RECOMMENDATIONS FOR PROPER PROTECTIONRECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the location of fire and burglary detection devices help provide proper
coverage for the protected premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
• Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection a smoke detector should be installed outside of
each separate sleeping area, and on each additional floor of a multi-floor family living unit, including
basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not
normally recommended.
• For additional protection the NFPA recommends that you install heat or smoke detectors in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up
the sleeper if the door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air
conditioners or humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room
could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION APPLIANCES.
SOUNDING OF FIRE NOTIFICATION APPLIANCES.
SOUNDING OF FIRE NOTIFICATION APPLIANCES.SOUNDING OF FIRE NOTIFICATION APPLIANCES.
DINING
LIVING ROOM
KITCHEN
BEDROOM
BEDROOM
BEDROOM
TV ROOM
BEDROOM
KITCHEN
LIVING ROOM
DINING
BDRM
BDRM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
BEDROOM
BEDROOM
LVNG RM
BASEMENT
TO
BR
BEDROOM
KTCHN
CLOSED
.
DOOR
Heat-Activated Detectors
GARAGE
floor_plan-001-V1
Recommendations for Proper Intrusion Protection
• For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
premises. This would include any skylights that may be present, and the upper windows in a multi-level
building.
• In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals
can be sent to the alarm monitoring station in the event that the communications are out of order (if
connected to an alarm monitoring station).
This Honeywell security system is designed for use with devices manufactured or approved by Honeywell for use with the
system. The security system is not designed for use with any device that may be attached to the system's control or other
communicating bus if Honeywell has not approved such device for use with the system. Use of any such unauthorized device
may cause damage or compromise the performance of the security system and affect the validity of the end user’s Honeywell
limited warranty. When you install devices that have been manufactured or approved by Honeywell, you give the end user
the assurance that these devices have been thoroughly tested to ensure optimum performance when used with this
Honeywell security system.
- 2 -
Lyric Controller Installation and Reference Guide
Table of Contents
System Features
System Features .................................................................................................................................................................................................. 5
AC Power ............................................................................................................................................................................................................... 10
Install and Configure Communications Module ...................................................................................................................................... 11
Wireless Zones
Wireless Zones ................................................................................................................................................................................................... 13
Wireless ZonesWireless Zones
General Information ........................................................................................................................................................................................... 13
Zone Response Type Definitions ............................................................................................................................................................. 20
Zone Response Type DefinitionsZone Response Type Definitions
General Information .......................................................................................................................................................................................... 20
System Operation
System Operation ............................................................................................................................................................................................ 22
System Displays ................................................................................................................................................................................................. 24
Zone Status Displays ........................................................................................................................................................................................ 24
Installing the Rechargeable Backup Battery .................................................................................................................................... 7
Replacing the Rechargeable Backup Battery .................................................................................................................................. 7
Replace the Back Plate ............................................................................................................................................................................. 9
Install the Desk Stand ................................................................................................................................................................................ 9
Make Electrical Connections .................................................................................................................................................................. 10
Communications Module 24-Hour Standby power ...................................................................................................................... 11
Installing the Cellular Module ................................................................................................................................................................. 11
Checking Signal Strength ....................................................................................................................................................................... 12
Zones ............................................................................................................................................................................................................... 13
Range ............................................................................................................................................................................................................... 13
House Identification .................................................................................................................................................................................. 13
Transmitter Battery Life .......................................................................................................................................................................... 13
Home Screen ................................................................................................................................................................................................ 16
Master User Tools Screen ....................................................................................................................................................................... 17
Enter Installer Programming Mode ..................................................................................................................................................... 18
Select a Default Configuration.............................................................................................................................................................. 19
Enter/Change the Master Code by Installer .................................................................................................................................. 22
Secondary User Codes ............................................................................................................................................................................ 22
Contact ID Event Log Codes ................................................................................................................................................................ 26
- 3 -
Lyric Controller Installation and Reference Guide
Table of Contents (Continued)
Central Station Messages .......................................................................................................................................................................27
Testing the System
Testing the System ......................................................................................................................................................................................... 28
Testing the SystemTesting the System
Test Modes ................................................................................................................................................................................................... 28
Testing the System ................................................................................................................................................................................... 28
Armed System Test .................................................................................................................................................................................. 28
Zone Discovery Mode ............................................................................................................................................................................. 29
Rebooting the System ............................................................................................................................................................................ 29
LLLLyric
yric Programming Default
Programming Default Values
yricyric
Programming Default Programming Default
Zone Assignment/Alarm Response Types ..................................................................................................................................... 31
Zone Response Type
Zone Response Type Matrix
Zone Response Type Zone Response Type
Regulatory Agency Statements
SpecificationsSpecifications
Contacting Technical Support
Contacting Technical Support .................................................................................................................................................................. 36
Contacting Technical SupportContacting Technical Support
Glossary
Index ....................................................................................................................................................................................................................... 38
IndexIndex
Summary
Summary of
Summary Summary
Warranty Information
Warranty Information ................................................................................................................................................................ Rear Cover
Warranty InformationWarranty Information
of tttthis System Statement
his System Statement .................................................................................................................................................. 34
This system supports Lyric Lock, an advanced feature designed to keep it functioning optimally. Lyric Lock
capabilities include: the ability to interact with Honeywell and your company’s network for the setup and
programming of system features, support for remote software updates and the ability (when enabled) to
enhance the end user’s security by preventing unauthorized takeover of the system by another monitoring
company.
In the event that the end user wishes to authorize another company to take over the system, the end user may
request that Honeywell remotely disable Lyric Lock. Honeywell will require documentation that the end user
has attempted to contact your company three times and that your company has failed to respond, or failed to
agree to the end user’s request.
- 4 -
The Lyric Controller is a self-contained, rechargeable wireless control/communicator that features easy
installation and usage. A built-in speaker provides voice annunciation of system status along with voice
descriptors of each zone. An internal module allows the controller to communicate with the Central Station via
the Internet or (if installed) Cellular Wireless.
Lyric
Lyric Controller
Controller is not intended for UL985 Household Fire appl
Lyric Lyric
ETL
System Features
System Features
System FeaturesSystem Features
• 7.0-inch Color Graphic Touch Screen
• Message Center (for user recorded messages)
• Voice Announcement of System and Zone Status
• Ten User-selectable Chime Sounds
• Automatic Stay Arming
• Night Stay Arming
• 48 User Codes (Installer, Master, Guest, Duress)
• Panic Functions (Police, Fire, Medical)
• Programmable Reminders
• Video Camera Control (requires Wi-Fi® connection)
• Supports Mobile Devices (Tablet, iPAD, etc.) that duplicate functions of the Lyric Controller (i.e.;
Security, Web Content Home Automation and Video Control)
• Built-in Camera
Home Automation
Home Automation
Home AutomationHome Automation
• Integrated Z-Wave Support
• Control up to 72 Z-Wave Home Automation Devices including:
- Thermostats (up to 6)
- Door Locks (up to 6)
- Devices (outlets, switches, lamps/appliances) (up to 60)
• Displays Local Weather (requires Total Connect Service)
• Dealer/Central Station Messages (requires Total Connect Service)
- 6 -
Lyric Controller Installation and Reference Guide
SCREW
lyric-031-V1
SCREW
LCP500-4B
STANDARD CAPACITY
BATTERY PACK
(p/n 300-03864-AIO)
RETAINER
OR
RETAINER
LCP500-24B
HIGH CAPACITY
BATTERY PACK
(p/n 300-03866-AIO)
In
Installing
stalling the Control
InIn
stallingstalling
Backup
Backup Battery Installation
BackupBackup
The Lyric Controller is equipped with an integral, replaceable, rechargeable battery pack rated at 7.2Vdc. In the
event of an AC power loss, the system is supported by the long life backup battery that is supervised for
connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a
“low battery” message is displayed and a report is sent to the Central Station. In addition, the system will beep
once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping). Select
the appropriate battery pack, based on the installation’s requirement, and install the battery pack. Follow the
steps and refer to the figure below to install and connect the battery.
Battery Selection
Battery Selection
Battery SelectionBattery Selection
Select the appropriate battery pack, based on the installation’s requirement, and install the battery pack.
Battery Part Number
Battery Part Number Battery StandbyTime
Battery Part NumberBattery Part Number
LCP500-4B (300-03864-AIO) 4-hours (minimum) Approximately 1-hour before battery depletion
LCP500-24B (300-03866-AIO) 24-hours (minimum) At least 1-hour before battery depletion
Installing the Rechargeable Backup Battery
Installing the Rechargeable Backup Battery
Installing the Rechargeable Backup BatteryInstalling the Rechargeable Backup Battery
1. Insert the battery pack into controller’s rear case.
2. Install the battery retainer.
3. Secure the battery retainer with the provided screw.
4. Connect the battery pack connector to the receptacle on the back of the controller.
5. Align the slots on the back of the controller with the hooks on the wall mount as shown below.
6. Once attached, insert the screw to secure the controller to the wall mount.
7. Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the “System Standby!”
screen will be displayed.
Battery Installation
Battery InstallationBattery Installation
Battery StandbyTime Low Battery Notification
Battery StandbyTimeBattery StandbyTime
Low Battery Notification
Low Battery NotificationLow Battery Notification
the Control
the Controlthe Control
Rechargeable batteries may take up to 48
Rechargeable batteries may take up to 48----hours to fully charge. The “Low Battery” message
Rechargeable batteries may take up to 48Rechargeable batteries may take up to 48
should clear within four hours or by entering Test Mode.
should clear within four hours or by entering Test Mode.
should clear within four hours or by entering Test Mode.should clear within four hours or by entering Test Mode.
Replacing the Rechargeable Backup Battery
Replacing the Rechargeable Backup Battery
Replacing the Rechargeable Backup BatteryReplacing the Rechargeable Backup Battery
1. When battery replacement is required, at the Installer Programming Tools Menu select “Test” OR at the
Master User Tools Menu screen select the “Advanced” icon.
2. Select “Install Backup Battery” and follow the displayed steps to replace the battery or follow the steps
below.
RRRRemove the battery
emove the battery
emove the batteryemove the battery
1. Unscrew the screw securing the controller to the wall mount (if used).
2. Release the catch that secures the controller to the wall mount.
3. Rotate the controller away from the wall and lift it from the wall mount, being careful not to damage the
wiring.
hours to fully charge. The “Low Battery” message
hours to fully charge. The “Low Battery” message hours to fully charge. The “Low Battery” message
- 7 -
Lyric Controller Installation and Reference Guide
lyric-036-V1
INSERT SCREW
(IF APPLICABLE)
WALL
MOUNT
WALL
SURFACE
TAMPER
SCREW
(OPTIONAL)
MOUNTING
SCREW (4)
TYP.
Installing
Installing the Control
InstallingInstalling
the Control (Continued)
the Control the Control
4. Disconnect the battery pack connector from the receptacle on the back of the controller.
5. Remove the screw that secures the battery retainer and remove the battery retainer.
6. Remove the battery pack from the back case.
Install the replacement battery
Install the replacement battery
Install the replacement batteryInstall the replacement battery
1. Install a replacement battery pack LCP500-4B (p/n 300-03864-AIO) OR LCP500-24B (p/n 300-03866AIO) into the back of the controller.
2. Install the battery retainer.
3. Secure the battery retainer with the provided screw.
4. Connect the battery pack connector to the receptacle on the back of the controller.
5. Align the slots on the back of the controller with the hooks on the wall mount as shown below.
6. Once attached, insert the screw to secure the Lyric to the wall mount.
NOTE:
NOTE: If a Cellular Communication Module is being installed, verify the module’s signal strength before
NOTE:NOTE:
selecting a final mounting location. Refer to Checking the Signal Strength in the Communications
Module section.
Wall Mounting
Wall Mounting
Wall MountingWall Mounting
NOTE:
NOTE: When selecting a location for the Lyric Controller, be sure to provide a separation of at least 10 feet
NOTE: NOTE:
between 2.4GHz devices such as Wi-Fi Routers/Access Points.
For wall mounting follow the steps and refer to the figure below.
1. Feed the field wiring through the appropriate openings in the wall mount.
2. Attach the wall mount to a sturdy wall using the four provided screws.
3. If required, install an additional mounting screw in the case tamper.
4. Align the slots on the back of the controller with the hooks on the wall mount as shown below.
5. Once attached, insert the screw to secure the Lyric to the wall mount.
- 8 -
Lyric Controller Installation and Reference Guide
lyric-050-V0
SCREW
REMOVE
INSTALL
lyric-052-V0
STAND LOCATION 60
STAND LOCATION 30
Installing
Installing the Control
InstallingInstalling
Desktop Mounting
Desktop Mounting
Desktop MountingDesktop Mounting
NOTE:
NOTE: When selecting a location for the Lyric Controller, be sure to provide a separation of at least 10 feet
NOTE: NOTE:
between 2.4GHz devices such as Wi-Fi Routers/Access Points.
For desktop mounting the Lyric Desk Stand (LCP500-DK) is installed in place of the wall mount. The desk Stand
can be installed in two positions that provide a viewing angle of 30 degrees or 60 degrees. Follow the steps and
refer to the figures below.
Replace the Back Plate
Replace the Back Plate
Replace the Back Plate Replace the Back Plate
1. Remove the screw securing the rear cover to the controller.
2. Remove the rear cover.
NOTE
NOTE: If using the high-capacity (24-hour) backup battery (Kit LCP500-24B, battery p/n 300-03866-AIO),
NOTENOTE
remove the battery retainer clip. The clip is not required when the desk mount is installed.
3. Feed the field wiring through the appropriate openings in the rear cover included with the Lyric Desk Stand
(LCP500-DK).
4. Install the new rear cover.
5. Install the screw to secure the rear cover to the Lyric Controller.
the Control (Continued)
the Control the Control
Install Desk Stand
Install Desk Stand
Install Desk StandInstall Desk Stand
1. Align the slots on the back of the controller with the hooks on the desk stand as shown below.
2. Insert the stand into the slots on the rear case to provide the desired viewing angle and slide up to lock in
place.
- 9 -
Lyric Controller Installation and Reference Guide
MAXIMUM DISTANCE BETWEEN POWER
MAXIMUM DISTANCE BETWEEN POWER MAXIMUM DISTANCE BETWEEN POWER
MAXIMUM DISTANCE BETWEEN POWER
WIRE
WIRE WIRE
WIRE
Up to 8 feet (2.44 m)
# 22
Up to 13 feet (3.96 m)
# 20
Up to 20 feet (6.1 m)
# 18
3
1
2
4
lyric-035-V1
USB PORT
DETAIL A
BATTERY
RECEPTACLE
TAMPER
TERMINAL
BOARD
HWZ2
GND
HWZ1
+9VDC
GND
Installing
Installing the Control
InstallingInstalling
AC Power
AC Power
AC PowerAC Power
the Control (Continued)
the Control the Control
The Lyric Controller is powered by a 110VAC, 60 Hz/9 Volt DC, 2.5 Amp Plug-in Power Supply, 300-04705V1
(300-04063V1 in Canada). Refer to the wiring table below for wire gauge and length.
WIRING TABLE
WIRING TABLE
WIRING TABLEWIRING TABLE
Use only the 300
SUPPLY AND CONTROLLER
SUPPLY AND CONTROLLER
SUPPLY AND CONTROLLERSUPPLY AND CONTROLLER
Wiring Overview
Wiring Overview
Wiring OverviewWiring Overview
GAUGE
GAUGE
GAUGEGAUGE
Use only the 300----04705V1
Use only the 300Use only the 300
Canada) Po
Canada) Power Supply. Do not plug the
Canada) PoCanada) Po
power supply into the AC outlet until after
power supply into the AC outlet until after
power supply into the AC outlet until after power supply into the AC outlet until after
all wiring connections have been made
all wiring connections have been made ....
all wiring connections have been madeall wiring connections have been made
04705V1 (300
04705V1 04705V1
wer Supply. Do not plug the
wer Supply. Do not plug the wer Supply. Do not plug the
(300----04063V1
04063V1
(300(300
04063V1 04063V1
The following summarizes the electrical connections associated with the Lyric Controller. Follow the steps and
refer to the figure below when making connections. Refer to the Summary of Connections diagram for
additional information.
Make Electrical Connections
Make Electrical Connections
Make Electrical ConnectionsMake Electrical Connections
1. Temporarily hang the controller from the hook on the wall mount.
2. If used, connect the hardwire sensors/contacts to the HWZ1/HWZ2 (+) and GND (-) terminals.
3. Remove the Power Supply Sleeve from the Power Supply.
4. Route the wiring through the Power Supply Sleeve (if used).
5. Connect the wires to the +9VDC and GND terminals on the Power Supply and reinstall the Sleeve.
6. Align the slots on the back of the controller with the hooks on the wall mount as shown below.
7. Once attached, insert the screw to secure the controller to the wall mount.
8. Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the “System Standby!”
screen will be displayed.
- 10 -
Lyric Controller Installation and Reference Guide
!
Model
ModelModel
Model
Description
DescriptionDescription
Description
LYRIC
-3G GSM Cellular Communications Module
L
YRIC
-3GC (Canada)
GSM Cellular Communi
cations Module
LYRIC
-
CDMA
CDMA Cellular Communications Module
LYRIC
-
LTE (Series)
LTE Cellular
Communications Module
!
WARNING: The
WARNING: The WARNING: The
WARNING: The
in (20 cm) from all persons and not co
in (20 cm) from all persons and not coin (20 cm) from all persons and not co
in (20 cm) from all persons and not co
transmitter except in accordance with FCC multi
transmitter except in accordance with FCC multitransmitter except in accordance with FCC multi
transmitter except in accordance with FCC multi
The
The The
The
alarm reporting can take place.
alarm reporting can take place.alarm reporting can take place.
alarm reporting can take place.
Installing
Installing the Control (Continued)
InstallingInstalling
The
The LYRIC
LYRIC----CDMA
The The
LYRICLYRIC
Alaska
Alaska and Hawaii
Alaska Alaska
Communication Modules
Communication Modules
Communication ModulesCommunication Modules
The Lyric Controller supports Central Station reporting using wireless/cellular and Wi-Fi communications
devices. They also support upload/download programming capability via the Internet. This allows site
maintenance independent of Central Station monitoring, and modification to sites globally via the Internet. Refer
to the Programming Guide (p/n 800-18077) for information regarding programming and registration.
Additionally, an internal Z-Wave module allows the Lyric Controller to support Home Automation functions.
(refer to the Lyric User Guide (p/n 800-16078 for additional information.) The controllers are compatible with
the following AlarmNet Communication Modules:
Communic
Communications Module
CommunicCommunic
If 24-hour standby is required, the Super High Capacity battery (p/n 300-03866-AIO) must be installed.
ations Module 24
ations Moduleations Module
CDMA Communications Module is only available in the continental United States,
CDMACDMA
and Hawaii....
and Hawaiiand Hawaii
Communications Module is only available in the continental United States,
Communications Module is only available in the continental United States, Communications Module is only available in the continental United States,
24----Hour Standby Power
Hour Standby Power
2424
Hour Standby PowerHour Standby Power
RF E
RF Exposure
xposure
RF ERF E
xposurexposure
Lyric
Lyric Controller
Controller must be installed to provide a separation distance of at least 7.8
Lyric Lyric
ControllerController
must be installed to provide a separation distance of at least 7.8
must be installed to provide a separation distance of at least 7.8 must be installed to provide a separation distance of at least 7.8
----located or operated in conjunction with any other
located or operated in conjunction with any other
located or operated in conjunction with any other located or operated in conjunction with any other
----transmitter pr
transmitter product procedures.
transmitter prtransmitter pr
the Control (Continued)
the Control (Continued)the Control (Continued)
oduct procedures.
oduct procedures.oduct procedures.
Insta
Install
InstaInsta
Follow the steps and refer to the figure below to install the Communications Module.
Installing the
Installing the Cellular
Installing the Installing the
1. At the Installer Programming Tools Menu screen select “Test” OR at the Master User Tools Menu
2. Select “Install Cellular Module” and follow the prompts displayed on the controller or follow the steps below.
3. Remove controller side cover (bezel).
4. Remove the screw securing the module to the controller (if installed).
5. Remove the existing Cellular Communications Module (if installed).
6. Install the Cellular Communications Module into the controller.
7. Ensure that the Communications Module is properly seated into the controller.
8. Insert the side cover (bezel) into the controller.
9. Slide the side cover (bezel) down to lock it in place and secure the Communications Module.
10. Select OK to complete the installation.
11. Enable the Communications Module, configure alarm reporting and module supervision and register the
ll and Confi
and Configur
llll
and Confiand Confi
Cellular Communications Module
Cellular Cellular
Programming screen select “Advanced”.
NNNNOTE
OTE:::: The Communication Path will be dynamically adjusted when a Cellular Communication Module is
OTEOTE
installed or removed.
device. Refer to the “Program Communicator” and “Communications Diagnostics” sections in the
Programming Guide (p/n 800-18077). OR Log on to the AlarmNet 360 website (http://alarmnet360.com).
Communications Module
Communications Module must be registered
Communications ModuleCommunications Module
gureeee CCCCommunication
gurgur
ommunication Module
ommunication ommunication
Communications Module
Communications ModuleCommunications Module
must be registered with
must be registered must be registered
Module
ModuleModule
with AlarmNet 360
AlarmNet 360 before downloading o
with with
AlarmNet 360AlarmNet 360
before downloading or
before downloading obefore downloading o
r
r r
- 11 -
Lyric Controller Installation and Reference Guide
PUSH UP THEN SLIDE OUT
SLIDE IN THEN PUSH DOWN
COMMUNICATION
MODULE
lyric-060-V0
2
1
2
1
12
Installing
Installing the Cont
InstallingInstalling
Communication Modules
Communication Modules
Communication ModulesCommunication Modules
the Control (Continued)
the Contthe Cont
rol (Continued)
rol (Continued)rol (Continued)
Checking Signal Strength
Checking Signal Strength
Checking Signal StrengthChecking Signal Strength
When choosing a suitable mounting location, check the communications module’s signal strength to
ensure proper operation. For most installations, using the module’s internal antenna, mounting the
Lyric controller as high as practical, and avoiding large metal components provides adequate signal
strength for proper operation. To check signal strength, perform the following test.
Check Signal Strength
Check Signal Strength
Check Signal StrengthCheck Signal Strength
1. With the System in the Installer Programming mode, select the “Comm. Diagnostics” button and
then select the “Cellular Information” button. The Cellular Information will be displayed and
signal strength is displayed in bars (1 -5 bars).
2. Verify that adequate Signal Strength (greater than 1 bar) is available. If necessary, relocate the
Controller to obtain better signal strength (select “Cellular Information” again to refresh the
reading).
3. If adequate signal strength cannot be achieved, External Antenna Kit model Cell-ANTST (Lyric3G/3GC, Lyric-CDMA) or Cell-ANTU (Lyric-LTE Series) should be used.