Honeywell RP920A, RP920C, RP920B, RP920D Installation Instructions Manual

Modular Pneumatic Controllers
3 (75) MINIMUM CLEARANCE
4
(102)
3-3/8 (86)
9/32
(7)
RP920A: 1-1/2 (36)
RP920B-D: 3-1/4 (83)
5-7/8 (148)
1/8 (3) MINIMUM SPACING BETWEEN MODULES
RP920A: 1-7/8 (48)
RP920B-D: 3-13/16 (96)
M17581
INSTALLATION
Adjustments Before Mounting
1.
If a connection to port 4, 6, 7, or 8 (Fig. 2) is required, remove the self-tapping screw from port 8 and use the screw to tap the appropriate port.
2.
Install 14003755-001 Barb Fit ting and O-ring fing er-tight in the appropriate port.
3.
Reinstall the screw in port 8 if not used.
4.
If a remote restriction is used for the primary sensor, block the internal air supply (adjustable after gage installation, but easier to adjust before installation): a. Loosen the screw one turn (Fig. 3) and rotate the
switchplate (light grey) 90 degrees co unterclockwise to the sensor supply blocked position.
b. Retighten the screw and check for leaks. If a leak is
found, reposition the switchplate.
RP920A,B,C,D
INSTALLATION INSTRUCTIONS
Device Mounting
1.
2.
Connections
1.
2.
NOTES: — The switchplate screw mu st be tightene d securely
to prevent a false inoperative senso r condi tio n.
— The compensation sensor on port 5 requires an
external restricted main air supply.
Mark and drill two No. 8 fastener mounting holes using the controller or Fig. 1 dimensions as a template. Mount the controller with two No. 8 fasteners (not supplied).
Push the tubing on the port barb fittings according to the job drawings. See Fig. 2 for port locations. Install the gage or plug: a. If no gage is used, tighten gage plugs finger-tight.
If a gage is used, remove the plug and, by hand, screw the gage into the gage port three turns.
b. If the gage is not oriented for correct viewing, rotate
the gage counterclockwise unti l corre ct.
NOTE: A soft-rubber, factory-installed seal allows
plug or gage rotation (for alignment) without leakage.
Fig. 1. RP920 Dimensions in in. (mm).
After Mounting Adjustments and Changes
Controller Action Change
1.
Loosen the four Proportional Module screws (Fig. 4).
2.
Remove the module.
3.
Rotate the module and its gasket 180 degrees, and reinstall. Ensure that the notch on the module lines up with the proper indication on the controller label (base).
4.
Retighten the four screws.
5.
Recalibrate if required.
Negative (Winter) to Positive (Summer) Compensation Change (RP920 B and D only)
1.
Loosen the four compensation module screws (Fig. 5).
2.
Remove the module.
3.
Rotate the module and its gasket 180 degrees, and reinstall. Ensure that the notch on the module lines up with the proper indication on the controller label (base).
4.
Retighten the four screws.
5.
Recalibrate, if required.
® U.S. Registered Trademark Copyright © 2000 Honeywell • All Rights Reserved
95- 7392EF
RP920A,B,C,D MODULAR PNEUMATIC CONTROLLERS
GAGE PLUG
PRIMARY SENSOR GAGE PORT
Connector Block Module
BLP TEST TAP
Setpoint Module
Proportional Module
RP920A
4 8 9
2 3 1
60
40
20
W
1
0
%
5
10
20
40
30
DIR.
REV.
RP920A
1 – MAIN 2 – BRANCH 3 – PRIMARY
SENSOR
132
4 – VENT 8 – CLOSED/REMOTE
SETPOINT
9 – CPA
80
100
Xp (%)
45
PRIMARY SENSOR GAGE PORT
Connector
Block Module
BLP TEST TAP
Setpoint
Module
PROPORTIONAL BAND ADJUSTMENT KNOB
Proportional
Module
RP920B,C,D
4 8 9
32
2 3 1
60
40
20
W
1
0
%
5
10
20
40
30
DIR. REV.
100
Xp (%)
45
1
80
RP920D
7
GAGE PLUGS
7 6 5
100
80
60
20
40
TR
0.5
1
300
Ac (%)
5
50
1 – MAIN 2 – BRANCH
5
6
Wc
%
0
B
+
C
+
B C
Min
20
15
10
4
3
1.5
2
250
200
150
100
NEG.
POS.
3 – PRIMARY
SENSOR 4 – VENT 5 – COMPENSATION
SENSOR 6 – VENT 7 – VENT 8 – CLOSED/REMOTE
SETPOINT 9 – CPA
COMPENSATION SENSOR OR BRANCH GAGE PORT
COMPENSATION STARTPOINT ADJUSTMENT KNOB
Switch Block Module
Integral
7
Module
5
Compensation Module
MODULE KNOB SCREWS (DO NOT LOOSEN)
1
2
RP920C,D ONLY.
1
Fig. 2. Module and port Locations.
Connector Block Module
SENSOR SUPPLY OPEN
SWITCHPLATE
POSITION INDICATOR
2 3 1
SCREW
OPEN POSITION
BLOCKED POSITION
SENSOR SUPPLY BLOCKED (EXTERNAL RESTRICTOR)
SWITCHPLATE
C5102
Fig. 3. Primary sensor air supply.
Gage Function and Integral Action Cut-off Adjustment (RP920C and D)
The position of the gasket located under the switch block module (Fig. 2) determines the function of the field-installed Switch Block Module gage and enables/disables the integral action cut-off function. See Table 1 for factory and field settings.
RP920B,D ONLY.
2
CAPTIVE SCREW (4)
5
10
Xp (%)
20
45
40
30
DIR. REV. DIR. REV.
DO NOT ADJUST SCREW
NOTE LOCATION OF NOTCH
CONTROLLER LABEL
DIRECT ACTING
PROPORTIONAL MODULE
40
45
Xp (%)
5
REVERSE ACTING
Fig. 4. Changing controller action.
Table 1. Switch Block Gasket Position.
Model Field Setting
a
Options
RP920B B C RP920C B B+ RP920D B C, C+, B+
a
Shipped from the factory in this position. B = Branch line gage. C = Compensation sensor gage. + = Integral action cut-off enabled.
M17584
30
20
10
C5103
95-7392EF 2
CAPTIVE SCREW (4)
CAUTION
250
300
Ac (%)
5
50
100
POS.
NEG.
NEGATIVE COMP. (FACTORY SET)
200
150
DO NOT ADJUST SCREW
COMPENSATION MODULE
NOTE LOCATION OF NOTCH
100
150
200
250
POS.NEG.
POSITIVE COMP.
50
5
Ac (%)
300
C5104
Fig. 5. Changing from negative to positive compensation.
1.
Check the gasket tab position (Fig. 6, front view).
2.
Loosen the three switch block module screws and remove the module.
3.
Remove the gasket and note the letters (B, B+, C, C+) embossed on the module back.
4.
Rotate and/or flip the gasket until the gasket position matches the functions desired (Fig. 6, back view).
RP920A,B,C,D MODULAR PNEUMATIC CONTROLLERS
Adjustments:
1.
If using a scaleplate o ve r lay, insert the overlay betw ee n the setpoint knob and the transparent overlay retainer. Note positions of the key and non-coded scaleplate overlay notch (Fig. 7).
2.
Adjust the setpoint (W using the setpoint knob.
3.
If the control point deviates excessively from the setpoint (W consideration.
), calibrate, taking the throttling range into
1
), according to the job drawings,
1
REMOTE SETPOINT
Setpoint (W primary sensor span from a remote 3 to 15 ps i (21 to 103 k Pa)
) is controlled from 0 to 100 percent of the
1
bleed-type signal. Adjustments:
1.
Adjust the setpoint knob to 100 percent (Fig. 7) or to the maximum remote setpoint limit to be applied.
2.
Install the 14003755-001 Barb Fitting and O-ring to port 8 and connect to a bleed-type remote setpoint device (e.g., SP970) and a remote setpoint gage.
NOTE: With the correct gasket position, only the
desired let ter shows.
5.
Install the gasket on the switch block module back.
6.
Reinstall the module, and tighten the three screws.
7.
If used, connect the integral action cut-off switching components to ports 6 and 7.
GASKET SHOWN IN C POSTION. B, B+, AND C+ LEGENDS CANNOT BE SEEN WITH GASKET IN THE C POSTION, BUT ARE ILLUSTRATED HERE TO DISLPLAY LOCATION.
CAPTIVE SCREW (3)
Switch Block
+
B
+
C B C
B
B
+
GASKET TAB IN C POSITION
C
C
+
BACK
C5105
60
FRONT
7 6 5
W
100
80
%
0
40
20
c
+
B
+
C B C
Fig. 6. Integral action cut-off and gage
function gasket position.
Setpoint (W1) Adjustment
The setpoint knob is embossed with a 0 to 100 percent scale which correlates with the values in Table 3 (see Appendix). Scaleplate overlays are included to directly match various sensor ranges.
Three methods of controlling setpoint (W
LOCAL SETPOINT
Adjust setpoint (W
) directly on the controller.
1
) are available:
1
CONTROL POINT ADJUSTMENT (CPA)—AVAILABLE ON SPECIFIC MODELS
Local (baseline) setpoint (W and can be varied ±15 percent of the primary sensor span
) is adjusted on the controller
1
from a remote 3 to 15 psi (21 to 103 kPa) signal. Adjustments:
1.
Pipe CPA to port 9.
2.
If used, select the proper scaleplate overlay.
3.
Note the position of key on the setpoint knob and the non-coded scaleplate overlay notch (Fig. 7) for controllers with U.S. A. labels. Controlle rs (RP920B,C,D) with German labels must use “R” coded scaleplate overlay notch when using a CPA device.
4.
Insert the scaleplate overlay between the setpoint knob and the transparent overlay retainer.
5.
Adjust the setpoint (W using the setpoint knob.
) according to the job drawings
1
Proportional Band (Xp) Adjustment
Adjust the proportional band (Xp), according to the job drawings, using the proportional module proportional band adjustment knob (see Fig. 2).
Control Loss Hazard. Loosening knob screws can induce controller leaks.
Use CCT819 and Authority S etting Ad justment Tool or a narrow, stiff-blade putty knife to rotate adjustment knobs (Xp and Ac).
Authority (Ac) Adjustment (RP920B and D only)
Adjust the authority (Ac), according to the job drawings, with the compensation module authority adjustment knob (see Fig. 2).
3 95-7392EF
RP920A,B,C,D MODULAR PNEUMATIC CONTROLLERS
SCALEPLATE OVERLAY
"R" CODED SCALEPLATE OVERLAY NOTCH
OVERLAY RETAINER
SETPOINT KNOB
Setpoint Module
LABEL
C5106
SETPOINT KNOB KEY
R
NON-CODED SCALEPLATE OVERLAY NOTCH
60
40
20
20
80
W
1
100
0
%
5
10
Xp (%)
45
40
30
DIR. REV. POS. NEG.
HONEYWELL
RP920
SETPOINT
KNOB
TR
0.5
1
Ac (%)
5
Min
20
15
10
7 5
4
3
1.5
2
250
300
200
150
50
100
Fig. 7. Setpoint (W1) Adjustment.
Compensation Startpoint (Wc) Adjustment (RP920B and D only)
Adjust the compensation startpoint (Wc), according to the job drawings (reset schedule), using the compensation startpoint adjustment knob (see Fig. 2). For direct-acting sensors, the knob setting is equal to the compensation value corresponding to th e lowest value given for the pr imary senso r (from the reset schedule). See Fig. 9 and 10. If the value given is not a percentage, convert it to a percentage of the compensation sensor range using Table 3 (see Appendix):
1.
Find the correct sensor range column.
2.
Find the desired temperature in the column.
3.
Read the equivalent pressure in the second column.
4.
Read the equivalent pe rcentage in the first co lumn.
Reset Time (Tr) Adjustment (RP920C and D only)
Adjust the reset time (Tr), according to the job drawing s, using the reset time adjustment knob (see Fig. 2):
1.
Decrease setting until the system becomes unstable.
2.
Increase the setting slightly until the system becomes stable.
Replacing Cover
1.
If a cover is used, snap the cover straight on the front.
2.
The cover can be secured further by tightening the self­tapping screw in the cover lower right corner.
CALIBRATION
Sensors
Sensors are calibrated to the sy st em a nd req uire n o separate calibration.
Systems
All RP920 Controllers a re f actory calibrat ed. It i s int end ed tha t the controller be adjusted to the field-calculated values listed on the job drawing. This controller startup approach will be adequate for most systems. If it is determined that closer calibration is required, use the following procedures:
NOTES:
— The controller allows all adjustments to be made
independently. For example, changing the proportional band (X calibration of the: setpoint (W startpoi nt (W
— If a CPA device is used, apply 9 psi (62 kPa) to
), or authority (Ac) adjustment.
c
port 9.
— If a remote setpoint is used, block port 8.
RP920A System
1.
Install either: a. a temporary receiver gage (matching the primary
sensor) or a 0 to 30 psi (0 to 207 kPa) gage in the primary sensor gage port if one is not permanently installed, or
b. a “tee” gage into the sensor line (port 3).
2.
Apply mainline pressure (MLP) to the system.
3.
Install a 0 to 3 0 psi (0 to 207 kPa) gag e in the branchli ne pressure (BLP) test tap (moisten the needle before inserting).
4.
If the sensor reading is greater than ±10 percent of the expected setpoint, remove the se nsor tubing from por t 3 and apply a pressure equivalent (expected setpoint) using a CCT816B Calibration Unit.
NOTE: For the most accurate calibration, the actual
measured variable at the sensor must be ±10 percent of the expec ted se tpo int.
5.
With the sensor at or near the desired control point, adjust the setpoint knob until the BLP equals the controlled device throttling range midpoint, e.g., 8 psi (55 kPa) for a 3 to 13 psi (21 to 90 kPa) range device.
6.
If the setpoint (W match, remove the setpoint knob and replace it so the
) and primary sensor gage do not
1
setpoint matches the primary sensor gage reading.
7.
Ensure W
8.
Calibration is complete.
is at the desired setpoint.
1
RP920B Systems
1.
Install in port 5 either a receiver gage that matches the compensation sensor, or a 0 to 30 psi (0 to 207 kPa) gage (see Fig. 8).
) setting does not affect the
p
), compensation
1
95-7392EF 4
NOTE: If the controller is setup for a compensation
gage in the right gage p ort, plug port 5 and use the existing gage.
RP920A,B,C,D MODULAR PNEUMATIC CONTROLLERS
PRIMARY SENSOR
FULL COMP
SETPOINT
(W1 )
COMPENSATION STARTPOINT (Wc )
COMPENSATION SENSOR
C5111
2.
Install a 0 to 30 psi (0 to 207 kPa) gage in BLP test tap or in BLP gage port if one is not permanently installed.
3.
Apply MLP to the system.
4.
Adjust the authority knob to minimum.
5.
Adjust the compensation startpoint knob until the receiver gage (port 5) reads the pressure equivalent of the compensation startpoint (W
6.
If the compensation startpoint (W startpoint do not match, rem ov e the k no b and re pla ce it
) (Fig. 9 or 10).
c
) and desired
c
so they do match.
7.
The compensation startpoint (W
) is now calibrated.
c
NOTE: The response of the receiver gage may be
slow (up to one minute). The controller is not defective under these conditions.
8.
Set up the CCT816B Calibration Unit (Fig. 11) to connect to port 3 (primary sensor).
NOTE: Sensors are not connected.
THE GAGE RANGE MUST MATCH THE RANGE OF THE SENSOR FEEDING PORT 5
PRIMARY SENSOR
4 8 9 7 5 2 3 1 6
M
C5109
17.
Remove the CCT816B Calibration Unit and pipe sensors.
RP920C and D Systems
1.
Remove the integral module screw (Fig. 13) and install the 14003755-001 Barb Fitting and O-ring in its place.
2.
Apply 8 psi (55 kPa) to the integral module.
3.
Calibrate the RP920: a. RP920C: follow the procedure for the RP920A. b. RP920D: follow the procedure for the RP920B
except that the calibration value of the BLP for
4.
Fig. 9. Negative compensation calibration reset sc hedule.
Steps 10 and 15 should both be 8 psi (55 kPa). When calibration is complete, remove the barb fitting from the integral module and replace the screw.
FULL COMP
PRIMARY SENSOR
SETPOINT
(W 1)
COMPENSATION STARTPOINT (Wc )
C5110
COMPENSATION SENSOR
Fig. 8. Piping for RP920B compensation
startpoint (W
9.
Apply a pressu re equ ivale nt of the p rimary sen sor valu e
c
corresponding to the compensation start ( the reset schedule (Fig. 9 or 10).
10.
Adjust the setpoint knob until the BLP equals the expected pressur e of the cont rolled device at conditions.
11.
If needed, remove the setpoint knob and replace it so the setpoint matches the primary sensor value at
comp start
12.
The setpoint (W
13.
Set up the CCT816B Calibration Unit (Fig. 12) to
.
) is now calibrated.
1
connect to port 3 (primary sensor) and port 5 (compensation sensor).
14.
Apply sensor input pressures equivalent to the full compensation on the building schedule.
15.
Adjust the authority (A expected pressure of the controlled device at full
) knob until the BLP equals the
c
compensation conditions.
16.
Calibration is complete.
IMPORTANT
Changing compensation startpoi nt (W (W1) affects only the one corresponding value of the reset schedule, while changing authority (A only the slope of the reset schedule.
NOTE: See the Compensation Startpoint (W
Adjustment section for more information.
) setting.
comp start
comp start
) or setpoint
c
) affects
c
)
c
) on
Fig. 10. Positive co m pen sa ti on c al ibr a ti on r e se t sc he du le .
RP920B Calibration Example
Assume the following conditions: — A 10°F (5.6K) throttling range. — Using a 2.5 to 6.5 psi (17 to 45 kPa) operator with a
normally open (N.O.) valve where conditions are: 6.5 psi
(45 kPa) with no load and 2.5 psi (17 kPa) with full load. — See Fig. 14 for the schedule graph. — See Table 2 for the reset schedule.
Table 2. Reset Schedule.
Compensation
Range
Start 120°F (49°C) (40%) 60°F (16°C) (50%) Full 160°F (71°C) (60%) 0°F (-18°C) (20%) Operating Span 40°F (22K) 60°F (33K) Sensor Range 40 to 240°F
5 95-7392EF
Primary Sensor
(Discharge)
(4 to 11 6°C)
Compensation
Sensor (OA)
-40 to 160°F (-40 to 71°C)
Loading...
+ 11 hidden pages