Honeywell RF6GB Installation Instructions Manual

The RF6GB is a wireless glassbreak detector intended for use with Honeywell controls that support SiX™
Mounting
To remove the mounting bracket:
Note
BETA DRAFT – 01/12/15
Series devices.
within 7.6 m (25 feet) of the protected glass;
within clear view of the protected glass;
at least 2 m (6.5 feet) from the floor;
at least 1 m (3.3 feet) from forced air ducts;
at least 1 m (3.3 feet) from sirens or bells greater than 5 cm (2 inches) in diameter.
between the protected glass and any heavy window coverings.
when heavy window coverings are present, the detector can be mounted on the window frame.
Avoid mounting the detector on the same wall as the protected glass, on free­standing posts or pillars, or in rooms with noisy equipment (air compressors, bells, power tools, etc.), if this equipment is operated when the detector is armed.
UL requirements: TBD
Turn the top of the detector 15 degrees counter-clockwise and separate the mounting bracket.
: Before mounting the RF6GB permanently, conduct Go/No Go tests (see control’s instructions) to verify adequate signal strength and adjust the device location and orientation as necessary.
The RF6GB can be mounted on the wall
or on the ceiling.
The rear tamper plate MUST be mounted
to a stud, solid wood, or with a robust wall anchor.
Enroll
This device can be enrolled and programmed either before or after installation.
*Note
Note
Program the RF6GB
Temperature Sensing
Sensitivity Setting
Approximate Range
1. Set the Lyric Smart Controller in
Programming Mode.
2. Remove the battery tab to activate the
device and begin the enrollment process.
3. The RF6GB Green LED flashes during
enrollment (about 8 seconds*)
: Depending on the signal strength between the device and the control, the enrollment period may take longer than 8 seconds.
The device sends its unique MAC ID address (Serial Number) and Services information to the control.
The control registers the device and displays the transmitter data on screen.
4. Enrollment is confirmed When the RF6GB Green LED is ON for 3 seconds
[and the control beeps TBD].
5. If the sensor is not successfully enrolled during the enrollment period, the LED turns off and the device powers down. Activate the tamper, power down and up again, or use the FG701 Glassbreak Simulator to restart the enrollment process.
: Once enrolled in a system, the detector cannot be used with another control panel until it is removed from the current control panel. See the Control’s instructions for details on removing devices.
Consult the Control’s instructions for programming the device in the system.
Fault device features to “Learn” device “Services” in the control:
- Tamper switch
- Selectable Sensitivity Settings
- Temperature sensing
Temperature sensing range is 0 – 50°C / 32 – 122°F and is always enabled. Program the system to use the temperature information at the panel.
High 4.6-7.6m / 15-25 ft.
Medium 3-4.6m / 10-15 ft.
Low 1.5-3m / 5-10 ft.
Lowest 0-1.5m / 0-5 ft.
The RF6GB detector is Factory set at HIGH sensitivity. Change the sensitivity setting at the Control Panel.