Honeywell ST9141A1002 User Manual

ST9141A1002 Electronic Fan T imer
Application
The ST9141A1002 Electronic Fan Timer integrates con­trol of all combustion blower and circulating fan operations in a gas warm air appliance. This control is the central wiring point for most of the electrical components in the furnace. The basic purposes of the ST9141A1002 are to monitor the thermostat for heat, cool, and fan demands and run the induced draft blower motor and up to a two-speed circulating fan as required. The ST9141A1002 monitors an spdt pressure switch, burner limit and primary limit. A Honeywell SV9500 Hot Surface Pilot Ignition System Control manages the burner, which is energized through the pressure switch. A light-emitting diode (LED) indicates system status.
In addition, this model includes electronic air cleaner and humidifier convenience terminal connections.
NOTE: Use this control to replace an identical ST9141A1002
Electronic Fan Timer only. This control is not for use in
general applications.
Specifications
ELECTRICAL RATINGS:
Power Requirements:
Voltage: 18-30 Vac, 60 Hz.
Contact Ratings:
Combustion Blower:
1.5A Full Load, 10A Locked Rotor at 115 Vac. .75A Full Load, 5A Locked Rotor at 230 Vac. Reduce full load rating by humidifier load.
Circulating Fan (Heat-Cool Speed):
15A Full Load, 30A Locked Rotor at 115 Vac.
7.5A Full Load, 15A Locked Rotor at 230 Vac. Reduce full load rating by electronic air cleaner
load.
Thermostat Load: 0.06A plus ignition system current
draw.
ON/OFF DELAY SETTINGS:
Heat Speed:
Delay On: 30 seconds, fixed. Delay Off: 60, 100, 140 or 180 seconds, field
adjustable.
Cool Speed:
Delay On: 6 seconds, fixed. Delay Off: 60 seconds, fixed.
Timing Tolerance: Larger of ±5% or ±2 seconds.
POSTPURGE TIMING: 5 seconds. ENVIRONMENTAL RATINGS
Temperature: -40° to +175° F [-40° to +79° C]. Humidity: 5 to 95%, noncondensing.
LIGHT-EMITTING DIODE (LED) INDICATIONS:
LED flashing dim-bright indicates normal operation. LED off when control is powered indicates defective
control.
LED on continuously when control is powered indicates
defective control.
LED flashing in a cycle with LED on followed by one
Number
of Off Flash Pulses System Condition
1 Burner limit circuit is open. 2 Primary limit circuit is open. 3 Pressure switch circuit is improp-
4 Control is in lockout due to air
erly closed.
not circulating (overheating).
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condi­tion.
2. Check the ratings and specifications given in the instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out the product operation as provided in these instructions.
CA UTION
!
Disconnect power supply before wiring to pre­vent electrical shock or equipment damage.
Location and Mounting
The ST9141A1002 is mounted in the appliance wiring compartment using four No. 6 screws (obtained locally) through holes on the corners of the enclosure.
Wiring
All wiring must comply with local codes and ordi­nances. Disconnect power before making wiring connec­tions. Refer to Fig. 1 for standard wiring connections. Refer to Fig. 2 for an internal schematic.
1 69-0780
C.H. • 6-93 • ©Honeywell Inc. 1993 • Form Number 69-0780
Fig. 1—Typical ST9141A1002 wiring connections.
HUMIDIFIER
AIR CLEANER
COMBUSTION BLOWER
STARTING CAP
LO
ML
MH
HI
CIRCULATING FAN
THERMOSTAT
NOTE:
3 DI
HUM N
12
Z1
Z2
DELAY
1
GRW
Y
2
OFF
= DENOTES STANDARD TERMINAL.
= DENOTES TERMINAL NOT PROVIDED.
DENOTES LINE VOLTAGE CONNECTIONS.
DENOTES LOW VOLTAGE CONNECTIONS.
UNUSED
EAC N
SPEED
UP
MOTOR
CY
N
LEADS
123
ST9141
NEUTRAL
CIR
C
CONT
COOL
G
4
BLWR
HEAT
FUSE
Y
XFMR
CX
W
120 VAC
TRANSFORMER
24 VAC
SEC
X
R
L1 (H)
TO 120 VAC POWER SUPPLY
L2 (N)
PRIMARY LIMIT
COOLING CONTACTOR
N.C.
BURNER LIMIT
PRESSURE SWITCH
SV9500 HOT SURFACE PILOT IGNITION SYSTEM CONTROL
N.O.
24 VOLT COMMON
24 VOLT THERMOSTAT OR PRESSURE SWITCH
24 VOLT HOT
EFT OUTPUT
M5607
2
Fig. 2—ST9141A1002 internal schematic.
L1-1
N.O.
K1
BURNER LIMIT
PRIMARY LIMIT
COM.
PRESSURE SWITCH
N.C.
L1-2
CN1
1
6
8
3
7
EAC (S)
K2 HEAT
K2
R-OT
PS1
PS2
COOL
K3A
X-OT
FUSE
HUM (S)
DI
L1 (H)
TO 120 VAC POWER SUPPLY
INTERLOCK
ELECTRONIC AIR CLEANER
M2
M1
HUMIDIFIER
X
K3B
MED-LOW
MED-HIGH
COMBUSTION AIR BLOWER
120 VAC
24 VAC
ST9141A ELECTRONIC FAN TIMER
FT
5
L2 (N)
LOW
HIGH
TRANSFORMER
24V
4
CIRCULATING FAN
C G
Y W R
C
2
EAC (N)
HUM (N)
N3
N4
N2
C
THERMOSTAT
N1
COOLING CONTACTOR
NOTE: DOTTED LINES REPRESENT PRINTED CIRCUIT BOARD WIRING.
3 69-0780
SV9500 HOT SURFACE PILOT IGNITION SYSTEM CONTROL
24V
TSTAT FT
GND
M5608
Setting the Heat Fan Off Delay DIP Switches
Set the heat fan off delay DIP switches to 60, 100, 140 or 180 seconds as shown in Fig. 3. The off delay is factory-set at 140 seconds. This delay time starts when the main gas valve is de-energized at the end of a thermostat call for heat.
Checkout
Fig. 3—Setting delay off DIP switches.
ST9141
12
3 DI
HUM N
UNUSED
EAC N
MOTOR
N
LEADS
123
NEUTRAL
CIR
CONT
COOL
4
BLWR
CX
HEAT
XFMR
SEC
X
Assure the system operates properly by operating the system through at least one complete heating cycle and cooling cycle. Troubleshoot by checking for appropriate voltages at the ST9141A1002 terminals controlling the combustion air blower and heat and cool speed circulating
Z1
Z2
fan. The ST9141A1002 schematic shows internal switch­ing to clarify operation and assist in troubleshooting. See Fig. 2.
DELAY
SPEED
1
2
UP
1
CY
2
C
140 SECONDS
OFF
1
2
60 SECONDS 100 SECONDS
DELAY OFF DIP SWITCH SETTINGS
G
1
2
Y
W
180 SECONDS
R
ON OFF
1
2
M5658
ST9141A1002 Operating Sequence
Action System Response
Thermostat calls for heat. • Pressure switch confirmed in no airflow position. (If pressure switch shows (W terminal is energized.) airflow, LED flashes three times.)
• Combustion air blower is energized.
• Air proving switch makes (air flow is established).
• Ignition system is energized.
• Gas valve opens and main burner lights.
• Heat fan on delay timing begins. When timing is complete, circulating blower is energized at heat speed.
Thermostat ends call for heat. • Ignition system is de-energized and gas valve closes. (W terminal is de-energized.) • Combustion air blower is de-energized after postpurge timing.
• Heat fan off delay timing begins. When timing is complete, the circulating fan is de-energized.
Thermostat begins call for cool. • Cooling contactor is energized. (G and Y terminals are energized.) • Circulating fan is energized at cool speed after cool fan on delay timing.
Thermostat ends call for cool. • Cooling contactor is de-energized. (G and Y terminals are de-energized.) • Circulating fan turns off after cool fan off delay timing.
Thermostat begins call for fan. • Circulating fan is energized at heat speed two seconds after G terminal is (G terminal is energized.) energized.
• If a call for heat occurs, circulating fan continues to run at heat speed.
• If a call for cool occurs, circulating fan switches to cool speed after four­second delay.
Thermostat ends call for fan. • Circulating fan is de-energized. (G terminal is de-energized.)
Primary limit switch string opens. • Thermostat and ignition system are de-energized and gas valve closes.
• Combustion air blower is de-energized.
• Circulating fan is energized at heat speed.
• LED flashes twice.
• If there is a call for cooling or fan, the circulating fan switches from heat speed to cool speed.
(continued)
4
ST9141A1002 Operating Sequence (Continued) Action System Response
Primary limit switch string closes. • Circulating fan turns off after the selected heat fan off delay timing.
Primary limit switch string is open • Combustion air blower, circulating fan and ignition system are de-energized. for more than 150 seconds (on each • Control goes into lockout mode. of three consecutive cycles). • LED flashes four times.
Burner limit opens. • Thermostat and ignition system are de-energized and gas valve closes.
Burner limit closes. • Combustion air blower remains energized for postpurge timing.
Electronic air cleaner is connected. • Electronic air cleaner is energized when the circulating fan heat or cool speed (Connector to 120 Vac electronic is energized. air cleaner.)
Humidity control is connected. • Humidifier is energized when combustion air blower is energized. (Connector to 120 Vac humidifier.)
• LED stops flashing.
• Normal operation resumes.
• Control remains in lockout until 24V power is removed and reapplied (control is reset).
• LED stops flashing.
• Normal operation resumes.
• Combustion air blower and circulating fan heat speed are energized.
• LED flashes once.
• The circulating fan remains energized for the selected delay off timing.
• LED stops flashing.
• Normal operation resumes.