Honeywell T678, T675 PRODUCT DATA

T675/T678

REMOTE BULB TEMPERATURE CONTROLLER

PRODUCT DATA

FEATURES

Liquid filled remote bulb for accurate temperature sensing

Ambient temperature compensation to eliminate control offset

Snap acting SPDT MICRO SWITCH with adjustable differential (T675 only)

Two snap acting SPDT MICRO SWITCHES for two stage operation with adjustable interstage differential (T678 only)

Front mounted adjustment knob with large clear scale

Temperature ranges to suit most air and liquid temperature control applications

Robust steel surface mount housing with knock-out conduit entry

Adjustable control differential (T675) or inter-stage differential (T678)

DESCRIPTION

The T675/T678 are two position remote bulb temperature controllers for controlling the temperature in ducts, tanks, boilers, etc.

The sensing element is connected to the controller by means of a liquid filled capilliary tube of specified length.

The T675 provides a single SPDT switching action with adjustable differential by means of a variable switch air gap.

The T678 provides two stage SPDT switching action with adjustable inter-stage differential.

EN0R8445

Honeywell T678, T675 PRODUCT DATA

SPECIFICATIONS

Supply voltage

: 120 ... 230 V~, 50 ... 60 Hz

Switch action

:

T675 - SPDT MICRO SWITCH

 

 

T678 - 2 x SPDT MICRO SWITCHES

Switch rating

: 8.0 A @ 120 V~, 5.1 A @ 230 V~ full

 

 

load

 

 

48.0 A @ 120 V~, 30.6 A @ 230 V~

 

 

locked rotor

Operating

:

52oC Maximum

temperature

 

 

Operating

:

345 kPa Maximum

pressure

 

 

Adjustment

:

Knob on dial

Differential

: 1.7 to 5.6 K adjustable (T675 only)

 

 

1.7 fixed (T678 only)

lnterstage

: 1.7 to 5.6 K adjustable (T678 only)

differential

 

 

Mounting

: Surface mounting using slotted holes in

 

 

back of case

Bulb

: 13 x 106 mm (1/2" dia. x 43/16")

dimensions

 

 

Capilliary length

:

1.5 m (5')

Case

: 143 x 51 x 67 (55/8" x 2" x 25/8") h x w x d

Dimensions

 

 

ORDERING SPECIFICATION

Model

Setpoint Range

Maximum

 

 

Element

 

 

Temperature

 

 

 

T675A1607

-15..35o C

52o C

T675A1615

30..80o C

93o C

T675A1623

75.. 125o C

138o C

T678A1551

-15..35o C

52o C

T678A1577

30..80o C

93o C

IMPORTANT

1.The installer must be a trained service engineer

2.Disconnect the power supply before beginning installation

DIMENSIONS

Dimensions in millimetres (inches in brackets)

INSTALLATION

Mounting

The controller can be surface mounted in any position using the slotted holes on the rear.

The bulb should be located where it will be exposed to the average temperature of the controlled medium. Do not kink or bend the capilliary tube sharply. Excess tubing should be coiled beneath the case.

WIRING

Honeywell Control Systems Limited

Helping You Control Your World

Newhouse Industrial Estate

 

Motherwell ML1 5SB

 

United Kingdom

 

EN0R 8445