Honeywell T8112C, T8112D User Manual

T8112C,D Electronic
Programmable Thermostats
INSTALLATION INSTRUCTIONS
APPLICATION
The T8112C,D thermostats provide electronic programmable control for 24 to 30 Vac heating and cooling systems.
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do
control in the trash. Contact your local waste management authority
for instructions regarding recycling and the proper disposal of the old thermostat.
not
place your old
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them could cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
1. Disconnect power supply to prevent electrical shock or equipment damage.
2. After wiring is complete, push excess wire back into the hole and plug hole with nonhardening caulk, putty or insulation to prevent drafts from affecting thermostat operation.
Location
Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature.
Do not install the thermostat where it can be affected by:
drafts, or dead spots behind doors and in corners.hot or cold air from ducts.radiant heat from sun or appliances.concealed pipes and chimneys.unheated (uncooled) areas such as an outside wall
behind the thermostat.
Mounting Plate Installation
Position mounting plate on the wall. Use a level to make sure mounting plate is level. Use a pencil to mark the two mounting holes. See Fig. 1.
WALL ANCHORS (2)
WIRES THROUGH WALL OPENING
WALL
MOUNTING PLATE
MOUNTING SCREWS (2)
Fig. 1. Mounting plate installation.
M1718
®U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • • All Rights Reserved
X-XX UL
69-0917-2
T8112C,D ELECTRONIC PROGRAMMABLE THERMOSTATS
1. Remove mounting plate from the wall, and drill 3/16 inch holes in wall (if drywall) as marked. For firmer material such as plaster or wood, drill 7/32 inch holes. Gently tap anchors (provided) into drilled holes until flush with the wall.
2. Reposition mounting plate over holes, pulling wires through wiring opening. Loosely insert two mounting screws into holes.
3. Level for appearance only; the thermostat will function properly even when not level. Tighten mounting screws. See Fig. 2.
LEVEL
M1714A
Fig. 2. Leveling mounting plate.
Adjust Fan Operation Switch, as Required
The Thermostat fan operation switch, labeled FUEL SWITCH is factory set in the F position. See Fig. 4. This is the correct setting for most systems. If your system is an electric heat system, set the switch to E. The E setting allows the fan to turn on immediately with the heating or cooling in a system where the G terminal is connected.
Adjust System On-time, as Required
The system on-time is factory-set for a warm air, gas or oil heating system. If you are installing it on another type of system, the system on-time must be adjusted accordingly by setting screws A and B on the back of the thermostat. Use the heating system table shown in Fig. 3 as a guide. The system on-time should be optimized according to the type of system to minimize room temperature swings. Setting the screw means turning the screw approximately 360° or one complete turn. Setting the screw in means tightening the screw completely down.
In the event that you want longer furnace on-time, readjust the screws A and B as follows:
Warm Air Furnaceset at the Hot Water setting (A out one turn, B—in).
Electric FurnaceLeave at the Warm Air Furnace setting (A—in, B—in).
NOTE: This thermostat does not have a setting for
steam/gravity air. Cycles would not be long enough for accurate temperature control.
out one turn
IMPORTANT
When using a high efficiency furnace such as a 90 percent or greater AFUE (Average Fuel Utilization Efficiency) unit, adjust screw A out one turn and screw B in.
THERMOSTAT BACK
FOR HIGH EFFICIENCY FURNACE (90%+ AFUE) ADJUST:
SCREW A–OUT 1 TURN SCREW B–IN FUEL SWITCH – F POSITION
A C
B D
FUEL SWITCH F
ADJUST SCREWS THROUGH HOLES TO SELECT OPERATION DESIRED
WARM AIR FURNACE
HOT WATER BOILER
ELECTRIC FURNACE
E
HEATING SYSTEM
A–IN
A–OUT 1 TURN
A–IN
W Y G
R
B–IN
B–IN
B–OUT 1 TURN
FUEL SWITCH
POSITION
F
F
E
Rc
M3669
Fig. 3. Back view of thermostat.
Wiring Thermostat
All wiring must comply with local electrical codes and ordinances. Ref er to Fig. 4 through 7 for typical hookups. A letter code is located near each terminal for identification. See Table 1 f or terminal cross referencing inf ormation.
CAUTION
Disconnect power before wiring to prevent electrical shock or equipment damage.
1. Connect the system wires to the thermostat. See Fig. 8. A letter code is located near each terminal for identification.
NOTE: Hold the thermostat as shown in Fig. 9 to
minimize need for wire extenders.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug hole with nonflammable insulation to prevent
drafts from affecting the thermostat.
Table 1. Typical Wire Colors and Functions
Thermostat
Terminal
G Green Fan
Y Yellow Cooling
W White Heating
Rc Blue Air Cond. Power
R Red Furnace Power
a
Wire colors are typical; verify at heating/cooling equipment connection.
Connect to
Wire Color
a
Function
69-0917—2
2
T8112C,D ELECTRONIC PROGRAMMABLE THERMOSTATS
R
Rc
W Y G
B D
A C
3-WIRE COOL-ONLY (JUMPER INTACT)
L1 (HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
JUMPER
M848A
COOLING CONTACTOR COIL
FAN RELAY
2-WIRE HEAT-ONLY (JUMPER INTACT)
A C
B D
W Y G
R
HEATING RELAY OR VALVE COIL
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 4. Typical hookup in two wire lead
only (jumper intact) application.
L1 (HOT)
L2
4-WIRE HEAT/COOL (JUMPER INTACT)
A C
B D
W Y G
R
HEATING RELAY OR VALVE COIL
1
COOLING CONTACTOR COIL
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 5. Typical hookup in four wire heat
and cool (jumper intact) application.
5-WIRE HEAT/COOL (JUMPER REMOVED)
A C
B D
JUMPER
Rc
HEATING RELAY OR
1
M1709B
JUMPER
Rc
L1 (HOT)
L2
M1710B
VALVE COIL
COOLING
1 1
L1 (HOT)
L2
1
Fig. 6. Typical hookup in five wire heat
and cool (jumper removed) application.
CONTACTOR COIL
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FAN RELAY
W Y G
R
Rc
L1 (HOT)
L2
M1711B
Fig. 7. Typical hookup in three wire cool
only (jumper intact) application.
3
69-0917—2
T8112C,D ELECTRONIC PROGRAMMABLE THERMOSTATS
T8112C
A.
THERMOSTAT AND MOUNTING PLATE.
5/16 in. (8 mm) STRIP
INSERT STRAIGHT UNDER SCREW HEAD
END OF WIRE VISIBLE HERE
c
R
JUMPER (FACTORY­INSTALLED) REMOVE IF 5-WIRE SYSTEM
R
WY G
M1712A
Fig. 8. Proper wiring technique.
T8112D
A. ENGAGE TABS AT TOP OF
THERMOSTAT AND MOUNTING PLATE.
M3002A
Fig. 9. Holding thermostat while installing.
Mounting Thermostat on Mounting Plate
1. Engage tabs at the top of thermostat and mounting
plate. See Fig. 10.
2. Press lower edge of case to latch.
NOTE: To remove the thermostat from the wall, first
pull out at the bottom of the thermostat; remove top last.
ENGAGE TABS AT TOP OF
C. SWING COVER OPEN TO
CHECK OPERATION.
B.
PRESS LOWER EDGE
OF CASE TO LATCH.
AM
TU
LEAVE
B. PRESS LOWER EDGE
OF CASE TO LATCH.
M13063
M5780
69-0917—2
Fig. 10. Mounting thermostat on mounting plate.
4
T8112C,D ELECTRONIC PROGRAMMABLE THERMOSTATS
Installing Batteries
IMPORTANT
Batteries must be installed for programming and operation of the thermostat and heating/cooling system.
1. Use two AA alkaline batteries; nonalkaline batteries will not last as long, and can leak, causing damage to the thermostat or wall surface. Energizer batteries are recommended.
2. Make sure the thermostat is set in the OFF position.
3. Use a coin to remove the battery door. See Fig. 11.
4. Install the new batteries making sure positive and
negative terminals are oriented correctly. See Fig. 12.
5. Replace battery door.
M5781
Fig. 11. Remo ving battery door.
INSTALL TWO AA ALKALINE BATTERIES AS SHOWN
AM
TU
LEAVE
As the batteries are running low, a bAt Lo” indicator flash for one to two months before batteries run out completely. Replace the batteries as soon as possible after the indicator starts flashing. If the batteries are not replaced sometime during the flashing bAt Lo,” the indicator eventually stops flashing. bAt Lo” will stay on without flashing, indicating the thermostat and heating/cooling system have stopped working and the batteries are almost completely dead.
After the batteries are completely dead, the bAt Lo indicator disappears, leaving a completely blank display.
To remove, press down on left ends of batteries. If the new batteries are installed within 20 to 30 seconds of removing the old ones, the thermostat does not have to be reprogrammed. If the display is blank, the batteries are dead or incorrectly installed and the thermostat has to be reprogrammed. See Owner’s Manual for programming instructions.
SETTINGS
Current Time/Day
To set time, press and release the Set Clock/Day key once. Press the Time keys until the current time shows.
To set day, press and release the Set Clock/Day key again. Press the Time ke ys until the current day shows. Press Run Program key.
See Owners Manual for complete programming instructions.
Fan Switch
FAN AUTO: Normal setting f or most homes. A single-
speed fan turns on automatically with the air conditioner of furnace. A two-speed fan usually runs on high with the air conditioner and on low with the furnace.
NOTE: When Fan Operation Switch on the back of the
thermostat is in E position, the fan operates with the furnace only.
FAN ON: The fan runs continuously. Used for improved
air circulation during special occasions or for more efficient electronic air cleaning.
Auto On
Fan
FAN SWITCH
Fig. 12. Installing batteries.
System
Cool Off Heat
SYSTEM SWITCH
M5782
System Switch
System switching positions control thermostat operation as follows:
COOL: The thermostat controls the air conditioning
system.
OFF: Both the heating and air conditioning systems
are off.
HEAT: The thermostat controls the heating system.
5
69-0917—2
T8112C,D ELECTRONIC PROGRAMMABLE THERMOSTATS
CHECKOUT
Heating
Do
not
check heating system operation by jumpering thermostat terminals at the primary control such as the gas valve, zone valve, or oil burner control This will damage the thermostat. Instead, you could jumper R and R wires at the thermostat.
Cooling
To avoid possible compressor damage, do not operate the cooling system when outside temperature is below 50°F (10°C). See compressor manufacturer instructions for further information.
NOTE: When cooling setting is changed, thermostat
can delay up to five minutes before turning on the air conditioner. This delay protects the compressor.
Fan
Move the thermostat system switch to OFF and the fan switch to ON. The fan should run continuously. With the system switch still in the OFF position, move the fan switch to AUTO; the fan should stop.
Move the system switch to HEAT and the fan switch to AUTO.
Press key until the setting is about 10°F (6°C) abov e room temperature. Heating should start and the fan should run after a short delay (immediately if fan operation switch is set in E position).
Press key until setting is about 10°F (6°C) below room temperature. The heating equipment should shut off.
Move the system switch to COOL and the fan switch to AUTO.
Press key until setting is about 10°F (6°C) below room temperature. The cooling equipment and fan should start.
Press key until the setting is about 10°F (6°C) abov e room temperature. The cooling equipment and fan should stop.
Move the system switch to OFF and the fan switch to AUTO. The system and fan should be off.
69-0917—2
6
T8112C,D ELECTRONIC PROGRAMMABLE THERMOSTATS
TROUBLESHOOTING GUIDE
If Then
Display will not come on. Set the system switch to OFF. Remove batteries. Insert batteries
Temperature display will not go lower than 45° F (7° C) or higher than 88° F (31° C) during programming.
Temperature change occurs at the wrong times.
Heating will not come on. Check that switch on thermostat is set to HEAT. Allow a minimum of five
Cooling will not come on. Check that switch on thermostat is set to COOL. Allow a minimum of five
Too warm or too cool. Press Run Program key to check the current temperature setting.
SYSTEM ON indicator is lit, but no heat is coming from the registers.
Thermostat current temperature setting does not match the display temperature to within ± 1°.
bAtLo remains on display after batteries are installed.
backward for at least five seconds to reset thermostat. Correctly replace batteries. Display should come on.
Make sure batteries are fresh and installed correctly.
Gently clean battery contacts using a soft pencil eraser. Do not use
anything abrasive on the clips.
The temperature setting limit is reached. The setting range is 45° F to 88° F (7° C to 31°C).
Check the program times for the period in question. Be sure that AM and PM indications are correct. Make sure the current day and time are correct. Reprogram if necessary.
minutes for time guard protection to expire.
Check the system fuse or circuit breaker and replace or reset if necessary.
Check for correct wiring and good connections.
Disconnect and jumper wires R and W. If heat does not come on, check
out the heating system.
If display is blank or says bAt Lo, install fresh batteries.
minutes for time guard protection to expire.
Check the system fuse or circuit breaker and replace or reset if necessary.
Check for correct wiring and good connections.
Disconnect and jumper wires R and Y. If cooling does not come on,
check out the cooling system.
If display is blank or says bAt Lo, install fresh batteries.
The thermostat has a built-in time delay on cooling. Allow at least five
minutes after changing the setting before the air conditioner starts.
Make sure outdoor disconnect is engaged (on).
If temperature setting is lower than current temperature, and SYSTEM
ON indicator is lit, move system switch from COOL to OFF for ten minutes. After ten minutes, return switch to COOL position. If air conditioner comes on, compressor could have reached its high limit temperature protection and shut down.
If 2- or 4-wire installation, verify that R-Rc jumper is installed
If desired, change the temperature setting. See the Owners Manual.
Allow time for the furnace to heat up and the fan to come on before
checking for heat at the register. (Check to make sure the Cycle Rate in the Installation section is correct.)
Check that the wiring hole in the wall behind the wallplate has been plugged with insulation to prevent drafts that might adversely affect thermostat operation.
Be aware that it is normal for the current setting and display temperature to differ on occasion.
During recovery from setback or setup, setting and display temperatures can differ for up to 30 minutes after recovery period.
Remove batteries. Wait one hour. Install fresh Alkaline batteries.
NOTICE This equipment is a Class B digital apparatus, which complies with Canadian Radio Interference Regulations, CRC c.1374.
7
69-0917—2
T8112C,D ELECTRONIC PROGRAMMABLE THERMOSTATS
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
69-09172
69-09172 G.H. Rev. 4-98 Printed in Mexico www.honeywell.com
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7
8
Loading...