Page 1

MCR 200 - SERVICE INSTRUCTIONS
CONTENTS
HEATING CONTROL
HEAT CONSUMERS........................................................................................................................................................... 3
HEATING CIRCUIT CONTROL........................................................................................................................................... 5
Time program ........................................................................................................... 3
Outside temperature controlled cut-off ..................................................................... 3
Room temperature controlled cut-off........................................................................ 4
Optimization.............................................................................................................. 4
Outside temperature controlled flow temperature control......................................... 5
Heating characteristic .......................................................................................... 5
Automatic adaptation of the heating characteristic .............................................. 7
Room temperature control......................................................................................13
Limitation of the heating up speed.....................................................................14
Maximum limitation of the room temperature..................................................... 14
Minimum limitation of the room temperature...................................................... 14
Overtime compensation with TF 26 ................................................................... 14
Overtime compensation via room sensor input.................................................. 15
Statistics................................................................................................................. 15
Determining the number of degree days............................................................ 15
Counter for operating hours ............................................................................... 15
External temperature demand ................................................................................ 16
Overlapping mixing circuit functions, sensors, device connections ................... 17
Passing on the outside temperature sensor value through the C bus ............... 17
Signal: Hot water priority switching and system overheating,
corrosion protection .............................................................................. 17
Janitor function, heating limits ................................................................................ 18
Flow temperature control........................................................................................ 19
Setpoint ramp (flow temperature)....................................................................... 19
Limitations, special functions.................................................................................. 20
Limitation of the heating flow temperature - minimum and maximum................ 20
Pump logic ......................................................................................................... 20
Boiler excess...................................................................................................... 20
Screed drying heating function according to DIN 4725/T4................................. 20
Protective functions................................................................................................ 21
Frost protection.................................................................................................. 21
Pump actuation.................................................................................................. 21
Mixing valve and pump forced operation ........................................................... 21
Domestic hot water control ..................................................................................... 22
Standard control................................................................................................. 22
Domestic hot water priority settings ................................................................... 22
Domestic hot water charging pump.................................................................... 22
Pump forced operation....................................................................................... 23
BOILER / BOILER SEQUENCE CONTROL ..................................................................................................................... 24
(EN\2R\EN2R1120.DOC) 01.04.98
Setpoint setting....................................................................................................... 24
1. Flow temperature demand from other MCR 200 controllers
through the LC or C bus................................................................................. 24
2. Flow temperature demand through analog voltage signal
(only for MCR 200-71).................................................................................... 24
3. Flow temperature demand by floating normally open contact
(only for MCR 200-71).................................................................................... 25
4. Minimum demand (only MCR 200-71) ........................................................... 27
5. Flow demand by EXCEL 5000 system.......................................................... 27
6. Flow demand by an internal heating circuit program HKZ ............................ 27
Setpoint formation .................................................................................................. 28
Excess................................................................................................................ 28
Limitations.......................................................................................................... 28
Minimum limitation / Boiler corrosion protection ................................................ 28
Maximum limitation / Boiler overheating (for single boiler)................................. 28
Boiler overheating for boiler sequence (MCR 200-71 only ................................ 28
Return temperature limitation control ..................................................................... 29
Minimum switch-on time of the burner (Code 706 / 806) ................................... 29
Minimum switch-off time of the burner (Code 707 / 807) ................................... 29
1 EN 2R-1120
Page 2

MCR 200 - SERVICE INSTRUCTIONS
Total shutdown of the boiler (Code 703 / 802) ................................................... 29
Boiler sequence exchange (only MCR 200-71).................................................. 29
Leading boiler .................................................................................................... 30
Parallel / sequential boiler sequence ................................................................. 30
Outside temperature blockage of the 2nd boiler................................................ 30
Strategy function (only MCR 200-71) ..................................................................... 31
Heating up time (Code 921)............................................................................... 31
Gradient waiting time (Code 708 / 808) ............................................................. 31
Overheating of strategy temperature ................................................................. 31
Control range strategy (Code 914)..................................................................... 32
PID method (only MCR 200-71) ............................................................................. 34
Starting circuit for modulating burner (MCR 200-71/22)......................................... 34
Boiler control for single-boiler systems:.................................................................. 35
Boiler sensor / Sensor detection:....................................................................... 35
Outside sensor:.................................................................................................. 35
Pump run-on time (only MCR 200-71) ............................................................... 35
Using a heating controller as boiler return temperature controller ..................... 35
Alarms / Faults........................................................................................................ 36
Burner fault ........................................................................................................ 36
Boiler pump fault ................................................................................................ 36
Status displays in the.............................................................................................. 36
operating sequence................................................................................................ 36
WE (total heat generator / strategy) only for MCR 200-71................................. 36
WE1 / WE2 ........................................................................................................ 36
DISTRICT HEATING CONTROLLER...................................................................................................... .......................... 37
Return temperature limitation ................................................................................. 37
Return interval flushing........................................................................................... 38
100 % function........................................................................................................ 38
Control parameters for district heating valve.......................................................... 39
Unmixed domestic hot water storage tank control.................................................. 39
Manuelle Warmwasserladung............................................................................ 39
Switch on conditions for the secondary loading pump....................................... 39
Sollwertbegrenzung Warmwasserladung........................................................... 39
Protection against calcification........................................................................... 40
Boiler or flow temperature requirement of the hot water control ....................... 40
Minimum valve lift for incidental amount suppression........................................ 40
Heat meter connection ........................................................................................... 41
Electrical connection.......................................................................................... 41
Computing the heat power and the volume flow.................................................... 42
AIR CONDITION CONTROL........................................................................................................................................................ 43
HARDWARE ................................................................................................................................................................................ 44
COMMUNICATION
CONTROLLER TO CONTROLLER SIGNALS .................................................................................................................. 45
MCR 200 Fax Controller...................................................................................... 46
MCR 200 Voice Controller................................................................................... 47
MCR 200 EXCEL................................................................................................. 47
C-Bus................................................................................................................. 47
Outside temperature indications............................................................................. 48
INSTALLATION CHECKLIST ...................................................................................................................................................... 49
CODE TABLES............................................................................................................................................................................ 50
EN 2R-1120 2
01.04.98 (EN\2R\EN2R1120.DOC)
Page 3

MCR 200 - SERVICE INSTRUCTIONS
HEATING CONTROL
Heat consumers
Time program
Different room temperatures can be selected in the time program of the MCR 200.
According to setting, one refers to heating operation (normal operation), tempera-
ture reduction (reduced operation) or cut-off. MCR 200 has time programs for every
mixing circuit for the switching points of which an individual setpoint can be set.
Example:
gymnastics hour in a multipurpose building (heating operation). In school sports
events on the other hand, a setpoint of 18 °C can be set. The heating is then oper-
ated reduced.
The corresponding time program looks like the following:
09:00 Setpoint 21 °C
10:00 Setpoint 18 °C
The heating can also be switched off with the time program for optimizing the en-
ergy consumption. The heating circuit pump is switched off and the mixing valve
closed for this purpose. If the heating is switched off, only frost protection functions
which prevent the heating system freezing are active.
So that the heating is switched off, the optimization for heating up must be switched
on in the time program.
Example:
09:00 Setpoint 21 °C Opt: yes
10:00 Setpoint 18 °C Opt: no
12:00 Setpoint 15 °C Opt: yes
According to the temperature sensors present, the controller switches off outside
temperature controlled or room temperature controlled.
A room temperature of 21 °C should be guaranteed in the senior citizens
after the school sports, the heating is switched off completely.
optimized heating up,
so that 21°C are reached
by 9.00 am
only reducing the room
setpoint to 18 °C
early cut-off
Outside temperature controlled cut-off
(EN\2R\EN2R1120.DOC) 01.04.98
So that the residual heat of the building is utilized optimally, the heating switches on
or off already before the switching points. Naturally the time period for optimization
with room temperature sensor is calculated depending upon the momentary tem-
peratures. In the case of optimization without room temperature sensor, the time
period is calculated only depending upon the outside temperature.
The outside temperature controlled cut-off function is activated if no room tempera-
ture sensor is present and "
If the outside temperature drops below the frost protection limit of 2 °C, for in-
stance, the heating circuit pump is switched on. The flow temperature is controlled
so that the heating system does not freeze.
3 EN 2R-1120
Opt: yes
" is selected.
Page 4

MCR 200 - SERVICE INSTRUCTIONS
Room temperature controlled cut-off
Optimization
The room temperature controlled cut-off function is activated automatically if a
room temperature sensor is connected to the corresponding heating circuit and
"
Opt:yes"
If the time program switches the heating off, the control is switched over to room
temperature control. In this way the heating is switched off in the night until the
temperature has dropped to the corresponding setpoint. To avoid the room cooling
down too much, the pump is switched on and the mixing valve opened.
If the outside temperature drops below the frost protection limit of 0 °C, for in-
stance, the heating circuit pump is switched on continuously.
The switching times of the time program can be shifted corresponding to the tem-
peratures to opimize the energy consumption. Since there can be heating circuits
without room temperature sensors, a distinction is made between optimization with
room temperature sensor and optimization without room temperature sensor.
CODE - 133 - 233 - 333 - 433
Room temperature sensor for optimization
=1
=0
is selected. (The
→
→
Optimization with room temperature sensor
Optimization without room temperature sensor
Code No. 133, 233, 333, 433
must also stand at 1).
EN 2R-1120 4
01.04.98 (EN\2R\EN2R1120.DOC)
Page 5

MCR 200 - SERVICE INSTRUCTIONS
Heating circuit control
Outside temperature controlled
flow temperature control
The heating circuits serve for temperature control with a mixing valve. The following
controls can be implemented by setting code values:
CODE 117 - 217 - 317 - 417
Type of control
=2
=1
=3
=4
=5
The MCR 200 control units are set in the factory as outside temperature controlled
flow temperature control, i.e. a certain flow temperature is assigned to each outside
temperature by the heating characteristic. If a room temperature sensor is con-
nected in addition, then the controller can automatically set (adapt) its heating
characteristic. The room temperature can be set for different requirements with a
time program. The night cut-off and optimizing the switching times enables energy
to be utilized optimally.
→
→
→
→
→
Outside temperature controlled flow temperature control
Room temperature control
Constant flow temperature control,
internal 0...10 V signal
External requirement with switching contact, outside
temperature controlled
External requirement with switching contact, independent of
outside temperature
Heating characteristic
In addition, the maximum room temperature can be limited by connecting a room
temperature sensor. This adjustable limiting function ensures that heating energy is
not consumed unnecessarily.
The outside temperature controlled flow temperature controller requires a heating
characteristic according to which it can provide the correct flow temperature for the
mixing circuit concerned corresponding to the outside temperature.
The heating characteristic shows the relationship between the outside temperature
and the associated flow temperature.
(EN\2R\EN2R1120.DOC) 01.04.98
Fig.
Heating characteristic
Basic setting for heating circuit 1
Slope 1.6, curvature 1.33
5 EN 2R-1120
Page 6

MCR 200 - SERVICE INSTRUCTIONS
Basic setting
Setting recommendation
After start-up, the controller works initially with a basic setting made in the factory.
The slope of this characteristics is 1.6.
The curvature of this characteristic is 1.33 and applies for DIN radiators.
The selected room temperature of this heating characteristic is 20 °C
Both the slope and the curvature can be changed in the settings menu with the in-
dex key.
The room temperature can be changed in the time program or through the external
remote control.
IMPORTANT NOTE:
The basic factory setting must be changed for a part of the system
which is designed as floor heating. Otherwise damage due to too high
flow temperatures could arise at low outside temperatures. We there-
fore basically recommend a limiting thermostat which switches off the
mixing valve at too high flow temperatures.
Fig.
Heating characteristic
Curvature
for floor heating approx. 1.1
DIN radiators or plate heaters approx. 1.3
Convectors approx. 1.5
Setting recommendation for floor heating:
•
Slope of the heating characteristic: 0.8
•
Curvature of the heating characteristic: 1.1
•
Maximum limitation of the flow temperature to design value, e.g. 50 °C.
This maximum limitation does not replace any safety measures such as the
safety temperature limiter required for floor heating systems
(CODE No. 102, 202, 302 and 402)
EN 2R-1120 6
.
01.04.98 (EN\2R\EN2R1120.DOC)
Page 7

MCR 200 - SERVICE INSTRUCTIONS
Automatic adaptation of the heating characteristic
The basic setting does not have to be changed for all other types of system in
which higher flow temperatures are permitted. The controller corrects the heating
characteristic by the adaptation automatically.
The curvature depends exclusively upon the type of heating system or upon the
type of the radiators. The larger the numerical value, the more is the heating char-
acteristic curved.
CODE 102 - 202 - 302 - 402
Maximum limitation [°C]
The ability of the controller to adapt the default heating characteristic (heating
curve) step by step automatically to the building heating characteristic is called ad-
aptation. The mean values of the room temperature, of the outside and flow tem-
perature are the working variables for the adaptation.
Adaptation with room temperature sensor
If a room temperature sensor is connected, then the adaptation for the control loop
concerned is automatic. The temperature is measured during the entire daily opera-
tion.
The correction of the heating characteristic by adaptation is not made until the 3rd
day. If the basic setting (1.6) is too high, it can be that too high flow temperatures
occur in the first days. If the adaptation has already been running over a longer pe-
riod, a well adapted heating characteristic has become established.
No thermostatic valve may be effective in the room (test room) in which the room
sensor is installed. The radiator in the test room must always be fully opened, oth-
erwise the automatic adaptation cannot work or leads to faulty interpretations.
Open fire places, tile stoves and too frequent airing in the initial phase after starting
the application can lead to faulty interpretations.
Prerequisites for each mixing circuit are:
•
A room sensor must be connected.
•
The room temperature setpoint must be higher than 18 °C and the heating circuit
pump running time must be at least 6 hours per day.
•
The outside temperature averaged during the heating circuit pump running time
must be below 15 °C.
•
The adaptation must be allowed
(CODE No. 131, 231, 331, 431)
.
If these conditions are fulfilled, then automatic adaptation takes place.
Adaptation must have taken place at least three times before the basic setting of
the heating characteristic can be changed.
The controller corrects the heating characteristic around midnight. In this case the
corrections for each following adaptation day are always weaker.
Note
The curvature can be changed only manually through the operating
unit and is preallocated with 1.33 for all heating circuits
(DIN radiators).
The curvature depends exclusively upon the type of the heating system or upon the
type of the radiators. The larger the numerical value, the more is the heating char-
acteristic curved.
(EN\2R\EN2R1120.DOC) 01.04.98
CODE 131 - 231 - 331 - 431
Allow / prevent adaptation
=0
=1
=2
→
→
→
Adaptation not allowed
Adaptation allowed
New start of the adaptation
7 EN 2R-1120
Page 8

MCR 200 - SERVICE INSTRUCTIONS
Optimization without room sensor (floor heating, ...)
(Code 133 = 0)
Heating up
The controller works in the heating up process with a fixed adjustable room tem-
perature excess (CODE No. 136, 236, 336, 436) and varies the heating up time
with the outside temperature.
The heating time at 0 °C outside temperature (Fig. on the left) can be set in the
Code Table (CODE No. 137, 237, 337, 437).
CODE 136 - 236 - 336 - 436
Room temperature excess [°C]
CODE 137 - 237 - 337 - 437
Heating up time at 0 °C [min]
The flow temperature for heating up is established according to the heating charac-
teristic plus the set room temperature excess. The settings of the time constants
and dead times are not relevant for this heating up optimization. If the target time is
reached (as in the example diagram 8.00 am), then the controller switches back to
normal control.
This type of optimization is recommended for floor heating systems, for instance.
Large dead times, as are customary in floor heating systems, have no influence on
the switch-on time in this method.
Cut-off
On cut-off, the outside temperature influences the cut-off time. Thus all relation-
ships are determined by the diagram without it being possible to take account of
the room temperature. The maximum early cut-off is 2 hours. The switching point
must always be set at the latest possible cut-off.
The limiting value of the outside temperature, t
can be used for the early cut-off
a min
in the Code Table (CODE No. 138, 238, 338, 438).
This means that the controller cuts off the heating earlier between this limiting value
and the current room setpoint.
CODE 138 - 238 - 338 - 438
Minimum outside temperature for early cut-off [°C]
If the outside temperature is below the set limiting value, there is no early cut-off.
The heating is switched off during the set back period (pump off, mixing valve
closed). A minimum limitation which may be set (CODE No. 101, 201, 301, 401)
has higher priority on the other hand and remains valid during the cut-off.
The controller switches the pumps on and the control circuit works with the current
night setpoint from the time program (supporting mode) only if the temperature
drops below the frost protection limit (CODE No. 109, 209, 309, 409).
CODE 109 - 209 - 309 - 409
Frost protection limit [°C]
EN 2R-1120 8
01.04.98 (EN\2R\EN2R1120.DOC)
Page 9

MCR 200 - SERVICE INSTRUCTIONS
Optimization with room sensor
(Code 133 = 1)
It is possible to record the residual heat in a building only if a room sensor is instal-
led.
Thus the controller can determine the heating up time with the additional informa-
tion of dead time and time constant and the values of outside temperature, maxi-
mum flow temperature and room temperature. There are two possibilities of heating
up the system optimally in heating up optimization with room sensor.
Temperature-variable heating up
The heating up time is constant in this case (CODE No. 134, 234, 334, 434).
The flow temperature is calculated depending upon the required energy.
CODE 134 - 234 - 334 - 434
Heating up time [min]
Time-variable heating up
If the maximum flow temperature is required for heating up, then with growing heat
demand the controller can only shift the heating up time towards earlier times. This
transition is influenced by a setting in the Code Table (CODE No. 134, 234, 334,
434 and 135, 235, 335, 435).
Here the minimum heating up time and the maximum flow temperature available
are determined for heating up. The heating up process starts at the calculated time
with the maximum flow temperature for heating up (CODE No. 135, 235, 335, 435).
CODE 134 - 234 - 334 - 434
Heating up time [min]
CODE 135 - 235 - 335 - 435
max. flow temperature for heating up [°C]
The heating system is switched off before heating up (pump off, mixing valve
closed). A minimum limitation which may be set (CODE No. 101, 201, 301, 401)
has on the other hand higher priority and remains valid during the cut-off. If the
room temperature drops below the set night setpoint during the temperature reduc-
tion time, then the controller switches automatically over to room temperature con-
trol.
If the room temperature reaches the setpoint before the target time, then the sys-
tem switches over to room control.
If the target time is reached, the controller works basically for a further 30 minutes
as room temperature controller. It then switches back to outside temperature con-
trol.
CODE 101 - 201 - 301 - 401
Minimum limitation [°C]
(EN\2R\EN2R1120.DOC) 01.04.98
9 EN 2R-1120
Page 10

MCR 200 - SERVICE INSTRUCTIONS
Cut-off with room sensor
In the cut-off with room sensor, the current room temperature is included in the
calculation of the early cut-off.
•
If the room temperature tRis equal to the setpoint tRS, then the early cut-off
applies
•
If the room temperature tRis greater than the setpoint tRS(solar radiation, per-
sonal heat, then the set characteristic becomes steeper, i.e. the heating
switches off earlier (max. 2 hours).
as in the case without room sensor.
Identification of time constant and dead time
NOTE:
In the code Table, the limiting value of the outer temperature t
early cut-off (CODE No. 138, 238, 338, 438).
This means that at this limiting value, the controller cuts off the heating earlier. If
the outside temperature is below the set limiting value, then there is no early cut-
off.
CODE 138 - 238 - 338 - 438
Minimum outside temperature for early cut-off [°C]
The program identifies the necessary time constants and dead times for heating up
optimization with room sensor.
Two parameter set are identified:
•
Dead time 1 (CODE No. 140, 240, 340, 440) and time constant 1
(CODE No. 141, 241, 341, 441) of the room model for short temperature reduc-
tions
(shorter than 24 hours).
CODE 140 - 240 - 340 - 440
Dead time for short temperature reduction [min]
If the room temperature t
characteristic becomes flatter. The heating remains switched on lon-
ger, as a maximum up to the programmed cut-off point.
is smaller than the setpoint tRS, then the set
R
can be set via the
a min
CODE 141 - 241 - 341 - 441
Time constant for short temperature reduction [min]
•
Dead time 2 (CODE No. 142, 242, 342, 442) and time constant 2 (CODE No.
143, 243, 343, 443) for temperature reductions lasting longer than 24 hours.
CODE 142 - 242 - 342 - 442
Dead time for long temperature reduction [min]
CODE 143 - 243 - 343 - 443
Time constant for long temperature reduction [min]
Dead times and time constants are determined in the heating up process. Proceed-
ing from the basic settings, the parameters are corrected automatically in each
heating up process.
After the end of the dead time, the room temperature is measured every 15 min-
utes and the new time constant is estimated.
The identification is completed when the room temperature controller starts. Before
the newly determined parameter set is made use of, there is a plausibility check.
The value present in the memory is then replaced by a mean value formed from the
old and new value.
EN 2R-1120 10
01.04.98 (EN\2R\EN2R1120.DOC)
Page 11

MCR 200 - SERVICE INSTRUCTIONS
Solar compensation
Depending upon the cut-off time of the heating system, the controller uses in each
case the first or second parameter set for calculating the heating up time.
The parameters can be identified only if the following conditions are fulfilled:
•
The identification is not disabled (CODE No. 132, 232, 332, 432).
CODE 132 - 232 - 332 - 432
Identification
=0
=1
=2
•
•
•
The basic setting values for the two parameter sets (dead time, time constant) rep-
resent the starting point of the identification.
The solar radiation influences the value of the damped outside temperature through
the SAF20. A radiation power of 500 W/m2has around the same effects as an out-
side temperature which is 20 K warmer.
The influence of the compensation can be adjusted between 0 and -1 for all heating
circuits (CODE No. 116, 216, 316, 416).
→→
→→
→→
A room sensor is connected.
The temperature difference between room temperature on switching on the
heating and room temperature setpoint at the target time is greater than 2 K.
The outside temperature is less than 10 °C.
disabled
enabled
New start
CODE 116 - 216 - 316 - 416
Solar compensation
=0
=-1
→
→
off
on
(EN\2R\EN2R1120.DOC) 01.04.98
11 EN 2R-1120
Page 12

MCR 200 - SERVICE INSTRUCTIONS
Wind compensation
The wind compensation acts exactly in the opposite way as the solar compensa-
tion. At maximum wind loading (15 m/sec.), the value of the outside temperature is
reduced by max. 20 K.
The influence of the wind compensation can be set between 0 and +1 for all three
heating circuits (CODE No. 116, 216, 316, 416).
CODE 116 - 216 - 316 - 416
Wind compensation
=0
=+1
→
→
off
on
Dynamic outside temperature adaptation
To take account of residual heat in the building, the outside temperature control
does not work with the current outside temperature, but with a delayed outside
temperature.
The effect of this is that the delayed outside temperature passes on fast outside
temperature changes later and also weaker to the controller, just as in the case of
the wind influence.
The building parameter T (CODE No. 112, 212, 312, 412) is a direct measure for
the delay.
CODE 113 - 213 - 313 - 413
Building parameter T [h]
Typical values:
very light construction approx. 0.5 h
light construction approx. 2 h
medium heavy construction approx. 5 h
heavy construction approx. 10 h
EN 2R-1120 12
01.04.98 (EN\2R\EN2R1120.DOC)
Page 13

MCR 200 - SERVICE INSTRUCTIONS
Room temperature control
If wanted, the controller can also work as room temperature controller.
Set the CODE No. 117, 217, 317, 417 to "1" for this purpose.
In room temperature control, the controller decides by reference to the actual room
temperature and the room temperature set point the flow temperature which the
mixing valve must set. If room temperature control is wanted, no thermostatic valve
may be attached to the radiator in the room in which the room sensor is installed.
All radiator valves must be fully opened.
The room temperature controller is designed as cascade controller, whereby the
main controller is the room temperature controller and the auxiliary controller is the
flow temperature controller.
The sensitivity of the room temperature controller is set with the proportional band.
The proportional band changes the flow temperature setpoint immediately if the
room temperature changes.
A change of the room temperature by 1 K results (at P band X
= 5 K; CODE No.
p
122, 222, 322, 422) in a change of the flow setpoint by 20 K.
At Xp= 2 K, the flow setpoint changes by 50 K.
It applies that: 1 / XPx100K=∆t
flow
The working point of the room temperature controller is determined by the heating
characteristic (heating curve).
An outside temperature sensor is also required for the room temperature
control.
The integral action time (CODE No. 123, 223, 323, 423) states the time after which,
with unchanging system deviation, the controller increases the flow setpoint by the
same amount as it reaches due to the P component. The control circuit works as
pure P controller with integral action times < 15 s.
In most cases, the P controller is sufficient for the room temperature control, since
the working point is determined by the heating characteristic and thus a low P de-
viation can be expected.
So that not too high setpoint temperature requirements are placed on the boiler
during the morning heating up, the P controller is set as basic setting for the room
control.
A response threshold (CODE No. 124, 224, 324, 424) prevents continuous inter-
vention for small changes.
(EN\2R\EN2R1120.DOC) 01.04.98
CODE 122 - 222 - 322 - 422
Proportional band of the room temperature control [K/K]
CODE 123 - 223 - 323 - 423
Integral action time [sec]
CODE 124 - 224 - 324 - 424
Response threshold [K]
13 EN 2R-1120
Page 14

MCR 200 - SERVICE INSTRUCTIONS
Limitation of the heating up speed
Maximum limitation of the room temperature
The user can reduce the heating up speed for special applications. By setting a
room temperature setpoint ramp (CODE No. 106, 206, 306,406) it is possible to let
the room setpoint rise slowly. The cooling down speed is limited correspondingly.
The room equipment and building are conserved by limiting the heating up speed
(application e.g. in church buildings, museums etc.).
The switching point is always the starting point of the ramp.
CODE 106 - 206 - 306 - 406
Room temperature setpoint ramp [K/h]
This function requires a room sensor!
With connected room sensor and if an adjustable room temperature limitation is
exceeded, the flow temperature setpoint is lowered.
Example:
Room temperature setpoint 20 °C, maximum limitation of the room temperature to
22 °C. It results from this that starting from a room temperature of 22 °C, the flow
temperature of the heating circuit constantly starts to decrease. The maximum
permissible room limitation setpoint must be set under the CODE No. 105, 205,
305, 405. If the room temperature (actual value) exceeds the room limitation set-
point, then the heating flow temperature setpoint is decreased via the shift factor
(CODE No. 122, 222, 322, 422) and the momentary deviation (actual value of the
room temperature - room limitation setpoint).
Minimum limitation of the room temperature
Overtime compensation with TF 26
CODE 105 - 205 - 305 - 405
Maximum limitation of the room temperature [°C]
CODE 122 - 222 - 322 - 422
Proportional band of the room temperature control [K/K]
If the flow temperature does not reach the room setpoint with connected room sen-
sor and if this is below the set room temperature limit, the flow temperature setpoint
is set to 0 °C.
CODE 104 - 204 - 304 - 404
Minimum limitation of the room temperature [°C]
The set overtime setpoint (CODE No. 107, 207, 307, 407) is active if the TF 26 be-
longing to the mixing circuit stands at the "Sun" symbol. "TW day" then appears on
the operating unit, since the timer no longer has any influence. The night setpoint
(CODE No. 108, 208, 308, 408) is used if the TF 26 stands at "NIGHT".
Note:
The maximum permissible room temperature always has priority, i.e.
overtime setpoints which are larger than the max. permissible room
temperature (CODE No. 105, 205, 305, 405) cannot be maintained.
The minimum limitation of the room temperature has the same functi-
on. The minimum room temperature is set in CODE 104, 204, 304, 404.
CODE 107 - 207 - 307 - 407
→
Overtime setpoint for TW intervention
[°C]
CODE 108 - 208 - 308 - 408
CODE 104 - 204 - 304 - 404
CODE 105 - 205 - 305 - 405
→
→
→
Night setpoint for TW intervention
Minimum room temperature
Maximum room temperature
EN 2R-1120 14
01.04.98 (EN\2R\EN2R1120.DOC)
Page 15

MCR 200 - SERVICE INSTRUCTIONS
Overtime compensation via room sensor input
Statistics
Determining the number of degree days
In order to start the overtime function, the room sensor input of the control circuit
has to be short circuited for at least 10 seconds. This will start a timer, starts coun-
ting back to zero from the time set under
CODE 129 - 229 - 329 - 429
time for overtime function
During this period of time the overtime setpoint under Code 107 - 207 - 307 - 407 is
activated.
The number of degree days is required for determining the energy consumption of
an appliance for a heating period. The MCR200 controllers can determine the real,
system-specific number of degree days. The number of degree days is the product
of the heating days of a heating period and the temperature difference between the
fixed room setpoint of 18 °C and the mean outside temperature (the base tempera-
ture is adjustable, Code 1650).
The calculations required for this are performed by the controller. The correspond-
ing information can be called up in the text field of the operating unit. For this pur-
pose the computer measures the outside temperature every five minutes and aver-
ages these measurements at the end of the day.
Counter for operating hours
These measurements are made in the time window from September 1 to May 31,
provided the outside temperature is below +15 °C (time window according to VDI
2067 BL 1).
In code 1650 the basic outdoor temperature for the degree day calculation can be
set:
CODE 1650
degree day calculation: basic temperature [°C]
One counter each is available in the MCR200 for recording the operating hours of
the individual control circuits. The counter registers all times in which the pumps or
burners are in operation.
(EN\2R\EN2R1120.DOC) 01.04.98
15 EN 2R-1120
Page 16

MCR 200 - SERVICE INSTRUCTIONS
External temperature demand
The heating circuit control system also offers the possibility of reacting to external
setpoint demand. This external setpoint demand can be triggered by different func-
tions:
1. by a temperature selector
2. by a 0...10 V signal
3. by a switching contact (e.g. of a ventilation device)
The settings for the relevant function must be made in Code 117.
External room setpoint
(Code 117, 217, 317, 417=1or2)
The room setpoint setting of the time program can be overwritten by a temperature
selector (TF 26).
The TF 26 has a selector switch with the following functions:
auto automatic operation according to time program
Day constant day setpoint (overtime)
Night constant night setpoint
The setpoints for "Day" and "Night" can be set in the Code Table. The setpoint of
the time program and the overtime setpoint can be changed in 1 °C steps with the
setting knob of the TF 26.
The TF 26 can be used only for room controlled and outside temperature controlled
control.
External temperature demand by 0...10V signal
(Code 117, 217, 317, 417 = 3)
The MCR 200 can be used as pre-control for arbitrary heat consumers. For this
purpose a flow setpoint is calculated from a 0...10 V signal (117, 217, 317, 417 = 3)
or queried by a contact (117, 217, 317, 417 = 4).
It applies for this that the flow setpoint varies between min. and max. limitation ac-
cording to the level of the input signal. There is a switch-on threshold of 0.3V.
The switching program is not in operation here.
On connection of the 0...10 V signal, the voltage signal of 0.3 to 10 V is converted
to minimum flow temperature (101, 201, 301, 401) up to maximum flow tempera-
ture (102, 202, 302, 402) (see adjacent Fig.).
The heating circuit pump always runs if the flow setpoint is > 20°C.
The janitor function is in operation.
External switching contact mode 1
(Code 117, 217, 317, 417 = 4)
On connection of a contact, the setpoint is calculated by a heating characteristic.
With a closed contact, the heating characteristic is calculated according to 107,
207, 307, 407 according to the room setpoint. The temperature limitations 101,
201, 301, 401 and 102, 202, 302, 402 always apply.
The external switching contact has the following meaning:
Closed contact The controller works without switching program with the
setpoint from Code No. 107, 207, 307, 407
as outside temperature controlled controller
Open contact The controller works without switching program with the
setpoint from Code 108 , 208, 308, 408
as outside temperature controlled controller.
External switching contact mode 2
(Code 117, 217, 317, 417 = 5)
The external switching contact has the following meaning:
Closed contact The controller works without switching program
Open contact The controller works without switching program
EN 2R-1120 16
with the setpoint from Code No. 102
with the setpoint from Code 101
01.04.98 (EN\2R\EN2R1120.DOC)
Page 17

MCR 200 - SERVICE INSTRUCTIONS
The heating circuit pump always runs if the flow setpoint is > 20°C.
The janitor function is in operation.
Overlapping mixing circuit functions,
sensors, device connections
Passing on the outside temperature sensor value
through the C bus
CODE 101 - 201 - 301 - 401
CODE 102 - 202 - 302 - 402
CODE 107 - 207 - 307 - 407
CODE 108 - 208 - 308 - 408
→
→
→
→
Minimum limitation [°C]
Maximum limitation [°C]
Overtime setpoint TW
Night setpoint for TW intervention [°C]
In an extensive system with several control groups, different sensors can be used
jointly. This means: a common outside sensor can be used for several MCR 200.
The same applies, for instance, also for the wind or the solar sensor.
The MCR 200 allows the boiler to be controlled according to a maximum selection;
i.e. the MCR 200 control circuit which requires currently the highest setpoint con-
trols the boiler.
For the signal transmission, the MCR 200 must be equipped in each case with a
plug-in module GV1, for longer distances (> 2 m) also with GV2 and be connected
with one another through a cable.
If several MCR 200 are connected through GV1 (GV2), the measured outside tem-
perature of a device is passed on to all other MCR 200. If outside temperature sen-
sors are connected to several devices, the locally connected outside temperature
sensor is used as standard for the control system. Should a certain sensor be se-
lected for several outside temperature sensors, CODE No. 115, 215, 315, 415 must
be changed. The
highest
of all values in each case is transmitted through the de-
vice connection (GV1/GV2).
Signal: Hot water priority switching
and system overheating, corrosion protection
CODE 115 - 215- 315 - 415
Number of the valid outside temperature sensor
=0
=1
=2
→
→
→
local
bus
automatic
Signals can be branched in an extensive system with several control groups. This
means that the hot water priority of a MCR 200 acts on all connected MCR 200.
Since individual mixing circuits must also continue to be supplied with hot water
priority, the influence (CODE No. 114, 214, 314, 414) of the hot water priority can
be changed continuously.
CODE 114 - 214- 314 - 414
Hot water priority
=0
=1
>2
The priority signal is also used simultaneously as
corrosion protection signal
→
→
→
off
on
intensified
overheating signal
and
boiler
.
In the case of boiler overheating, the allowed heating circuits open (see also Maxi-
mum limitation / Boiler overheating).
In the case of boiler corrosion protection (boiler temperature < boiler minimum
temperature), the allowed heating circuits close (see also Maximum limitation /
Boiler corrosion protecting).
(EN\2R\EN2R1120.DOC) 01.04.98
17 EN 2R-1120
Page 18

MCR 200 - SERVICE INSTRUCTIONS
Janitor function, heating limits
Because of the storage masses of the building, a reduction of the outside tempera-
ture does not immediately affect the room temperature. Thus not only the momen-
tary outside temperature is a measure for switching on but in addition the outside
temperature delayed by the storage masses of the building. Under this we under-
stand averaging the outside temperature or assessment of the time constant of the
building.
For instance, the limiting value of the delayed outside temperature prevents the
heating switching on too early and thus unnecessary energy consumption if it be-
comes colder outside.
A building no longer loses heat if the room temperatures are just as high as the
outside temperatures. Heating energy is no longer required at the latest at this
time. However, external heat is always available in a residential building: direct or
diffuse solar radiation, personal heat, heat from lighting or possibly existing electri-
cal machines.
Since these internal heat loads cover the losses starting from an outside tempera-
ture of approx. 17...18 °C, the heating can be switched off correspondingly already
at around this outside temperature. This cut-off point is defined as heating limit.
The momentary and the delayed outside temperature run differently and are phase-
shifted. Therefore both temperatures must also be set separately.
For switching on and off it applies that:
•
If one of the two temperatures rises above the relevant set value, then the
heating switches off (e.g. point A).
•
If the momentary outside temperature (ta- CODE No. 110, 210, 310, 410) and
the delayed outside temperature (t
low its relevant set value, then the heating is switched on (e.g. point B).
- CODE No. 111, 211, 311, 411) drops be-
am
Caution: Hysteresis??
CODE 110 - 210 - 310 - 410
Momentary outside temperature heating limit [°C]
CODE 111 - 211 - 311- 411
Delayed outside temperature heating limit [°C]
Example:
set value and the heating is switched off (point A). At around 2.45 am, the delayed
outside temperature drops below the set value, the momentary outside temperature
has already been below the set value since 6.45 pm, the heating is switched on
(point B).
At around 10.30 am, the momentary outside temperature ta exceeds the
EN 2R-1120 18
01.04.98 (EN\2R\EN2R1120.DOC)
Page 19

MCR 200 - SERVICE INSTRUCTIONS
Flow temperature control
The controller computes the setpoint for the flow temperature control from several
variables. Flow setpoints of heating characteristic, optimization, room temperature
control, room temperature limitation, 0...10 V input or contact requirement are
available for selection. The controller decides which of the flow setpoints is valid.
The current flow setpoint for each heating circuit is stated in the system
status menu (index key and 2).
The sensitivity of the flow temperature controller is set with the proportional band
and the integral action time.
The proportional band has a basic setting of 100 K, i.e. a system deviation of 2K,
for instance, means that the servomotor opens or closes the mixing valve by 2 %.
To pass the manipulated variable on to the mixing valve motor, the controller con-
verts the manipulated variable into an actuating time. The motor running time of the
servomotor used (CODE No. 121, 221, 321, 421) must be set for this purpose.
Deviations between the actual and the set motor running time are critical only if the
set motor running time is significantly larger (or shorter) than the actual motor run-
ning time. The calculated actuating time is then too long; oscillations of the control
system occur. If the deviation is significantly smaller, the control response of the
control system becomes more inert.
CODE 118 - 218 - 318 - 418
Proportional band of the flow temperature controller [%/K]
Setpoint ramp (flow temperature)
CODE 121 - 221 - 321 - 421
Motor running time [sec]
The integral action time (CODE No. 119, 219, 319, 419) states the time after which
with unchanging system deviation the controller increases the manipulated value
by the same amount which is given by the gain factor multiplied by the system de-
viation.
Integral action times < 15 sec are not taken into account, the controller then works
as pure P controller.
A response threshold (CODE No. 120, 220, 320, 420) prevents continuous inter-
vention for small changes of the system deviation.
CODE 119 - 219 - 319 - 419
Integral action time [sec]
CODE 120 - 220 - 320 - 420
Response threshold [K]
Limiting the heating up speed
The user can reduce the heating up speed for special applications and to reduce
crackling noises in the pipelines. It is possible by setting a flow temperature set-
point ramp (CODE No. 103, 203, 303, 403) to let the flow setpoint rise slowly
(12...500 K/h). The cooling down speed is limited correspondingly.
CODE 103 - 203 - 303 - 403
Flow temperature setpoint ramp [K/h]
(EN\2R\EN2R1120.DOC) 01.04.98
19 EN 2R-1120
Page 20

MCR 200 - SERVICE INSTRUCTIONS
Limitations, special functions
Limitation of the heating flow temperature minimum and maximum
In some systems, the heating flow temperature must not be less than or exceed
certain limits. For example, the maximum limitation of the heating flow temperature
is very expedient in floor heating systems. An additional temperature sensor is not
required, since the limiting temperature is acquired with the existing flow tempera-
ture sensor. If minimum limitation is set, then it is constantly effective. Only the
heating limits determined by the controller can put the minimum limitation out of
force.
Pump logic
Boiler excess
Screed drying heating function
according to DIN4725/T4
Note:
CODE 101 - 201 - 301 - 401
Heating flow temperature minimum limitation [°C]
CODE 102 - 202 - 302 - 402
Heating flow temperature maximum limitation [°C]
To prevent the heating pump running unnecessarily, the controller decides whether
heat is required or not. The pump is switched off if heat is no longer required.
When the last heating circuit pump switches off, it runs on for 15 minutes (CODE
No. 128, 228, 328, 428) to utilize the residual heat from the hydraulic network.
CODE 128 - 228 - 328 - 428
Pump cut-off delay [min]
The highest of all temperature demands is passed on to the boiler controller (in the
case of several MCR 200 controllers through GV1 / GV2). An adjustable excess
ensures simultaneously that pipe losses up to the consumers are compensated for.
Screeds must be dried before starting up the floor heating. They are dried by con-
trolled heating up according to DIN 4725 / T4. In this case the flow temperature in
the first days is regulated to 25 °C for instance (CODE No. 130, 230, 330, 430 =
25). After 72 h, the flow setpoint is raised to the maximum allowed value (CODE
No. 102, 202, 302, 402).
The limitation does not replace safety measures, such as the limiting
thermostat of a floor heating system.
The screed drying heating function starts as soon as CODE No. 130, 230, 330, 430
is > 2 °C.
Note
: Do not forget to set the maximum flow temperature
(CODE 102, 202, 302, 402).
CODE 130 - 230 - 330 - 430
Flow temperature for floor heating function [°C]
CODE 102 - 202 - 302 - 402
Maximum limitation [°C]
EN 2R-1120 20
01.04.98 (EN\2R\EN2R1120.DOC)
Page 21

MCR 200 - SERVICE INSTRUCTIONS
Protective functions
Frost protection
Pump actuation
Mixing valve and pump forced operation
Important note:
To avoid the heating circuit freezing at unfavourable places of the piping system,
the frost protection function bypasses the
If the outside temperature drops below a value to be set (frost limit), the circulating
pump is switched on forcibly, even if there is no heat demand.
If the flow temperature drops below 10 °C (CODE 101, 201, 301, 401) or below the
minimum room temperature setpoint (CODE 104, 204, 304, 404), the flow tempera-
ture is regulated to the setpoint from the time program according to the heating
characteristic. The flow temperature control is switched off again after two hours
until the flow temperature drops below one of the limiting values again.
To avoid the mixing valve seizing (e.g. during the summer), the mixing valve is
opened once daily and closed again in heating breaks. To avoid the heating circuit
pump seizing, it is switched on if it has been switched off for one week (= 168 h).
The pump switches on for 60 sec (CODE H26 and H27, see also pump forced op-
eration).
The protective functions are always active. The protective functions
are not performed only in the 0 position of the operating mode switch.
demand driven pump actuation.
CODE 126 - 226 - 326 - 426
Pump protection interval [h]
CODE 127 - 227 - 327 - 427
Running time of the pump protective function [sec]
(EN\2R\EN2R1120.DOC) 01.04.98
21 EN 2R-1120
Page 22

MCR 200 - SERVICE INSTRUCTIONS
Domestic hot water control
Standard control
Domestic hot water priority settings
If a standard hot water storage tank (hot water storage tank with integrated heat
exchanger) is installed in the heating system, the charging pump is switched on as
soon as the temperature drops below the temperature set point.
So that the hot water charging process takes place as quickly as possible, the set-
point of the heat generator for the time of hot water charging is raised to a value
15 K above the hot water setpoint (CODE No. 504, 604, and 503, 603).
CODE 504 - 604
Hot water charging excess [°C]
CODE 503 - 603
Switching hysteresis [°C]
It is possible to choose between three types of hot water priority (see "Settings"
operating instructions):
•
Absolute hot water priority: As long as hot water charging is taking place, the
mixers are closed continuously. If the hot water temperature rises, the mixers
open again.
•
Parallel operation: Hot water charging has no influence on the mixing circuits.
•
Time-dependent hot water priority parallel operation e.g. for 20 minutes. If the
set hot water temperature is not reached within this time, the system switches
over to absolute hot water priority.
Domestic hot water charging pump
Switch-on conditions
Cut-off condition
In the factory setting, the MCR 200 works with time-dependent hot water priority.
The hot water priority is switched off in all cases 60 minutes after starting hot water
charging.
Example:
means no priority, "40 min." means 40 minutes priority. Thus the priority circuit
starts 20 minutes after start of hot water charging.
CODE 501 - 601
Hot water priority [min]
Prerequisites for switching on the hot water charging pumps are:
•
•
CODE 506 - 606
Boiler temperature influence
=0
=1
The hot water temperature must be greater than or equal to the water temperature
plus a switching difference (CODE No. 503, 603).
The duration of the hot water priority can be set in CODE 501, 601. "0"
The hot water setpoint must be higher than the current water temperature at the
sensor
The boiler temperature must be higher than the measured water temperature at
the sensor (only for MCR 200-12, -13, -22, -32 and CODE No. 506 = 1).
→
→
off
on
CODE 503 - 603
Switching difference [°C]
Charging pump run-on
EN 2R-1120 22
01.04.98 (EN\2R\EN2R1120.DOC)
Page 23

MCR 200 - SERVICE INSTRUCTIONS
Boiler setpoint for hot water charging
Automatic anti-legionnaire's bacteria system
This function enables the boiler residual heat to be utilized in hot water charging in
summer operation and in the transitional period. The charging pump runs on until
the temperature in the storage tank no longer rises.
The charging pump does not run on if other control circuits require heat.
There is an additional max. running time to be set under Code 521. If this time has
elapsed, the pump will stop even the temperature in the tank is still rising.
The boiler temperature setpoint required for hot water charging is calculated from
the hot water setpoint plus a boiler temperature excess (CODE No. 504, 604) plus
the switching difference (CODE No. 503, 603).
CODE 503 - 603
Switching hysteresis [°C]
CODE 504 - 604
Hot water charging temperature excess [°C]
To kill off legionnaire's bacteria, DVGW Worksheet 551 for hot water heaters > 400
litres water contents requires certain heating up temperatures which must be
reached once daily. The temperatures are set in the time program of the hot water
temperature. To avoid the risk of scalding in smaller systems, no heating up to high
temperature is preset as standard.
Hot water heating with separately
heated hot water storage tank
(special application)
Pump forced operation
There are heating systems in which the hot water is not heated by the boiler, e.g.
with a free standing hot water storage tank with its own atmospheric gas burner or
with an electrical heating element. In the case of hot water charging, the gas burner
is actuated instead of the charging pump.
The requirements for an increased boiler temperature setpoint is thus not applica-
ble.
It can be set with CODE 505, 605 of the MCR 200 whether the boiler temperature
setpoint is influenced or not during hot water charging.
CODE 505 - 605
Boiler requirement
=0
=1
→
→
off
on
To prevent the charging pump seizing, it is switched on if it was off for one week
(Code 507). The pump switches on for 60 sec (Code 508).
CODE 507 - 607
Pump protection interval [h]
CODE 508 - 608
Running time of the pump protective function [sec]
(EN\2R\EN2R1120.DOC) 01.04.98
23 EN 2R-1120
Page 24

MCR 200 - SERVICE INSTRUCTIONS
Boiler / Boiler sequence control
Setpoint setting
1. Flow temperature demand from other
MCR 200 controllers through the LC or C bus.
2. Flow temperature demand through analog
voltage signal (only for MCR 200-71)
The setpoint setting can be made in 6 different ways.
Each of these possibilities can also arise simultaneously in an arbitrary combina-
tion. The highest value from the flow temperature demands described below is
processed.
The highest demand in each case of a heat consumer is automatically transmitted
through GV 1. The controller with the heat generator(s) controls according to the
highest demand which is received through GV 1.
An analog voltage signal which is connected through the input EX1 to the
MCR 200-71.
This signal places a demand on the heat generator(s) according to the simple rela-
tionship:
The boiler pumps switch off if the analog signal is < 0.3 V.
0...10 V input
E.g. all MCR 32 / 33 or other controllers installed in the field can pass on their heat
demand through a 0...10 V signal (see also MCR 32 operating instructions).
This signal can be impressed at the MCR 200-71, input EX1 to pass on a flow set-
point to the boiler controller.
Note:
To quickly pass on from the outside a higher demand to the boiler
controller, it is important to activate its output through Code 922. With
activated input and open contact, the demand is automatically approx.
80 °C. There is no demand with closed contact. This function can be
used, for instance, for an external hot water heater.
EN 2R-1120 24
01.04.98 (EN\2R\EN2R1120.DOC)
Page 25

MCR 200 - SERVICE INSTRUCTIONS
3. Flow temperature demand by floating
normally open contact (only for MCR 200-71)
A floating normally open contact, which is connected through the input EX2. (E.g.
from MCR 52 or ZG devices). In this case the demand is calculated using an addi-
tional integral function.
A heating characteristic serves as basis for determining the common flow setpoint.
This heating characteristic is set with Code 904 - 905 - 906.
The maximum shift of the setpoint from this heating characteristic, up or down, is
set by Code 907.
From this results a "Working band" outside the set heating characteristic, which is
also restricted by the min. and max. limitation of the common flow temperature.
A minimum setpoint can be determined by the MCR 200-71 time program (day-year
program) or via the code table Code 901. The setpoint applies for the common flow
temperature in the hydraulic crossover.
What happens when the floating contact closes?
1. The demand for the boiler sequence circuit starts on the heating charac-
teristic (I).
2. According to the time the contact is closed, the setpoint is increased con-
stantly with Code 908 until the next burner stage switches on (II).
(EN\2R\EN2R1120.DOC) 01.04.98
25 EN 2R-1120
Page 26

MCR 200 - SERVICE INSTRUCTIONS
3. The setpoint remains constant as long as either the gradient waiting time
or minimum on or minimum off time are active (III).
4. The setpoint increases further with the same slope only after the waiting
time has elapsed provided the external contact is still closed.
5. If the demand contact is open (IV), then the setpoint requirement de-
creases initially slowly and then increasingly faster.
6. If the burner switches off during this phase, only the minimum off time runs
down and the setpoint remains constant for this time (V).
7. After each waiting time, the setpoint demand decreases further with the
last slope (VI). The setpoint requirement is limited by strategy minimum
temperature and the maximum shift of the heating characteristic (Code
907).
Setting recommendations when using the switching contact:
Code Setting
904 20 °C
905 1.6 (maximum selection)
906 1.3
907 20 °C (without hot water charging)
908 1
Note:
We recommend a separate connection through the input EX
for the
1
hot water charging of the external controllers to improve the dynamic
response
EN 2R-1120 26
01.04.98 (EN\2R\EN2R1120.DOC)
Page 27

MCR 200 - SERVICE INSTRUCTIONS
4. Minimum demand (only MCR 200-71)
5. Flow demand by
EXCEL 5000 system.
A minimum demand can be determined through the MCR 200-71 time program
WEZ (day/year program). The setpoint applies for the common flow temperature in
the hydraulic crossover. These setpoints are always fixed flow setpoints and
not
outside temperature dependent.
A data point of an EXCEL 5000 system can transfer the setpoint to the MCR 200-
71 heat generator, so that the MCR 200 heat generator receives the correct flow
setpoint.
For this purpose there is a user adress defined as VA_EXCEL________XX, where-
by XX is the controller number.
6. Flow demand by an
internal heating circuit program HKZ
An outside temperature controlled demand can be determined through the MCR
200-71 time program HKZ.
This internal heating circuit program also works with an independent year timer and
serves for generating an internal flow demand if the controller should work "alone".
The heating circuit therefore has no outputs for mixing valve and pump and also no
inputs for room sensor and flow temperature sensor.
Functions such as switching on and off optimization, janitor function, room control,
adaptation of the heating characteristic, solar and wind influence, delayed outside
temperature and number of degree days calculation are not integrated.
(EN\2R\EN2R1120.DOC) 01.04.98
27 EN 2R-1120
Page 28

MCR 200 - SERVICE INSTRUCTIONS
Setpoint formation
Excess
Limitations
Minimum limitation / Boiler corrosion protection
The setpoint of the boiler or of the boiler sequence results from the maximum heat
demand of the consumers and an adjustable excess.
For the single boiler controllers this is Code 709 and for the boiler sequence Code
903.
The excess takes account of piping losses.
In all boiler controllers, both the minimum (701 / 801) and maximum (702 / 802)
boiler setpoint temperature can be limited.
In addition, in the boiler sequence circuit, the minimum (901) and maximum (902)
common flow setpoint can be limited.
If there is a condition in which the minimum boiler temperature is not reached, then
the actuators in the series connected control circuits close constantly.
The reaction depends upon the setting under Code 114 / 214 / 314 / 414 and the
temperature difference between setpoint and actual value.
Example:
If the actual boiler temperature drops by 10 K below the minimum setpoint and if
the setting is Code 114 = 5, then the momentary output signal of this heating circuit
is reduced by 10 K×5=50%.
At the same time as this proportional reaction, there is an adjustable integrating
time under CODE 753.
To obtain stable operation, the boiler corrosion protection function can be delayed
with CODE 754 (overheating function).
Maximum limitation / Boiler overheating
(for single boiler)
Boiler overheating for boiler sequence
(MCR 200-71 only
If there is a condition in which the maximum boiler temperature is exceeded, then
the actuators in the connected control circuits open constantly.
The reaction depends upon the setting under Code 114, 214, 314, 414 and the
temperature difference between setpoint and actual value.
Example:
If the actual boiler temperature rises by 10 K above the max. setpoint and if the
setting is Code 114 = 5, then the momentary output signal of this heating circuit is
increased by 10 K×5=50%.
At the same time as this proportional reaction, there is an adjustable integrating
time under CODE 753.
To obtain stable operation, the boiler overheating function can be delayed with
CODE 754 (overheating function).
If the boiler temperature is above the max. limit then the following will happen:
EN 2R-1120 28
01.04.98 (EN\2R\EN2R1120.DOC)
Page 29

MCR 200 - SERVICE INSTRUCTIONS
Return temperature limitation control
Minimum switch-on time of the burner
(Code 706 / 806)
Minimum switch-off time of the burner
(Code 707 / 807)
Total shutdown of the boiler
(Code 703 / 802)
Boiler sequence exchange
(only MCR 200-71)
A constant return temperature control is provided for the boilers of the boiler se-
quence circuit in controller MCR 200-71. The setpoint is entered under Code 717 /
817. The controller is a fixed value controller with adjustable P band and fixed inte-
grating time(2 min.).
(The working point is the setpoint and corresponds to 0 % output).
This return limitation can be switched off through Code 718 / 818, i.e. the output
can be used for a butterfly valve. The butterfly valve opens if the minimum tempera-
ture is reached after heating up the boiler. If the temperature drops below the mini-
mum temperature in further operation, then the butterfly valve remains open.
However, the actuators of the heat consumers react through the "boiler corrosion
protection" function.
To ensure economic combustion, for the safe drying out of the combustion space
and to avoid chimney sooting, it is expedient to set the burner a longer running
time. The minimum switch-on times and / or minimum exhaust gas temperatures
can be set for this. After switching on, the burner remains in operation until the
minimum switch-on time has ended. The minimum exhaust gas temperature must
also be reached before it switches off. Switching off earlier is possible only on
reaching the maximum permissible boiler temperature.
The adjustable minimum switch-off time for the burner ensures that the switching
frequency is reduced. Even if the temperature is below the temperature setpoint,
the burner cannot start before the minimum switch-off time has ended. Thus too
frequent pulsing around the setpoint is reduced and uneconomic heating operation
is avoided.
If the boiler is suitable for low or extra low temperature operation, it can also shut
down heat generation completely to save energy outside the times of use. This
must be notified to the controller at start-up through the parameter. If because of
the temperature conditions the conditions for total shutdown are fulfilled, the con-
troller ensures that the possibly set minimum limitation is ineffective in the shut-
down times. However, the controller constantly performs the frost protection func-
tion, it has absolute priority. As soon as the heat generation plant has to switch on
because of the frost protection function, the minimum limitations are also in opera-
tion again (Code 913). When heat is required by the consumer circuits, the boiler,
as long as it has not reached the minimum temperature, will send a priority signal
(influence adjustable under Code 114, 214, 314, 414) to the consumers, which at a
high setting results in the consumers not receiving heat until the boiler minimum
temperature is reached.
Code 909 determines the conditions for the boiler sequence exchange:
0 = no exchange
i.e. the sequence of the boilers always remains the same. Boiler 1 is required
firstly; if the heat output is not reached, boiler 2 switches on.
1 = according to operating hours
If the set operating time (Code 716, 816) of the base load boiler has ended, the se-
quence of the boiler requirement changes at the next switch-on and the previous
following boiler becomes the base load boiler.
2 = according to outside temperature
If the 72h mean value of the outside temperature exceeds the set limit of Code 912,
then the 1st boiler becomes the base load boiler and the 2nd boiler the following
boiler. The sequence of the requirement is the other way round below this outside
temperature limit.
(EN\2R\EN2R1120.DOC) 01.04.98
CAUTION:
If boilers are of different size, the summer boiler must always be con-
nected to the electrical connections for boiler 1.
29 EN 2R-1120
Page 30

MCR 200 - SERVICE INSTRUCTIONS
Leading boiler
In systems without hydraulic crossover, it is necessary that system water can
circulate through a boiler (the heating circuit pump runs with flow temperature de-
mands > 15°C).
For this reason a leading boiler is defined under Code 920, i.e. the base load boiler
is always connected hydraulically with the heating circuit distributor, so that system
water can flow through it.
In the case of boilers which are shut off with butterfly valves, the butterfly valve is
open. In boilers with return temperature control, the three-way valve opens.
This means that cold system water may come into the boiler return since the return
temperature control for the leading boiler is not in operation.
Parallel / sequential boiler sequence
Outside temperature blockage of the 2nd boiler
NOTE:
We therefore urgently recommend installing a hydraulic crossover for
each boiler sequence circuit, since without hydraulic crossover, relia-
ble control of the return temperature and all flow temperatures is not
possible in all operating conditions.
In special cases it is possible with Code 910 to change the sequence of the stages
from sequential to parallel. In parallel operation, the stages are called up in the fol-
lowing sequence:
Boiler 1, stage a
Boiler 2, stage a
Boiler 1, stage b
Boiler 2, stage b
NOTE:
Manual sequence exchange: If the second boiler must always start
first for technical reasons, then this is possible by setting Code 912 to
"100" and Code 909 to "2". In this way the winter condition is always
simulated (boiler 2 = base load).
The summer / winter switch-over has a hysteresis of 2 K.
CAUTION:
An hydraulic crossover is not always the ideal solution with regard to
energy for condensing boilers.
If the 72-hour mean value of the outside temperature exceeds the temperature set
in Code 919, then the following boiler is blocked in each case.
Code 919
Outside temperature blockage of 2nd boiler
This blockage is cancelled if there is a fault in the 1st boiler (see also alarms /
faults).
EN 2R-1120 30
01.04.98 (EN\2R\EN2R1120.DOC)
Page 31

MCR 200 - SERVICE INSTRUCTIONS
Strategy function
(only MCR 200-71)
Heating up time (Code 921)
Gradient waiting time (Code 708 / 808)
If Code 911 is 0 (= strategy), then the following settings are important for the op-
eration of the boiler sequence circuit:
As long as the system deviation is larger than set via Code 914, and increases, the
target time for heating up shifts continuously, i.e. the target time is always 60 min.
(Code 921) in the future. The target time is not fixed until the system deviation
starts to become smaller.
To acquire an accurate temperature gradient with the heat generation running, the
gradient waiting time must first have ended, to balance out the effect of all storage
processes.
After the end of this gradient waiting time, the controller determines the tempera-
ture gradient which is compared with the target point to be reached.
Overheating of strategy temperature
(EN\2R\EN2R1120.DOC) 01.04.98
If the strategy temperature exceeds the value of Code 902 the overheating function
is activated, that means that the temperature difference between strategy tempera-
ture and Code 902 is sent via the bus to all heat consumers, which will react ac-
cording to their settings in Code 114 / 214 / 314 / 414 (priority settings).
If there is no overheating, this bussignal (code 1612) displays -888.
31 EN 2R-1120
Page 32

MCR 200 - SERVICE INSTRUCTIONS
Control range strategy (Code 914)
This setting above and below the setpoint to be reached is used to define the cut-in
and cut-out of burner stages.
When must the next burner stage cut in?
1. The gradient leads to larger deviation of the setpoint at the target time
than defined in Code 914 (see Figure), i.e. the next stage or the next
boiler can cut in. (Case I)
2. The gradient leads to a deviation below the setpoint but within the strategy
control range, i.e. the next stage may cut in, but a second boiler not.
(Case II)
When must the next burner stage cut out?
1. The last switched on burner stage cuts out if the setpoint is exceeded by
3 K and the waiting times have elapsed (Case III).
2. The last switched on boiler can cut out if the setpoint + Code 914 is
reached and the waiting times have elapsed (Case IV).
The same applies if the maximum boiler temperature is reached.
EN 2R-1120 32
01.04.98 (EN\2R\EN2R1120.DOC)
Page 33

MCR 200 - SERVICE INSTRUCTIONS
What happens in the strategy control range?
1. Actual value<setpoint
If there is a system deviation within the strategy, then the next stage can be
switched on. If this system deviation is present for longer than the heating up
time Code 921, then the next boiler can also be called up.
All the waiting times apply at the same time.
2. If the actual value moves between setpoint and setpoint +3 K, then nothing
happens.
3. If the actual value>setpoint+3Kthelast stage switched on will cut out.
4. If the actual value>setpoint + Code 914 (control range) the las boiler swithed
on will cut out.
5. The modulating stage controls with the PID settings.
(EN\2R\EN2R1120.DOC) 01.04.98
33 EN 2R-1120
Page 34

MCR 200 - SERVICE INSTRUCTIONS
PID method
(only MCR 200-71)
If Code No. 911 is at 1 = PID, then the following settings are important for opera-
tion:
Code 915 P band
916 Integral action time
917 Derivative action time
918 Response threshold
The stages switch on and off for the following output signal
(shown here as P controller):
Starting circuit for modulating burner
(MCR 200-71/22)
A maximum duty cycle is switched on for the modulating burner through Code 713
(factory setting 50 %). This means that at 100 % signal, the time for reaching the
steady stage condition is twice as long as if Code 713 is at 100 %.
In this way fast, modulating stages work slower and more stably.
At the first runup, this value is set fixed to 20 % deviating from the setting of Code
713, i.e. it lasts five times as long as would be possible with maximum speed.
The modulating stage of boiler 1 can start only when the first stage of burner 1 has
been running for at least the minimum running time. If then the internal PID signal
>
25 % the modulating output signal will increase also.
During this time all other stages of the second boiler are disabled. Only when the
modulating output is 100 % and all delay times have elapsed a decision can be
made (depending on the PID signal) if a further stage will be switched on.
EN 2R-1120 34
01.04.98 (EN\2R\EN2R1120.DOC)
Page 35

MCR 200 - SERVICE INSTRUCTIONS
Boiler control for single-boiler systems:
The modulating component cannot be switched in until the gradient waiting time
(minimum switch-on time + delay time for 2nd stage) has ended, if controller output
with running stage > 0.
The second modulating stage is set by the PI controller (Code 711 / 712).
Output is 0...100 %
Code No. 710-714 Settings!
Boiler sensor / Sensor detection:
If the boiler sensor is not present, then the functions of boiler control and its limita-
tions are not activated. So that unnecessary sensor breakage alarm messages do
not arise, the final sensor configuration should be confirmed through the operating
sequence.
Outside sensor:
Pump run-on time
(only MCR 200-71)
Using a heating controller as
boiler return temperature controller
If no outside sensor is connected, and if there is no outside sensor information on
the C bus, then the controllers work with a fixed outside temperature of 0° C.
Here as well the final sensor configuration should be confirmed through the operat-
ing sequence.
The condition for the pump run-on time can be set individually for each boiler of the
boiler sequence circuit.
Code 722 / 822: Maximum run-on time
Code 723 / 823: Temperature difference run-on time.
The temperature difference between the boiler flow or return.
If the temperature difference is smaller than the set value,
the pump stops.
If no return sensor is connected, then the pump runs according to Code 722 / 822
with the maximum run-on time.
A heating controller can, if the flow temperature demand ist switched of with Code
156 / 256 / 356 / 456, be used as an independant return temperature controller.
The following codes must be set according by
Code 101 for return temperature set point e.g. 50 °C
Code 117 to 5
Code 110 and 111 adjusted to highest values, so that janitor function is out of order.
(EN\2R\EN2R1120.DOC) 01.04.98
35 EN 2R-1120
Page 36

MCR 200 - SERVICE INSTRUCTIONS
Alarms / Faults
Burner fault
Boiler pump fault
Status displays in the
operating sequence
WE (total heat generator / strategy)
Only for MCR 200-71
If the temperature gradient (boiler sensor) is not positive once within 60 minutes
after the burner relay pulling in, then a burner fault is reported.
The waiting time is adjustable in Code 721 / 821.
A value of 10,001 deactivates the alarm.
Only for MCR 200-71:
Within 10 seconds a burner fault will be reported, if the inputs SK 1 and SK 2 are
used. This delay time is not adjustable.
The fault will be reported if the inputs are closed. At the same time the outdoor
temperature disable function of the second boiler will be cancelled so that the sec-
ond boiler can cut in if necessary.
If the temperature difference between flow and return is > 30 K for more than 15
minutes, then a boiler pump fault is reported.
The temperature difference can be set with Code 724 / 824. A value of 100 K deac-
tivates the alarm.
The status display explains the load conditions of the heat generator(s) and indi-
cates the actual and setpoint values as well as the current statuses of the output
relays.
WE1 / WE2
WE: Off
FK:0 w: 50°C
A :Int. x: 52°C
MORE
WE1: Mini.T
P :On x : 75°C
ST:St2 mod:100%
BACK MORE
First line:
WE Total heat generator
Off Operating mode switch to "0" or "Holiday"
Parallel Code 910 to 0
Sequence Code 910 to 1
Second line:
FK: 0/1/2 Leading boiler
W Setpoint for common flow sensor
Third line:
A : Int. Internal requirement of the time program
A : Bus. External requirement through bus
A : ext. External requirement through EX2
A:0-10V External requirement EX1
X Actual temperature at the common flow sensor
First line:
WE... WE1 or WE2: Number of the heat generator
Mini.T Minimum limitation for boiler active
if there isnodemand and the boiler temperature<t
and total shut down is
As soon as there is a demand the line will show "normal".
Totaloff Total cut-off of the heat generator
if there isnodemand and the boiler temperature<t
and total shut down is permitted
As soon as there is a demand the line will show "normal".
off if the burner is cut off
Normal if operating mode normal
Overheat if boiler temperature>Code 702
Second line:
P : Pump
x : Boiler temperature actual value
Third line:
ST: St1 or St2: Burner stage 1 or 2
mod: ... % Component of the modulating stage
not
permitted.
k min
k min
EN 2R-1120 36
01.04.98 (EN\2R\EN2R1120.DOC)
Page 37

MCR 200 - SERVICE INSTRUCTIONS
District heating controller
Return temperature limitation
All MCR 200 heating and district heating controllers offer the possibility of continu-
ous return temperature limitation. The return temperature limitation can be set
separately both for the individual mixing circuits and the total system.
Code 735 specifies the lower value of the return temperature limit
Code 736 specifies the upper value of the return temperature limit
Code 737 is the onset point of the outside temperature. The onset point
determines from which outside temperature the shift starts.
Examples:
(EN\2R\EN2R1120.DOC) 01.04.98
37 EN 2R-1120
Page 38

MCR 200 - SERVICE INSTRUCTIONS
Return interval flushing
So that the return temperature can be measured with sufficient accuracy even with
the distant heating valve closed, the distant heating valve is opened briefly every
10 minutes. This guarantees that the limitation sensor in the distant heating return
is sufficiently flushed.
This function is active only if the distant heating valve has been closed in the
distant heating return by reaching the maximum limitation.
100 % function
In order to achieve stable control conditions for one or more heating circuits we ha-
ve the 100 % function.
This function takes care that the heat consumer with the highest flow set point ope-
nes the valve 100 % and is controlled by the heat exchanger valve directly.
'This function can be diabled with Code 763 if temperatures due to minimum limita-
tions must not enter this heating circuit.
EN 2R-1120 38
01.04.98 (EN\2R\EN2R1120.DOC)
Page 39

MCR 200 - SERVICE INSTRUCTIONS
Control parameters for district heating valve
For the district heating valve control there are three different parameters
(proportional band):
1. for only one heating circuit Code 728 default = 100
2. for two and more heating circuits Code 751 default = 20
3. for unmixed DHW control Code 752 default = 10
In order to achieve a stable condition it may be necessary to adjust these parame-
ters to the heating system.
Unmixed domestic hot water storage tank control
The MCR 200-52 and MCR 200-53 offer the possibility of hot water heating with an
unmixed domestic hot water storage tank. The water is not heated by a heat ex-
changer fitted in the unmixed domestic hot water storage tank but by an external
heat exchanger.
•
The heated water flows from above into the unmixed domestic hot water storage
tank.
•
At the same time cold water flows from the bottom of the unmixed domestic hot
water storage tank to the heat exchanger. In this way the return temperature of
the heating medium is relatively low during the entire heating time, also in after-
heating processes.
•
As soon as the sensor WW1 located at the top measures a temperature lying
below the setpoint, the charging process is started.
•
Hot water charging is ended when the sensor WW2 located at the bottom of the
unmixed domestic hot water storage tank has reached the hot water setpoint.
A setpoint increased by Code 504 applies at the sensor VF3 for the charging
process.
Manuelle Warmwasserladung
Switch on conditions for the secondary loading pump
If Code 506 is set to 1, the controller will wait with the loading process until the flow
temperature is>regular loading temperature.
In case the flow sensor is not in flowing water then it is necessary to change this
switch on condition by changing Code 506 to 0.
Ideal is a correct mounting of the sensor, as shown in picture left.
Sollwertbegrenzung Warmwasserladung
(EN\2R\EN2R1120.DOC) 01.04.98
39 EN 2R-1120
Page 40

MCR 200 - SERVICE INSTRUCTIONS
Protection against calcification
To protect from calcification the external heat exchanger, which is required in un-
mixed domestic hot water storage tank charging, a maximum inlet temperature in
the hot water heat exchanger can be determined especially for unmixed domestic
hot water storage tank charging.
Boiler or flow temperature requirement
of the hot water control
Minimum valve lift for
incidental amount suppression
This is measured at the sensor VF3.
This maximum limitation is always active
in hot water charging.
The hot water control determines its own setpoint for the heat requirement. This
setpoint is passed onto the heat generators (boiler, heat exchanger).
The heat quantity metering necessary in district heat transfer stations represents a
technical problem in the range of strongly reduced flow quantities.
Whereas in the normal working range the measurement is sufficiently accurate for
heating cost calculation, in light load operation, therefore if the valve is opened only
a little, clearly noticeable faulty messages can occur.
The "Minimum valve lift" function ensures that there is constant control only in the
range of the flow volume which can be reliably measured, in that the MCR 200-52
changes from constant to two-point control below adjustable limiting values for the
valve lift. The heat quantity can be recorded exactly with this function even in light
load operation.
EN 2R-1120 40
01.04.98 (EN\2R\EN2R1120.DOC)
Page 41

MCR 200 - SERVICE INSTRUCTIONS
Heat meter connection
Electrical connection
The MCR 200 can process the volume and heat quantity signal of the heat meter
for power and volume limitation.
•
With the aid of the primary flow and return sensor, the MCR 200 converts the
volume flow signal into the actual power and vice versa.
•
The MCR 200 can limit both the volume flow and the delivered power, indepen-
dent of the signal which it receives from the heat quantity meter.
The corresponding settings are made in Code 743...750.
(EN\2R\EN2R1120.DOC) 01.04.98
41 EN 2R-1120
Page 42

MCR 200 - SERVICE INSTRUCTIONS
Computing the heat power
and the volume flow
The MCR 200 code tables must be adjusted to the heat meter.
In the ideal case it is calibrated so that a signal is transmitted about every second.
Example:
The maximum power hint is entered under Code 748 and the maximum volume
flow under Code 749. The distant heating valve will be closed continously if these
values are exceeded.
EN 2R-1120 42
01.04.98 (EN\2R\EN2R1120.DOC)
Page 43

MCR 200 - SERVICE INSTRUCTIONS
AIR CONDITION CONTROL
(EN\2R\EN2R1120.DOC) 01.04.98
43 EN 2R-1120
Page 44

MCR 200 - SERVICE INSTRUCTIONS
HARDWARE
EN 2R-1120 44
01.04.98 (EN\2R\EN2R1120.DOC)
Page 45

MCR 200 - SERVICE INSTRUCTIONS
COMMUNICATION
Controller to controller signals
In order to exchange data between the MCR 200 controllers there must be installed
a serial bus connection.
Through this bus there is a continuous exchange of, at the moment, 6 values:
1. The max. flow set point of all MCR 200 controllers in the system.
This value will be received by all connecxted MCR 200 controllers an is used by
the heat generators for the control of boilers and/or heat exchangers.
2. The priority signal
This signal serves the purpose to override the heat consumer output signals an
can have three different causes:
The DHW priority:
when loading DHW there is an adjustable signal for each heat consumer, which
will individually close the control valves.
Boiler corrosion protection:
if there are boiler temperatures lower than the minimum limit then this function
takes care that the consumer control valves will close, to take care that the
boiler will reach ist minimum temperature as fast as possible.
Boiler overheating
if there are boiler temperatures higher than the max. limitation this function
will take care that the consumer valves will open and so reduce the excess
temperature as quick as possible.
3. Collective alarm signal
Wherever there is an alarm in the system (connected by the bus) this signal
well be activated an can be utilized in every controller asa5Vsignal.
4. Outside temperature
For a MCR 200 system only ohne outside temperature sensor is necessary, be-
cause this value is transmitted to every other controller on the bus. This sensor
can be connected to any MCR 200 controller.
If a different outside temperature is needed for a special purpose (north/south
values) then may controllers have inputs for an individual outside temperature
sensor. This value must then be defined for every consumer of the correspon-
ding controller.
5. Solar / Wind sensor
The information of solar and wind influence is available for every controller on
the bus. There can be only one wind or one solar sensor.
6. Especially for district heating controllers this combined signal was created. It
serves the following purpose:
to inform every heat consumer, that the heat generator is a district heating
heat generator
to tell every district heating heat generator how many heat consumers are
active at the moment
to tell every heat consumer, that an unmixed DHW storage tank of MCR 200-
53 is beeing loaded (this function will disable the max. selection of the flow
temperature demand)
to find the heat consumer with the highest flow temperature demand in order
to open this control valve 100 %.
(EN\2R\EN2R1120.DOC) 01.04.98
45 EN 2R-1120
Page 46

MCR 200 - SERVICE INSTRUCTIONS
MCR 200 Fax – Controller
In order to show the values of datapoints on an alarm fax, these datapoints must
have the attribute "Fax".
This attribute is currently added to the following user adresses:
1. All sensor inputs except LQR, all TW remote setpoint selectors and all SM ge-
neral alarm inputs
2. All digital, floating an analogue outputs
3. All set points
4. Datapoint for VD_MK1_STATUS Status of controller
5. Datapoint for VD_DHW_STATUS DHW status (Code 509)
6. Heat energy if heat meter with
heat energy signal is connected
7. Datapoint for heat power Code 746
8. Datapoint for volume flow Code 747
9. Status vent. controller Code 1001 Code 1001
10. Aux output 0...100 %
11. Operating mode switch (MODE_SWITCH_POS)
12. real set point for vent. controller
13. Vent. stage
14. Set point from switching program
15. VA_Excel
16. Sensor input ?? quality control in ppm or %
17. Datapoint for max. outside temperature
on the bus
EN 2R-1120 46
01.04.98 (EN\2R\EN2R1120.DOC)
Page 47

MCR 200 - SERVICE INSTRUCTIONS
MCR 200 Voice – Controller
MCR 200 – EXCEL
C-Bus
In order to transmit values of datapoints by means of a "spoken word", these corre-
sponding datapoints must have the attribute "Voice".
This is, by the moment, utilized with the following datapoints:
1. Outside temperature on the bus
2. Room temperature for heating an ventilation controllers
3. Status of remote set point selector TF 26
4. Status of remote set point selector T 4712D
In order to transmit a flow temperature demand from MCR 200 to an EXCEL heat
generator the following steps are necessary:
(EN\2R\EN2R1120.DOC) 01.04.98
If without exception all heat consumers shall pass a flow temperature demand to
the Excel heat generator, then the common signal from the bus may be used as
datapoint for Excel
LCGesAnf--------XX
___________________
18 characters
Please take care that the controller numbers are manually set for mixed systems,
to prevent that they will change in case of a power cut.
47 EN 2R-1120
(XX = Controller-Nr.)
Page 48

MCR 200 - SERVICE INSTRUCTIONS
Outside temperature indications
OT display
Code 1604
Code 1614
Code 1639
Code 1640
Code 112
Code 146
either local sensor or if not mounted,
bus value of outside temperature (without delay)
input from bus without local sensor information (without delay)
value of local sensor (without delay)
as Code 1640 but without delay
OT sensor information as set under Code 1017
sensor with 1 h delay time (for vent. controller)
OT sensor information with 72 h delay
OT sensor information with the delay of the
building time constant (Code 113)
EN 2R-1120 48
01.04.98 (EN\2R\EN2R1120.DOC)
Page 49

MCR 200 - SERVICE INSTRUCTIONS
INSTALLATION CHECKLIST
(EN\2R\EN2R1120.DOC) 01.04.98
49 EN 2R-1120
Page 50

MCR 200 - SERVICE INSTRUCTIONS
CODE TABLES
EN 2R-1120 50
01.04.98 (EN\2R\EN2R1120.DOC)
Page 51

Microprozessor Controller MCR 200
SERVICE INSTRUCTIONS
110°
100°
90°
80°
70°
Flow temperature in °C
60°
50°
40°
30°
+10
+5
20°
+20°
0
Room setpoint
-5
Outside temperature in °C
-10
Fast
heating up time
Setting value
in code table
0°C
t=t
a
Outside temperature
Room temperature
possible early cut-off
Daysetpoint
Excess
2h
6:00 8:00
with intervention of the frost protection
CB-2079-E
4,5 3,5 3,0 2,5
-15°+10° -10°+5° -5°0°
t
[°C]
Code 902
Code 901
Returntemperature limitation
Characteristic of the moving return
temperature limitation
Code 735
152 / 252
Code 736
RS
CB-2077-E
153/253
Early cut-off at ...h
Roomtemp.> room setpoint
2
Time
t
amin
Slope
2,0
1,8
1,6
1,4
1,2
1,0
0,8
0,6
0,4
-20°
0,3010
0...0,3 V: no requirement!
Slope
Code 734
151 / 251
Code 737
154 / 254
Roomtemp.= room setpoint
Outside temperature
Roomtemp.< room setpoint
k*(t t )
RRS
k*(t t )
RS R
t= t
RS
a
Outside temperature
V
CB-2084-E
t Requirement
VL
Slope Code 908
t
HC
Boil er off
Waiting
time
Boil er on
Contac t open
I II III IV V VI
Setpoint
CB-2340-E
Setpoint
step
Code 914 Control range
Time 1, step b
Time 1, step a Time 1, step a
Code 704 / 804
Gradient waiting time
t
HC
t
[°C]
Kmax
CB-2383-E
Slope /curvature
(Code 905 / 906)
t
Kmin
Code 904
20 10 0 -10 -20
t = Starting temperature of the heating characteristics
HC
Waiting
time
Contac t openContac t cl ose d
Temperature
gradient
Time 1, step a
Maximum shift
(Code 907)
Boil er off
Target point
t [°C]
a
CB-2352d-E
Time
CB-2348-E
CB-2342-E
CBRSATE
SI
EN 2R-1120 GE51 PRERELEASE 0797