The T834C Thermostat (see Fig. 1) controls 24 to 30 Vac single-stage heating-cooling systems. See Table 1 for
application information. An spdt mercury switch makes R to W on a temperature fall for heating, and R to Y on a
temperature rise for cooling.
Table 1. T834C Specifications.
Model No.ApplicationHeat Anticipation
T834CFor use in standard heating-
AN
WITCH
cooling systems.
.18
.9
.7
.2
.5
L
O
N
G
R
E
.3
.25
TEMPERATURE
SETTING LEVER
MOUNTING HOLE
(THERMOSTAT
TO WALL OR
OUTLET BOX)
BIMETAL ELEMEN
BEHIND SCALE
ADJUSTABLE HEA
ANTICIPATOR
INDICATOR
SYSTEM
SWITCH
MOUNTING HOLE
Fig. 1. T834C internal view.
0.18A to 1.0A,
adjustable.
M2118
INSTALLATION
When Installing This Product . . .
1. Read these instructions carefully. Failure to follow
2. Check the ratings given in the instructions and on
3. Installer must be a trained, experienced service
4. After installation is complete, check out the product
Switching
Heat-OffCool
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of an old control.
them could damage the product or cause a hazardous condition.
the product to make sure the product is suitable for
your application.
Locate the thermostat about 5 ft (1.5m) above the floor
on an inside wall in an area with good air circulation at
average temperature.
Do not mount the thermostat where it can be affected by:
— drafts or dead spots behind doors or in corner.
— hot or cold air from ducts.
— radiant heat from the sun, fireplaces or appliances.
— unheated (uncooled) areas such as outside walls
behind the thermostats.
This thermostat is a precision instrument and was
carefully adjusted at the factory. Handle it carefully.
Wiring and Mounting
CAUTION
Electrical Shock Hazard.
Can cause personal electrical shock and
equipment damage.
Disconnect power supply before beginning
installation.
IMPORTANT
All wiring must comply with local codes and
ordinances.
The T834C can be mounted directly on a wall or vertical
outlet box:
Use the 209649A (taupe) or 209650A (white)
Universal Cover Plate (ordered separately) to mount
on outlet box or to cover wall marks left by old
thermostat.
If the cover plate is used, review the instructions pro-
vided with it before wiring and mounting the
thermostat.
To wire and mount the thermostat:
1. In replacement applications, check the existing
thermostat wires for cracked or frayed insulation.
Replace any wires in poor condition. If the wire is
plastered into the wall, make a hole next to the
wires and loosen the wires so they can be pushed
back into the wall later.
2. In new installations, run wiring (if necessary) to the
thermostat location.
3. Set the adjustable heat anticipator indicator to
match the current draw of the primary heating
control or as recommended by the equipment
manufacturer (see Heat Anticipator Setting).
4. Connect the wires to the terminals on the back of
the thermostat. See Fig. 2 for internal schematic
and typical hookup diagram.
5. Remove thermostat cover by pulling outward on
right edge of cover until it snaps free of the
thermostat base. Carefully remove and discard the
foam plastic shipping insert that protects the switch
and bimetal assembly during shipping.
6. Push excess wire back through the hole and plug
any opening with insulation to prevent drafts that
can affect thermostat performance.
7. Loosely fasten the thermostat (with wallplate, if
applicable) to the wall or outlet box with a screw
through the top mounting hole. Adjust the
thermostat so it is approximately level and fasten
the second screw through the bottom mounting
hole. Do not tighten.
8. For optimum performance, level the thermostat
using a spirit level or plumb line. Tighten the
mounting screws.
9. Adjust temperature setting lever so mercury bulb is
in horizontal position as shown in Fig. 1.
10. Carefully replace the thermostat cover.
IMPORTANT
An incorrectly leveled thermostat causes the
temperature control to deviate from setpoint.
SWITCH
H1
69-16882
C1
TEMP. FALL
C1
ANTICIPATOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 2. Internal schematic and typical hookup for T834C in standard heating-cooling system.
ON
AUTO
SYSTEM
SWITCH
COOL
OFF
HEAT
HEAT
OFF
COOL
R
G
Y
W
FAN RELAY
COOL RELAY
HEAT RELAY
L1
(HO
L2
1
M21181
Page 3
SETTINGS AND ADJUSTMENTS
T834C HEATING AND COOLING THERMOSTAT
Temperature Setting
Push the temperature setting lever to the desired control
point on the temperature scale. The same lever controls
the temperature setting for either heating or cooling.
System and Fan Switching
The T834C has System and Fan switches to control the
heating-cooling systems and fan.
The System switch controls system operation:
Heat: Operates only heating system.
Off: Both heating and cooling systems are
disconnected.
Cool: Operates only cooling system.
The Fan switch controls fan operation:
Auto: For gas-or oil-fired systems; the fan operates in
response to the thermostat in cooling and in
response to the plenum fan control in heating.
On: The fan runs continuously.
To switch positions, use thumb and index finger to slide
lever to desired position. Stop switch lever in detent
directly over desired position. Stop switch lever in detent
directly over desired function indicator mark for correct
circuit operation.
Heat Anticipator Setting
IMPORTANT
The T834C Thermostat has an adjustable heat
anticipator and operates correctly only if the
anticipator is adjusted to match the current draw
of the primary control. Use this thermostat only
on systems with current draw that falls within
the range of the heat anticipator. Do not use this
device on Powerpile® Systems (millivolt).
Look for the current rating stamped on the nameplate of
the primary control. Set the adjustable heat anticipator
indicator to match the value shown on the nameplate.
If the current rating is not available, proceed as follows to
determine the rating:
1. Turn off the power.
2. Wire the thermostat, but do not mount it on the
wall.
3. Connect the ammeter between the W wire and the
W terminal on the thermostat (in series with the
primary control).
4. Prepare the system for operation.
5. Turn on the power.
6. Turn the System switch to Heat.
7. Increase the thermostat setpoint, as necessary, to
begin operating the system.
8. With the system operating through the ammeter,
wait one minute, then read the ammeter.
9. Turn the System switch to Off and turn off the
power.
10. Adjust the heat anticipator to match the ammeter
reading.
11. Disconnect the ammeter, reconnect the W wire,
and mount the thermostat.
NOTE: For best performance, the heat anticipator may
require further adjustment. To lengthen burneron time, move the indicator in the direction of
the longer arrows but not more than one-half
scale marking at one time. To shorten burner-on
time, move the indicator in the opposite
direction.
CHECKOUT
CAUTION
Equipment Damage Hazard.
Heat anticipator can be damaged.
Do not check operation by shorting across
system control terminals.
IMPORTANT
To assure accurate temperature control, do not
touch or breathe on bimetal or thermometer.
Heating
With System switch set at Heat, and Fan switch set at
Auto, move the temperature setting lever about 10°F
(6°C) above room temperature:
Gas or oil-fired systems: heating should start; fan
should start after a short delay.
Move the temperature setting lever about 10°F (6°C)
below room temperature:
Gas or oil-fired systems: heating should shut off and
fan should shut off after a short delay.
369-1688
Page 4
T834C HEATING AND COOLING THERMOSTAT
T
Cooling
CAUTION
Equipment Damage Hazard.
Air conditioning equipment (compressor) can
be damaged.
Do not operate cooling when outdoor
temperature is below 50°F (10°C). Refer to
manufacturer’s recommendations.
IMPORTANT
To prevent compressor short cycling, some
manufacturer’s equipment includes a minimumoff timer to provide a five-minute time delay
from when the thermostat last turned off the
compressor, or from when the system first
received power. This delay protects the compressor.
WIth the System switch set at Cool and the Fan switch
set to Auto, move the temperature setting lever about
10°F (6°C) below room temperature. Cooling and fan
should start (see Important above). Move the
temperature setting lever about 10°F (6°C) above room
temperature. Cooling and fan should shut off.
Fan
With the System switch set to Off and the Fan switch set
to On, the fan should run continuously. Move the Fan
switch to Auto. In gas- or oil-fired systems, fan operation
is controlled by the plenum fan control in heating and by
the thermostat in cooling.
Recalibration
These thermostats are calibrated at the factory and
should not need recalibration. If the thermostat seems
out of adjustment, first check for accurate leveling.
To check calibration:
1. Move the temperature setting lever to the lower
end of the temperature scale. Place the System
switch to the Off position. Wait at least five minutes.
2. Remove the thermostat cover. Move the setting
lever until the switch just makes contact. (The mercury in the switch rolls to the left end of the tube.)
3. Replace the cover and wait five minutes for the
cover and the thermostat to lose the heat it has
gained from your hands. If the thermometer pointer
and the setting lever indicator read approximately
the same, no recalibration is needed.
If recalibration appears necessary:
1. Place the temperature setting lever at the same
setting as the thermometer. Remove the cover by
pulling out on the right edge of the cover until it
snaps free of the thermostat base.
2. Insert the 104994A Calibration Wrench (ordered
separately) onto the hex nut under the coil. (See
Fig. 3.) Holding the setting lever so it does not
move, turn the wrench clockwise until the mercury
rolls to the right end of the tube. Remove the
wrench and replace the cover.
IMPORTANT
To assure accurate temperature control, do not
touch or breathe on bimetal or thermometer.
3. Move the setting lever to a lower setting. Wait at
least five minutes for the temperature to stabilize.
4. Slowly move the setting lever until it reads the
same as the thermometer.
5. Remove the cover. Holding the setting lever so it
does not move, reinsert the wrench and carefully
turn it counterclockwise just until the mercury rolls
to the left end of the tube but no farther.
6. Recheck the calibration. Set the thermostat
System switch for the desired operation.
7. Adjust the temperature setting lever so the mercury
bulb is in position as shown in Fig. 3.
8. Carefully replace the thermostat cover.
COIL SHOWN WITHOU
HEAT ANTICIPATOR
CALIBRATION
WRENCH
M2044A
Fig. 3. Recalibrating the thermostat.
M1V 4Z9
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North35 Dynamic Drive
Golden Valley, MN 55422Scarborough, Ontario
69-1688 G.H. 05-03 www.honeywell.com/yourhome
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.