S6040A1003
Air FLOW SWITCHES
SPECIFICATION DATA & MOUNTING INSTRUCTIONS
FEATURES
• Cost-effective flow switches for HVAC applications.
• High-capacity, fully-encapsulated NC/NO micro-switch.
SPECIFICATIONS
Switching capacity 15 (8) A, 24...250 Vac
Lifetime 50000 cycles at nominal load
Working temperature -40...+85 °C at 90% rel. humidity,
non-condensing
Internal duct temperature -40...+85 °C
Electrical connection Screw terminal, wire up to 1.5 mm
cable ∅ 6...9 mm
Protection class I according to EN60730
Protection standard IP65 according to EN60529
Housing material ABS and corrosion-protected steel
Accessories PA1 Paddle set
2
S6040A1003
GENERAL
The S6040A1003 Air Flow Switch monitors air flow and the
flow of non-aggressive gases in the air ducts of air
conditioning systems and air treatment systems.
MODELS
Specification S6040A1003
Flow medium air
Mounting vertically through a 20-mm hole in the duct; mount paddle inside
Maximum duct temperature 85 °C
Pressure 0.25 bar
Paddle material 1.4301
Lever yellow brass
Sensor body zinc-plated steel
Housing dimensions 108 x 70 x 72 mm
Weight 700 g
Approvals --
® U.S. Registered Trademark EN0B-0637GE51 R01008
Copyright © 2008 Honeywell Inc. • All rights reserved
S6040A1003 AIR FLOW SWITCH
MOUNTING
The S6040A1003 Air Flow Switch (with separate paddle) is
mounted in the vertical position (i.e. with the switch box at the
top).
In order to avoid air turbulence and paddle instability, the
device should be installed in straight duct runs having a
length of at least 5 times the duct diameter both upstream
and downstream from the location of installation.
The device must be mounted with the seal plate (included in
the package) through an approx. 20-mm hole in the duct. The
device must be fixed with two screws (included in the
package.) The paddle must then be mounted with a screw on
the shaft inside of the duct.
NOTE: The flow switch is factory-set to the min. flow rate.
To adjust the device to other levels, turn the adjustment screw clockwise. Because of the risk of
breakage at air speeds greater than 5 m/s, when
installed in ducts in which high air speeds are
expected, the paddle must be cut off along the two
markings. When the paddle is narrowed in this way,
the minimum switch point is increased from 1 m/s to
2.5 m/s.
SWITCH-POINT ADJUSTMENT
Min. switch point: approx. 2.5 m/s; reset point: 1 m/s.
Max. switch point: approx. 9.2 m/s; reset point: 8.0 m/s.
DIMENSIONS
70 mm
50 mm
80 mm
Fig. 2. S6040A1003 dimensions
1.5 mm
135 mm
113 mm
65 mm175 mm
24
mm
265.5 mm
NOTES:
1) THE MIN. SWITCH POINT IS ADJUSTED TO 1 M/S. IT
CHANGES TO 2.5 M/S WHEN THE PADDLE IS COMPLETELY
CUT OFF ALONG BOTH LINES.
2 IF THE ADJUSTMENT SCREW IS SET TO MORE THAN 5 M/S,
)
THE PADDLE MUST BE COMPLETELY CUT OFF ALONG BOTH
LINES.
PG11
FIELD WIRING
COMMON
RED
NORMALLY OPEN
NORMALLY CLOSED
Connect the red and the white contacts. The contact redwhite opens when the flow drops below the switch point.
When the flow is absent, the contact red-blue closes and can
be used as a signal or alarm contact.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich
Germany
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0637GE51 R1008
BLUE
WHITE
ADJUSTMENT SCREW
FOR FLOW RATE
Fig. 1. Field wiring