Honeywell LCBS Connect Installation Instructions Manual

Page 1
LCBS Connect Wall Module
M36282
4-49/64
(121)
3-5/16
(84)
53/64
(21)
INSTALLATION INSTRUCTIONS
PRODUCT DESCRIPTION
The LCBS Connect Wall Module is a Sylk bus communicating device which is exclusively compatible with the LCBS Connect controller. It contains integral temperature and humidity sensors to control any given space’s comfort. This device enables local controller configuration through an easy-to-use touch screen interface with menu driven selections. The wall module communicates and is powered by the Sylk bus, so no additional wiring is necessary.
Dimensions
The TS120 consists of a back plate and a front cover which contains a circuit board.
Fig. 1. Dimensions in in. (mm).
INSTALLATION
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check ratings given in instructions and on the prod-
uct to ensure the product is suitable for the applica­tion.
3. Installer must be a trained, experienced service tech-
nician.
4. After installation is complete, check out product
operation as provided in these instructions.
MOUNTING
Mount the wall module on an inside wall approximately 48 in (1.2m) from the floor (or in the specified location) to allow for exposure to the average zone temperature. Do not mount the device on an outside wall, on a wall containing water pipes or near air ducts. Avoid locations that are exposed to discharge air from registers or radiation from appliances, lights or the sun.
31-00084-01
Page 2
LCBS CONNECT WALL MODULE
CAUTION
4 FEET
(1.2 METERS)
YES
NO
NO
NO
M36229
Do not install the wall module where it can be affected by: — drafts or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
WHEN USED TO SENSE ROOM TEMPERATURE
Install the wall module about 4 ft. (1.2m) above the floor in an area with good air circulation at average temperature. (See Fig. 2.) Confirm mounting height meets Americans with Disabilities Act requirements.
WHEN NOT USED TO SENSE ROOM TEMPERATURE
When using the remote-mounted temperature (and humidity) sensor(s) to sense ambient conditions, install the wall module in an area that is accessible for setting and adjusting the temperature and settings.
STANDARD UTILITY
CONDUIT BOX
SCREW
SCREW
SCREW
WALL
OUTLET BOX
SCREW
Fig. 3. Mounting the wall module to electrical boxes.
WIRING
M36283
Fig. 2. Typical location of wall module
or remote-mounted sensor.
When mounting the wall module to the wall, note the arrows indicating which direction is up, as indicated on the inside of the back plate. The wall module can only be mounted horizontally, so it is important to properly identify a suitable mounting location.
The wall module can be mounted on a wall, on a standard utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm wall outlet box (see Fig. 3). When mounting directly on a wall, use screws appropriate for the wall material. Use a wall plate, 50028399-001, to cover any visible screw holes.
The wall module is shipped with the front cover and subbase assembled together. These two parts need to be separated (see Fig. 4) in order to properly wire the device.
There are no field adjustable/replaceable components inside the module.
M36296
Fig. 4. Separate the front cover from the subbase.
31-00084—01 2
IMPORTANT
All wiring must comply with local electrical codes and ordinances or as specified on wiring diagrams.
Improper Electrical Contact Hazard
Screw-type terminal blocks are designed to accept no more than one 14AWG (2.5mm sq) conductor.
Page 3
LCBS CONNECT WALL MODULE
Wire the terminal block as shown in Fig. 5:
1. For single wires, strip 3/16 in. (5 mm); for multiple
wires going into one terminal, strip 1/2 in. (13 mm) insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. Review and verify the terminal connection wiring
illustrated in Fig. 5.
M36289
Fig. 5. Connecting wires to the terminal block.
4. See Fig. 6 for wiring multiple Sylk devices.
TWO WIRES INTO ONE TERMINAL
1.
(13)
1/2
STRIP 1/2 IN. (13MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
WALL MODULE TERMINALS
5. When wiring is complete, align the pins from the
front cover to the terminal block on the subbase.
6. Firmly push the front cover onto the subbase. If the
wall module is powered, a loading screen will be dis­played.
Sylk Bus
The wall module communicates with the LCBS Connect controller via Sylk, which is a two-wire, polarity-insensitive bus that provides both 18 Vdc power and communications. This enables a faster and cheaper installation all while minimizing errors. The recommended wire for Sylk is 18-24 AWG (0.82 to 0.20 sq mm) single twisted pair, solid or stranded wire, unshielded for a maximum distance from the controller of 200ft (60m). Standard thermostat wire (non-twisted pair) can be used for runs up to 100ft (30m). See Table 1.
Table 1. Maximun Distance.
Recommended maximum distance from
controller to any Sylk device
Single twisted pair, non­shielded, stranded or solid
18-22 AWG 24 AWG 18-24 AWG
500ft (150m) 400ft (120m) 100ft (30m)
The wall module is intended to always communicate using Sylk address 1 and is shipped from the factory with this address configured. Other Sylk sensors are compatible with the LCBS Connect controller and wall module but limitations must be observed. Up to FOUR additional Sylk sensors can be used unless a TR40-H, TR40-CO2 or TR40­H-CO2 is used. Then the allowed additional sensors drops to THREE. See Table 2 for a listing of the compatible Sylk sensors.
Standard thermostat wire, (non-twisted), shielded or non-shielded, stranded or solid
3.
2.
TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
DAISY-CHAINING MULTIPLE SYLK DEVICES
TO CONTROLLER
TO SYLK DEVICE
CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
HOME RUNNING MULTIPLE SYLK DEVICES
TO CONTROLLER
M36315
Fig. 6. Options for wiring multiple Sylk devices.
Compatibility
The LCBS wall module has been designed specifically for the LCBS controller. They are a one-to-one pair and adding an additional LCBS wall module will result in a loss of operation. Connecting an LCBS wall module to another Honeywell controller will also result in the loss of operation for the wall module.
3 31-00084—01
Page 4
LCBS CONNECT WALL MODULE
SPECIFICATIONS
Operating Temperature: 32°F to 122°F (0°C to 50°C)
Shipping Temperature: -4°F to 150°F (20°C to 65°C)
Relative Humidity: 5% to 95%, Non-condensing
Related Parts
Parts that are commonly used with the LCBS Connect controller and wall module are shown in Table 2.
Table 2. Compatible Sylk Sensors.
Sylk
Device Description
YCRL6438SR1000 Controller and Wall
Module Pack
TR40 Sylk Wall Module with
Temperature Sensor
TR40-H Sylk Wall Module with
Temperature & Humidity Sensors
TR40-CO2 Sylk Wall Module with
Temperature & CO2 Sensors
TR40-H-CO2 Sylk Wall Module with
Temperature, Humidity & CO2 Sensors
C7400S1000 Sylk Enthalpy Sensor 8, 9
50028399-0001 Wall Plate N/A
Sylk
Address(s)
N/A
3, 4, 5, 6
3 Only
3 Only
3 Only
Approvals
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: — Reorient or relocate the receiving antenna. — Increase the separation between the equipment and
receiver.
— Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
This device complies with Industry Canada license­exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Home and Building Technologies
In the U.S.:
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422-3992
customer.honeywell.com
® U.S. Registered Trademark © 2017 Honeywell International Inc. 31-00084—01 M.S. 01-17 Printed in United States
Loading...