room temperature. Cooling and fan should start (see Important above). Move the temperature setting lever about 10°F (6°C) above room temperature. Cooling and fan should shut off.
Fan
With the System switch set to Off and the Fan switch set to On, the fan should run continuously. Move the Fan switch to Auto. In gas- or oil-fired systems, fan operation is controlled by the plenum fan control in heating and by the thermostat in cooling.

Recalibration

These thermostats are calibrated at the factory and should not need recalibration. If the thermostat seems out of adjustment, first check for accurate leveling.
To check calibration:
1. Move the temperature setting lever to the lower end of the temperature scale. Place the System switch to the Off position. Wait at least five min­utes.
2. Remove the thermostat cover. Move the setting lever until the switch just makes contact. (The mer­cury in the switch rolls to the left end of the tube.)
3. Replace the cover and wait five minutes for the cover and the thermostat to lose the heat it has gained from your hands. If the thermometer pointer and the setting lever indicator read approximately the same, no recalibration is needed.
If recalibration appears necessary:
1. Place the temperature setting lever at the same setting as the thermometer. Remove the cover by pulling out on the right edge of the cover until it snaps free of the thermostat base.
2. Insert the 104994A Calibration Wrench (ordered separately) onto the hex nut under the coil. (See Fig. 3.) Holding the setting lever so it does not move, turn the wrench clockwise until the mercury rolls to the right end of the tube. Remove the wrench and replace the cover.
IMPORTANT
To assure accurate temperature control, do not touch or breathe on bimetal or thermometer.
3. Move the setting lever to a lower setting. Wait at least five minutes for the temperature to stabilize.
4. Slowly move the setting lever until it reads the same as the thermometer.
5. Remove the cover. Holding the setting lever so it does not move, reinsert the wrench and carefully turn it counterclockwise just until the mercury rolls to the left end of the tube but no farther.
6. Recheck the calibration. Set the thermostat System switch for the desired operation.
7. Adjust the temperature setting lever so the mercury bulb is in position as shown in Fig. 3.
8. Carefully replace the thermostat cover.
COIL SHOWN WITHOU HEAT ANTICIPATOR
CALIBRATION WRENCH
M2044A
Fig. 3. Recalibrating the thermostat.
M1V 4Z9
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
69-1688 G.H. 05-03 www.honeywell.com/yourhome
Loading...