Honeywell RAEGuard 2 PID Installation Guide

Technical Note
Installation and Maintenance of a RAEGuard 2 PID
INTRODUCTION
The Honeywell® RAEGuard 2 PID is a fixed photoionization detector (PID) that measures a broad range of Volatile Organic Compounds (VOCs). The RAEGuard 2 PID monitor operates in flow through mode. Housed in an explosion-proof stainless-steel enclosure, the RAEGuard 2 PID can be used in most environments, including hazardous environment applications for measuring toxic gases. Therefore, correct installation and maintenance is required to ensure effectiveness as a VOC monitor.
This technical note describes guidelines for installation, commissioning, testing, calibration and maintenance of the RAEGuard 2 PID and the factors that need to be considered.
INSTALLATION
This instrument can be installed as a stand-alone unit or as part of a multi-point VOC monitoring system.
Preface
1998-1001 Rev 1 11/16
It is vital to understand the gas and conditions to be measured. Many factors can impact the performance of an active sampling system, including dust, water condensation, gas condensation, and pressure within a duct.
Dust
Unless the particle size is less than 1 micron, the only impact on the performance is the filter replacement interval.
Water condensation
The RAEGuard 2 PID system is able to operate within a relative humidity range of 0 to 95%, non-condensing, without distortion of the actual VOC concentration reading. Nevertheless, water vapors are very often present within VOC samples, especially in many duct sampling applications. The sample temperature very often is high enough, and is higher than at the measurement point. On the way from the sampling point to the instrument, the sample gas is cooling. As temperature decreases, relative humidity (RH) of the water vapors in the VOC samples increases and may reach 100% or the dew point. If the temperature at the measuring point is lower than the dew point, water vapor may condense in the tubing, on the PID lamp, and on the PID electrodes. The amount of condensed water may be significant and may affect the accuracy of the measurement.
For example
If the sampling temperature is 122° F (50° C) and 40% RH, and at the measurement point the temperature is 77° F (25° C), about 10 g of water may condense from 1m3 of the sampling air within two (2) to three (3) days.
1
Technical Note
Installation and Maintenance of a RAEGuard 2 PID
Presence of water must be considered at the lowest ambient temperature and the highest RH at the highest temperature in the sample line. This calculation must be performed when sampling from ducts (additional sampling equipment may be required). Honeywell recommends using a water-collecting filter; housing part number 490-0163-000 and filter replacement 490-0164-010 (pack of 10).
Figure 1. Water-collecting filter
Note: Filter housing and filter replacement elements are currently available only in North America. Contact Honeywell for more information. The filter is installed between the sample source and the instrument, at a location where the temperature does not exceed the instrument’s rated operating temperature.
1998-1001 Rev 1 11/16
Target and background gases condensation
Many toxic gases have a low vapor pressure. Therefore, gas may become a liquid or a crystal even at very low concentrations if the temperature at the measurement point is lower than at the sampling point. This factor must be considered before selecting an active sampling system.
The following example illustrates the fundamentals of the vapor pressure issue:
Phenol
The Honeywell® RAEGuard 2 PID can be used in phenol factories all over the world. Phenol can crystallize from the gas phase to the solid phase when its vapor pressure in the gas state is higher than that of the sublimation vapor of the solid phenol. This process depends greatly on the temperature variations, since vapor pressures depend on them.
The approximate maximum Phenol gas concentrations in air at different temperatures are as follows:
At 122° F (50° C): The maximum concentration of phenol is around 3600 ppm.
At 77° F (25° C): The maximum concentration of phenol is around 440 ppm.
Pressure
Until pressure variation is within a specified range of 90 to 110 kPa, a monitoring instrument gives a correct reading. Make sure the pressure in the sampling duct does not exceed these values. Slightly exceeding them is acceptable, but the reading may be distorted. That distortion does not relate to the PID itself, which is rather stable in terms of pressure variation, but it does relate to sampling gas density variation.
2
Loading...
+ 3 hidden pages