Honeywell MIDAS LonWorks Data sheet

Midas® SPECIFICATIONS
LonWorks® Interface Module
Module Dimensions Midas® LonWorks® Interface Module
®
Size (without Midas
Weight (without Midas
Power Requirements
Operating Voltage 24VDC Nominal + / - 15%
Output to Midas Transmitter 48VDC via proprietary Power over Ethernet (PoE) connection
Power Consumption
LonWorks Module ~ 3.0W
Module with Midas ~ 8.0W
Module with Midas & Pyrolyzer
Outputs
Visual LED indicates network status
Digital Communications LonWorks
Relays Local activation of three (3) on board Midas
Inputs
Service Test Mode Button Broadcasts the LonWorks
Certification & Specification
RFI EMC CE marked: meets EN 5022:1998 Ammendment A2 and EN 5024 (24V supply)
Operating Temperature
Module with Midas Unit 0°C (32°F) to 40°C (104°F)
Wiring Requirement
Power 16 AWG Maximum 1.5mm
LonWorks® Transceiver FT-10
Warranty
Module 1 year
Ordering Information
Midas® LonWorks® Interface Module MIDAS-T-LON
unit) 120 x 100 x 35mm (H x W x D)
®
unit) 1.0kg
~ 15.0W
®
digital communication within a 78kbps FTT sub-loop system
®
neuron ID
2
®
relays for fault and alarm or remote activation of 3 relays using LonWorks
®
www.honeywellanalytics.com Toll-free: 800.538.0363
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract.
SS01115Z_v1 3/12 © 2012 Honeywell Analytics