Honeywell Midas Operating Manual

Midas Gas Detector
Operating Instructions
• TOC
• General Description
• Product Overview
• Default Configuration
• Installation
• Detector Start-up
• Navigating Menus
• Routine Maintenance
• Pyrolyzer Module Options
• LonWorks® Interface
• Troubleshooting/Faults
• Reflex
• Internal Web Server
• Installation Topologies
• Ordering Information
• Specifications
• Calibration/Bump Testing
• Modbus/TCP Interface
®
• Gas Tables
• Warranty
Midas® Gas Detector
Table of Contents
Contents 1 General Description
1 General Description �������������������������������������������������������������������������������������������������������� 1-2
2 Product Overview
2 Product Overview ����������������������������������������������������������������������������������������������������������� 2-2
2�1 Main Chassis ���������������������������������������������������������������������������������������������������������� 2-2
2.1.1 Display ............................................................................................................ 2-2
2.1.2 Pump Module .................................................................................................. 2-3
2.1.3 Sensor Cartridge Chamber ............................................................................. 2-3
2�2 Mounting Bracket Assembly ��������������������������������������������������������������������������������� 2-3
2.2.1 Mounting Bracket ............................................................................................ 2-4
2.2.2 Terminal Module .............................................................................................. 2-4
2�3 Sensor Cartridge ��������������������������������������������������������������������������������������������������� 2-4
2.3.1 Biased Sensor Cartridges ............................................................................... 2-4
2�4 Cover ����������������������������������������������������������������������������������������������������������������������� 2-5
3 Default Configuration
3 Default Configuration ����������������������������������������������������������������������������������������������������� 3-2
4 Installation
4 Installation ����������������������������������������������������������������������������������������������������������������������� 4-2
4�1 Mounting and Location of Detector ��������������������������������������������������������������������� 4-2 4�2 Mechanical Installation ������������������������������������������������������������������������������������������ 4-4 4�3 Sample and Exhaust Tubing Calculations ���������������������������������������������������������� 4-7 4�4 In-line Filters ����������������������������������������������������������������������������������������������������������� 4-8 4�5 Local Detector Option ������������������������������������������������������������������������������������������� 4-8 4�6 Electrical Installation ��������������������������������������������������������������������������������������������� 4-8 4�7 Electrical Connections ���������������������������������������������������������������������������������������� 4-11 4�8 Refitting the Main Chassis ���������������������������������������������������������������������������������� 4-23 4�9 Installing the Sensor Cartridge ��������������������������������������������������������������������������� 4-23
5 Detector Start-Up Procedures
5 Detector Start Up Procedures ��������������������������������������������������������������������������������������� 5-2
Midas Technical Handbook
i
Midas® Gas Detector
6 General Operation
6 General Operation ���������������������������������������������������������������������������������������������������������� 6-2
6�1 Normal Operation Mode ���������������������������������������������������������������������������� 6-2
6.1.1 Resetting Alarms, and Faults .......................................................................... 6-4
6�2 Review Mode ����������������������������������������������������������������������������������������������������������������� 6-4
6.2.1 Review Mode Menu Overview ................................................................... 6-4
6�3 Overview of Set-up, Calibration and Test Mode ������������������������������������������������ 6-6
6.3.1 Set-up Menu Overview .............................................................................. 6-6
6.3.2 Calibration Menu Overview ‘ CAL’ ......................................................................... 6-8
6.3.3 Test Menu Overview ‘ tESt’ ........................................................................ 6-9
7 Detailed Procedures for Navigating Mode Submenus
7 Detailed Procedures for Navigating Mode Submenus ���������������������������������������������������������������������������������������������������7-2
7�1 Review Mode ���������������������������������������������������������������������������������������������������� 7-2
7.1.1 Review Software ‘SW’ ..................................................................................... 7-2
7.1.2 Review Alarms ‘ ALm’ .................................................................................. 7-2
7.1.3 Review Faults ‘ FLt’ ..................................................................................... 7-3
7.1.4 Review Calibration ‘ CAL’ ................................................................................ 7-3
7.1.5 Review Date and Time ‘timE’ ........................................................................... 7-3
7.1.6 Review Detector Address ‘ nEt’ ....................................................................7-3
7.1.7 Review Event Log ‘ Hi St’ .......................................................................... 7-4
7.1.8 Review LCD Backlight Mode ‘LCD’ ................................................................. 7-4
7�2 Set-up, Calibration and Test Modes �������������������������������������������������������������������� 7-4
7.2.1 Set-up Menu ‘ SEt’ ........................................................................................ 7-5
7.2.2 Set Alarms ‘ ALm’ .......................................................................................... 7-5
7.2.3 Set Faults ‘ FLt’ .............................................................................................. 7-6
7.2.4 Set Calibration Interval ‘ CAL’ ......................................................................... 7-7
7.2.5 Set Date and Time ‘timE’ ................................................................................. 7-7
7.2.6 Set Address ‘ nEt’ ........................................................................................ 7-8
7.2.7 Set pass code ‘ PWd’ .................................................................................... 7-8
7.2.8 Set LCD Backlight mode ................................................................................. 7-9
Midas Technical Handbook
ii
Midas® Gas Detector
7.2.9 Set Pump control frequency ............................................................................ 7-9
7�3 Calibration Menu ‘ CAL’ ������������������������������������������������������������������������������������ 7-10
7.3.1 Zero Calibration ‘ 0CAL’ ................................................................................. 7-10
7.3.2 Span Calibration ‘ SPAn’ ............................................................................... 7-10
7.3.3 Flow Calibration ‘ FLoW’ ................................................................................ 7-11
7.3.4 mA Calibration ‘mA 4-20’ ............................................................................... 7-12
7�4 Test Menu ‘ tESt’ ��������������������������������������������������������������������������������������������� 7-13
7.4.1 Bump Test ‘ bUmP’ ....................................................................................... 7-13
7.4.2 Alarm/Fault Test ‘ SIm’ ................................................................................ 7-13
7.4.3 Inhibit State ‘ InH’ ....................................................................................... 7-14
7.4.4 Stimulate 4-20mA ‘4-20 mA’ .......................................................................... 7-14
8 Routine Maintenance
8 Routine Maintenance ������������������������������������������������������������������������������������������������������ 8-2
8�1 Sensor Cartridge Replacement ���������������������������������������������������������������������������� 8-3
8.1.1 Sensor Cartridge Fitting/Replacement ............................................................ 8-3
8�2 Pump Replacement ������������������������������������������������������������������������������������������������ 8-4 8�3 Reassembling the Detector ����������������������������������������������������������������������������������� 8-5 8�4 Filter Replacement ������������������������������������������������������������������������������������������������� 8-6 8�5 System Leak Check Procedure ���������������������������������������������������������������������������� 8-7
9 Pyrolyzer Module Options
9 Pyrolyzer Module Options ��������������������������������������������������������������������������������������������� 9-2
9�1 Fitting the Pyrolyzer Module ��������������������������������������������������������������������������������� 9-4 9�2 Reassembling the Detector ����������������������������������������������������������������������������������� 9-6 9�3 Configuring the Detector ��������������������������������������������������������������������������������������� 9-7 9�4 Replacing the Pyrolyzer Heater Block ����������������������������������������������������������������� 9-7
10 Optional LonWorks® Interface Installation
10 Midas LonWorks® Interface Module �������������������������������������������������������������������������� 10-2
10�1 LonWorks® Installation �������������������������������������������������������������������������������������� 10-2
10.1.1 Fitting the LonWorks® Module .................................................................... 10-2
10.1.2 Wiring the Midas® for LonWorks® ............................................................... 10-3
10.1.3 Configuring the Midas® for LonWorks® ...................................................... 10-3
Midas Technical Handbook
iii
Midas® Gas Detector
10�2 LonWorks® Software ����������������������������������������������������������������������������������������� 10-4
10.2.1 LonWorks® Overview ................................................................................... 10-4
10.2.2 Network Variable Behaviors ........................................................................ 10-5
10.2.3 Other Characteristics .................................................................................. 10-9
11 Troubleshooting and Fault Diagnosis
11 Troubleshooting and Fault Diagnosis ���������������������������������������������������������������������� 11-2
12 Reflex
12 REFLEX® ��������������������������������������������������������������������������������������������������������������������� 12-2
13 Internal Web Server
13 Internal Web Server ���������������������������������������������������������������������������������������������������� 13-2
14 Typical Installation Topologies
14 Typical Installation Topologies ��������������������������������������������������������������������������������� 14-2
15 Ordering Information
15 Ordering information �������������������������������������������������������������������������������������������������� 15-2
16 Specifications
16 General Specifications ����������������������������������������������������������������������������������������������� 16-2
17 Calibration and Bump Testing
17 Calibration and Bump Testing ����������������������������������������������������������������������������������� 17-2
A Modbus® / TCP Interface
®
13�1 Physical Network Components ������������������������������������������������������������������������ 13-2 13�2 Internet Settings ������������������������������������������������������������������������������������������������� 13-2 13�3 Running the Web Browser �������������������������������������������������������������������������������� 13-4
14�1 Conventional Installation ���������������������������������������������������������������������������������� 14-2 14�2 Modbus/TCP Installation ����������������������������������������������������������������������������������� 14-3 14�3 Power over Ethernet (PoE) Installation ������������������������������������������������������������ 14-3
15�1 Midas® Transmitter �������������������������������������������������������������������������������������������� 15-2 15�2 Midas® Pyrolyzer for NF3 ���������������������������������������������������������������������������������� 15-2 15�3 Midas® High-Temperature Pyrolyzer for Perfluoro Compounds ������������������� 15-2 15�4 Midas® LonWorks® Module ������������������������������������������������������������������������������� 15-2 15�5 Midas® Complete Gas Detector Kits ����������������������������������������������������������������� 15-3 15�6 Accessories and Spares ����������������������������������������������������������������������������������� 15-4
Midas Technical Handbook
iv
Midas® Gas Detector
A Modbus/TCP Interface ���������������������������������������������������������������������������������������������������A-2
A�1 Reading Status from the Midas® �������������������������������������������������������������������������A-2 A�2 Sending Commands to the Midas® ���������������������������������������������������������������������A-5
A�3 Determining the MAC Address ����������������������������������������������������������������������������A-6 B Gas Tables C Warranty Statement
C Warranty Statement �������������������������������������������������������������������������������������������������������C-2
Sensor Cartridge Warranty ����������������������������������������������������������������������������������������C-3
Pyrolyzer Warranty �����������������������������������������������������������������������������������������������������C-3
Midas Technical Handbook
v
Midas® Gas Detector
1 General Description
Midas Technical Handbook
1-1
Midas® Gas Detector
1 General Description
The Midas® gas detector is an extractive gas sampling system that draws a sample locally or from a remote point to a sensor cartridge that is located inside the detector’s chassis. A wide range of Asphyxiant, Toxic, Flammable, Pyrophoric, Corrosive, and Oxidizer (including Oxygen) gas sensor cartridges are available that enable detection of gases used or generated in the Semiconductor and other industries.
Midas® is wall mounted and displays gas concentration, alarm, fault and status information via its backlit LCD and LEDs. A simple to use 4-button keypad located under the display provides the facility to set-up, review, operate and make changes to the detector’s configuration.
Midas® has flexible power and communications capabilities built in as standard. These include 3 on board relays, 0-21 mA analog output, Modbus/TCP outputs for signal and service connectivity as well as the innovative Power over Ethernet (PoE) connection that enables a single Ethernet connection to be made for all power, control and communication requirements. An optional LonWorks® interface is available.
Midas Technical Handbook
1-2
Midas® Gas Detector
2 Product Overview
Midas Technical Handbook
2-1
Midas® Gas Detector
?
?
?
??
?
?
?
??
?
?
??
? ?
?
?
?
?
?
?
?
??
????
?
???
?
???
?
?
?
?
?
?
?
?
??
?
?
?
??
?
?
?
?
?
??
??
?
?
?
??
?
?
???
???
?
?
??
?
??
?
?
?
?
??
?
?
?
?
?
??
??
??
??
?
?????
??????
?
?
?
??
?
???
2 Product Overview
The Midas® gas detector comprises of 4 parts: the main chassis, the mounting bracket assembly, the sensor cartridge and the unit cover. Diagram 2-1 details the Midas® general arrangement. Additionally, optional Pyrolyzer modules for the detection of NF3 or various PFCs and an optional LonWorks® module are available. Please refer to Section 9 and 10 respectively for details of these options.
Diagram 2-1� Midas® general arrangement exploded view
2�1 Main Chassis
The main chassis comprises of the display, pump assembly, and plug in sensor cartridge chamber.
Diagram 2-2� Main chassis
Service Port
Display
Pump module
Sensor cartridge chamber
Caution
The Service Port is only for use with approved connectors by Honeywell Analytics service personnel operating a system diagnostic� Unauthorized connection to this port may lead to damage of the Midas® and external equipment and will not be covered by the normal product warranty conditions�
2�1�1 Display
The display is located at the front of the main chassis and consists of a large alphanumerical and graphical backlit LCD, 3 LED indicators and a 4-button keypad. Under normal operation the LCD and LEDs display gas concentration, alarm and system status. In set-up, review, calibration and test modes, the LCD shows the relevant menu options. These menus are simply navigated using the ‘s’ up, ‘t’ down, ‘3’ accept and ‘X’ cancel buttons.
Midas Technical Handbook
2-2
Midas® Gas Detector
Diagram 2-3� Midas® display module layout
1
1
1
1
1
21
1
20
3
1
1
2
4
MDA Scientific Midas
1
1
16
18
1
1
17
19
1
5
7
1
1
6
8
1
1
12
14
1
1
13
15
2�1�2 Pump Module
1. Red alarm LED
2. Normal operation icon
3. Review mode icon
4. Green power LED
5. Set-up mode icon
6. Calibration mode icon
7. Yellow Fault LED
8. Test mode icon
9. Gas concentration and
1
9
1
10
1
11
message display area
10. Displayed units
11. Pass code icon
12. Accept button
13. Network icon
14. Down button
15. Inhibit icon
16. Fault icon
17. Up button
18. Alarm level 1 icon s Alarm level 2 icon (For flammable and toxic)
Depletion level 1 icon t Depletion alarm level 2
19. Cancel button
20. Zero and Span calibration icons
21. Flow indicator
The pump module is located at the back of the main chassis. It draws the gas sample from the inlet port located at the bottom of the mounting bracket assembly via an inline filter to the sensor cartridge chamber located at the front of the main chassis. The inline filter is to protect the elements after the sensor. The sample goes from the inlet straight to the sensor face, and then through the rest of the flow system. The sample is then exhausted via the exhaust port located at the bottom of the mounting bracket assembly. The pump and filter assemblies are designed for easy replacement. For replacement details refer to Sections 8.2 and 8.4 respectively.
2�1�3 Sensor Cartridge Chamber
The sensor cartridge chamber is located at the front of the main chassis below the display module. The plug in sensor cartridge is fitted into this area which makes the electrical connection between the sensor cartridge and the rest of the electronics as well as providing the chamber where the sensor cartridge is exposed to the sampled gas. This connection is lightly lubricated for ease of sensor replacement. Avoid contact of sensor cartridge chamber with contaminants (such as dust and debris). For details of fitting sensor cartridge refer to Section 4.9.
2�2 Mounting Bracket Assembly
The mounting bracket assembly comprises of the detector mounting bracket, the terminal module, the gas sample inlet and outlet ports, the cable/conduit entry and Ethernet (Modbus/TCP) communications socket.
Diagram 2-4� Mounting bracket assembly
Mounting bracket
Cable entry
Ethernet/PoE socket
Terminal module
Gas inlet port
Gas outlet port
Midas Technical Handbook
2-3
Midas® Gas Detector
REMOVE
AT TIME OF
INSTALLATION
2�2�1 Mounting Bracket
The metal mounting bracket has two slots that allow the detector to be easily mounted to a wall using two suitable screws (DIN rail or horizontal mounting options are also available). For further details of mounting the detector refer to Section 4.
2�2�2 Terminal Module
The terminal module is located on the mounting bracket. All electrical connections to Midas® are made via this module. Wire entry to the terminal module area is via the PG16 cable entry/conduit entry located at the bottom of the mounting bracket assembly.
2�3 Sensor Cartridge
A wide range of Flammable, Pyrophoric, Corrosive, and Oxidizer (including Oxygen) sensor cartridges can be fitted to Midas®. The plug in sensor cartridges are fitted in the sensor cartridge chamber at the front of the main chassis. To access the chamber the unit cover is removed by unscrewing the thumbscrew located at the front of the detector. The pre-calibrated smart sensor cartridges can easily be fitted or replaced as they simply plug into the detector without the need for any tools. The sensor cartridge is firmly held in place by two locking tabs. Some cartridges are shipped with a protective cap to shield them from contaminants during shipping. This cap must be removed before inserting the cartridge into the Midas® unit, failure to do so may damage the Midas® transmitter.
Diagram 2-5� Sensor cartridge
Locking tabs
Front Back
Protective Cap (remove before use)
Connector
2�3�1 Biased Sensor Cartridges
Some sensor cartridges are shipped with a battery powered electrical supply in order to keep the cell effectively ‘warmed up’ and ready to monitor once installed in the Midas® unit. Battery powered bias circuits are supplied for TEOS, NO, and CO2. The bias circuit is removed just before insertion into the Midas® system and the sensor cartridge is thus ready sooner for effective gas detection.
Should a bias voltage not be applied (e.g. during a power failure), the cell will take a longer time to recover before effective gas detection can take place. The longer the loss of applied power, the longer the recovery time. During this recovery time, there is a chance for false/inaccurate readings. Refer to the relevant sensor cartridge data sheet for information on each sensor cartridge.
Midas Technical Handbook
In order to avoid the risk of loss of gas detection due to unforeseen power loss, we recommend that a power management solution such as uninterruptible power supplies are used.
2-4
Midas® Gas Detector
Sensor Cartridge
Note
Sensor warranty is void if the sensor cartridge is opened by unauthorized user.
Diagram 2-6� Biased Sensor�
2�4 Cover
The standard cover provides environmental protection and fits over the top, front and sides of the main chassis. The front panel has viewing windows for the LCD, LEDs and sensor cartridge fitted in the sensor cartridge chamber. Underneath the LCD window are the 4 push buttons used for navigating the detector’s software menus. The cover is easily removed to allow access to the chassis by unscrewing the thumbscrew on the front panel and pulling the cover forwards off the main chassis.
Midas units fitted with a pyrolyzer utilize a ventilated cover due to the high temperatures generated by the pyrolyzer unit (See Diagram 2-7)
Diagram 2-7� Midas® covers
LED Windows
LCD Window
Pushbuttons Sensor Cartridge viewing window
Thumbscrew
Standard Cover
LED Windows
LCD Window
Pushbuttons
viewing window
Thumbscrew
Ventilated Pyrolyzer Cover
Midas Technical Handbook
2-5
Midas® Gas Detector
3 Default Conguration
Midas Technical Handbook
3-1
3 Default Conguration
As standard, the Midas® gas detector is factory configured as below:
Table 3-1� Midas® default conguration
1.0 mA Fault
Current source with:
2.0 mA Inhibit
3.0 mA Maintenance Fault
4.0 to 20.0 mA Gas reading (normal operation)
21.0 mA Over range
Toxic Gas Flammable Gas Oxygen
Midas® Gas Detector
Full Scale (FS)
Lowest Alarm Level (LAL)
Lower Detectable Limit
(LDL)
Alarm 1
(Relay 1)
Alarm 2
(Relay 2)
Fault
(Relay 3)
Latching
Pass code
IP Address
®
1
Midas
detectors are not ETL approved for monitoring in or sampling from classied areas above 25% LEL
Typically 4 x Threshold Limit
Value (TLV)
Typically 1/2 TLV 10% LEL 5% v/v
Typically 0.4 TLV 9% LEL 0% v/v
The LDL is the minimum level that is reliably distinguishable from zero.
1/2 TLV 10% LEL 23.5% v/v (Rising)
Contact Normally Open (NO), closes on alarm.
TLV 20% LEL 19.5% v/v (Falling)
Contact Normally Open (NO), closes on alarm.
Contact Normally Open (NO). Instrument Fault Only
Latching. Alarm and fault relays DO NOT automatically reset when reading falls below alarm
thresholds. Relays MUST be manually reset.
169.254.60.47 subnet mask 255.255.255.0
100% Lower Explosive Limit
Normally de-energized, energizes on alarm.
Normally de-energized, energizes on alarm.
Normally energized, de-energizes on fault.
No pass code set.
(LEL)
1
25% Volume (v/v)
See Table 7-3 for more information on Relay Configuration
Midas Technical Handbook
3-2
Midas® Gas Detector
4 Installation
Midas Technical Handbook
4-1
Midas® Gas Detector
4 Installation
For ease of installation Midas® has been designed to allow the installation of the mounting bracket assembly and terminal module separately from the other parts of the detector. The detector location and
hard wiring can therefore be completed before tting
the detector’s main chassis and sensor cartridge.
WARNING
Midas® is designed for installation and use in indoor safe area non-explosive atmospheres� Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned� Prior to carrying out any installation ensure local
regulations and site procedures are followed�
Diagram 4-1. Midas® outline dimensions
5.91 in [150.00mm]
MDA Scientific Midas
4�1 Mounting and Location of Detector
The Midas® gas detector has an integral mounting bracket assembly that is easily mounted to a suitable vertical surface such as a wall, tool housing, mounting plate on a pole etc.
Drill Template
Drill 2 x M4 holes
2�3 in (58�50mm)
honeywell
PN: MIDAS-E-CDX SN: 12K-48397 Activate by 24-Nov-12
honeywell
2.48 in [63.00]
Midas Technical Handbook
z
zellweger analytics
GAS DETECTOR
4.72 in [120.00mm]
4-2
Note
This drill template is not to scale. The Midas Quick Start Guide (MIDAS-A-020) contains a full scale drawing.
Ensure all measurements are correct before using as an actual drill template.
Use 2 x M4 Screws or equivalent for mounting (head size 6-12 mm (1/4” - 1/2”))
Midas® Gas Detector
Note: Heat shield not present on all pyrolyzers.
3.9 in.
(98 mm)
3.9 in. (205 mm)
Midas-A-039
9.6 in.
(244 mm)
5.2 in.
(132 mm)
2.4 in. (60 mm)
Midas® Transmitters and Pyrolyzers
Midas-T-OOP
MDA Scientific Midas
honeywell
PN: MIDAS-E-CDX SN: 12K-48397 Activate by 24-Nov-12
honeywell
6.0 in (152 mm)
3.2 in
(83 mm)
2.3 in. (59 mm)
7.9 in (201 mm)
3.2 in
(81 mm)
2.5 in (62 mm)
Midas-T-HTP
Midas Technical Handbook
4-3
8.2 in.
(209 mm)
9.1 in. (233 mm)
4.4 in. (113 mm)
5.5 in.
(140 mm)
4.0 in. (101 mm)
Midas® Gas Detector
Below are some considerations when installing the Midas® Gas Detector:
1. Mount the detector on a surface that is flat, firm and suitable for its size and weight.
2. Use the drill template supplied to drill the holes for the fixings.
3. Use fasteners appropriate for the surface being mounted to.
4. Ensure the head size of fastener used will not snag the terminal PCB 6-12 mm (.25 in - .5 in).
5. Consider the conduit/cable weight and its stress on the installation.
6. Position the detector so that it can be easily accessed.
7. Position the detector so that it is at a suitable height (normally eye level) for the display to be clearly seen.
8. Take into consideration the space required to remove the detector’s cover and locking/ unlocking the sensor cartridge locking clips. Minimum recommended spacing between multiple Midas® units is 82 mm (3.23 in).
9. Take into consideration the space required for sample inlet and exhaust tubing (for remote monitoring), and for the inlet filter (for local monitoring).
10. Take into consideration the space required for cable or conduit access.
4�2 Mechanical Installation
The following steps and diagrams show how to separate the mounting bracket assembly from the main chassis and mount it on a vertical flat surface.
1. Unscrew the thumbscrew located on the front panel.
2. Remove the cover by pulling it forwards off the main chassis. Be sure to remove the internal packing card securing the pump. Failure to remove this packing will result in damage to the Midas® unit. (See Diagram 4-2)
3. Unscrew the two retaining screws located at the bottom front of the chassis.
4. Holding the mounting bracket assembly with one hand use the other to carefully pull the main chassis forward to disconnect it from the mounting bracket assembly.
5. Using the drill template provided drill two holes
58.50 mm vertically apart for 2 x round head M4 fixing screws.
6. Partially screw the fixings into the mounting surface.
7. Place the mounting bracket assembly over the screws so they pass through the mounting holes and then slide down to locate in the slots.
8. Tighten the screws to secure the mounting bracket assembly.
Midas Technical Handbook
4-4
Removing cover
Midas® Gas Detector
Diagram 4-2� Mechanical installation
chassis
Removing chassis
mounting bracket
chassis
TICE !
IMPORTANT NO
ve internal
ore
Remo
shipping protection from
the pump module brf
installation
Internal packing card
Remove before use.
loosen
cover
Chassis Mounting Screws
mounting bracket
IMPORTANT NOTICE !
Remove internal
shipping protection from the pump module brfore
installation
Internal packing card
Remove before use.
Midas Technical Handbook
4-5
Midas® Gas Detector
screws
Optional Midas
Diagram 4-3. Mechanical installation
mounting bracket
Standard Midas® Wall Mount
®
Pyrolyzer Adjustable “L” Bracket Mount
(MIDAS-A-032)
DIN Rail Bracket
Spacer Bracket
2x M4 Screws Secures Midas Spacer Bracket
®
to
Optional Midas® DIN Rail
Mount (MIDAS-A-036)
4x M3 Screws Secures DIN Rail to Spacer Bracket
MDA Scientific Midas
honeywell
PN: MIDAS-E-CDX SN: 12K-48397 Activate by 24-Nov-12
honeywell
Top Access Tubing Connector
(MIDAS-A-031)
Midas Technical Handbook
Note:
When using the Adjustable “L” bracket with the High­Temperature Pyrolyzer unit, (2) Top Access Tubing Connectors (MIDAS-A-
031) must be used to insure proper operation.
Optional Midas® Adjustable “L” Bracket Mount
(MIDAS-A-032)
4-6
Midas® Gas Detector
4�3 Sample and Exhaust Tubing Calculations
The following tables show the flow rate, tubing length, transport time, and maximum pressure and vacuum at the inlet and exhaust points. Tubing lengths vary among gases. See Appendix B for recommended lengths.
Table 4-1. Inlet sample specications
Inlet Sample Specifications:
Maximum
Tubing Length, m (ft)
Transport Time (sec), ID 1/8”
Transport Time (sec), ID 3/16”
Sample Point Vacuum (Negative pressure)
Flow rate, cc/min.
Tubing OD, mm (in)
Tubing ID, mm (in)
1
Honeywell Analytics recommends the thick-wall tubing (1/8”
ID) for best speed of response.
2
The ow rate is electronically maintained at approximately
500 cc/min and may vary within acceptable tolerances.
Table 4-2. Outlet sample specications
Outlet Sample Specifications:
Tubing Length, m (ft)
Back Pressure at Exhaust Point (Excluding tubing)
Tubing OD, mm (in)
Tubing ID, mm (in)
30 (100) 20 (66) 10 (33) 0
1
28 19 10 1
63 43 23 1
-25.4 cm H2O (-10 in H2O) Maximum
500 (Flow is constant)
6.35 (0.25)
3.18 (0.125)
Maximum
30 (100)
20.3 cm H2O (8 in H2O) Maximum
6.35 (0.25)
4.76 (0.188)
2
Note
Honeywell Analytics recommends the use of
Teon FEP (Fluorinated Ethylene Polymer)
tubing to assure proper sample transport.
The properties of Teon FEP make it the
best choice for transporting sample toxic gases to instruments when compared with the properties of other similar tubing materials.
If the pressure/vacuum on the inlet/exhaust lines does not meet the recommended values in Tables 4-1 and 4-2, the following chart describes potential fault conditions that may be brought on by the
external inuences thus resulting in an F81 Flow
Fault.
External Flow Fluctuation Fault 81 Explanation
Low
1
(0-150 cc/min)
Low
2
(0-150 cc/min)
Medium
3
(~200-450 cc/min)
High
4
(> 600 cc/min)
None No Midas® will auto-adjust
Midas® changes the flow
Ye s
(up to 100 cc/min
flow swings)
Yes and No Ye s
Yes and No Ye s
gradually. If external flow changes are large and rapid,
Likely
the final reading will be different from what Midas® expected. Midas® will issue Fault 81.
Minimum flow rate for the pump is ~300 cc/min. With this external flow, the auto-adjust cannot work because the pump cannot produce a flow at this low level. The problem is worse if there are flow fluctuations.
Midas® cannot reduce the external flow. Midas® will issue Fault 81 due to high flow
Midas Technical Handbook
4-7
Midas® Gas Detector
4�4 In-line Filters
External filters must be used to protect the tubing from contamination. Use particulate
lter part number 780248 for normal gases and
1830-0055 or 1991-0147 for corrosive gases. Replace the filter every 3 months. Refer to
Appendix B for specic gases.
4�5 Local Detector Option
The Midas® gas detector can also be used to monitor for gas at the location of the detector. To
do this an inline lter is simply connected to the
sensor cartridge gas inlet port. The external dust
lter part number is 780248 for normal gases and
1830-0055 or 1991-0147 for corrosive gases. The area around the detector is then being monitored as opposed to a sample being drawn from a remote location.
Diagram 4-4� Local gas detector option
MDA Scientific Midas
4�6 Electrical Installation
Access for the electrical wires to the terminal module is made via the PG16 cable gland located at the bottom of the mounting bracket assembly. The cable gland can be removed and replaced with a suitable conduit fitting if required. The wire routing of a typical installation is shown in the diagram below, wiring details are shown in Diagram 4-6.
Diagram 4-5� Typical wire routing
4-20mA Analog Output Terminals
Relay Contact Terminals
Relay NO/NC Jumpers
Power Switch
MIDAS-T-001 transmitter installed with in line particulate
lter for local ambient monitoring
mode
Midas Technical Handbook
honeywell
PN: MIDAS-E-CDX SN: 12K-48397 Activate by 24-Nov-12
honeywell
Ethernet Cable
Cable Gland
The terminals used are suitable for conductors of 24 to 14 AWG (0.5 to 1.8mm Dia.). The use of 16 AWG (1.5 mm Dia.) conductors is recommended.
4-8
If Power over Ethernet (PoE) is used to power the device, then 24 VDC power must not also be connected to the device, (or conversely if 24 VDC is used to power the Midas®, then electrical power via the Ethernet port must not be applied). Failure to observe this requirement may cause damage to the gas detection system and will not be covered by the standard warranty.
When connecting the wires ensure that the power switch is in the off position.
Diagram 4-5 shows the terminal module layout
and terminal identication as well as the jumper
locations.
Note: Earthing Requirements
If the Midas® unit’s metal chassis is not connected directly to a metal surface for earthing purposes, an additional earth wire will be required. Connect a wire via the
PG16 gland to the dedicated earth tag (screw
terminal) located on the bottom bracket and connect the other end of the wire to a dedicated external earthing point.
Midas® Gas Detector
If Power over Ethernet (PoE) power supply
is being used, shielded CAT5 Ethernet cable is recommended.
Please ensure that your wiring avoids earth
ground loops that may affect the performance of your equipment
Midas Technical Handbook
4-9
Midas® Gas Detector
RJ-45
8
7
2
3
4
5
6
1
DC
PWR
+24 V
COM
NO
NC
Relay3
Relay2
Relay1
ON
SW
OFF
11
10
9
Analog Current
Loop 4-20 mA
INT EXT
EXT INT
-supply J5
J4
+supply
J1
NO
NC
J2
NO
NC
J3
PYROLYZER
CONNECTOR
Relay1
}
Relay2
}
Relay3
}
Diagram 4-6� Midas® terminal layout and identication
See Relay
function
table below
Display Description Relay 1 Relay 2 Relay 3
Note
1FLt
2Flt
CmbF
nEtr
Instrument Fault
Only
Separate Fault
Relays
Combined Fault
Relay
Remote control of
relays via Modbus/
TCP or LonWorks
The 3 relays onboard the Midas® unit can be controlled remotely from a separate controller system using
Modbus/TCP commands (or via LonWorks® if the optional interface is used). In this remote mode, the relays
cannot be controlled by the Midas® itself and only by the remote controller device (PLC, SCADA, etc.)
Alarm 1 Alarm 2
Any Alarm
Maintenance
Fault
Alarm 1 Alarm 2 Any Fault
Relays respond to Modbus or
LonWorks® holding registers only.
®
Instrument
Fault
Instrument
Fault
Relays
are user
congurable
Midas Technical Handbook
4-10
Midas® Gas Detector
4-20 mA
Controlled
Current Source
Internal
Power
Loads
J4
INT EXT
J5
EXT INT
11
10
9
MIDAS
Simplified Internal Schematic
2
1
-
+
+
-
24 VDC
+
-
24 VDC
R
Load
4-20 mA
Controlled
Current Source
Internal
Power
Loads
J4
INT EXT
J5
EXT INT
11
10
9
MIDAS
Simplified Internal Schematic
2
1
-
+
+
-
24 VDC
R
Load
4-20 mA
Controlled
Current Source
Internal
Power
Loads
J4
INT EXT
J5
EXT INT
11
10
9
MIDAS
Simplified Internal Schematic
2
1
-
+
+
-
24 VDC
R
Load
4-20 mA
Controlled
Current Source
Internal
Power
Loads
J4
INT EXT
J5
EXT INT
11
10
9
MIDAS
Simplified Internal Schematic
2
1
-
+
+
-
Ethernet
+
-
24 VDC
R
Load
RJ-45 Connector
48 VDC
4�7 Electrical Connections
Midas® can be powered by either 24 VDC via traditional discrete wiring or by approximately 48 VDC delivered through the Ethernet cable from a PoE source. In either case the 4-20 mA analog
output can be used. This can be congured for
fully isolated operation. With 24 VDC power the
4-20 mA output can be congured for sink, source
or isolated output operations.. Below are some schematic diagrams of typical electrical connection
Diagram 4-7� Generic Example
Midas® 4-Wire Isolated Output
configurations. Specific wiring instructions for connecting a Midas to a Honeywell Analytics Sieger System-57TM are provided on pages 4-12 to 4-16.
Specic instructions for connection to a Honeywell
Analytics TouchPointTM are provided on pages 4-17 to 4-20 and the HA71 on pages 4-21 and 4-22.
Note:
When wiring the Midas Transmitter to a
controller, program the controller for a 1-2 second delay before reporting to prevent false alarms.
Diagram 4-9� Generic Example
Midas® 3-Wire Sinking Output
Diagram 4-8� Generic Example
Midas® 3-Wire Sourcing
Midas Technical Handbook
Diagram 4-10� Generic Example
Midas® Isolated 4-20 mA Output w/PoE Power
4-11
Midas® Gas Detector
Diagram 4-11� Midas® to 5701 4-Wire Isolated Connection
J4
+supply
INT EXT
11
10
9
Loop 4-20 mA
Analog Current
EXT INT
-supply J5
PYROLYZER
CONNECTOR
MIDAS
Simplified Internal Schematic
2
+
Internal Power Loads
-
1
INT EXT
4-20 mA
Controlled
Current Source
EXT INT
Sieger System 57 Relay/Field Interface Card
NC
J1
NO
NC
J2
NO
NC
J3
NO
+24 V
COM
Relay1
Relay2
Relay3
8
}
7
6
5
4
3
2
1
Relay1
}
Relay2
}
Relay3
DC
PWR
ON
SW
OFF
Shielded Cable
05701-A-0326 05701-A-0327 05701-A-0328 05701-A-0329 05701-A-0330
Cabinet
29
35
28
36
5701 Card
RJ-45
Sensor Drive Module Link Positions
LK13
LK12
System 57
J4
11
10
J5
9
35
28
29
36
Relay/Field
Interface Card
5701 Control Card
VDC
Sense
Resistor
Isolated Loop
Supply
~40 mA max + 24
­Transmitter
Supply
VDC
+ 24
-
LK11
LK10
LK9
LK8
LK7
LK6
LK5
LK4
LK3
LK2
LK1
Midas Technical Handbook
4-12
Midas® Gas Detector
4-20 mA
Controlled
Current Source
Internal
Power
Loads
J4
INT EXT
J5
EXT INT
11
10
9
MIDAS
Simplified Internal Schematic
2
1
-
+
Sieger System 57 Relay/Field Interface Card 05701-A-0326 05701-A-0327 05701-A-0328 05701-A-0329 05701-A-0330
System 57
Relay/Field
Interface Card
5701 Control Card
+
24
VDC
-
27
29
28
Sense
Resistor
~170 Ohm
Cabinet
29
2827
Shielded Cable
Transmitter
Supply
5701 Card Sensor Drive Module Link Positions
LK12
LK5
LK6
LK7
LK8
LK9
LK10
LK11
LK1
LK2
LK3
LK4
LK13
RJ-45
8
7
2
3
4
5
6
1
DC
PWR
+24 V
COM
NO
NC
Relay3
Relay2
Relay1
ON
SW
OFF
11
10
9
Analog Current
Loop 4-20 mA
INT EXT
EXT INT
-supply J5
J4
+supply
J1
NO
NC
J2
NO
NC
J3
PYROLYZER
CONNECTOR
Relay1
}
Relay2
}
Relay3
}
Diagram 4-12� Midas® to 5701 3-Wire Sourcing Connection
Midas Technical Handbook
4-13
Midas® Gas Detector
4-20 mA
Controlled
Current Source
Internal
Power
Loads
J4
INT EXT
J5
EXT INT
11
10
9
MIDAS
Simplified Internal Schematic
2
1
-
+
Sieger System 57 Relay/Field Interface Card 05701-A-0326 05701-A-0327 05701-A-0328 05701-A-0329 05701-A-0330
System 57
Relay/Field
Interface Card
5701 Control Card
+
24
VDC
-
27
29
28
Sense
Resistor
~170 ohm
Cabinet
29
28
27
Shielded Cable
Transmitter
Supply
5701 Card Sensor Drive Module Link Positions
LK12
LK5
LK6
LK7
LK8
LK9
LK10
LK11
LK1
LK2
LK3
LK4
LK13
RJ-45
8
7
2
3
4
5
6
1
DC
PWR
+24 V
COM
NO
NC
Relay3
Relay2
Relay1
ON
SW
OFF
11
10
9
Analog Current
Loop 4-20 mA
INT EXT
EXT INT
-supply J5
J4
+supply
J1
NO
NC
J2
NO
NC
J3
PYROLYZER
CONNECTOR
Relay1
}
Relay2
}
Relay3
}
Diagram 4-13� Midas® to 5701 3-Wire Sinking Connection
Midas Technical Handbook
4-14
4-20 mA
Controlled
Current Source
Internal
Power Loads
J4
INT EXT
J5
EXT INT
11
10
9
MIDAS
Simplified Internal Schematic
2
1
-
+
Sieger System 57 Quad Relay Interface Card 05704-A-0121 with 4 Channel Control Card 05704-A-0145
Cabinet
(01) 17
(S) 15
36
Shielded Cable
RJ-45
8
7
2
3
4
5
6
1
DC
PWR
+24 V
COM
NO
NC
Relay3
Relay2
Relay1
ON
SW
OFF
11
10
9
Analog Current
Loop 4-20 mA
INT EXT
EXT INT
-supply J5
J4
+supply
J1
NO
NC
J2
NO
NC
J3
PYROLYZER
CONNECTOR
Relay1
}
Relay2
}
Relay3
}
+
24
VDC
-
+
24
VDC
-
Note:
The above schematic shows the MIDAS connected to channel 1 on the 5704 card. The terminal numbers for all four channels are as follows:
MIDAS Function Loop + Loop ­Midas Ter minal Number
Color in this figure 5704 Channel 1 Terminal
5704 Channel 4 Terminal
5704 Channel 3 Terminal
5704 Channel 2 Terminal
11
Brown
15
22
21
16
System 57 Function S
10
Blue
17
24
23
18
01
17
15
System 57
Relay/Field
Interface Card
5704 Control Card
+
24
VDC
-
Sense
Resistor
Loop
Supply
Not optically isolated
Diagram 4-14� Midas® to 5704 4-Wire Connection
Midas® Gas Detector
Midas Technical Handbook
4-15
Loading...
+ 120 hidden pages