M9484 AND M9494 MODUTROL MOTORS ARE LOW
VOLTAGE, REVERSING PROPORTIONAL CONTROL
ACTUATORS FOR VALVES, DAMPERS AND AUXILIARY EQUIPMENT. THEY ARE ESPECIALLY DESIGNED
GAS BURNER CONTROL SYSTEMS.
•i Replace M941 motors.
0
formance and long life.
0
0
AC. Models available with factory installed transformer,
or internal transformer can be field added.
Cl
adapter available.
FORCOMMERCIALOR INDUSTRIALOILOR
Oil immersed motor and gear train for reliable per-
Wiring box provides NEMA 3 weather protection.
Actuator motor and circuitry operate from 24 volts
Quick-connect terminals standard - screw terminal
Cl
Adapter bracket for matching shaft height of older
motors is standard with replacement motors.
0
Field adjustable stroke (90” to 160’) models avail-
able.
q
Nominal timing of 30 seconds for 90” and 60 sec-
onds for
available.
0
Die-cast magnesium housing.
q Available accessories include valve and damper
linkages, explosion proof housing, and auxiliary
,
switches.
0
wiring box to upgrade actuator to Series 70 (electronic)
control.
•i
0
dard timings.
cl
minute timings for
160”
stroke is standard. Other timings are
Field addable interface modules can be mounted in
Models available with tapped output shaft.
M9481,
M9484 rated for 150 lb.-in. torque at stan-
M9491,
M9494 rated for 300 lb.-in. torque at 2 or 4
160“
stroke.
S.M.
Rev. 11-90
Form Number 63-2195-l
@Honeywell Inc. 1990
Page 2
STANDARD MODELS
control Type
94 is Series 90
Power Rating
8
is high torque
150 lb.-in. at
standard timing
9 is high torque
300
2 or 4 min timing
Output Drive
4 is dual-ended shaft,
non-spring return
1 is single-ended shaft,
non-spring return
NOTE: Some motors furnished to equipment manufactur-
ers will have no adapter bracket, a single-ended shaft
and/or no wiring box.
CONTROLLER TYPE: Series 90 Control Circuit-135
ohm series 90 proportioning controller. Series 90 high
or low limit controller with manual minimum position po-
tentiometer (with a combined total resistance of up to
500 ohms) may also be used in the control circuit.
MOTOR ROTATION: Normally
tion is the limit of counterclockwise rotation as viewed
from the power end of the motor. See Fig 2.
clockwise (as viewed from the power end). Motors are
shipped in the closed position.
~~ I
lb.-in.at
T
TTLix
D:
is adjustable stroke
(90°
No auxiliary switches
E:
is adjustable stroke
(90°
1 auxiliary switch
is adjustable stroke
F:
(90°
2 auxiliary switches
closeda.
Letter
to 1
60°)
to 1
60°)
to 1
60°)
The closed posi-
Motor opens
ELECTRICAL RATINGS:
POWER
CONSUMP-
TfON
(W)
18
Without
VOLTAGE
CURRENT
DRAW (A)
24
0.8
Transformer
With internal
120
0.24
23
Transformer
208 0.14
240 0.12
STROKE: Field adjustable from
90”
to
160”.
23
23
Start position
of shaft changes with adjustment of stroke. (Midpoint of
stroke remains fixed as stroke is adjusted, as shown in
Fig. 2.) Stroke is adjusted by means of cams located in
wiring compartment. (See Stroke Setting Procedure.)
Motors are shipped with stroke set at
90”.
DEAD WEIGHT LOAD ON SHAFT:
Power or Auxiliary End-200 lb.
Maximum Combined Load-300 lb.
[90.8
kg] maximum.
[136
kg].
AMBIENT TEMPERATURE RATINGS:
Maximum-150°
Minimum-minus 40” F
CRANKSHAFT:
F [66” C] @ 25% duty cycle.
[-40°
318
inch
[9.5mm]
C].
square
M9484, M9494 have double-ended shaft.
M9481, M9491 have single-ended shaft.
aThe
normal position is the position the motor will assume
ranges (4-7 Vdc, 6-9 Vdc, and 10.5-13.5 Vdc).
Adapts motor to M71 XX function.
rent control, with adjustable null and span. Adapts
motor to
plications. Adapts motor to
with minimum position capability. Adapts motor to
M76XX
from one Series 90 controller.
Single-zone Logic Panel or
Controller.
Controller.
mA
in wiring box of M9lXX motor. Can be used in place
of
tions described above).
inches shorter than the 7616BR crank arm, can
rotate through the downward position and clear
base of motor without requiring use of adapter
bracket.
M72XX
function.
Controller.
Resistor Board-Plugs onto quick-connects
4074BYK,
EAU, EDC, or EED resistor kits (func-
50/60
Hz (for electrical iso-
Vat; 50160
function; 4 to 20 mA or 2 to 10 Vdc.
Module, 3-wire 14-17 Vdc control
M91
M91XX
M91
Hz.
50160
Hz.
50160
Hz.
M73XX
function.
XX motors from a W973
W7100
Discharge Air
motor from a 4-20
XX motors from a 4-20
mA
WHEN INSTALLING
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Checkthe
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
THIS PRODUCT...
ratings given in the instructions
andon
the
Disconnect power supply before beginning
1.
stallation to prevent
ment damage.
Never turn the motor shaft by hand or with a
2.
wrench-this will damage the motor.
Always conduct a thorough checkout when in-
3.
stallation is complete.
1
3
eiectrical
shock and equip-
in-
63-2195-l
Page 4
ADAPTER
BRACKET
f---
5.37 [136]
FIG.
1-UIMtNSIUNS
IN
NOTE: M9481, M9491 do not have auxiliary shaft. All other dimensions are the same.
LOCATION
install the Modutrol motor in any location
except where
acid fumes or other deteriorating vapors might attack the
metal parts, or in atmospheres of escaping gas or the
duit
weather protection.
MOUNTtNG
explosive vaporsin excessive salt environments, mount-
ing base and screws should be zincorcadmium plated, not
stainless steel or brass:
Use the
220738A
adapter bracket
for mounting on these surfaces.
Allow enough clearance for installing accessories and
servicing the motor when selecting a location. See Fig. 1.
If
located outdoors, mount upright and use liquid-tight
con-
motor housing are drilled for
screws or bolts.
(at the limit of counterclockwise rotation as viewed from the
power end of the motor, as shown in Fig. 2) with the stroke
set at
4
In.
connectors with wiring box to provide NEMA 3
Always install motors with the crankshaft horizontal.
Mounting flanges extending from the bottom of the
l/4
inch
[6.4mm]
machine
Motors are shipped from the factory in closed position
90”.
Page 5
NON SPRING RETURN MOTORS
E373C
FIG. 2-LIMITS OF MOTOR ROTATION.
ADAPTER BRACKET
The220738A
motor and the equipment, raises the shaft height
Adaptor Bracket, positioned between the
ptthe-
M9484 motor by 0.75 inch to match that of the M941 motor.
This is required on all valve linkage applications,
Q607
External Auxiliary Switch applications, and on some
damper linkage applications (either to provide clearance
for the crank arm to rotate through the downward position,
or to allow the damper linkage to reach the shaft).
To mount the motor with the bracket:
1. Mount the bracket to the equipment with existing or
standard bolts.
2. Mount the motor to the bracket using the bolts pro-
vided into the threaded holes of the bracket (see Fig. 3).
For valve linkage applications, the bracket should first
be mounted to the linkage (see Fig. 4). The bracket then
provides a convenient base on which the motor can be
positioned. After the motor shaft is aligned to the linkage,
it can then be attached to the bracket with the 4 bolts
provided. These bolts go through the inner set of holes in
the motor
flanae
BOLTS
PROVIDED (4)
and into the threaded holes of the bracket.
1
#12 OR
l/4”
n
FIG.
“MOUNTING
with standard bolts.
which thread into the threaded bracket holes.
ZINC PLATED MACHINE SCREWS OR BOLTS
M 3076
MOTOR WITH 220738A ADAPTER BRACKET. The
The motor is then mounted
to
DAMPER LINKAGES
A 220738A Adapter Bracket is packed with replace-
ment motors. Use of this bracket is optional for many
damper applications but may be needed in damper applications requiring the crank arm to rotate through the
bottom plane of the actuator. If the bracket is not used in a
replacement application, the damper linkage will have to
be adjusted to the new shaft position.
The motor comes without a crank arm. The crank arm
is included in the Q605 linkage or may be ordered separately (see Accessories).
For detailed instructions on the assembly of specific
linkages, refer to the instruction sheet packed with each
5
bracket is first mounted to the
the
bracket using the bolts provided with
equipmel
the
bracKet,
linkage. In general, however, check the following points of
operation when installing a motor and linkage.
1.
Linkages for valves and louver type dampers should
be adjusted so that the damper or valve moves through
only the maximum required distance when the motor
moves through its full stroke.
2. With modulating control, maximum damper
should be no more than
60”.
Little additional airflow is
opening
provided beyond this point.
3. The motor must be stopped at the end of its stroke
by the limit switch and must not be stalled by the damper
or valve. The motor will be damaged if it is not permitted to
complete its full stroke.
63-2195-l
Page 6
Y
BOLTS PROVIDED (4)
WIRING BOX
MOTOR
MACHINE SCREWS OR BOLTS.
M
31% TIGHTEN AFTER SECURING MOTOR TO THE BRACKET USING FOUR BOLTS PROVIDED.
FIG. 4-MOTOR
4.
Do not exceed the motor ratings in any installation.
5.
Do not turn motor shaft manually or with a
wrench-
this will damage the motor.
LTS SECURING BRACKET TO LINKAGE.
MOUNTING
ONVALVE LINKAGE,.
of theprintedcircuit boardshown in
adapter is standard on all Trade models and also may be
VALVE LINKAGES
The 220738A Mounting Bracket must be used with the
Ql
00,
Q601 and Q618 linkages in all valve applications.
WIRING
Disconnect power supply before wiring to prevent electrical shock or equipment damage. All wiring must agree with
applicable codes, ordinances, and regulations.
A transformer is required to supply 24
Vat power to the
motor. Make sure that the power requirements stamped on
the motor correspond to the characteristics of the power
supply.
added to all models. Access to the wiring compartment is
gained
and lifting off the cover.
WIRING BOX
When used with liquid-tight conduit connectors, the wiring
box provides NEMA 3 weather protection for the motor.
The box also provides knockouts for wiring conduits and
encloses terminals. The wiring box, standard with replace-
ment motors, is required for housing an internal trans-
former, internal auxiliary switches or Series 70 Interface
Modules.
Figs. 5 and 6 show internal schematics.
The motor terminals are quick-connects located on top
Fig.7.Ascrewterminal
byremovingthe4screws
inthetoppf the wiring box
6
Page 7
CLOSE
LIMIT
DIRECTION OF MOTOR TRAVEL AS VIEWED FROM POWER END.
&
CONNECT 24V POWER TO
POWER SUPPLY TO CONTROLLER TERMINALS. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION AS REQUIRED.
3 TURN
LIMIT
n
COUNTERCLOCKWISEr?FOR 90’
FIG.
5-lNTERNAL
POT FULL
Tl-T2
TERMINALS ONLY. DO NOT CONNECT
CLOCKWISE~FOR 160’
WIRING OF
STROKE.
An9494
STROKE, FULL
MOTORS.
MODUTROL
A
BLUE LEAD
I
YELLOW LEAD
1
REDLEAD
2
‘n
1
WIRING SHOULD BE NEC CLASS 1 UNLESS POWER SUPPLY
n
MEETS CLASS 2 REQUIREMENTS. TAPE UNUSED LEADS. MAKE
CERTAIN THE CURRENT DRAW OF THE EXTERNAL CIRCUIT IS
LESS THAN CONTACT RATING OF SWITCH.
2
ON TWO-SWITCH MOTORS SECOND SWITCH HAS BLACK
n
LEADS WITH BLUE, YELLOW. AND RED TRACERS.
FIG.
6-AUXILIARY
SWITCH INTERNAL WIRING.
A
A
M
254
I
STROKE
MINIMUM
:zTloN
I
STROKE POT
NOTE: FEATURES AVAILABLE ON SOME MODELS ONLY.
ADJUSl
CAMS (YELLOW)
FIG. 7-TERMINALS AND ADJUSTMENTS.
INNER AUXILIARY
INNER AUXILIARY
SWITCH CAM (BLUE)
OUTER AUXILIARY
SWITCH CAM (RED)
OUTER AUXILIARY
*
M ml/\
63-2195-l
Page 8
AUXILIARY SWITCH
M9484E
The
wires are color-coded as follows: solid yellow-normally
closed (N.C.); solid red-common (COM.); solid
blue-normally open (N.O.).
SWITCH/CAM COLOR-CODING:
CONNECTIONS
supplies to de-energize the
has 1 internal auxiliary switch. The switch
CAM
SWITCH
LOCATlON’
Left
Right
aViewed
bSee
from power end of motor.
Fig. 6.
ASSEMBLY
LOCATIONa
Outer
Inner
CAM
COLOR CODE
Red
Blue
The
M9484F
may be used to prove low fire and high fire positions.
1.
To prove low fire use red (common) and yellow wires
connected to outer (left) switch. This switch makes red to
yellow and breaks red to blue as motor closes.
2.
Wires connected to the inner (right) switch are black
with colored tracers. To prove high fire, use red tracer
(common) and blue tracer wires. The right switch makes
red tracer to blue tracer and breaks red tracer to yellow
tracer as motor opens.
Color coding and switching action are tabulated below
to aid the installer.
TABLE 1
has 2 internal auxiliary switches which
SWITCH
COLOR
Solid Yellow
Solid Red
Solid Blue
Yellow Tracer
Red Tracer
Blue Tracer
WIRESb
DESIGNATION
Normally Closed (N.C.)
Common (COM.)
Normally Open (N.O.)
Normally Closed (N.C.)
Common (COM.)
Normally Open (N.O.)
SWITCHING ACTION:
SWITCH
LOCATIONa
Left
Right
aViewed
bSee
from power end of motor.
Fig. 9
NORMAL
FUNCTION
Proves
Low Fire
Position
Proves
High Fire
Position
MAKES
Red
to to
Yellow
Red Tracer Red Tracer
to
Blue Tracer
STROKE SEl-lING
On M94XXD,E,F motors, stroke is field adjustable and
can be set from 90” to 160”. Motors are shipped in 90”
position. In order to set stroke, both mechanical and electrical adjustments are required. The mechanical adjust-
n
ments (cams) establish the full open (clockwise,
viewed from the power end) and full closed (counterclockwise
0
)
positions of the motor shaft. The electrical
adjustment (trim pot) provides sufficient total stroke angle
to ensure that cams will actuate both limit switches.
STROKE SETTING PROCEDURE
See Fig. 8.
Detach linkage from motor before adjusting stroke.
as
TABLE 2
CAM
BREAKES
Red
Blue
to
Yellow Tracer
BEFORE SETTING STROKE:
1. Remove top cover from motor.
2. Disconnect controller from motor.
3. Connect
ter (Q209 or S963) to matching terminals on motor.
SETTING
(Q209 or
yellow cam and MOVE TOP OF SCREWDRIVER as far as
possible counterclockwise n (viewed from power
end). Repeat in successive cam slots until inner cam is
against counterclockwise
160”
1. Turn stroke pot fully clockwise
2. Drive motor to mid-position using 135 ohm pot
S963),
3. Insert
l/8
POSITIONb
High portion of cam
not in Contact
with Cam follower.
High portion of cam
in Contact
with Cam follower.
R,B,W
terminals on 135 ohm potentiome-
STROKE (Fig. 8):
or by jumpering B-R-W.
in. screwdriver blade into slot on inner
0
stop.
POSITION
f7
.
MOTOR
Closing
Opening
8
Page 9
MOVE SCREWDRIVER
ONLY TO ADJUST CAM:
AT TOP
l/8 IN. STRAIGHT BLADE
SCREWDRIVER
OUTER STROKE
ADJUST CAMS
RY SWITCH CAMS
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
A
OVERLOAD PROTECTION AS REQUIRED.
2 TRANSFORMER MAY BE EXTERNAL OR INTERNAL.
A
FIG.
M 3,3A
8-STROKE
ADJUSTMENT SETUP.
OUTER CAM
NOTE: CAMS ARE OFFSET
PROVIDE BETTER VIEW OF BACK CAM.
l/8
IN. STRAIGHT-BLADE
SCREWDRIVER
M305
STROKE ADJUST
CAMS (YELLOW)
INNER AUXILIARY CAM (BLUE)
OUTER AUXILIARY CAM (RED)
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
A
OVERLOAD PROTECTION AS REOUIRED.
2
TRANSFORMER MAY BE EXTERNAL OR INTERNAL.
A
FIG. O-AUXILIARY SWITCH ADJUSTMENT SETUP.
RIGHT/INNER
M 315c
NOTE: CAMS ARE OFFSET VERTICALLY TO
PROVIDE BETTER VIEW OF BACK CAM.
POWER END
9
OTOR CLOSE
M 3060
63-2195-l
Page 10
IMPORTANT
Set cams by moving top of screwdriver only. Pressing screwdriver against sides of cam slots could
cause damage to motor end switches.
4. Insert
yellow cam and MOVE TOP OF SCREWDRIVER as far as
possible clockwise
until outer cam is against clockwise q stop.
NOTE: Excessive force will damage cam stop on hub.
possible clockwise
peat in successive cam slots until inner cam is against
clockwise stop.
NOTE: Excessive force will damage cam stop on hub.
4. Insert
yellow cam and MOVE TOP OF SCREWDRIVER as far as
possible counterclockwise
cam slots until outer cam is against counterclockwise stop.
NOTE: Excessive force will damage cam stop on hub.
5. Check motor stroke before connecting linkage.
6. Disconnect 135 ohm pot, reconnect controller, replace top cover on motor.
7. Attach linkage to motor.
AUXILIARY SWITCHES
The auxiliary switches in
ated by adjustable cams. The cams are mounted on the
motor shaft at the power end of the motor. The settings of
the cams determine the point in motor shaft rotation at
which the auxiliary equipment will be switched on or off.
These cams can be set to actuate switches at any angle
within the stroke of the motor. Also each cam provides a
fast rise portion for switching (1
rise portion for slow switching (10’ differential).
l/8
in. screwdriver blade into slot on outer
n
.
Repeat in successive cam slots
90”
STROKE (Fig. 8):
S963),
or by jumpering B-R-W.
l/8
in. screwdriver into slot on inner yellow
q
(viewed from power end). Re-
l/8
in. screwdriver blade into slot on outer
c
.
Repeat in successive
M9484E,F
motors are actu-
o
differential) and a slow
0
.
Switching action and color coding are shown in Tables
1 and 2 on page 8.
Motors with factory added auxiliary switches are
shipped in the closed position (counterclockwise
as viewed from power end) with auxiliary cams set to
actuate switches
provide 1” differential. Wiih motor in closed (full counter-
clockwise
AUXIUARY
terminals and cam adjustments.
ohm manual potentiometer with R-W-B terminals on pot
connected to corresponding terminals on motor (Fig. 9).
position where auxiliary equipment is to be switched.
cam associated with selected auxiliary switch. The inner
(blue) cam actuates the inner (right) switch, the outer (red)
cam actuates the outer (left) switch. MOVE TOP OF
SCREWDRIVER to set cams.
iliary switch R-B contacts and rotate cam as follows:
auxiliary switch R-B contacts and rotate cam as follows:
ing action is reversed, thus: switch contacts R-B make
and R-W
30” from the closed position, and to
)
position, auxiliary switch breaks R-B.
IMPORTANT
SWlTCH SElllNG
l/8
in., straight-blade screwdriver into slot on
until R-B contacts open.
breakon
acounterclockwise (closed) rotation.
PROCEDURE (Fig. 9)
1”
to
lo”,
fi
r\.
the switch-
,
MODULATlNG
The potentiometers, one in the controller and one in the
motor, along with resistor network, form a bridge circuit. As
long as the value of the controlled medium remains at the
controller set point, the circuit is balanced, and the motor
does not run.
When the value of the controlled medium changes, the
potentiometer wiper in the controller is moved, which
unbalances the bridge circuit. This unbalance is amplified,
and energizes
direction necessary to correct the change in temperature
or pressure. The motor turns the feedback potentiometer
to rebalance the circuit and stop the motor.
SERIES 90 CIRCUIT
Triac switching to run the motor in the
10
CONNECTION DIAGRAMS (Figs. 10-13)
These motors are designed for use in series 90 proportioning control circuits employing a 135 ohm series 90
controller. Series 90 high or low limit controls or manual
minimum position potentiometers may also be used in the
control circuit.
The M9484 can also be used with some electronic
mA
controllers which provide a 4-20
necessary to use a resistor kii (4074EED for controlling up
to 6 motors) or Q7230 Interface Module to interface to the
4-20 mA source.
The standard series 90 controller has R, W, and B
terminals. As the controller reduces Rto W resistance, the
motor will drive closed (CCW as viewed from the power
end).
control output. lt is
Page 11
SERIES 99
CONTROLLER
OPTIONAL CONNECTIONS
WITH 2-135 OHM POTENTIOMETERS IN SERIES.
SERIES 90
CONTROLLER
-
MOTOR
MOTOR
1
POWER SUPPLY.
n
PROTECTION AS REQUIRED.
2
TRANSFORMER MAY BE INTERNAL OR EXTERNAL TO MOTOR.
n
PROVlDE
SPDT SWITCH
OR SERIES 60
CONTROLLER
USED ASA
DISCONNECT MEANS AND OVERLOAD
EJ74C
SERIES 90 HIGH
LIMIT CONTROL
1
POWER SUPPLY.
n
PROTECTION AS REQUIRED.
2
TRANSFORMER MAY BE INTERNAL OR EXTERNALTO MOTOR.
n
IG.
1 l-MOTOR
PROVIDE
USED
DISCONNECT MEANS AN,, OVERLOAD
WITH
ASERIESSO
LER AND A SERIES 90 LOW OR HIGH
CONTROL.
4.20 mA
SOURCE
TRANSFORMER
SINGLE MOTOR
E2rM4
CONTROI
LIMI
I
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
1
PROTECTION AS REOUIRED.
USE SOLID LINE CONNECTION FOR POSITIVE CLOSING TO
2
!h
MINIMUM POSITON. SUBSTITUTE DOTTED LINE CONNECTION
FOR POSITIVE FULL CLOSURE.
TRANSFORMER MAY BE INTERNAL OR EXTERNAL TO MOTOR.
3
!I
12-CONNECTIONS FOR MOTOR, SERIES 90
;.
CONTROLLER, MINIMUM POSITION POTENTIOMETER (ETC.).
M428
SLAVE MOTOR(S)
UP TO 4 ADDITIONAL SLAVE MOTORS (6 TOTAL,
A
RESISTOR (A) DEPENDS ON NUMBER OF SLAVES. SEE RESISTOR SELECT-
ION CHART IN TEXT.
2
SEE MOTOR SPECIFICATIONS FOR
n
ACTUAL TERMINAL ARRANGEMENT.
E474A
L
13-CONNECTlONS FOR MOTOR USED WITH 4
FIG.
11
TO 20 mA CONTROL.
63-2195-I
Page 12
4074EED
MOTORS
1
2 2.0
:
5
6
a
Not part of this kit, obtain separately.
b
These values represent the controller output voltage
required to drive the motors.
RESISTOR SELECTION CHART FOR
4-20
mA
MIINIMUM
OUTPUT
VOLTAGE
REQUIRED
(Vdc)b
RESISTOR (A)
(Ohms) Part No.
1.7 23780213QCDHA
150
2.3 2.7 124 113802139BCEA 802139BBDA
3.0
105a
3.3 97.6”
802139BFAA
-
-
CHECKOUT
After installation and linkage adjustment, check the entire
motor and control hookup to ensure that-
*
The motor operates the damper or valve properly.
l The motor responds properly to the controller.
Inspect the motor, linkage, and valve or damper to see
that all mechanical connections are correct and secure. In
damper installations, the
pushrod
should not extend more
than a few inches past the ball joints. Check to see that
there is adequate clearance for the linkage to move
through its stroke without binding or striking other objects.
Check to see that cams operate the auxiliary switches,
if used, at the desired point of motor rotation.
NOTE: Motors are shipped in the fully closed position (the
limit of counterclockwise rotation as viewed from the
power end of the motor) with the stroke set at
SERIES 90 MOTORS OPERATION CHECK WITH MODUTROL MOTOR DISCONNECTED FROM CONTROLLER
90”.
STEP ACTION
1.
2.
3.
4.
Apply 24
Vaca.
Open terminal B and short W to R. Motor drives closed. Proceed to Step 6.
Open terminal W and short B to R. Motor drives open.
Connect terminals R to B to W.
RESPONSE
None.
Motor must drive to
Mid-
IF NO OR LIMITED RESPONSE
-
Proceed to Step 6.
Proceed to Step 6.
position.
5.
Remove jumpers from R, B, and W.
17 to 20 Vdc.
Check voltage between B and R,
No voltage or out of range. Proceed
to Step 7.
and W and R.
6.
7.
Motor does not drive.
Voltage out of range.
Motor is defective.
Motor printed wiring board
Replace motor.
Replace motor.
is defective.
8.
Disconnect 24
Vat.
Spring return motors return
Spring mechanism defective
to their normal mechanical -replace motor.
position.
NOTES:
a
Ensure motor transformer is sized properly. If a common transformer is used to power multiple motors, ensure power
input is in phase with all motors.
b
Motors may operate in Series 90 or two-position control applications. However, checking voltage between terminals
R
to B and R to W is necessary to confirm proper operation in electronic (W973, 4 to 20 mA etc.) applications.
DAMPER APPLICATION
1. Turn off power and remove wiring from the old
actuator.
2. Remove crank arm from shaft of old actuator and
remove the old actuator.
3.
Checkto
see
whether or
not the mounting bracket is
needed. lf the linkage can reach the lowershaft position of
the new actuator and if the crank arm has clearance for the
needed rotation, then the bracket is not needed. Use
4b.ffthe
sections and see Fig. 3 as well as the INSTALLATION,
SETTINGS &ADJUSTMENTS, and
of these instructions.
5. Use old mounting bolts to mount the new actuator.
6. Mountthedampercrankarmandlinkagetotheshaft
of the new actuator.
8. Use the CHECKOUT procedures to test the proper
adjustment of the crank arm and linkage.
bracket is needed,
referto
the Adapter Bracket
CHECKOUTsections
.
220738A Adapter Bracket or 221455A crank arm if crank
arm must rotate through the bottom plane of the motor (for
damper applications).
4a.If
the bracket is not needed, mount the new actuator
directly to the equipment and refer to the INSTALLATION,
SETTlNGS&ADJUSTMENTS,andCHECKOUTsections
of these instructions as needed.
VALVE APPLICATION
When installing a M9484, M9494 motor in a valve ap-
plication which has a
QlOO,
Q601 or
0618
it will be
necessary to use the 220738A Adapter Bracket provided
to
raisethe
motor. Ensure motor stroke is
V5011
motorshafttothesame height asthatof
160”
to operate Honeywell
two-way or
V5013
three-way valves.
theold
Honeywell
U.S.A.:
1885 Douglas Drive N. Australia, Canada, Finland, Franc%, Germany, Japan, Mexico, Netherlands,
Inc.
International Sates Offices
in all
principal cities of the world. Manufacturing in
Golden Valley, MN 55422-4386 Spain, Taiwan, United Kingdom, U.S.A.
CANADA: 740 Ellesmere Road
Scarborough, Ontario Ml P
2V9
PRINTED IN U.S.A.
@
Lz3
QUALITY IS KEY
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.