Installation Instructions for the Trained Service Technician.
Preparation
Recycling Notice
Check thermostat and subbase (if used) suitability for the
heating, cooling, or heating/cooling system. Refer to Table 1.
Assemble tools required: flat bladed screwdriver, hand or
power drill with 3/16-in. drill bit, wire cutter/stripper or
sharp knife, bubble level or plumb bob and line.
Assure power is off to the heating, cooling, or heating/
cooling system at the main fuse panel. Most buildings have
a separate switch box or circuit breaker for disconnecting
power to the heating and cooling (if applicable) equipment.
This thermostat is compatible with most heating, cooling,
or heating/cooling systems. Refer to Table 1 for thermostat
and system compatibility information.
TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY.
Type of Heating System
to be ControlledConditions/Compatibility
Electric (Line Voltage)—typical
baseboard and radiant
Fan Coil Unit• Compatible. Assure correct subbase identity is selected for fan control.
Gas—Direct Spark Ignition
(DSI), Intermittent Pilot (IP), and
Standing Pilot (SP)
Heat Pump• Compatible. Assure correct subbase identity is selected for fan control and
Hot Water Zone• Honeywell 2-wire valves are compatible.
Oil• Assure that the 24V control transformer common is accessible for connection
Vent Damper• Honeywell damper motors are compatible.
Warm Air Zone• Most are compatible.
a
If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermostat will not be damaged unless it is used to directly control a line voltage system. For proper system operation, a Honeywell
R841 or R8239D1015 Isolating Relay must be added to the thermostat control circuit.
b
Consult manufacturer for installation requirements.
• The R8239D1015 Isolating Relay or R841 Silent Switching Center must be
installed in the thermostat control circuit.
• Compatible. Assure that 24V control transformer common is accessible for
connection to thermostat cable conductor and power to the transformer is not
regularly interrupted by high temperature or limit operation.
changeover control (O terminal for cool and B terminal for heat). Jumper Y
to W for heat pump compressor control.
• Some non-Honeywell 2-wire valves require an R8239D1015 Isolating Relay
in the thermostat control circuit.
• Some 3-wire valves require an R8239A1052 Isolating Relay in the
thermostat control circuit.
to thermostat cable conductor and power to the transformer is not regularly
interrupted by high temperature, purge cycle, or limit operation.
• Some non-Honeywell damper motors require an R8239D1015 Isolating
Relay in the thermostat control circuit.a Check control amperage
requirement.
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury
in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of this
control, or of an old control containing mercury in a sealed
tube.
If you have questions, call Honeywell Inc. at 1-800468-1502.
1. Read these instructions carefully. Failure to follow
them could cause a hazardous condition.
2. Installer must be a trained experienced service technician.
3. After installation is complete, check out product op-
eration as provided in these instructions.
IMPORTANT: An incorrectly leveled subbase will cause
the temperature control to deviate from setpoint. It is
not a calibration problem.
Fig. 1—Unpack thermostat.
CAPTIVE MOUNTING
SCREWS
1
12
2
3
11
4
1
0
5
9
6
8
7
7
8
6
9
10
1
1
12
LIFT
COVER
THERMOSTAT
COVER
CAUTION
1. Disconnect power supply to prevent electrical
shock or equipment damage.
2. To prevent interference with the thermostat linkage, keep wire length to a minimum and run
wires as close as possible to the subbase.
3. Do not overtighten thermostat captive mounting screws because damage to subbase threads
can result.
4. Do not short across coil terminals on relay. This
can burn out the thermostat heat anticipator.
LOCATION
Locate thermostat about 5 ft [1.5m] above the floor in an
area with good air circulation at average temperature.
Do not mount the thermostat where it may be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
Run wires from the heating, cooling, or heating/cooling
equipment to the new thermostat location.
IMPORTANT: This control requires an additional con-
ductor to the control transformer common (e.g., a
typical 2-wire heating system requires three wires be
pulled, a 4-wire heating/cooling requires five wires).
UNPACK THERMOSTAT
Handle your new thermostat carefully; rough handling
may interfere with its accuracy. Before unpacking, refer to
Fig. 1.
Remove and discard the shipping wrap.
IMPORTANT: Save package of screws and instructions
for the homeowner.
Remove the thermostat cover by lifting from the bottom.
Set aside cover until needed later.
Carefully remove the material protecting the mercury
switch bulb.
Loosen two captive mounting screws, and separate wallplate (if provided) from back of thermostat base.
MOUNT WALLPLATE OR SUBBASE
Wall Mounting (Fig. 2)
Hold the wallplate or subbase in position on wall (Fig. 2).
Mark holes on the wall for anchors. Use spirit level to
make sure the wallplate or subbase is level.
THERMOSTAT BASE
REMOVE
PACKING
MATERIAL
M8605
Drill 3/16-in. holes, and gently tap anchors into holes
until flush with the wall.
Pull wires through the large wiring hole in the wallplate or
subbase.
Loosely fasten the wallplate or subbase to the wall with
the three screws. Do not completely tighten the screws.
Carefully level the wallplate or subbase (Fig. 3), and
firmly tighten the screws.
Fig. 2—Mounting wallplate or subbase to wall.
3 SCREW HOLES
WITH PLASTIC
ANCHORS
O
B
R
W
G
FAN
HEATING/COOLING SUBBASE
3 SCREW HOLES
WITH PLASTIC
ANCHORS
HEATING-ONLY
WALLPLATE
Y
AUTOOFF
HEATON
COOL
M1552A
M857
69-0564—32
Fig. 3—Leveling methods for wallplate or
subbase.
or heating/cooling equipment manufacturer. If not available,
refer to the Typical Wiring Diagrams section at the end of
this publication.
WIRE WALLPLATE OR SUBBASE
PLUMB
LINE
PLUMB
BOB OR
WEIGHT
FAN
SPIRIT LEVEL
O
B
R
W
G
Y
AUTOOFF
HEATON
COOL
M1555
nections to prevent electrical shock or equipment damage.
NOTE: All wiring must comply with local electrical codes
Wallplate (Heating or Cooling Systems)
necessary.
terminals. For cooling-only systems, connect wires R, Y,
and C terminals. Firmly tighten the screws. The system lowvoltage transformer powers the timer (Fig. 11).
or nonflammable insulation to prevent drafts from affecting
Outlet Box Mounting (Fig. 4)
thermostat operation.
Use a horizontally mounted outlet box if possible. If a
vertical outlet box is used, mount the wallplate or subbase on
Subbase (Heating/Cooling Systems)
a 202689A Cover Plate Assembly (ordered separately). Follow the instructions provided with the cover plate assembly.
necessary.
Align the wallplate or subbase mounting holes on the
outlet box and loosely fasten with two screws.
Carefully level the wallplate or subbase (Fig. 3), and
firmly tighten the screws.
Fig. 4—Mounting wallplate or subbase on horizontal outlet box.
subbase. If labels do not agree with your new subbase, refer
to Table 2 and the installation instructions furnished with
the subbase.
Follow the instructions provided by the heating, cooling
Disconnect the power supply before making wiring con-
and ordinances.
Refer to Fig. 5 and strip the thermostat wire insulation as
For heating-only systems, connect wires to R, W, and C
Push excess wire back into the wall.
Plug the hole in the wall with nonhardening caulk, putty,
Refer to Fig. 5, and strip the thermostat wire insulation as
Connect the wires to the corresponding terminals on the
EXISTING
HORIZONTAL
OUTLET BOX
FAN
O
B
R
W
G
Y
AUTOOFF
HEATON
HEATING/
COOLING
SUBBASE
COOL
M1553A
VERTICAL
OUTLET
BOX
NOT INCLUDED WITH UNIT.
1
ACCESSORY PARTS AVAILABLE.
2
EXISTING
HORIZONTAL
OUTLET BOX
R
W
WALLPLATE
M856
1
2
SUBBASE OR
WALLPLATE
ADAPTER
RING
MOUNTING
SCREWS (2)
COVER
PLATE
2
R
G
O
B
W
Y
M1554A
369-0564—3
Fig. 5—Methods of connecting terminals.
FOR STRAIGHT
CONNECTION—
STRIP 5/16 in. [8 mm]
Fig. 6—Thermostat mounting.
FOR WRAPAROUND
CONNECTION—
STRIP 7/16 in. [11 mm]
BARRIER
M1556B
TABLE 2—TERMINAL DESIGNATIONS.
Subbase
Terminal
Control
Function
RControl transformer power.
WHeating control circuit.
YCooling control circuit; jumper to W
for heat pump compressor control if
no P terminal on subbase.
GFan control circuit.
CClock control (transformer common).
OCooling damper or changeover/
reversing valve, makes continuously
in cool.
BHeating damper or changeover/
reversing valve, makes continuously
in heat.
The timer is powered by the system low-voltage trans-
former. 24 Vac must be maintained across terminals R and C.
Push excess wire back into the wall.
Plug the hole in wall with nonhardening caulk, putty, or
nonflammable insulation to prevent drafts from affecting
thermostat operation.
MOUNT THE THERMOSTAT
Note the tabs on the top inside edge of the thermostat base.
These tabs fit the slots molded into the top of the wallplate or
subbase.
Hang the thermostat base on the wallplate or subbase.
Insert the two captive mounting screws located in the
bottom corners of the base (Fig. 6).
Firmly tighten the screws.
INSERT TIMER BATTERIES (OPTIONAL)
Power is supplied to the clock by the 24-Vac transformer.
Two AAA alkaline backup batteries (not included) may be
installed to supply power to the timer if power is interrupted
due to power failure.
Install the batteries in the thermostat (Fig. 7).
Once a year or when batteries are dead, replace with two
new AAA alkaline batteries. We recommend Energizer
batteries.
TAB (2)
MOUNTING SLOT (2)
1
12
2
3
1
1
4
10
5
9
6
8
7
7
8
6
9
10
11
12
THERMOSTAT
BASE
WALLPLATE
OR SUBBASE
Fig. 7—Insert timer backup batteries.
BATTERY LOCATION FOR
(2) AAA BATTERIES;
INSTALL WITH POSITIVE
ENDS UP
SET TIMER
Adjust the clock by moving the knob clockwise . Do
not reverse the knob.
When time is correctly set, the time indicator arrow
(triangle shape) points to the corresponding daytime (light)
or nighttime (dark) portion of the program dial.
ATTACH THERMOSTAT COVER
Make sure the packing inserts in the thermostat base are
removed.
Place the two tabs on the upper edge of the cover into the
mounting slots in the thermostat base (Fig. 9).
Swing the cover downward until it catches at the bottom of the base.
®
CAPTIVE
MOUNTING SCREWS
M8603
M8585
69-0564—34
Fig. 8—Set timer.
50
60
70
80
M8604
PROGRAM
PINS (4)
SEE OWNER'S
MANUAL FOR
DETAILS
TIMER
SETTING
KNOB
TIME
INDICATOR
ARROW
M5161
Fig. 9—Attach cover.
Fig. 10—Temperature control levers.
LOW TEMPERATURE
(BLUE MARK)
SET LEVER
HIGH TEMPERATURE
(RED MARK)
SET LEVER
SET TEMPERATURE CONTROL LEVERS
The two levers on the top of the thermostat control the
low and high temperatures for energy savings and comfort
control (Fig. 10). The lever on the left (blue mark) controls
the lower temperature. The lever on the right (red mark)
controls the higher temperature.
We recommend pushing the levers together at an appropriate temperature for either heat or cool until the occupant
programs the thermostat and makes the final temperature
selections.
SET SUBBASE SWITCHES (IF APPLICABLE)
The subbase system switch controls system operation as
follows:
HEAT: Heating system is controlled by the thermostat.
Cooling system is off.
COOL: Cooling system is controlled by the thermostat.
Heating system is off.
OFF: Both the heating and cooling systems are off. If the
fan switch is in the AUTO position, the fan is also off.
The subbase fan switch controls fan operation as follows:
ON: Fan operates continuously.
AUTO: Fan operates with the cooling equipment as con-
trolled by the thermostat or with the heating equipment
as controlled by the plenum switch. In electric heat,
heat pump, and fan coil systems, the fan is controlled
by the thermostat in heating and cooling.
To switch positions, use thumb or index finger to slide
lever to the desired position. For proper circuit operation,
switch lever must stop in detent over the desired function
indicator mark.
70
60
50
80
M859
Checkout
CAUTION
Do not check operation by shorting across terminals of system controls. This will damage the heat
anticipator.
HEATING-ONLY SYSTEM
Turn on power to the furnace.
Push both temperature setting levers together at least 5° F
[3° C] above the room temperature. The main burner should
come on. The fan will start when the furnace heats up.
Move both levers 5° F [3° C] below the room temperature. The burner should shut off.
Operate the entire heating system at least one complete
cycle.
If thermostat fails any test, refer to the Troubleshooting
Guide in the Owner’s Manual.
Reset both the temperature setting levers to the desired
temperatures.
569-0564—3
COOLING-ONLY SYSTEM
Turn on power to the cooling equipment.
Push both temperature setting levers together at least 5° F
[3° C] below the room temperature. The cooling equipment
will operate, and the fan will start. Allow for any time delay
that may be built into the compressor control circuit.
NOTE: To avoid compressor damage, do not operate the
system when outdoor temperature is below 50° F [10° C].
Refer to manufacturer recommendations.
Move both levers 5° F [3° C] above room temperature.
The cooling equipment and the fan should shut off.
Operate the entire cooling system at least one complete
cycle.
If thermostat fails any test, refer to the Troubleshooting
Guide in the Owner’s Manual.
Reset both the temperature setting levers to the desired
temperatures.
HEATING/COOLING SYSTEM
Turn on power to the furnace and cooling system.
Place the system switch lever to HEAT and fan switch
lever to AUTO.
Push both temperature setting levers together at least 5° F
[3° C] above room temperature. The main burner should
come on. The fan will start when the furnace heats up. (If
central electric heat, fan coil or heat pump system, fan starts
immediately.)
Move both levers 5° F [3° C] below room temperature.
The burner should shut off.
Place the system switch lever to COOL and the fan switch
lever to AUTO. The cooling equipment will operate, and the
fan will start. Allow for any time delay that may be built into
the compressor control circuit.
NOTE: To avoid compressor damage, do not operate the
system when outdoor temperature is below 50° F [10° C].
Refer to manufacturer recommendations.
Move both temperature setting levers together at least
5° F [3° C] above the room temperature. The cooling equipment should shut off.
Place the fan switch to ON. The fan should run continuously with the system switch in any position.
Place the system switch to OFF. Move both temperature
setting levers to various positions. The heating and cooling
systems should not operate.
Operate the entire system for at least one complete cycle
with the system switch at COOL and one complete cycle
with the switch at HEAT.
If thermostat fails any test, refer to the Troubleshooting
Guide in the Owner’s Manual.
Reset both the temperature setting levers to the desired
temperatures.
Leave Owner’s Manual and Assistance Information in a
convenient place for the building occupant or provide with
other appliance manuals.
Typical Wiring Diagrams
Follow the hookup diagram supplied with your heating,
cooling, or heating/cooling equipment. If not available, use
Figs. 11 through 13 as a guide.
REMEMBER: Your wiring must follow local electrical codes
and ordinances.
Fig. 11—Typical hookup for T8195B Thermo-
stat and Q682C Wallplate in gas heating
control system.
H
FALL
HEAT
ANTICIPATOR
W
THERMOSTAT
C
Y
WALLPLATE
M503A
TIMER
H
C
FALL
HEAT
ANTICIPATOR
COOL
ANTICIPATOR
R
C
GAS
L1
(HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
CONTROL
69-0564—36
Fig. 12—Typical hookup for T8195B Thermostat and Q682B Subbase in conventional heating/
cooling system.
TIMER
THERMOSTAT
SUBBASE
L1
(HOT)
L2
THERMOSTAT
HEAT/COOL
ANTICIPATOR
SYSTEM
SWITCH
OFF
HEAT
COOL
C
R
B
HEATING
1
DAMPER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
REMOTE INDICATION FOR FILTER OPTIONAL.
2
TIMER
O
COOLING
DAMPER
HEAT
ANTICIPATORS
FAN
RELAY
H
FALL
FAN
SWITCH
ON
AUTO
G
H
FALL
C
HEAT
RELAY
C
H
FALL
2
FILTER
LED
OFF
HEAT
COOL
W
Y
COOLING
RELAY
C
X
SWITCH
M8606
H
C
FALL
SUBBASE
L2
1
L1
(HOT)
COOL
ANTICIPATORS
SYSTEM
SWITCH
OFF
HEAT
COOL
C
W
HEAT
RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.1
Y
COMPRESSOR
CONTACTOR
AUTO
G
FAN
RELAY
ON
FAN
SWITCH
HEAT
OFF
COOL
R
M573B
769-0564—3
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North35 Dynamic Drive
Golden Valley, MN 55422Scarborough, Ontario M1V 4Z9
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.