The LCBS Connect Wall Module is a Sylk bus
communicating device which is exclusively compatible
with the LCBS Connect controller. It contains integral
temperature and humidity sensors to control any given
space’s comfort. This device enables local controller
configuration through an easy-to-use touch screen
interface with menu driven selections. The wall module
communicates and is powered by the Sylk bus, so no
additional wiring is necessary.
Dimensions
The TS120 consists of a back plate and a front cover which
contains a circuit board.
Fig. 1. Dimensions in in. (mm).
INSTALLATION
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the prod-
uct to ensure the product is suitable for the application.
3. Installer must be a trained, experienced service tech-
nician.
4. After installation is complete, check out product
operation as provided in these instructions.
MOUNTING
Mount the wall module on an inside wall approximately 48
in (1.2m) from the floor (or in the specified location) to
allow for exposure to the average zone temperature. Do
not mount the device on an outside wall, on a wall
containing water pipes or near air ducts. Avoid locations
that are exposed to discharge air from registers or
radiation from appliances, lights or the sun.
31-00084-01
Page 2
LCBS CONNECT WALL MODULE
CAUTION
4 FEET
(1.2 METERS)
YES
NO
NO
NO
M36229
Do not install the wall module where it can be affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
WHEN USED TO SENSE ROOM TEMPERATURE
Install the wall module about 4 ft. (1.2m) above the floor in
an area with good air circulation at average temperature.
(See Fig. 2.) Confirm mounting height meets Americans
with Disabilities Act requirements.
WHEN NOT USED TO SENSE ROOM TEMPERATURE
When using the remote-mounted temperature (and
humidity) sensor(s) to sense ambient conditions, install
the wall module in an area that is accessible for setting
and adjusting the temperature and settings.
STANDARD UTILITY
CONDUIT BOX
SCREW
SCREW
SCREW
WALL
OUTLET BOX
SCREW
Fig. 3. Mounting the wall module to electrical boxes.
WIRING
M36283
Fig. 2. Typical location of wall module
or remote-mounted sensor.
When mounting the wall module to the wall, note the
arrows indicating which direction is up, as indicated on
the inside of the back plate. The wall module can only be
mounted horizontally, so it is important to properly
identify a suitable mounting location.
The wall module can be mounted on a wall, on a standard
utility conduit box using No. 6 (3.5 mm) screws or on a 60
mm wall outlet box (see Fig. 3). When mounting directly on
a wall, use screws appropriate for the wall material. Use a
wall plate, 50028399-001, to cover any visible screw
holes.
The wall module is shipped with the front cover and
subbase assembled together. These two parts need to be
separated (see Fig. 4) in order to properly wire the device.
There are no field adjustable/replaceable components
inside the module.
M36296
Fig. 4. Separate the front cover from the subbase.
31-00084—012
IMPORTANT
All wiring must comply with local electrical codes
and ordinances or as specified on wiring diagrams.
Improper Electrical Contact Hazard
Screw-type terminal blocks are designed to accept
no more than one 14AWG (2.5mm sq) conductor.
Page 3
LCBS CONNECT WALL MODULE
Wire the terminal block as shown in Fig. 5:
1. For single wires, strip 3/16 in. (5 mm); for multiple
wires going into one terminal, strip 1/2 in. (13 mm)
insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. Review and verify the terminal connection wiring
illustrated in Fig. 5.
M36289
Fig. 5. Connecting wires to the terminal block.
4. See Fig. 6 for wiring multiple Sylk devices.
TWO WIRES INTO ONE TERMINAL
1.
(13)
1/2
STRIP 1/2 IN.
(13MM) FROM
WIRES TO BE
ATTACHED AT
ONE TERMINAL.
WALL MODULE
TERMINALS
5. When wiring is complete, align the pins from the
front cover to the terminal block on the subbase.
6. Firmly push the front cover onto the subbase. If the
wall module is powered, a loading screen will be displayed.
Sylk Bus
The wall module communicates with the LCBS Connect
controller via Sylk, which is a two-wire, polarity-insensitive
bus that provides both 18 Vdc power and
communications. This enables a faster and cheaper
installation all while minimizing errors. The recommended
wire for Sylk is 18-24 AWG (0.82 to 0.20 sq mm) single
twisted pair, solid or stranded wire, unshielded for a
maximum distance from the controller of 200ft (60m).
Standard thermostat wire (non-twisted pair) can be used
for runs up to 100ft (30m). See Table 1.
Table 1. Maximun Distance.
Recommended maximum distance from
controller to any Sylk device
Single twisted pair, nonshielded, stranded or solid
18-22 AWG24 AWG18-24 AWG
500ft (150m) 400ft (120m)100ft (30m)
The wall module is intended to always communicate using
Sylk address 1 and is shipped from the factory with this
address configured. Other Sylk sensors are compatible
with the LCBS Connect controller and wall module but
limitations must be observed. Up to FOUR additional Sylk
sensors can be used unless a TR40-H, TR40-CO2 or TR40H-CO2 is used. Then the allowed additional sensors drops
to THREE. See Table 2 for a listing of the compatible Sylk
sensors.
Standard thermostat wire,
(non-twisted), shielded or
non-shielded, stranded or
solid
3.
2.
TWIST WIRES
TOGETHER
WITH PLIERS
(A MINIMUM OF
THREE TURNS).
DAISY-CHAINING MULTIPLE
SYLK DEVICES
TO CONTROLLER
TO SYLK DEVICE
CUT TWISTED END OF WIRES TO
3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING
SCREW. THEN PULL ON EACH WIRE
IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
HOME RUNNING MULTIPLE
SYLK DEVICES
TO CONTROLLER
M36315
Fig. 6. Options for wiring multiple Sylk devices.
Compatibility
The LCBS wall module has been designed specifically for
the LCBS controller. They are a one-to-one pair and
adding an additional LCBS wall module will result in a loss
of operation. Connecting an LCBS wall module to another
Honeywell controller will also result in the loss of
operation for the wall module.
331-00084—01
Page 4
LCBS CONNECT WALL MODULE
SPECIFICATIONS
Operating Temperature: 32°F to 122°F (0°C to 50°C)
Shipping Temperature: -4°F to 150°F (20°C to 65°C)
Relative Humidity: 5% to 95%, Non-condensing
Related Parts
Parts that are commonly used with the LCBS Connect
controller and wall module are shown in Table 2.
Table 2. Compatible Sylk Sensors.
Sylk
DeviceDescription
YCRL6438SR1000 Controller and Wall
Module Pack
TR40Sylk Wall Module with
Temperature Sensor
TR40-HSylk Wall Module with
Temperature & Humidity
Sensors
TR40-CO2Sylk Wall Module with
Temperature & CO2
Sensors
TR40-H-CO2Sylk Wall Module with
Temperature, Humidity
& CO2 Sensors
C7400S1000Sylk Enthalpy Sensor8, 9
50028399-0001Wall PlateN/A
Sylk
Address(s)
N/A
3, 4, 5, 6
3 Only
3 Only
3 Only
Approvals
This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a
residential installation. This equipment generates uses
and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions,
may cause harmful interference to radio communications.
However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does
cause harmful interference to radio or television
reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following
measures:
— Reorient or relocate the receiving antenna.
— Increase the separation between the equipment and
receiver.
— Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions: (1)
this device may not cause harmful interference, and (2)
this device must accept any interference received,
including interference that may cause undesired
operation.
This Class B digital apparatus complies with Canadian
ICES-003.
Cet appareil numérique de la classe B est conforme à la
norme NMB-003 du Canada.
This device complies with Industry Canada licenseexempt RSS standard(s). Operation is subject to the
following two conditions: (1) this device may not cause
interference, and (2) this device must accept any
interference, including interference that may cause
undesired operation of the device.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or
modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any
liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.