Honeywell S6040A1003 SPECIFICATION DATA & MOUNTING INSTRUCTIONS

S6040A1003
Air FLOW SWITCHES
SPECIFICATION DATA & MOUNTING INSTRUCTIONS
FEATURES
Cost-effective flow switches for HVAC applications.
High-capacity, fully-encapsulated NC/NO micro-switch.
SPECIFICATIONS
Switching capacity 15 (8) A, 24...250 Vac Lifetime 50000 cycles at nominal load Working temperature -40...+85 °C at 90% rel. humidity,
non-condensing Internal duct temperature -40...+85 °C Electrical connection Screw terminal, wire up to 1.5 mm
cable 6...9 mm Protection class I according to EN60730 Protection standard IP65 according to EN60529 Housing material ABS and corrosion-protected steel Accessories PA1 Paddle set
2
GENERAL
The S6040A1003 Air Flow Switch monitors air flow and the flow of non-aggressive gases in the air ducts of air conditioning systems and air treatment systems.
MODELS
Specification S6040A1003
Flow medium air Mounting vertically through a 20-mm hole in the duct; mount paddle inside Maximum duct temperature 85 °C Pressure 0.25 bar Paddle material 1.4301 Lever yellow brass Sensor body zinc-plated steel Housing dimensions 108 x 70 x 72 mm Weight 700 g Approvals --
® U.S. Registered Trademark EN0B-0637GE51 R01008 Copyright © 2008 Honeywell Inc. • All rights reserved
S6040A1003 AIR FLOW SWITCH
MOUNTING
The S6040A1003 Air Flow Switch (with separate paddle) is mounted in the vertical position (i.e. with the switch box at the top).
In order to avoid air turbulence and paddle instability, the device should be installed in straight duct runs having a length of at least 5 times the duct diameter both upstream and downstream from the location of installation.
The device must be mounted with the seal plate (included in the package) through an approx. 20-mm hole in the duct. The device must be fixed with two screws (included in the package.) The paddle must then be mounted with a screw on the shaft inside of the duct.
NOTE: The flow switch is factory-set to the min. flow rate.
To adjust the device to other levels, turn the adjust­ment screw clockwise. Because of the risk of breakage at air speeds greater than 5 m/s, when installed in ducts in which high air speeds are expected, the paddle must be cut off along the two markings. When the paddle is narrowed in this way, the minimum switch point is increased from 1 m/s to
2.5 m/s.
SWITCH-POINT ADJUSTMENT
Min. switch point: approx. 2.5 m/s; reset point: 1 m/s.
Max. switch point: approx. 9.2 m/s; reset point: 8.0 m/s.
DIMENSIONS
70 mm
50 mm
80 mm
Fig. 2. S6040A1003 dimensions
1.5 mm
135 mm
113 mm
65 mm175 mm
24
mm
265.5 mm
NOTES:
1) THE MIN. SWITCH POINT IS ADJUSTED TO 1 M/S. IT CHANGES TO 2.5 M/S WHEN THE PADDLE IS COMPLETELY
CUT OFF ALONG BOTH LINES. 2 IF THE ADJUSTMENT SCREW IS SET TO MORE THAN 5 M/S,
)
THE PADDLE MUST BE COMPLETELY CUT OFF ALONG BOTH
LINES.
PG11
FIELD WIRING
COMMON
RED
NORMALLY OPEN
NORMALLY CLOSED
Connect the red and the white contacts. The contact red­white opens when the flow drops below the switch point.
When the flow is absent, the contact red-blue closes and can be used as a signal or alarm contact.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany
EN0B-0637GE51 R1008
BLUE
WHITE
ADJUSTMENT SCREW FOR FLOW RATE
Fig. 1. Field wiring