Honeywell L8124B, L8124C, L8124A, L8124G, L8124E Product Data

...
L8124A,B,C,E,G,L,M
Aquastat® Relays
PRODUCT DATA

GENERAL

These immersion type controllers are for use with forced hydronic heating systems that include domestic hot water service.

FEATURES

• L8124 Aquastat® Relays provide high limit, low limit, and circulator control for maintaining boiler temperatures.
• L8124 Aquastat Relays can provide multizone control by using a separate circulator and R845 Relay for each zone.
• All L8124 Aquastat Relays mount directly on the boiler.
• L8124E,G and L have large transformers and extra terminals for supplying power to low voltage zone valves.
• L8124M is for use in a wood-coal/gas-oil multifuel heating system. Circulator is independently controlled by the thermostat.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
Contents
General ............................................................................. 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 5
Wiring ............................................................................... 7
Operation .......................................................................... 10
Setting And Checkout ....................................................... 10
Checkout .......................................................................... 14
Material Safety Data Sheet (MSDS) ................................. 14
60- 2061- 10
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

TRADELINE® Models

TRADELINE models are selected and packaged for ease of handling, ease of stocking, and maximum replacement value. TRADELINE model specifications are the same as those of standard models except as noted in Table 1.
Tradeline Models Available L8124B,E,G,L Aquastat Relays
without well and spud.
Additional Features:
• Heat-conductive compound for better bulb response in oversized well.
• Case can be vertically or horizontally mounted.
• Field-addable limit stops.
• TRADELINE pack with cross reference label and special instructions.
Pressure Rating:
200 psi (1380 kPa) on outside of immersion well. 100 psi (690 kPa) on capsule if inserted directly.
Maximum Ambient Temperature:
Case: 150°F (66°C).
Sensing element: 265°F (129°C).
Thermostat Heat Anticipator Setting: 0.2A.
Low Limit:
Setting: 110°F to 220°F, adjustable (43°C to 104°C). Differential: 10°F to 25°F, adjustable (6°C to 14°C).
High Limit:
Setting: 130°F to 240°F, adjustable (54°C to 116°C). Differential: 10°F, fixed (6°C).
Mounting Means: 1/2 or 3/4 in. taper pipe threaded.
Dimensions: See Fig. 1 and 2.
Sensing Element: 3/8 x 2-7/8 in (10 x 73 mm).
Insulation Depth: 1-1/2 or 3 in. (38 or 76 mm);
see Fig. 1 and 2.
Insertion Length: 3-3/8 in. (86 mm).
Approvals:
Underwriters Laboratories Inc.:
Listed (L8124 models with well): File No. MP466,
Guide No. MBPR.
Component Recognized (L8124 Models Without Well):
File No. MP466, Guide No. MBPR2.
Canadian Standards Association:
Component Recognized: File No. LR1620,
Guide No. 400-E-O.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2061—10 2
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
Table 1. Aquastat Relay models.
Electrical
Ratings
Burner Circuit
Model
Number
Burner
Control
Circuit
Case Dimensions
Height Width Depth
in. mm in. mm in. mm
Can be
Used For
Multizone
With
Circulators
No. of V8043
Zone Valves
Powered
Without
Additional
a
Transformer
L8124A 120V 6-1/8 156 4-3/8 111 3-1/16 78 Yes Same as
L8124A-G,L circulator rating
L8124B
b
6-1/8 156 4-3/8 111 3-1/16 78 0.25A at 1/4
to 12 Vdc
L8124C 120V 4-3/8 111 6-1/8 156 3-1/16 78 Yes Same as
L8124A-G,L circulator rating
L8124E 24V 6-1/8 156 4-3/8 111 3-1/16 78 Yes 2 1.25A at 24
Vac ; 3 0 VA (total load) B1-B2 TV-Z
L8124G 120V 6-1/8 156 4-3/8 111 3-1/16 78 2 Same as
L8124A-G,L circulator rating
L8124L 120V 4-3/8 111 6-1/8 156 3-1/16 78 Yes 2 Same as
L8124A-6,L circulator rating
L8124M 120V 4-3/8 111 6-1/8 156 3-1/16 78 Yes Same as
L8124A
a
Multizone control can be provided by using a separate circulator and R845 Relay for each zone.
b
Contacts are not powered; they are rated for switching of millivoltage loads.
Circulat
or
Circuit
120 Vac:
7.4A (full load);
44.4A (locked rotor)
240 Vac:3.7A (full load);
22.2A (locked rotor)
Mounting
Vertical
Vertical or horizontal
Horizontal
Vertical or horizontal
Horizontal
Replacement Aquastat Assemblies:
See Table 2 and Fig. 3 through 7.
Table 2. Replacement Aquastat assemblies.
Celsius (L8124A,
Model
L8124A-C,
Fahrenheit
1-1/2 in. or 3 in. (38
or 76 mm) insulation
125026AAE 125026BAC
100/220V Model Only)
1-1/2 in. or 3 in. (38
or 76 mm) insulation
E,G,L,M
3 60-2061—10
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
6 (
2-1/8 (54)
5
T
T
(VERTICAL MOUNT)
4-5/16 (110)
-1/8
156)
3-1/8
(79)
1/8 (3)
1-1/4 (32) (HORIZONTAL MOUNT—BOTTOM)
KNOCKOUTS FOR 1/2 (13) CONDUIT
3-3/8
(86)
1-1/4 (32) (VERTICAL MOUNT)
3-1/16 (78) (HORIZONTAL MOUNT)
Fig. 1. L8124 mounting dimensions in in. (mm).
CONTROL MOUNT
FITS BOILER TAPPED HOLE
1/2 OR 3/4 IN. NPT
M892
VOLTAGE BARRIER
TRANSFORMER FOR THERMOSTA CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY
LOW LIMIT SETTING
HIGH LIMIT SETTING
Fig. 3. Internal view of L8124A and C.
TRANSFORMER FOR THERMOSTA CIRCUIT
M8961
DIFFERENTIAL SETTING
INSULATION LENGTH 1-1/2 OR 3 IN. (38 OR 76 MM)
INSERTION LENGTH 3-3/8 IN. (86 MM)
M1797
CIRCULATOR RELAY
LOW LIMIT SETTING
Fig. 2. Immersion well dimensions. (Refer
to form 68-0040, Wells and Fittings for
Temperature Controllers, to order well.)
Fig. 4. Internal view of L8124B.
HIGH LIMIT SETTING
GROUND SCREW
M8964
60-2061—10 4
TRANSFORMER
T
T
T
FOR THERMOSTA CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY
LOW LIMIT SETTING
HIGH LIMIT SETTING
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
GROUND SCREW
VOLTAGE BARRIER
TRANSFORMER FOR THERMOSTA CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY
Fig. 5. Internal view of L8124E.
GROUND
HIGH LIMIT SETTING
SCREW
Fig. 6. Internal view of L8124G and L.
GROUND SCREW
M8962
TRANSFORMER FOR THERMOSTA CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY
LOW LIMIT SETTING
M8853
LOW LIMIT SETTING
HIGH LIMIT SETTING
Fig. 7. Internal view of L8124M.

INSTALLATION

When Installing This Product…

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
Product is for use only in a system with a pressure relief valve.
M8963
WARNING
5 60-2061—10
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.