Honeywell STA822, STA840, STA87L Technical Information

SmartLine
STA800 SmartLine Absolute Pressure Specification 34-ST-03-85, Jan 2021
Introduction
Part of the SmartLine® family of products, the STA800 and STA80L are high performance absolute pressure transmitters featuring piezoresistive sensor technology combining pressure sensing with on chip temperature compensation capabilities providing high accuracy, stability and performance over a wide range of application pressures and temperatures. The SmartLine family is also fully tested and compliant with Experion® PKS providing the highest level of compatibility assurance and integration capabilities. SmartLine easily meets the most demanding application needs for pressure measurement applications..
Best in Class Features:
Accuracies up to 0.0375% of span standard &
0.025% of span optional
Stability up to 0.01% of URL per year for 15 years  Automatic temperature compensation  Rangeability up to 100:1  Response times as fast as 80ms  Multiple local display capabilities  External zero, span, & configuration capability  Polarity insensitive electrical connections  Comprehensive on-board diagnostic capabilities  Integral Dual Seal design for highest safety based
on ANSI/NFPA 70-202 and ANSI/ISA 12.27.2
Full compliance to SIL 2/3 requirements  Modular design characteristics  Available with additional 15-year warranty  Plugged Impulse Line Detection Option  Dual/Triple Calibration Option (HART & Fieldbus
Only)
Figure 1 – STA800 Absolute Pressure
Transmitters feature field-proven piezoresistive
sensor technology
Communications/Output Options:
4-20mA dc  Honeywell Digitally Enhanced (DE)  HART ® (version 7.0)  FOUNDATION™ Fieldbus
All transmitters are available with the above listed communications protocols.
Span & Range Limits:
Model
URL mmHgA (mbarA)
LRL mmHgA (mbarA)
Min Span
mm HgA
(mbarA)
STA822/82L
780 (1040)
0 (0)
50 (65)
Model
psia
(barA)
psi (barA)
psi (barA)
STA840/84L
500 (35)
0 (0)
5 (.35)
STA87L
3000 (210)
0 (0)
30 (2.1)
2 STA800 Smart Pressure Transmitter
Description
The SmartLine family of gauge pressure, differential pressure, and absolute pressure transmitters is designed around a high performance piezo-resistive sensor. This one sensor actually integrates multiple sensors linking process pressure measurement with on-board static pressure (DP Models) and temperature compensation measurements resulting in the best total performance available. This level of performance allows the ST 800 to replace virtually any competitive transmitter available today. ()
Unique Indication/Display Options
The ST 800 modular design accommodates a basic alphanumeric LCD display or a unique advanced graphics LCD display with many unparalleled features.
Basic Alphanumeric LCD Display Features
Modular (may be added or removed in the field)  0, 90,180, & 270 degree position adjustments  Configurable (HART only) and standard (Pa, KPa,
MPa, KGcm2, Torr, ATM, inH2O, mH2O, bar, mbar, inH2O, inHG, FTH2O, mmH2O, mm HG, & psi) measurement units
2 Lines 16 Characters (4.13H x 1.83W mm)  Square root output indication
Advanced Graphics LCD Display Features
Modular (may be added or removed in the field)  0, 90, 180, & 270 degree position adjustments  Standard and custom measurement units
available.
Up to eight display screens with 3 formats are
possible
(Large PV with Bar Graph or PV with Trend Graph)  Configurable screen rotation timing (1 to 30 sec)  Display Square Root capabilities may be set
separately from the 4-20mA dc output signal
Unique “Health Watch” indication provides instant
visibility of diagnostics
Multiple language capability. (EN, GE, FR, IT, SP,
RU, TR, CN and JP)
Diagnostics
SmartLine transmitters all offer digitally accessible diagnostics which aid in providing advanced warning of possible failure events minimizing unplanned shutdowns, providing lower overall operational costs
Configuration Tools
Integral Three Button Configuration Option
Suitable for all electrical and environmental requirements, SmartLine offer the ability to configure the transmitter and display via three externally accessible buttons when either display option is selected. Zero/span capabilities are also optionally available via these buttons with or without selection of a display option.
Hand Held Configuration SmartLine transmitters feature two-way communication and
configuration capability between the operator and the transmitter. All Honeywell transmitters are designed and tested for compliance with the offered communication protocols and are designed to operate with any Standards compliant handheld configuration device.
Personal Computer Configuration
Honeywell’s SCT 3000 Configuration Toolkit provides an easy way to configure Digitally Enhanced (DE) instruments using a personal computer as the configuration interface. Field Device Manager (FDM) Software and FDM Express are also available for managing HART & Fieldbus device configurations.
System Integration
SmartLine communications protocols all meet the
most current published standards for HART/DE/Fieldbus.
Integration with Honeywell’s Experion PKS offers the
following unique advantages.
o Transmitter messaging o Maintenance mode indication o Tamper reporting o FDM Plant Area Views with Health summaries o All ST 800 units are Experion tested to provide
the highest level of compatibility assurance
STA800 Smart Pressure Transmitter 3
Modular Design
To help contain maintenance & inventory costs, all ST 800
transmitters are modular in design supporting the user’s
ability to replace meter bodies, add indicators or change electronic modules without affecting overall performance or approval body certifications. Each meter body is uniquely characterized to provide in-tolerance performance over a wide range of application variations in temperature and pressure and due to the Honeywell advanced interface, electronic modules may be swapped with any electronics module without losing in-tolerance performance characteristics.
Modular Features
Meter body replacement  Exchange/replace electronics/comms modules*  Add or remove integral indicators*  Add or remove lightning protection (terminal
connection)*
* Field replaceable in all electrical environments (including IS) except flameproof without violating agency approvals.
With no performance effects, Honeywell’s unique
modularity results in lower inventory needs and lower overall operating costs.
Plugged Impulse Line Detection:
STA800 models are offered with a PILD option which provides indication of a plugged impulse line or process connection. When used in conjunction with a basic or advanced display, a non-critical diagnostic indication appears on the integral display. For units without an integral display, an indication can be seen via the host or hand held device when HART Protocol is utilized.
Dual/Triple Calibration:
STA800 models are optionally offered with multiple calibrations. In lieu of a standard factory calibration, units can be supplied with 1, 2, or 3 customer specified calibrations. These calibrations are stored in the meter body and provide users with factory calibrated performance at up to three different calibrated ranges. This increases application flexibility without requiring any costly recalibration or additional inventory.
Performance Specifications
Reference Accuracy:(conformance to +/-3 Sigma)
Table 1
Model
URL
LRL
Min Span
Maximum
Turndown
Ratio
Stability
(% URL/
Year for 15
years)
Reference
Accuracy
1,2
% Span
Std/Opt.
STA822
780 mmHgA
(1040 mbarA)
0.0 mmHgA (0.0 mbarA)
50 mmHgA (65 mbarA)
15:1
0.010
0.0375/0.025 STA840
500 psia (35 barA)
0.0 mmHgA (0.0 mbarA)
5 psia (0.35 barA)
100:1
STA82L
780 mmHgA
(1040 mbarA)
0.0 mmHgA (0.0 mbarA)
50 mmHgA (65 mbarA)
15:1
0.015
0.0375
STA84L
500 psia (35 barA)
0.0 mmHgA (0.0 mbarA)
5 psia (0.35 barA)
100:1
0.010
0.0375/0.025
STA87L
3000 psi (210 barA)
0.0 mmHgA (0.0 mbarA)
30 psia (2.1 barA)
100:1
Zero and span may be set anywhere within the listed (URL/LRL) range limits.
4 STA800 Smart Pressure Transmitter
Performance Specifications
Accuracy at Specified Span and Temperature: (Combined Zero & Span, conformance to +/-3 Sigma)
Table 2
Accuracy
1,2
(% of Span)
Combined Zero & Span
Temperature Effect
(% Span/ 28oC (50oF))
Model
URL
Reference Turndown
A
B
C
(see URL
units)
D
E
Standard Accuracy
STA822
780 mmHgA
(1040 mbarA)
8.7:1
0.005
0.0325
90 (120)
0.050
0.040
STA840
500 psia
(35 barA)
25:1
20 (1.4)
0.025
0.005
STA82L
780 mmHgA
(1040 mbarA)
5.6:1
140 (187)
0.050
0.080
STA84L
500 psia
(35 barA)
25:1
20 (1.4)
0.025
0.007
STA87L
3000 psi (210
barA)
10:1
300 (21)
0.025
0.007 High Accuracy Option
STA822
780 mmHgA
(1040 mbarA)
8.7:1
0.005
0.0200
90 (120)
0.050
0.040
STA840
500 psia
(35 barA)
25:1
20 (1.4)
0.025
0.005
STA84L
500 psia
(35 barA)
25:1
20 (1.4)
0.025
0.007
STA87L
3000 psi
(210 barA)
10:1
300 (21)
0.007
Turn Down Effect
Temp Effect
󰇟  󰇠  
    

   
󰇟   


󰇠
Total Performance (% of Span):
Total Performance Calculation: = +/- (Accuracy)2 + (Temperature Effect)2
Total Performance Examples (for comparison): standard accuracy 5:1 Turndown, +/-50 oF (28oC) shift
STA822 @ 156 mmHgA: 0.253% of span STA82L @ 156 mmHgA: 0.451% of span STA840 @ 100 psia: 0.063% of span STA84L @ 100 psia: 0.071% of span STA87L @ 600 psia: 0.071% of span
Typical Calibration Frequency:
Calibration verification is recommended every four (4) years.
Notes:
1. Terminal Based Accuracy - Includes combined effects of linearity, hysteresis, and repeatability. Analog output adds 0 .005% of span.
2. For zero based spans and reference conditions of: 25 oC (77oF), 10 to 55% RH, and 316 Stainless Steel barrier diaphragm.
STA800 Smart Pressure Transmitter 5
Operating Conditions – All Models
Parameter
Reference
Condition
Rated Condition
Operative Limits
Transportation and
Storage
C
F
C
F
C
F
C
F
Ambient Temperature1
25±1
77±2
-40 to 85
-40 to 185
-40 to 85
-40 to 185
-55 to 120
-67 to 248
Meter Body Temperature2
STA822/STA82L
25±1
77±2
See Figure 2
See Figure 2
-55 to 125
-67 to 257
STA840, 84L, 87L
25±1
77±2
-40 to 110
-40 to 230
-40 to 125
-40 to 257
-55 to 125
-67 to 257
Humidity %RH
10 to 55
0 to 100
0 to 100
0 to 100
Vacuum Region - Minimum Pressure
STA822, 82L, 840,84L, 87L
See Figure 2. Operate within specifications above 25 mmHgA (33 mbarA). Short term3 exposure to full vacuum will not result in damage.
Supply Voltage, Current, and Load Resistance
(HART & DE)
10.8 to 42.4 Vdc at terminals (IS versions limited to 30 Vdc) 0 to 1,440 ohms (as shown in Figure 3)
Maximum Allowable Working Pressure (MAWP) 4, 5
STA822, 82L = 780 mmHgA, 1,040 mbarA STA840, 84L = 500 psia, 35 barA STA87L = 3,000 psia, 210 barA
1
LCD Display operating temperature -20C to +70C Storage temperature -30C to 80C.
2
Silicone 704 minimum temperature rating is 0
o
C (32oF). CTFE minimum temperature rating is -30C (-22F).
3
Short term equals 2 hours at 70C (158F)
4
Units can withstand overpressure of 1.5 x MAWP without damage
5
Consult factory for MAWP of ST 700 transmitters with CRN approval
6 STA800 Smart Pressure Transmitter
-40
-30
-20
40
50
60
70
80
90
100
110
120
ºC
ºF
-40
-22
-4
104
122
140
158
176
194
212
230
248
0.1
1.0
10
100
1000
2
3 4 5 6 7 8 9 2 3 4 5
6
7 8 9
2 3 4 5 6
7 8 9
2
3 4 5 6 7 8 9
] [
] [
] [
Meter Body Temperature
] [
NOTE:
Short term exposure (2 hours at
70°C/158°F) to hard vacuum will not
result in damage.
0
32
Measured
Pressure
mmHgA
Rated Operating Area
Silicone Oil
200®
Operative
Limit
Silicone Oil
704®
CTFE
LEGEND:
Rated operating area
Contact Marketing
Applications for "special"
quote.
25 mmHgA
(33.3 mbarA)
23065
Figure 2 - Measured pressure versus meter body temperature chart for STA722, 72L
Figure 3 - Supply voltage and loop resistance chart & calculations
STA800 Smart Pressure Transmitter 7
Performance Under Rated Conditions – All Models
Parameter
Description
Analog Output Digital Communications:
Two-wire, 4 to 20 mA (HART & DE Transmitters only) Honeywell DE, HART 7 protocol or FOUNDATION Fieldbus ITK 6.0.1 compliant All transmitters, irrespective of protocol have polarity insensitive connection.
HART & DE Output Failure Modes
(NAMUR for DE Units requires selecting display and configuration buttons or factory configuration)
Honeywell Standard: NAMUR NE 43 Compliance: Normal Limits: 3.8 – 20.8 mA 3.8 – 20.5
mA Failure Mode: ≤ 3.6 mA and ≥ 21.0 mA ≤ 3.6 mA and ≥
21.0 mA
Supply Voltage Effect
0.005% of span per volt.
Transmitter Turn on Time (includes power up & test algorithms)
HART or DE: 2.5 sec Foundation Fieldbus: Host dependant
Response Time (delay + time constant)
DE/HART Protocol FOUNDATION Fieldbus 80ms 150ms (Host Dependant)
Damping Time Constant
HART: Adjustable from 0 to 32 seconds in 0.1 increments. Default Value: 0.5
seconds DE: Discrete values 0, .16, .32, .48, 1, 2, 4, 8, 16, 32 seconds. Default Value: 0.48 seconds
Vibration Effect
Less than +/- 0.1% of URL w/o damping Per IEC60770-1 field or pipeline, high vibration level (10-2000Hz: 0.21 displacement/3g max acceleration)
Electromagnetic Compatibility
Meets IEC61326
Lightning Protection Option
Leakage Current: 10uA max @ 42.4VDC 93C Impulse rating:
8/20uS 5000A (>10 strikes) 10000A (1 strike min.) 10/1000uS 200A (> 300 strikes)