Honeywell RAEGuard 2 PID Operating Manual

RAEGuard 2 PID
___________________________________
User Guide
___________________________________
P/N: H-D03-4001-000 Rev M February 2018
RAEGuard 2 PID User’s Guide
Contents
Section 1: RAEGuard 2 PID User’s Guide
1 General Information ............................................................ 6
2 General Specifications ......................................................... 8
2.1 RAEGuard 2 PID Specifications ........................... 8
2.2 Proper Product Disposal At End Of Life ............... 9
3 Operation ........................................................................... 10
4 Physical Description .......................................................... 11
5 Physical Dimensions ......................................................... 11
6 Installation and Access Instructions .................................. 12
6.1 Mounting ............................................................. 12
6.2 Instrument Disassembly ...................................... 14
6.3 Electrical Wiring ................................................. 15
6.4 Wiring Procedure ................................................. 16
6.5 Earth Grounding Instructions .............................. 17
6.5.1 External Earth Grounding ................................ 17
6.5.2 Internal Earth Grounding ................................. 17
6.5.3 Finished Grounding Wires .............................. 18
6.6 Alarm Contact Setup ........................................... 18
7 Display And User Interface ............................................... 20
7.1 User Interface ...................................................... 20
7.2 Magnet Key ......................................................... 20
7.3 Using The Magnet Key ....................................... 21
7.4 System Initialization ............................................ 21
7.5 Reading Display .................................................. 21
7.6 Instrument Status Display .................................... 22
8 Navigating Settings ........................................................... 23
9 Programming Menus ......................................................... 27
Zero/Fresh Calibration......................................................... 27
Meas. Unit* ...................................................................... 27
High Alarm ....................................................................... 27
Temp. Unit ........................................................................ 27
Span Calibration ................................................................. 27
Meas. Range* ................................................................... 27
Low Alarm ........................................................................ 27
1
2
RAEGuard 2 PID User’s Guid e
Language .......................................................................... 27
Set Span Value ................................................................. 27
Meas. Gas* ....................................................................... 27
Ext. Alarm Delay* ............................................................ 27
Pump Duty (%)* ............................................................... 27
Calibration Type* ............................................................. 27
Pump Cycle(s)* ................................................................ 27
Calibration Gas* ............................................................... 27
Pump Status* .................................................................... 27
Bus Baudrate .................................................................... 27
Analogout 4mA ................................................................ 27
Analogout 20mA ................................................................ 27
Unit ID .............................................................................. 27
LCD Contrast .................................................................... 27
LCD Backlight .................................................................. 27
Change Password* ............................................................ 27
9.1 Entering Programming Mode .............................. 28
9.2 Calibration ........................................................... 29
9.3 Measurement (Advanced Mode) ......................... 32
9.4 Alarm Setting ....................................................... 35
9.5 Monitor Setup ...................................................... 37
10 Calibration .................................................................. 43
10.1 Zero Calibration ................................................... 44
10.2 Span Calibration .................................................. 46
11 Alarm Signal Summary .............................................. 48
12 Maintenance ............................................................... 50
13 DigiPID Sensor Module Replacement ....................... 50
14 Troubleshooting .......................................................... 52
SECTION 2: DigiPID User’s Guide
SAFETY INSTRUCTIONS ..................................................... 54
15 Read Before Operating ............................................... 55
15.1 DigiPID Marking ................................................. 56
15.2 Operation Area and Conditions ........................... 57
15.2.1 Hazardous Areas classified by Zones ............ 57
15.2.2 Hazardous Areas classified by Divisions ...... 57
3
RAEGuard 2 PID User’s Guid e
15.3 Instruction For Safe Use ...................................... 57
15.4 Use In Hazardous Areas ...................................... 58
15.5 Year of manufacture ............................................ 58
15.6 Specifications ...................................................... 59
16 General Informatio n ................................................... 60
17 Grounding (Earth Connection) ................................... 61
18 Physical Description ................................................... 62
19 Sensor Parts And Dimensions .................................... 63
20 Operating the Sensor Module ..................................... 64
20.1 Preparing The Sensor For Use ............................. 64
21 Using The Sensor Module .......................................... 65
21.1 Gas Flow Routing Connection ............................ 65
21.2 Sensor Module Calibration .................................. 66
21.3 Maintenance And Calibration .............................. 68
21.4 Replacing the Lamp And Filter ........................... 68
22 Replacing The Sensor’s Teflon UV Shield ................ 70
23 Sensor & Lamp Cleaning/Replacement ..................... 73
23.1 Cleaning The PID Sensor .................................... 73
23.2 Cleaning The Lamp Housing Or
Changing The Lamp ............................................ 74
23.3 Cleaning The Instrument ..................................... 75
23.4 Ordering Replacement Parts ................................ 75
23.5 Special Servicing Note ........................................ 75
24 Electronic Waste Disposal .......................................... 76
25 Appendix A: Range, Sensor and
Related Configuration ................................................ 77
26 ModBus/RS-485 Information ..................................... 77
27 Appendix B: Controlled Section ................................ 79
27.1 Scope ................................................................... 79
27.2 Contents ............................................................... 79
27.3 Scope ................................................................... 81
27.4 Responsibility ...................................................... 81
27.5 Contents ............................................................... 81
28 Technical Support ....................................................... 89
29 Honeywell Analytics Contacts ................................... 89
4
RAEGuard 2 PID User’s Guid e
© Honeywell International ©2018. All Rights Reserved.
This document is the confidential and proprietary information of Honeywell. Reproduction and distribution of these materials without the express written consent of Honeywell is strictly forbidden. While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a purpose and makes no express warranties except as may be stated in its written agreement with and for its customer.
In no event is Honeywell liable to anyone for any direct, special, or consequential damages. The information and specifications in this document are subject to change without notice.
These commodities, technology, or software were exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law prohibited.
This product may contain or be derived from materials, including software, of third parties. The third-party materials may be subject to licenses, notices, restrictions and obligations imposed by the licensor. The licenses, notices, restrictions and obligations, if any, may be found in the materials accompanying the product, in the documents or files accompanying such third party materials, in a file named third­party licenses on the media containing the product, or at http://www.honeywell.com/ps/thirdpartylicenses.
Honeywell, RAEGuard 2 PID, and DigiPID are U.S. registered trademarks of Honeywell International Inc. Other brand or product names are trademarks of their respective owners.
5
RAEGuard 2 PID User’s Guid e
Section 1: RAEGuard 2 PID User’s Guide
6
RAEGuard 2 PID User’s Guid e

1 General Information

The RAEGuard 2 PID is a fixed photoionization detector (PID) that measures a broad range of volatile organic compounds (VOCs). It operates on 10 to 28 VDC and provides an analog (4-20mA) three­wire signal output, and RS-485 Modbus digital signal output. RAEGuard 2 PID uses an intelligent processing platform and digital sensor technology, supports multiple ranges and resolutions, and can perform off-line calibration and environmental self-adaptation. RAEGuard 2 PID has a graphic display and local sound alarm and light status indicator. A magnetic key interface enables the detecto r to be calibrated and operational parameters adjusted with the explosion­proof enclosure in place. In addition, the PID module can be easily removed in hazardous locations for calibration or maintenance.
Key features:
Digital Smart Sensor Technology
Three wires, supports 4-20mA analog output
Operates in flow-through mode and can be used in most
environments
RS-485 digital communication in ModBus protocol
Explosion-proof stainless-steel enclosure for hazardous
environment applications
Magnetic-key interface eliminates the need to open the explosion-
proof housing when adjusting parameters.
Matrix LCD of 128x64 supports graphic display
LED alarms when High or Low alarm point is reached
Operation at 10 to 28 VDC
Three dry contacts (<30V, 2A) normally open (or normally closed),
one for High and Low alarm, another for Fault alarm
7
ATEX
II 2 (1) G Ex db [ia Ga] IIC T4 Gb
UL/CSA
Class I, Div. 1, Groups A B C D T4
IECEx TR CU
Ex db [ia Ga] IIC T4 Gb 1Ex d [ia Ga] IIC T4 Gb X
RAEGuard 2 PID User’s Guid e
Applications:
Refineries, petrochemical and natural gas plants
Metallurgical
Chemical, medication
Environmental protection
Electricity, communications
Fire protection
Utilities
Pulp and paper, printing
Storage
Sewage disposal
Food, brewing
Scientific research, education, homeland security
Hazardous Location Classification:
8
Basic Parameters
Principle
PID (photoionization detector)
Sensor
Digital Smart Sensor
Sampling
Internal diaphragm pump
Working Current
DC 10 to 28V, 210mA at 24V
Power
<5W
4-20mA
RS-485 (Supports Modbus)
IP Rating
IP-65
Mechanical Interface
3/4" NPT Male
Installation
2" pipe-holding or wall mounting
User Interface
Three-key magnetic bar adjustment
Calibration
Two or three points
Environmental Parameters
Temperature
-20° C to +55° C (-4° F to 131° F)
Humidity
0 to 95% relative humidity, non-condensing
Pressure
90 to 110kPa
Display
128x64 matrix backlit LCD, supports graphic display
RAEGuard 2 PID User’s Guid e

2 General Specifications

2.1 RAEGuard 2 PID Specifications

Output
Display
Three-level programmable alarm relays
(30 VDC, 2A)
9
Physical Parameters
Dimensions, L x W x H
257 x 201 x 107 mm (10.1" x 7.9" x 4.2")
Material
Stainless steel
Weight
3.5 kg (7.7 lbs)
Certification
ATEX
II 2 (1) G Ex db [ia Ga] IIC T4 Gb
UL/CSA
Class I, Div. 1, Groups A B C D T4
IECEx
Ex db [ia Ga] IIC T4 Gb
TR CU
1Ex d [ia Ga] IIC T4 Gb X
Ex Entity Parameters
Um: 28VDC (input supply)
RAEGuard 2 PID User’s Guid e
RAEGuard 2 PID Specifications (continued)
Sensor Specifications: See DigiPID sensor section on page 59.

2.2 Proper Product Disposal At End Of Life

The Waste Electrical and Electronic Equipment (WEEE) directive (2012/19/EU) is intended to promote recycling of electrical and electronic equipment and their components at end of life. This symbol (crossed-out wheeled bin) indicates separate collection of waste electrical and electronic equipment in the EU countries. This product may contain one or more Nickel-metal hydride (NiMH), Lithium-ion, or Alkaline batteries. Batteries must
be recycled or disposed of properly. At the end of its life, this product must undergo separate
collection and recycling from general or household waste. Please use the return and collection system available in your country for the disposal of this product.
10
RAEGuard 2 PID User’s Guid e

3 Operation

The calibration of all newly purchased Honeywell Analytics instruments should be tested by exposing the sensor to a known concentration calibration gas before the instrument is used or put into service. Prior to factory shipment, the RAEGuard 2 PID is calibrated and tested. However, the user should calibrate the instrument before the first use.
Kit Accessories include: RAEGuard 2 Magnet Key, and User’s Guide.
11
201mm (7.9")
290 mm (11.4")
133 mm
107mm
RAEGuard 2 PID User’s Guid e

4 Physical Desc ript ion

The RAEGuard 2 PID can be easily installed and integrated with various control systems. It is designed with flexible pipe­holding/wall-mounting options and standard connection terminals.

5 Physical Dimen sio ns

The physical dimensions are as shown:
(4.2")
(5.23")
12
WARNING
RAEGuard 2 PID User’s Guid e

6 Installation and Access Instructions

1. To prevent ignition of hazardous atmospheres, area must
be free of flammable vapors and supply circuit must be disconnected before removing cover.
2. For European application, the installation must comply with the requirements of EN 60079-14.

6.1 Mounting

First, decide where the transmitter will be mounted. (Refer to installation drawing, below.) Drill two holes in mounting surface, with the center of the holes 5.25" (133mm) apart.
Besides directly mounting the RAEGuard 2 PID to a wall, it can be mounted on a pipe.
13
Wall
Pole
RAEGuard 2 PID User’s Guid e
Note: When installing the RAEGuard 2 PID, make sure the sensor is vertically oriented (pointing straight down). Also, make sure the water-trap filter is connecte d to the gas inlet labeled “IN” (the longer of the two inlets). Note: Only operate the RAEGuard 2 PID in a non­condensing environment.
14
1. Loosen the fastening bolt
3. Tilt the instrument assembly
4.
5.
6.
Disassembled instrument.
2. Pull off the retaining
RAEGuard 2 PID User’s Guid e

6.2 Instrument Disassembly

Prior to service: Make sure power is OFF. Observe all Hazardous Location Safety procedures.
before unscrewing the housing lid. Unscr ew the housing lid from th e housing body by rotating it counter­clockwise. (As shipped, one of the conduit holes is covered by the provided hex­head plug. The other c onduit is for wire connections.)
clip to release the instrument assembly.
90˚.
Unlock the 24-pin connector on the ribbon cable. Lift the entire instrument assembly out of the housing. Unscrew the sensor by turning it counterclockwise.
15
Terminal blocks
RAEGuard 2 PID User’s Guid e
To reassemble the instrument: 1 Reconnect the 24-pin connector of the ribbon cable and lock it in
place.
2 Fasten the cable to the board. 3 Mate the board with the clip on the left side and tilt it over. 4 Click the board into place. 5 Screw on the sensor, making sure not to block the gas inlet hole
and connectors.
6 Screw on the housing top. 7 Screw down the fastening bolt.

6.3 Electrical Wiring

The detector connects to peripheral equipment via three terminal blocks. These blocks accept 12AWG to 24AWG wire (0.2 to 4.0
2
mm
).
16
Terminal
description
Failure Alarm Contact
ERR
1
Low Level Alarm Contact
LOW
2
High Level Alarm Contact
HIGH
3
Switch signal Common Contact
COM
4
4-20 mA Output
OUT
5
Power Supply Negative
GND
6
Power Supply Positive
+V
7
RS485A terminal
485A
8
RS485B terminal
485B
9
RAEGuard 2 PID User’s Guid e

6.4 Wiring Procedure

1. Inside the housing bottom, unplug the two green terminal block
plugs from the terminal block on the PC boards.
Note: The terminal block plugs accept 12 AWG to 24 AWG wire.
2. Lace the wires through the RAEGuard 2 PID’s wire hole(s) and
connect wires to the corresponding pin numbers of the terminal blocks:
Terminal Terminal Definition
Block 1
Block 2
Block 3
No.
17
M4 flat washer
M4 Split washer
M4 Screw
Wire Crimped terminal
Internal earth
RAEGuard 2 PID User’s Guid e

6.5 Earth Grounding Instructions

6.5.1 External Earth Grounding

Fasten the crimped ground wire with hardware as illustrated below. The wire should have a minimum cross-section area of 4mm conductor.
(Min. 4 mm2 cross-section)

6.5.2 Internal Earth Grounding

Use the same hardware as shown in the illustration of external earth grounding. The wire should be no less than the size of the power lines. Signal grounding can connect to a cable’s shielding layer if shielded cable is used. If a separate wire is used for g roun ding , its cross section should be greater than that of the power line.
grounding
2
for its
18
Alternate Internal earth
External earth
RAEGuard 2 PID User’s Guid e

6.5.3 Finished Grounding Wires

Internal and external grounding are shown here, as well as an alternate external grounding point. Always follow local electrical guidelines.
grounding
grounding
earth grounding point

6.6 Alarm Contact Setup

The alarm contacts can drive external alarms such as a light or buzzer. By default, the three relays are set for normally open (NO) operation, meaning that contact is closed when in alarm.
You can separately change each relay from normally open to normally closed (NC) operation by changing the position of the jumpers on the internal printed circuit board.
19
Jumper
Function
J1
High
J3
Low
J4
Error
Jumper blocks
Normally
Normally
RAEGuard 2 PID User’s Guid e
Three jumper blocks are located below the three green terminal blocks. They are labeled (from left to right): J4, J3, and J1. Here are their functions:
Lift off the jumper for each one that you want to change and slide it back on, either connecting the middle and top points or middle and bottom points.
Closed
Once the system is operational, test the functionality of all three relays.
Note: The relays may be disabled based on the sensor that is attached to the RAEGuard 2 PID. Certain sensors, such as the 1-1000 ppm DigiPID, disable the correction factor library and relays of the RAEGuard 2 unit. Users who require these functions should use the
0.1-1000 ppm DigiPID sensor module.
Open
Important!
20
Magnet
SIDE VIEW
RAEGuard 2 PID User’s Guid e

7 Display And User Interface

7.1 User Interface

The RAEGuard 2 PID’s user interface consists of a status LED, an LCD display, and three keys, [+], [MODE], and [-]. The three keys are operated by using the Magnet Key.
RAEGuard 2 PID user interface.

7.2 Magnet Key

The RAEGuard 2 PID has no external switches, but instead uses the magnetic end of the RAEGuard Magnet Key (p/n 033-3032-000) to activate switches built into the unit.
TOP VIEW
21
RAEGuard 2 PID User’s Guid e

7.3 Using The Magnet Key

Using the magnet end of the Magnet Key, briefly touch the glass above the MODE circle or the triangles labeled [+] and [-]. Then remove the key straight out and away from the RAEGuard 2 PID.
RAEGuard Magnet Key touching glass above the [+] triangle.
Important! Never drag the key sideways, or two functions may be activated.

7.4 System Initialization

When the RAEGuard 2 PID’s system power is turned on, it initializes and a Honeywell logo appears on the display. As the transmitter is warming up, each component is checked. The countdown timer appears on the screen for the warm-up.

7.5 Reading Display

As the transmitter enters the Reading Display, it automatically starts testing for errors and goes through a cycle of checking each alarm condition. If there are no errors or alarm conditions, the green “OK” LED is lit and the gas concentration is displayed.
22
External
Alarm
Output
Current
Normal
-
Green
Reading
Reading
Low alarm Alarm Limit
Red flashing, 2 Hz
High alarm Alarm Limit
Red flashing, 3 Hz
Red flashing, 3 Hz
Yellow flashing, 1 Hz
Yellow flashing, 1 Hz
Sensor
Drift
Calibration Fault
Yellow flashing, 1 Hz
Humidity Sensor Fault
RAEGuard 2 PID User’s Guid e
If there is an error, the “Fault” LED blinks and an error message blinks. Each alarm condition has a corresponding LED that blinks an amber color when the readings are outside a specified range or limit.

7.6 Instrument Status Display

After warm-up, the detector enters the Status Display. It automatically starts testing for errors and goes through a cycle of checking each alarm condition. If there is no error message or alarm condition, gas concentration is displayed and LED flashes green.
If there is an error or alarm, a corresponding message shows on the screen, and the LED indicates different statuses:
Status
LOW
HIGH
Over Range HIGH
Pump Error ERR
Lamp Error ERR
Negative
--
Yellow flashing, 1 Hz
ERR
ERR Green, 1 Hz
LED LCD
Reading Reading
Reading Reading
22mA
2mA
2mA
2mA
2mA
Reading
23
Hold
Reading
Sensor
breakdown
Sensor
breakdown
RAEGuard 2 PID User’s Guid e
Auto-zero Calibration
failure, sensor not installed, or barrier
failure or barrier
-- --
ERR
ERR
Yellow flashing,
Yellow flashing,
1 Hz
1 Hz
Present
2mA
2mA
Note: Electronic auto-zero calibration takes 1 minute every half-hour.

8 Navigating Settings

You can view the basic settings, clear the Peak and Minimum readings, and perform a test of the Analog system without entering P rogramm ing Mode.
At the main reading screen, hold the magnetic key over [-] for two seconds. The RAEGuard 2 screen changes to show the current peak value in memory:
If you do not want to clear the peak value, press [-].
To clear the peak value (reset it), press [+].
This screen appears:
24
RAEGuard 2 PID User’s Guid e
If you do not want to clear the peak value, press [-]. The screen
advances to Min. Clear.
To confirm that you want to clear the peak value (reset it), press
[+]. The value is cleared, and this screen is shown:
Advance to the next screen, Min value, by pressing [-].
If you do not want to clear the minimum value, press [-].
To clear the minimum value (reset it), press [+].
If you do not want to clear the minimum value, press [-]. The
screen advances to Min. Clear.
To confirm that you want to clear the minimum value (reset it),
press [+]. The value is cleared, and this screen is shown:
25
RAEGuard 2 PID User’s Guid e
Press [-] to advance to the screen showing the measurement gas, calibration gas, correction factor (CF), and molecular weight (MW) of the gas:
Press [-] to advance to the screen showing the measurement range (M.Range) and high alarm (H.Alarm) and low alarm (L.Alarm) values:
Press [-] to advance to the screen showing the firmware version and build time and date, and the serial number of the instrument:
Press [-] to advance to the Analog Output Test screen.
The analog output test is primarily used when commissioning a system. It ensures that the mA output at the sensor location is the same as the input received on the system controller. Run the analog test to make sure that the readings on the detector match the readings on the controller.
26
RAEGuard 2 PID User’s Guid e
The analog test uses a timed step function to output specific mA values in sequence. The test starts at 4 mA, which typic al ly corresponds to 0 ppm output. The analog test then progresses in increments of 2 mA (4, 6, 8, etc., all the way up to 20mA). The corresponding sensor reading in ppm is shown on the unit’s LCD display.
For example, if you have a sensor range of 0 to 1000 ppm, the detector LCD displays in sequence 0, 125, 250, 375…all the way up to 1000 ppm. These are the ppm equivalent values of 4,6, 8, 10, etc., all the way up to 20mA.
Note: You can stop the test and exit at any time by pressing [-].
27
Calibration
Measurement*
Alarm Setting
Monitor Setup
Zero/Fresh Calibration
Meas. Unit*
High Alarm
Temp. Unit Span Calibration
Meas. Range*
Low Alarm
Language
Set Span Value
Meas. Gas*
Ext. Alarm Delay*
Pump Duty (%)*
Calibration Type*
Pump Cycle(s)* Calibration Gas*
Pump Status*
Set Zero Offset*
Bus Baudrate
Analogout 4mA
Analogou t 20mA
Unit ID
LCD Contrast
LCD Backlight
Change Password*
RAEGuard 2 PID User’s Guid e

9 Programming Menus

Programming allows anyone with the password to change the instrument’s settings, calibrate the instrument, etc. Depending on whether you use the Basic or Advanced Mode, both of which have different passwords, you can access different menus and submenus.
This table shows the menus (and their icons) and submenus. Items marked with an asterisk (*) are only available in Advanced Mode. They are not available in Basic Mode.
Loading...
+ 63 hidden pages