T7411A / LF20 / LF20-C / C7068 
T7411A
LF20
GENERAL 
The T7411A/LF20/LF20-C/C7068 Duct Temperature 
Sensors are used in ventilating and air conditioning 
systems to measure discharge, return, or outside air 
temperature. They are designed for duct mounting. The 
T7411A is available with two different probe lengths. 
These sensors are used in the following control systems: 
• Excel 5000 
• MicroniK 200 
• MicroniK 100 
• Excel Classic 
• Excel Plus 
•  High Performance Excel Plus 
• Excel EMC 
or other systems using PT100, PT1000, or NTC 20kΩ  
temperature sensing elements. 
Further, the C7068 is also suitable for installation in fancoil 
units or at air outlets. 
C7068
LF20-C
DUCT TEMPERATURE SENSORS 
PRODUCT DATA 
FEATURES 
• PT100, PT1000, or NTC20kΩ temperature sensing 
element 
• Wide sensing range 
• High accuracy 
• Stainless steel probe 
SPECIFICATION 
Nominal value 
PT100 100 Ω at 0 °C  
PT1000 1000 Ω at 0 °C  
NTC20kΩ 20 kΩ at 25 °C 
Accuracy 
PT100 / PT1000  IEC751 Class B 
  0.3 K +0.5% • |t| (t in °C) 
NTC20kΩ  0.3 K at 25 °C 
Sensitivity 
PT100  ≈ 0.385 Ω / K 
PT1000  ≈ 3.85 Ω / K 
NTC20kΩ  ≈ -934.5 Ω / K at 25 °C  
 (non-linear) 
Response time (at air velocity of 5 m/s [16.4 ft/s]) 
τ
LF20, LF20-C 
T7411 
C7068 
Electrical connection 
T7411A/LF20  terminals for 2 x 1.5 mm² cable 
LF20-C  5 m cable, 2-core, 
 seawater-resistant, 
 conduit M16x1,5 
C7068  1.5-m cable, 2-core 
C7068-5m  5-m cable, 2-core 
Ambient Limits 
Storage temperature  -35...+70 °C (-31…+158 °F) 
Humidity (T7411, LF20) 5…95% rh, non-condensing 
Safety (terminal box) 
Protection standard 
T7411A IP54 
LF20 IP30 
LF20-C IP65 
C7068 IP54 
Flame retardant  V1 as per UL94 
 Plastic (PC) 
Dimensions  See Fig. 1 on page 2 
 ≈ 42 s 
0.5
τ
 ≈ 45 s 
0.5
τ
 ≈ 4 min (at 1 m/s [3.3 ft/s]) 
0.5
® U.S. Registered Trademark  EN0B-0361GE51 R0907 
Copyright © 2007 Honeywell Inc. • All rights reserved 

T7411A / LF20 / LF20-C / C7068 DUCT TEMPERATURE SENSORS 
Models 
OS number  sensor type  sensing range 
LF20 
LF20-C 
T7411A1001  PT1000  -40...+80 °C  185 (7.28)  152 (5.98) 
T7411A1019 PT1000 -40...+80 °C 338 (13.30)  305 (12.00) 
T7411A1043  PT100  -40...+80 °C  185 (7.28)  152 (5.98) 
C7068A1007 
C7068A1007-5m 
NTC20kΩ  
NTC20kΩ 
NTC20kΩ  
NTC20kΩ 
-40...+80 °C  338 (13.30)  305 (12.00) 
-40...+80 °C  305 (12.00)  -- 
0...+70 °C  cable length: 1.5 m 
0...+70 °C  cable length: 5 m 
length in mm (inches) 
L1  T1 
DIMENSIONS OF T7411A / LF20 
47 (1.85)
23 (0.91)
max. 275 mm
(10.8 in.)
L1
LF20-C
0
3
6
6 (0.23)
4
8
55 (2.17)
19.5
(0.75)
T7411A, LF20
50 (1.97)
6 (0.23)
T1
7 (0.28)
Fig. 1. Dimensions of T7411A / LF20 and LF20-C in mm (inches) 
case hole diameter
allows Pg9 cable
L1
19.5
(0.75)
33 (1.3)
65
(2.55)
EN0B-0361GE51 R0907 
2

T7411A / LF20 / LF20-C / C7068 DUCT TEMPERATURE SENSORS 
INSTALLATION 
wiring run  max. length 
sensor to controller  200 m (660 ft) 
The temperature offset due to wire resistance per 10 m 
distance from sensor to controller, when using the T7411A 
(PT100 / PT1000) is stated in the following table: 
type of wire  PT1000  PT100 
0.5 mm2 (AWG20) 
1.0 mm2 (AWG17) 
1.5 mm2 (AWG15) 
NOTE:
 Use shielded wiring in areas with high EMI. 
Maintain a minimum distance of 15 cm (5.9’’) 
between sensor lines and 230 Vac power lines. 
0.18 
°
C (0.324 °F) 1.8 °C (3.24 °F) 
0.09 
°
C (0.162 °F) 0.9 °C (1.62 °F) 
0.06 
°
C (0.108 °F) 0.6 °C (1.08 °F) 
INSTALLATION OF C7068 
Fig. 2. Installation of the C7068 in mm (inches) 
3
EN0B-0361GE51 R0907 

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions 
Honeywell GmbH 
Böblinger Straβe 17  
D-71101 Schönaich 
Phone: (49) 7031 63701 
Fax:   (49) 7031 637493 
http://ecc.emea.honeywell.com 
Subject to change without notice. Printed in Germany 
EN0B-0361GE51 R0907