Honeywell T8195B User Manual

T8195B/Q682B,C, Y8224A
M3375
Heating or Cooling and Heating/Cooling
New Construction Thermostat,
Wallplate and Subbase
Installation Instructions for the Trained Service Technician.
Preparation
Recycling Notice
heating, cooling, or heating/cooling system. Refer to Table 1.
Assemble tools required: flat bladed screwdriver, hand or power drill with 3/16-in. drill bit, wire cutter/stripper or sharp knife, bubble level or plumb bob and line.
Assure power is off to the heating, cooling, or heating/ cooling system at the main fuse panel. Most buildings have a separate switch box or circuit breaker for disconnecting power to the heating and cooling (if applicable) equipment.
This thermostat is compatible with most heating, cooling, or heating/cooling systems. Refer to Table 1 for thermostat and system compatibility information.
TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY.
Type of Heating System
to be Controlled Conditions/Compatibility
Electric (Line Voltage)—typical baseboard and radiant
Fan Coil Unit • Compatible. Assure correct subbase identity is selected for fan control. Gas—Direct Spark Ignition
(DSI), Intermittent Pilot (IP), and Standing Pilot (SP)
Heat Pump • Compatible. Assure correct subbase identity is selected for fan control and
Hot Water Zone • Honeywell 2-wire valves are compatible.
Oil • Assure that the 24V control transformer common is accessible for connection
Vent Damper • Honeywell damper motors are compatible.
Warm Air Zone • Most are compatible.
a
If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermo­stat will not be damaged unless it is used to directly control a line voltage system. For proper system operation, a Honeywell R841 or R8239D1015 Isolating Relay must be added to the thermostat control circuit.
b
Consult manufacturer for installation requirements.
• The R8239D1015 Isolating Relay or R841 Silent Switching Center must be installed in the thermostat control circuit.
• Compatible. Assure that 24V control transformer common is accessible for connection to thermostat cable conductor and power to the transformer is not regularly interrupted by high temperature or limit operation.
changeover control (O terminal for cool and B terminal for heat). Jumper Y to W for heat pump compressor control.
• Some non-Honeywell 2-wire valves require an R8239D1015 Isolating Relay in the thermostat control circuit.
• Some 3-wire valves require an R8239A1052 Isolating Relay in the thermostat control circuit.
to thermostat cable conductor and power to the transformer is not regularly interrupted by high temperature, purge cycle, or limit operation.
• Some non-Honeywell damper motors require an R8239D1015 Isolating Relay in the thermostat control circuit.a Check control amperage requirement.
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury
in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for in­structions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube.
If you have questions, call Honeywell Inc. at 1-800­468-1502.
a
a
a, b
D.F. • Rev. 11-94 • • ©Honeywell Inc. 1994 • Form Number 69-0564—3
1 69-0564—3
M3375
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could cause a hazardous condition.
2. Installer must be a trained experienced service technician.
3. After installation is complete, check out product op-
eration as provided in these instructions.
IMPORTANT: An incorrectly leveled subbase will cause
the temperature control to deviate from setpoint. It is not a calibration problem.
Fig. 1—Unpack thermostat.
CAPTIVE MOUNTING SCREWS
1
12
2
3
11
4
1 0
5
9
6
8
7
7
8
6
9
10
1
1
12
LIFT COVER
THERMOSTAT COVER
CAUTION
1. Disconnect power supply to prevent electrical shock or equipment damage.
2. To prevent interference with the thermostat link­age, keep wire length to a minimum and run wires as close as possible to the subbase.
3. Do not overtighten thermostat captive mount­ing screws because damage to subbase threads can result.
4. Do not short across coil terminals on relay. This can burn out the thermostat heat anticipator.
LOCATION
Locate thermostat about 5 ft [1.5m] above the floor in an
area with good air circulation at average temperature.
Do not mount the thermostat where it may be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from the sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
Run wires from the heating, cooling, or heating/cooling
equipment to the new thermostat location.
IMPORTANT: This control requires an additional con-
ductor to the control transformer common (e.g., a typical 2-wire heating system requires three wires be pulled, a 4-wire heating/cooling requires five wires).
UNPACK THERMOSTAT
Handle your new thermostat carefully; rough handling may interfere with its accuracy. Before unpacking, refer to Fig. 1.
Remove and discard the shipping wrap.
IMPORTANT: Save package of screws and instructions
for the homeowner.
Remove the thermostat cover by lifting from the bottom. Set aside cover until needed later.
Carefully remove the material protecting the mercury switch bulb.
Loosen two captive mounting screws, and separate wall­plate (if provided) from back of thermostat base.
MOUNT WALLPLATE OR SUBBASE Wall Mounting (Fig. 2)
Hold the wallplate or subbase in position on wall (Fig. 2).
Mark holes on the wall for anchors. Use spirit level to make sure the wallplate or subbase is level.
THERMOSTAT BASE
REMOVE PACKING MATERIAL
M8605
Drill 3/16-in. holes, and gently tap anchors into holes
until flush with the wall.
Pull wires through the large wiring hole in the wallplate or
subbase.
Loosely fasten the wallplate or subbase to the wall with
the three screws. Do not completely tighten the screws.
Carefully level the wallplate or subbase (Fig. 3), and
firmly tighten the screws.
Fig. 2—Mounting wallplate or subbase to wall.
3 SCREW HOLES WITH PLASTIC ANCHORS
O
B
R
W
G
FAN
HEATING/COOLING SUBBASE
3 SCREW HOLES WITH PLASTIC ANCHORS
HEATING-ONLY WALLPLATE
Y
AUTO OFF
HEATON
COOL
M1552A
M857
69-0564—3 2
Fig. 3—Leveling methods for wallplate or subbase.
or heating/cooling equipment manufacturer. If not available, refer to the Typical Wiring Diagrams section at the end of this publication.
WIRE WALLPLATE OR SUBBASE
PLUMB LINE
PLUMB BOB OR WEIGHT
FAN
SPIRIT LEVEL
O
B
R
W
G
Y
AUTO OFF
HEATON
COOL
M1555
nections to prevent electrical shock or equipment damage.
NOTE: All wiring must comply with local electrical codes
Wallplate (Heating or Cooling Systems)
necessary.
terminals. For cooling-only systems, connect wires R, Y, and C terminals. Firmly tighten the screws. The system low­voltage transformer powers the timer (Fig. 11).
or nonflammable insulation to prevent drafts from affecting
Outlet Box Mounting (Fig. 4)
thermostat operation.
Use a horizontally mounted outlet box if possible. If a
vertical outlet box is used, mount the wallplate or subbase on
Subbase (Heating/Cooling Systems)
a 202689A Cover Plate Assembly (ordered separately). Fol­low the instructions provided with the cover plate assembly.
necessary.
Align the wallplate or subbase mounting holes on the
outlet box and loosely fasten with two screws.
Carefully level the wallplate or subbase (Fig. 3), and
firmly tighten the screws.
Fig. 4—Mounting wallplate or subbase on horizontal outlet box.
subbase. If labels do not agree with your new subbase, refer to Table 2 and the installation instructions furnished with the subbase.
Follow the instructions provided by the heating, cooling
Disconnect the power supply before making wiring con-
and ordinances.
Refer to Fig. 5 and strip the thermostat wire insulation as
For heating-only systems, connect wires to R, W, and C
Push excess wire back into the wall. Plug the hole in the wall with nonhardening caulk, putty,
Refer to Fig. 5, and strip the thermostat wire insulation as
Connect the wires to the corresponding terminals on the
EXISTING HORIZONTAL OUTLET BOX
FAN
O
B
R
W
G
Y
AUTO OFF
HEATON
HEATING/ COOLING SUBBASE
COOL
M1553A
VERTICAL OUTLET BOX
NOT INCLUDED WITH UNIT.
1
ACCESSORY PARTS AVAILABLE.
2
EXISTING HORIZONTAL OUTLET BOX
R
W
WALLPLATE
M856
1
2
SUBBASE OR WALLPLATE
ADAPTER RING
MOUNTING SCREWS (2)
COVER PLATE
2
R
G
O
B
W
Y
M1554A
3 69-0564—3
Loading...
+ 5 hidden pages