MCBA14C
Commercial Boiler Control System
INSTALLATION INSTRUCTIONS
APPLICATION
The MCBA14C Commercial Boiler Control System provides heat
control, flame supervision, circulation pump control, fan control
and boiler control. It has electric ignition. It will also provide boiler
status and error reporting.
FEATURES
• NTC resistors for measuring and guarding temperatures.
• PWM-driven revolution controlled dc-fan for optimal
modulation control.
• 24 Vac gas valve.
• 24 Vac is fused (Fuse F3) with a 4AT fuse.
• PWM-driven circulation pump for optimal energy
consumption.
•DHW-pump.
• Various function-inputs.
• Connections for external comfort control.
• Connections for extra inputs/outputs.
• Easy modification of the parameters on three levels:
— End user.
— Installer/service mechanic.
— Manufacturer (OEM).
SPECIFICATIONS
Electrical Ratings
Line voltage requirement: 120 Vac (+10%/-15%).
Power Consumption: 8 W.
Gas Valve: 1.72A ac.
External load: 0.1A ac.
Fan: <35W dc.
Total 24 Vac: <75 VA.
Fan: <20W dc.
Total 24 Vac: <50 VA.
Electrical Connections:
Line Voltage: 120 Vac, 60 Hz.
Fuse (F1): 5A, fast acting.
Main Voltage Connection: X1, pins 1 and 2.
MCBA Earth Ground Connection: X1, pin 6.
Power Connection, Central Heating (CH) Pump: 120 Vac, 60Hz.;
5A maximum current; X1, pins 3 and 4.
Power Connection, Domestic Hot Water (DHW) pump; 120 Vac,
60 Hz; 1A maximum current; X1, pins 3 and 5.
Heat Request (CH), parallel shift input, X2, pins 8 and 9. Current:
2 mA, dc.
Air Pressure Switch; X2, pins 7 and 9. Requirements:
Current: 2 mA, dc.
Minimal Gas Pressure Switch: X2, pins 6 and 9. Requirements:
Current: 2 mA, dc.
Overheat Thermostat (optional): X2, pins 9 and 10.
Negative Temperature Coefficient (NTC) Inputs: X3, X4, X5.
Flow Temperature (NTC1): X3, pins 1 and 5.
Return Temperature (NTC2): X3, pins 2 and 5.
DHW Temperature (NTC3): X3, pins 3 and 5.
Outside Temperature (NTC4): X3, pins 4 and 5.
Flue Gas Temperature (NTC5): X4, pins 1 and 2.
Outside Temperature (NTC4): X5, pins 3 and 4.
Analog Input: X4, pins 2 and 3.
Used to connect a 0 to 10 volt analog input, a water pressure
sensor, or an extra NTC-6.
Switch Inputs:
DHW-Thermostat: X3, pins 3 and 5.
On/Off Switch: X3, pins 4 and 5.
Flame Sensor:
Flame Current: Minimum 3 microampere dc (typical 2 micro-
ampere).
Isolation Resistance: Minimum 50 megohms.
DC Fan: X2, pins 1, 2, 3, 4.
+ Connection (X2-3): Vopen maximum 45V.
PWM Control Output (X2-1):
Ri: 12 kilohms.
Fmin: 941 Hz.
Fmax: 3.3 kHz.
Tacho Input (X2-4).
Gas Valve Output: X2, pins 11 and 12:
Contact Voltage: 24 Vac, 60 Hz.
Current: 1.7A ac, maximum.
PWM-driven CH Pump (X3, pins 5 and 6):
Output VL: 0.5V maximum.
Output VH: 14V maximum (open).
High Voltage Connection (used for the ignition spark. High voltage
connection must have a good connection with the earth
ground contact of the MCBA.
Voltage: 15 kV.
Spark Gap: 1/8 in. (3 mm); maximum 3/16 in. (5 mm).
Communications (X5, pins 1 and 2):
Environmental Ratings:
Temperature Range:
Operating: 32°F to 150°F (0°C to 60°C).
Storage: -13°F to +167°F (-25°C to +75°C).
Humidity:
At 77°F (25°C): 85% RH.
At 150°F (60°C): 50% RH.
Approvals:
CSA
Component Approval, ANSI Z21.20 Automatic Ignition Systems.
INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Refer to the wiring diagram provided as part of the
appliance or refer to Product Data sheet, form 65-0279.
® U.S. Registered Trademark
Copyright © 2004 Honeywell International Inc.
All Rights Reserved
66-1142-1

MCBA14C COMMERCIAL BOILER CONTROL SYSTEM
3. Check the ratings given in the instructions and on the
product to make sure that the product is suitable for your
application.
4. Installer must be a trained, experienced combustion
service technician.
5. Disconnect the power supply before beginning installation
to prevent electrical shock and equipment damage. More
than one disconnect may be involved.
6. All wiring must comply with applicable local electrical
codes, ordinances and regulations.
7. After installation is complete, check out product operation
as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death, or property damage.
To prevent possible hazardous burner operation, verify
safety requirements each time a control is installed on a
burner.
WARNING
Electrical Shock Hazard.
Can cause serious injury, death or property damage.
Disconnect power supply before beginning installation to
prevent electrical shock and equipment damage. More
than one disconnect may be involved.
WIRING
WARNING
Electrical Shock Hazard.
Can cause serious injury, death or property damage.
Disconnect power supply before beginning wiring to
prevent electrical shock and equipment damage. More
than one disconnect may be involved.
Ground Connection
The ground connection on the controller must not be used as a
central ground connection for the 120 Vac connections.
1. Use the common ground terminal next to the controller,
close to connector X1.
2. Connect the central ground terminal with the connection
contact of the controller.
3. Connect the ground wire of the main power connector, the
CH pump, the DHW pump (if present) and the ignition wire
to the central ground terminal.
Electrical Connections
Main Power Line
1. Hot (L1) to connector X1-L.
2. Neutral (L2) to connector X1-N.
3. Ground to central ground terminal, not to Ground on X1.
CH Pump; DHW Pump Power Line(s)
1. Hot to connector X1-4 (CH Pump) or X1-5 (DHW Pump).
2. Neutral to connector X1-3.
3. Ground to central ground terminal, not to Ground on X1.
Low Voltage Connections
Use 18 AWG or larger wires.
1. Wire according to specifications, following all local ordinances and requirements.
2. Do not bundle the low voltage wires with the ignition cable,
120 Vac wires, CH Pump or DHW Pump.
3. The low voltage wires for the minimal gas pressure switch,
DHW thermostat, air pressure switch, and gas valve can be
bundled together.
4. Bundle the wires for the fan and join them with the other
24V low-voltage wires.
5. Bundle the wires for the NTC sensors and the PWM pump
control separately.
6. Do not bundle the ionization wire with the high voltage
cables, but it can be joined with the other 24V wires.
High Voltage Cable
1. Always use a grommet when placing the high voltage
cable.
2. Never join the high voltage cable with other wires.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario
66-1142—1 G.R. Rev. 03-04 www.honeywell.com
M1V 4Z9
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.