Honeywell RM7895A2014, RM7895A1048, RM7895B2013, RM7896A2012, RM7895C1020 Installation Instructions Manual

...
32-00156-01
RM7895A,B,C,D/EC7895A,C; RM7896A,C,D 7800 SERIES Relay Modules
INSTALLATION INSTRUCTIONS
APPLICATION
The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D are microprocessor-based integrated burner controls for automatically fired gas, oil, or combination fuel single burner applications. They are intended to replace the R4795 and R7795 Primary Controls. The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D systems consist of a relay module, subbase, amplifier, and purge card. Options include: 2-line VFD (see document 65­0090-6) or 4-line LCD (see document 32-00110-01) Keyboard Display Module, Personal Computer Interface, Data ControlBus™ Module, remote display mounting, expanded annunciator and Combustion System Manager® Software.
Functions provided by the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. The RM7896 provides a postpurge function.
This document covers the following 7800 Series Relay Modules:
• RM7895A1014
• RM7895A1048
• RM7895B1013
• RM7896A1012
• RM7895A2014
• RM7895A2048
• RM7895B2013
• RM7896A2012
• RM7895C1020
• RM7895C1012
• RM7895D1011
• RM7896C1010
• RM7896D1019
• RM7895C2020
• RM7895C2012
• RM7895D2011
• RM7896C2010
• RM7896D2019
• EC7895A1010
• EC7895A2010
• EC7895C1000
• EC7895C2000
This document provides installation and static checkout instructions. Other applicable publications are:
Publication
No. Product
32-00110 S7800A2142 4-line LCD Keyboard
Display Module Product Data
63-2278 Q7700 Network Interface Unit Product
Data
65-0084 Q7800A,B 22-Terminal Wiring Subbase
Product Data
65-0090 S7800A1142 2-line VF Keyboard Display
Module Product Data
65-0091 S7810A Data ControlBus Module™
Product Data
65-0095 S7820 Remote Reset Module Product
Data
65-0097 221729C Dust Cover Packing
Instructions
65-0101 S7830 Expanded Annunciator Product
Data
65-0102 ZM7850A Combustion System Manager™
Operating Instructions
65-0109 R7824, R7847, R7848, R7849, R7851,
R7861, R7886 Flame Amplifiers for the 7800 Series Product Data
65-0131 221818A Extension Cable Assembly
Product Data
65-0229 7800 SERIES Relay Modules Checkout
and Troubleshooting Product Data.
65-0092 QS7800A ControlBus™ Module, Standard
65-0227 QS7800B ControlBus™ Module,
Multidrop
SPECIFICATIONS
Electrical Ratings (See Table 3):
Voltage and Frequency: RM7895/RM7896: 120 Vac (+10/-15%), 50/60 Hz (±
10%).
EC7895A,C: 220/240 Vac (+10%/-15%), 50/60 Hz
(±10%) Power Dissipation: 10W maximum. Maximum Total Connected Load: 2000 VA.
SIL
3
Capable
RM7895A,B,C,D/EC7895A,C; RM7896A,C,D 7800 SERIES RELAY MODULES
WARNING
WARNING
Fusing Total Connected Load: 15A Fast Blow, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to +60°C). Storage: -40°F to 150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncon-
densing.
Vibration: 0.5G environment.
SIL 3 Capable
SIL 3 Capable in a properly designed Safety Instrumented
System. See form number 65-0312 for Certificate Agreement.
Approvals:
RM7895/RM7896:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ. Factory Mutual Approved: Report No. 1V9A0.AF. Swiss RE (formerly IRI): Acceptable. Federal Communications Commission: Part 15, Class
B, Emissions.
EC7895A,C:
Factory Mutual Approved.
INSTALLATION
When Installing this Product…
1.
Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi-
tion.
2. Check the ratings given in the instructions and
marked on the product to make sure the product is
suitable for the application.
3. Installer must be a trained, experienced, flame safe-
guard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
2. Wiring must comply with all applicable codes, ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wir­ing.
4. Loads connected to the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D must not exceed those listed on the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D label or the Specifications; see Table 1.
5. Limits and interlocks must be rated to simultane­ously carry and break current to the ignition trans­former, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component­recognized by authorities who have proper juris­diction.
7. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safeguard control and the main fuel valve(s).
8. Two flame detectors can be connected in parallel with the exception of Infrared Flame Detectors (C7015).
9. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, can cause interference with radio communications. It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference, in which case, the users, at their own expense, may be required to take whatever measures are required to correct this interference.
10. This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Location
Fire or Explosion Hazard. Can cause property damage, severe injury, or death.
Follow applicable safety requirements when installing a control on a burner to prevent death or severe injury.
Electrical Shock Hazard. Can cause serious injury, death or equipment damage. Disconnect power supply before beginning installation.
IMPORTANT
1. Wiring connections for the relay modules are unique; refer to Fig. 2 and 3 or the appropriate Specifications for proper subbase wiring.
32-00156—01 2
Humidity
Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85% relative humidity continuous, noncondensing, moisture environment. Condensing moisture can cause a safety shutdown.
Vibration
Do not install the relay module where it can be subjected to vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When installed outdoors, protect the relay module in an approved weather-tight enclosure.
RM7895A,B,C,D/EC7895A,C; RM7896A,C,D 7800 SERIES RELAY MODULES
WARNING
Mounting Wiring Subbase
1. Mount the subbase in any position except horizon-
tally with the bifurcated contacts pointing down. The standard vertical position is recommended. Any other position decreases the maximum ambient temperature rating.
2. Select a location on a wall, burner or electrical panel.
The Q7800 can be mounted directly in the control cabinet. Be sure to allow adequate clearance for ser­vicing, installation, access or removal of the relay module, Expanded Annunciator, Keyboard Display Module, flame amplifier, flame amplifier signal volt­age probes, Run/Test Switch, electrical signal volt­age probes and electrical field connections.
3. For surface mounting, use the back of the subbase
as a template to mark the four screw locations. Drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws.
Wiring Subbase
NOTE: There are several different subbase models that
can be purchased. It is important to note which subbase is compatible with the relay module when purchasing repair or replacement parts.
Series 1000 Subbase
All relay product codes that start with a 1 (example: RM7840G1 Q7800A1005/U. These relays can also be used on the Series 2000 subbase noted below.
Series 2000 Subbase
All relay product codes that start with a 2 (example: RM7840G2 Q7800A2005/U.
Subbase Compatibility
Any relay module in the 1000 series is fully backward compatible with any subbase already installed in the field (Q7800A1005/U, Q7800B1003/U, Q7800A2005/U, Q7800B2003/U).
014/U) can be used with existing subbase
014/U) can be used with subbase
Any relay module in the new 2000 series will only be able to be installed on subbase Q7800A2005/U, and will not be backward compatible with any Q7800A1005/U legacy subbases already installed in the field.
IMPORTANT
Make sure to check the relay model number and check the subbase compatibly prior to ordering or attempting a new installation or field upgrade.
If you attempt to place a 2000 series relay on a non-compatible 1000 series subbase, you will receive an error code of 101. This indicates that you must a) change out the subbase to a Q7800A2005/U or b) choose a compatible 1000 series relay module.
Electrical Shock Hazard. Can cause serious injury, death or equipment damage. Disconnect the power supply before beginning installation.
The internal block diagram of the RM7895A,B,C,D/EC7895A,C;RM7896A,B,C,D is shown in Fig. 1.
1. For proper subbase wiring and sequence chart, refer
to Fig. 2 and 3.
2. For remote wiring of the Keyboard Display Module,
refer to the Specifications for the 2-line VFD KDM (65-0090), the 4-line LCD KDM (32-00110), Net­work Interface Unit (63-2278), Data ControlBus™ Module (65-0091) or Extension Cable Assembly (65-
0131).
3. Disconnect the power supply from the main discon-
nect before beginning installation to prevent electri­cal shock and equipment damage. More than one disconnect can be required.
4. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where required, must comply with NEC, Class 1 (Line Volt­age) wiring.
5. For recommended wire size and type, see Table 1.
6. For recommended grounding practices, see Table 2.
3 32-00156—01
RM7895A,B,C,D/EC7895A,C; RM7896A,C,D 7800 SERIES RELAY MODULES
CONFIGURATION JUMPERS
MICROCOMPUTER
RESET PUSHBUTTON
RUN/TEST SWITCH
STATUS LEDs
PLUG-IN PURGE TIMER CARD
SAFETY RELAY CIRCUIT
POWER SUPPLY
OPTIONAL KEYBOARD DISPLAY MODULE
PLUG-IN FLAME AMPLIFIER
RELAY DRIVE CIRCUIT
CONTROL POWER
TEST JACK
REMOTE RESET
DDL
DDL COMMUNICATIONS
INDICATES FEEDBACK SENSING TO RELAY STATUS FEEDBACK AND LINE VOLT INPUTS
FIELD WIRING
INTERNAL WIRING
IGNITION
PILOT
MAIN VALVE
1K
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
LIMITS
CONTROLLER
INTERLOCK (INCLUDING AIRFLOW SWITCH)
1K1 2K1 5K1
FLAME SIGNAL
TEST
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
LOCKOUT IF JUMPER JR2 REMOVED.
RS485
1
2
3
L1 (HOT)
L2
5
6
7
4K1
2K2
10
8
9
7K
6K
5K
4K
3K
2K
F
G
22
1
BLOWER
6K1
4
ALARM
3K1
3
L2
M23996
1
RM7895, RM7896: 120 VAC, 50/60 HZ. EC7895A,C: 220-240 VAC, 50/60 HZ.
2
2
Fig. 1. Internal block diagram of RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D
(see Fig. 2 and 3 for detailed wiring instructions).
32-00156—01 4
M23997
G
L2
3
5
6
7
8
9
10
F
(L1)
13
14
15
16
17
18
19
20
21
22
12
MASTER SWITCH
IGNITION
MAIN FUEL VALVE(S)
BURNER CONTROLLER/LIMITS
BURNER MOTOR (BLOWER)
INTERMITTENT PILOT/IGNITION
RM7895, RM7896: 120 VAC , 50/60 HZ; EC7895: 220-240 VAC, 50/60 HZ POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
FOR EC7895, A 220 TO 240 VAC TO 120 VAC, 10 VA MINIMUM STEPDOWN TRANSFORMER (NOT PROVIDED) MUST BE USED TO DRIVE THE SHUTTER.
FOR DIRECT SPARK IGNITION (OIL OR GAS)
LINE VOLTAGE ALARM
L1 (HOT)
L2
1
8
10
IGNITION TRANSFORMER
MAIN VALVE
1
Q7800
2
2
L2
4
LOCKOUT INTERLOCK (INCLUDING AIRFLOW SWITCH)
FLAME DETECTOR
IGN
OPERATING CONTROLS AND INTERLOCKS
INITIATE
ALARM ALARM
STANDBY
POWER POWER
PILOT
FLAME
MAIN
TIMED PURGE
ALARM
POWER
PILOT
FLAME
MAIN
RUN
STANDBY
BURNER START
MAIN VALVE
LIMITS AND BURNER CONTROLLER CLOSED
IGN/ PILOT
SAFE START CHECK
FLAME PROVING
SSC
LED DISPLAY
POWER
PILOT
FLAME
MAIN
PFEP
4 OR 10 SEC
POWER
START
POWERPOWER
FLAME SIGNAL
SEE FLAME DETECTOR SPECIFICATIONS FOR CORRECT WIRING.
FOR RM7895A1048 (ONLY), IGNITION TERMINAL 10 IS DE-ENERGIZED WHEN FLAME IS PROVEN.
AIRFLOW SWITCH CHECK FEATURE IS FOR THE RM7895B,RM7896B.
RM7896A,B ONLY.
00 00 00
10
L1
TO
6
9
8
BURNER/BLOWER MOTOR
LOCKOUT INTERLOCK CLOSED
AFSC
TO
7
6
4
3
5
3
4
5
6
7
POST PURGE
15 SEC
POWER
6
7
7
AIRFLOW SW CHECK
4
RM7895A,B,C,D/EC7895A,C; RM7896A,C,D 7800 SERIES RELAY MODULES
Fig. 2. Wiring subbase and sequence chart for RM7895A,B/EC7895A; RM7896A,B.
5 32-00156—01