Honeywell L8124B, L8124C, L8124A, L8124G, L8124E Product Data

...
Page 1
L8124A,B,C,E,G,L,M
Aquastat® Relays
PRODUCT DATA

GENERAL

These immersion type controllers are for use with forced hydronic heating systems that include domestic hot water service.

FEATURES

• L8124 Aquastat® Relays provide high limit, low limit, and circulator control for maintaining boiler temperatures.
• L8124 Aquastat Relays can provide multizone control by using a separate circulator and R845 Relay for each zone.
• All L8124 Aquastat Relays mount directly on the boiler.
• L8124E,G and L have large transformers and extra terminals for supplying power to low voltage zone valves.
• L8124M is for use in a wood-coal/gas-oil multifuel heating system. Circulator is independently controlled by the thermostat.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
Contents
General ............................................................................. 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 5
Wiring ............................................................................... 7
Operation .......................................................................... 10
Setting And Checkout ....................................................... 10
Checkout .......................................................................... 14
Material Safety Data Sheet (MSDS) ................................. 14
60- 2061- 10
Page 2
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

TRADELINE® Models

TRADELINE models are selected and packaged for ease of handling, ease of stocking, and maximum replacement value. TRADELINE model specifications are the same as those of standard models except as noted in Table 1.
Tradeline Models Available L8124B,E,G,L Aquastat Relays
without well and spud.
Additional Features:
• Heat-conductive compound for better bulb response in oversized well.
• Case can be vertically or horizontally mounted.
• Field-addable limit stops.
• TRADELINE pack with cross reference label and special instructions.
Pressure Rating:
200 psi (1380 kPa) on outside of immersion well. 100 psi (690 kPa) on capsule if inserted directly.
Maximum Ambient Temperature:
Case: 150°F (66°C).
Sensing element: 265°F (129°C).
Thermostat Heat Anticipator Setting: 0.2A.
Low Limit:
Setting: 110°F to 220°F, adjustable (43°C to 104°C). Differential: 10°F to 25°F, adjustable (6°C to 14°C).
High Limit:
Setting: 130°F to 240°F, adjustable (54°C to 116°C). Differential: 10°F, fixed (6°C).
Mounting Means: 1/2 or 3/4 in. taper pipe threaded.
Dimensions: See Fig. 1 and 2.
Sensing Element: 3/8 x 2-7/8 in (10 x 73 mm).
Insulation Depth: 1-1/2 or 3 in. (38 or 76 mm);
see Fig. 1 and 2.
Insertion Length: 3-3/8 in. (86 mm).
Approvals:
Underwriters Laboratories Inc.:
Listed (L8124 models with well): File No. MP466,
Guide No. MBPR.
Component Recognized (L8124 Models Without Well):
File No. MP466, Guide No. MBPR2.
Canadian Standards Association:
Component Recognized: File No. LR1620,
Guide No. 400-E-O.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2061—10 2
Page 3
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
Table 1. Aquastat Relay models.
Electrical
Ratings
Burner Circuit
Model
Number
Burner
Control
Circuit
Case Dimensions
Height Width Depth
in. mm in. mm in. mm
Can be
Used For
Multizone
With
Circulators
No. of V8043
Zone Valves
Powered
Without
Additional
a
Transformer
L8124A 120V 6-1/8 156 4-3/8 111 3-1/16 78 Yes Same as
L8124A-G,L circulator rating
L8124B
b
6-1/8 156 4-3/8 111 3-1/16 78 0.25A at 1/4
to 12 Vdc
L8124C 120V 4-3/8 111 6-1/8 156 3-1/16 78 Yes Same as
L8124A-G,L circulator rating
L8124E 24V 6-1/8 156 4-3/8 111 3-1/16 78 Yes 2 1.25A at 24
Vac ; 3 0 VA (total load) B1-B2 TV-Z
L8124G 120V 6-1/8 156 4-3/8 111 3-1/16 78 2 Same as
L8124A-G,L circulator rating
L8124L 120V 4-3/8 111 6-1/8 156 3-1/16 78 Yes 2 Same as
L8124A-6,L circulator rating
L8124M 120V 4-3/8 111 6-1/8 156 3-1/16 78 Yes Same as
L8124A
a
Multizone control can be provided by using a separate circulator and R845 Relay for each zone.
b
Contacts are not powered; they are rated for switching of millivoltage loads.
Circulat
or
Circuit
120 Vac:
7.4A (full load);
44.4A (locked rotor)
240 Vac:3.7A (full load);
22.2A (locked rotor)
Mounting
Vertical
Vertical or horizontal
Horizontal
Vertical or horizontal
Horizontal
Replacement Aquastat Assemblies:
See Table 2 and Fig. 3 through 7.
Table 2. Replacement Aquastat assemblies.
Celsius (L8124A,
Model
L8124A-C,
Fahrenheit
1-1/2 in. or 3 in. (38
or 76 mm) insulation
125026AAE 125026BAC
100/220V Model Only)
1-1/2 in. or 3 in. (38
or 76 mm) insulation
E,G,L,M
3 60-2061—10
Page 4
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
6 (
2-1/8 (54)
5
T
T
(VERTICAL MOUNT)
4-5/16 (110)
-1/8
156)
3-1/8
(79)
1/8 (3)
1-1/4 (32) (HORIZONTAL MOUNT—BOTTOM)
KNOCKOUTS FOR 1/2 (13) CONDUIT
3-3/8
(86)
1-1/4 (32) (VERTICAL MOUNT)
3-1/16 (78) (HORIZONTAL MOUNT)
Fig. 1. L8124 mounting dimensions in in. (mm).
CONTROL MOUNT
FITS BOILER TAPPED HOLE
1/2 OR 3/4 IN. NPT
M892
VOLTAGE BARRIER
TRANSFORMER FOR THERMOSTA CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY
LOW LIMIT SETTING
HIGH LIMIT SETTING
Fig. 3. Internal view of L8124A and C.
TRANSFORMER FOR THERMOSTA CIRCUIT
M8961
DIFFERENTIAL SETTING
INSULATION LENGTH 1-1/2 OR 3 IN. (38 OR 76 MM)
INSERTION LENGTH 3-3/8 IN. (86 MM)
M1797
CIRCULATOR RELAY
LOW LIMIT SETTING
Fig. 2. Immersion well dimensions. (Refer
to form 68-0040, Wells and Fittings for
Temperature Controllers, to order well.)
Fig. 4. Internal view of L8124B.
HIGH LIMIT SETTING
GROUND SCREW
M8964
60-2061—10 4
Page 5
TRANSFORMER
T
T
T
FOR THERMOSTA CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY
LOW LIMIT SETTING
HIGH LIMIT SETTING
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
GROUND SCREW
VOLTAGE BARRIER
TRANSFORMER FOR THERMOSTA CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY
Fig. 5. Internal view of L8124E.
GROUND
HIGH LIMIT SETTING
SCREW
Fig. 6. Internal view of L8124G and L.
GROUND SCREW
M8962
TRANSFORMER FOR THERMOSTA CIRCUIT
DIFFERENTIAL SETTING
CIRCULATOR RELAY
LOW LIMIT SETTING
M8853
LOW LIMIT SETTING
HIGH LIMIT SETTING
Fig. 7. Internal view of L8124M.

INSTALLATION

When Installing This Product…

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
Product is for use only in a system with a pressure relief valve.
M8963
WARNING
5 60-2061—10
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
Page 6
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
8
IMPORTANT
1. Terminals on these Aquastat relays are approved only for copper wire.
2. Immersion well must snugly fit sensing element and bulb must rest against bottom of well. Bend the tubing, if necessary, to hold bulb against the bottom of the well. Do not make a sharp bend in the tubing that can produce a break in the tubing and cause loss of fill. This condition will cause the high and low limit controllers to be made continuously.

Mounting Standard Models

The boiler must be provided with a tapping that allows horizontal mounting of the well. It should be located where boiler water of average temperature can circulate around the well.
To mount the L8124, proceed as follows:
1. Turn off all power and drain the boiler.
2. If no tapping is provided, prepare one that is properly
sized and threaded at the location selected.
3. Install the immersion well (ordered separately) in the
boiler tapping and tighten securely.
NOTE: Do not attempt to tighten the well using the case as a
handle.
4. Refill the boiler and check for water leakage.
5. Loosen, but do not remove, the clamp screw on the
bottom (L8124A,B,E,G) or on the top (L8124C,L,M) of the case.
6. Insert the element in the well until it bottoms.
7. Fit the case onto the well so that the clamp on the case
slides over the flange on the well. Securely tighten the clamp screw.
NOTE: Do not attempt to tighten the well using the case as a
handle.
3. Loosen, but do not remove, the immersion well clamp
screw.
4. If the immersion well fits the L8124 Immersion Well
Clamp, proceed as follows: a. Partially fill the immersion well with heat-conductive
compound.
b. Insert the bulb into the well. The bulb must bottom in
the well.
c. Make sure the well fits into the hole in the case.
Properly position the clamp on the well flange; then tighten the clamp screw.
d. Center the loop of excess capillary tubing in front of
the immersion well so it cannot touch any electrical parts.
NOTE: Some models have a tubing length adjustable to
3 in. (76 mm). In these models, pull out extra tubing from inside the case if needed.
5. If the old immersion well is otherwise suitable but does
not fit the L8124 Clamp, a 124904 Well Adapter, ordered separately, must be used as follows: a. After loosening the immersion well clamp screw, fit
the adapter onto the capillary tube (Fig. 9).
b. Make sure the adapter fits into the hole in the case.
Properly position the clamp on the adapter flange; then tighten the clamp screw.
c. Return to step 4a above, and complete the
installation.

TRADELINE Models

IMPORTANT
Use the heat-conductive compound furnished with the TRADELINE L8124 to obtain best thermal response. Fold the plastic bag of compound lengthwise and twist it gently. Snip off end and work open end of the bag all the way into the well. Slowly pull out the bag while firmly squeezing it to evenly distribute the compound.
Position the mounting bracket on the back of the case for mounting the case horizontally or vertically as desired. See Fig. 8.
1. Shut off the electric power and remove the old control.
Leave the old immersion well in place if it is suitable for use with the L8124, either with or without an adapter. A 124904 Well Adapter can be ordered separately; see form 68-0040, Immersion Wells and Compression Fittings, for ordering information.
2. If the old well is unsuitable, drain the system, remove
the old well, and install a new immersion well. Refill the system. Refer to form 68-0040, Wells and Fittings for Temperature Controllers, to order a new well. Make sure the well is tightly screwed in to prevent leakage.
BRACKET POSITION FOR VERTICAL MOUNTING
BRACKET POSITION FOR HORIZONTAL MOUNTING
M179
Fig. 8. Convertible case on tradeline models is
designed for horizontal or vertical mounting.
60-2061—10 6
Page 7
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
3
E
BACK OF
CONTROLLER
CONTROLLER CASE
IMMERSION WELL CLAMP
IMMERSION WELL SPUD
ADAPTER
(C)
2
CAPILLARY TUBE
SETSCREW
IMMERSION WELL CLAMP SCREW
1
BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B).
2
ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D).
BOILER
1
SHORT TUBE FITS IN CENTRAL RECESS OF ADAPTER
(A)
CASE
OLD IMMERSION WELL ASSEMBLY
HEAT-CONDUCTIVE COMPOUND
IMMERSION WELL CLAMP SCREW
ADAPTER
IMMERSION WELL CLAMP
Fig. 9. Position of bulb in immersion well, and use of well adapter when required.
SENSING BULB
(B)
M8830
(D)

WIRING

IMPORTANT
Terminals on the L8124 Aquastat Relay are approved for use with only copper wire. The terminals allow only wrap-around wiring.
1. Strip 7/16 in. of insulation from
the wire end.
2. Wrap the wire at least 3/4 of the
distance around the screw as shown.
3. Using a standard, flat-headed
screwdriver, tighten the screw until the wire is snugly in contact with the screw and contact plate.
4. Tighten the screw an additional one-half turn.
NOTE: Do not use a push-type ratchet screwdriver.
All wiring must comply with local electrical codes and ordinances. Do not exceed the limits in the Specifications section when applying this control. Use manufacturer instructions when wiring controlled equipment or refer to typical hookups in Figs. 10 through 21.
M884
LOW VOLTAGE THERMOSTAT
T
T
1K
R
W
LOW LIMIT/ CIRCULATOR
1K2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
2
USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
L8124A,C
G
1
2
B
B
HIGH LIMIT
R
1K1
ZR
ZC
3
B1
B2
C1
C2
LINE VOLTAGE CIRCULATOR
2
L1 (HOT)
L2
1
LINE VOLTAG OIL BURNER RELAY OR GAS VALVE
M8802
Fig. 10. L8124A,C single zone connections
and internal schematic.
7 60-2061—10
Page 8
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
E
T87F
TT
L2 L1
(HOT)
2
G
1
C1
C2 B2
L1
L2
L8124A
3
T87F
2
R845 RELAY
3
45
6
ZC ZR B1
TT 1
TT 1
2
T87F
3
R845 RELAY
6
45
PUMP
PUMP
PUMP
R8184
T
T
BLACK
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
WHITE
F
F
ORANGE
C554
BURNER AND IGNITION
Fig. 11. L8124A in an oil-fired, forced hot water, tankless, zoned, pump system.
LOW VOLTAGE
T
1K
W
LOW LIMIT/ CIRCULATOR
THERMOSTAT
T
1K2
R
L8124B
2
G
1
2
1K3
B
R
HIGH LIMIT
B
1K1
C1
C2
3
B1
L1 (HOT)
L2
1
LINE VOLTAGE CIRCULATOR
TH
M8822
POWER SUPPLY. PROVIDE
1
DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE
2
CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
Fig. 12. L8124B single zone connections and internal schematic.
60-2061—10 8
POWERPILE®
B2
TH
PP
PP
MILLIVOLTAG GAS VALVE
M8842
Page 9
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
L (
E
.
T87F
R845 RELAY
TT
1
3
2
1
1
HOT)
L2
L8124E
2
G
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1 2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
PUMP PUMP PUMP
L2 L1
C1 C2
TT
B2 B1
45
3
6
THPP
TR
MILLIVOLTAGE GAS VALVE (eg, VS820)
TT
1
2
PP
T87F
3
R845 RELAY
6
45
TT
1
2
Q313A PILOT GENERATOR
T87F
3
R845 RELAY
6
45
M8841
Fig. 13. L8124B in a gas-fired, millivolt, forced hot water, tankless, zoned, pump system.
LOW VOLTAGE THERMOSTAT
T
TV
1K
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
2
USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
Z
W
LOW LIMIT/ CIRCULATOR
R
HIGH LIMIT
L8124E
1K2
B
R
B
G
1
2
1K1
C1
C2
3
B1
B2
2
L1 (HOT)
L2
1
LINE VOLTAG CIRCULATOR
TR
TH
LOW VOLTAGE GAS VALVE (eg, VR8300)
M8803
1
L1 (HOT)
L2
2
G
L2 L1
C1 C2
CIRCULATOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
B2 B1
TT
3
LOW VOLTAGE GAS VALVE (eg, VR8300)
T87F
L8124E
TH
TR
Fig. 15. L8124E in a 24V, gas-fired
forced hot water, tankless system.
M1796A
Fig. 14. L8124E single zone connections
and internal schematic.
9 60-2061—10
Page 10
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
L (

OPERATION

T87F
R845 RELAY
TT 1
3
2
1
1
HOT)
L2
2
G
L8124E AQUASTAT® RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1 2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
PUMP PUMP PUMP
L2 L1
C1 C2
TT
B2 B1
45
3
6
TH TR
TT 1
2
LOW VOLTAGE GAS VALVE (eg, VR8300)
T87F
3
R845 RELAY
6
45
TT 1
2
T87F
3
R845 RELAY
6
45
M1794A
Fig. 16. L8124E in a 24V, gas-fired forced hot water, tankless, zoned pump system.

SETTING AND CHECKOUT

High Limit Controller

The high limit opens and turns off the burner when the water temperature reaches the set point. The high limit automatically resets after the water temperature drops past the set point and through the 10°F (6°C) differential.
WARNING
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
Use product only in a system with a pressure relief valve.

Low Limit and Circulator Controllers

On a temperature rise, with the adjustable differential at the minimum setting of 10°F (°C), the burner circuit (R-B) breaks and the circulator circuit (R-W) makes at the control set point. On a temperature drop of 10° F (6°C) below the set point, the R-B circuit makes and the R-W circuit breaks. See Fig. 22.
At any differential setting greater than 10°F (6°C), the R-B make temperature and R-W break temperature will remain the same (control setting minus 10°F (6°C). The R-B break and R-W make temperature will be the set point temperature plus the difference between the differential setting and 10°F (6°C).
EXAMPLE:Set point of 140°F (60°C) differential set at 25°F (14°C). On a temperature rise, R-B will break and R-W will make at 155°F (68°C). On a temperature fall, R-B will make and R-W will break at 130°F (54°C).
On the L8124M, the burner and circulator circuits are controlled separately—the low limit controls the burner circuit (R-B) as described above, while the low voltage thermostat directly controls the circulator circuit (see Fig. 18).

Setting

Follow the boiler manufacturer recommendation when making the L8124 settings. The high limit setting must be at least 20°F (11°C) higher than the low limit setting. Place the indicators over the selected temperature marks. The low limit differential is set by turning the differential adjustment knob to the desired amount of differential.

Setting Stop

A setting stop (Honeywell part no. 126580, ordered separately) may be installed on the adjusting knob to prevent turning the knob beyond a predetermined point. Fig. 23 shows it installed on the high limit switch knob to prevent setting higher than 200°F (93°C).
IMPORTANT
The setting stop cannot be reset once it is in place. If the stop must be removed, snip it off with cutters; do not twist it off.
60-2061—10 10
Page 11
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
E
E
E
E
L8124G,L
B
ZONE 2 THERMOSTAT
V8043F
TR
TH
1K1
ZR
ZC
4
B1R
B2 C2
C1
G
1
2
ZONE 1 THERMOSTAT
V8043F
TH TR
2
TV
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED. UP TO TWO V8043F ZONE VALVES CAN BE POWERED WITH
2
L8124G,L. ADD ADDITIONAL TRANSFORMER FOR EVERY TWO OR LESS VALVES.
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
3
USE GROUNDING SCREW PROVIDED.
4
B1 IS 1/4 IN. TAB TERMINAL.
TH
T
W
1K2
TR
1K
LOW LIMIT/ CIRCULATOR
TH TR
Z
R
B
HIGH LIMIT
3
L1 (HOT)
1
L2
LINE VOLTAG OIL BURNER RELAY OR GAS VALVE
LINE VOLTAG CIRCULATOR
M1795B
LOW VOLTAGE THERMOSTAT
L8124M
TT
1K
R
W
LOW LIMIT
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH
2
GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
B
B
HIGH LIMIT
R
1K1
G
L1
L2
ZC
C1
C2
3
B1
B2
Fig. 18. L8124M single zone connections
and internal schematic.
2
L1 (HOT)
L2
1
LINE VOLTAG CIRCULATOR
LINE VOLTAG OIL BURNER RELAY OR GAS VALVE
M8804
Fig. 17. L8124G,L multizone system with zone
valve connections and internal schematic.
11 60-2061—10
Page 12
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
R
E
LOW VOLTAGE
T
THERMOSTAT
T
1K
L8124A,C
G
1
2
L1
(HOT)
2
R845A RELAYS
1
FOR OTHER ZONES
R845A RELAY ZONE 2
ZONE 2 CIRCULATO
TO ADDITIONAL
L2
6
5
W
LOW LIMIT/ CIRCULATOR
1K2
R
B
1K1
ZR
ZC
LINE VOLTAGE
B
HIGH LIMIT
R
3
B1
OIL BURNER RELAY OR GAS VALVE
3
4
1
2
B2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
C1
C2
LINE VOLTAGE CIRCULATOR
OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH
2
GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
Fig. 19. L8124A,C multizone system with circulator connections and internal schematic.
1
L1
L2
(HOT)
L8124E
T
W
LOW LIMIT/ CIRCULATOR
Z
1K2
R
HIGH LIMIT
B
R
B
1K1
C2
3
TV
1K
2
G
1
2
C1
B1
B2
LOW VOLTAGE GAS VALVE (eg, VR8300)
TR THTR
TH
TO ADDITIONAL R845A RELAYS FOR OTHER ZONES
R845A RELAY ZONE 1
6
5
3
4
1
2
ZONE 1 CIRCULATOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH
2
GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
ZONE 2 LOW VOLTAGE THERMOSTAT
M8827
ZONE 1 LOW VOLTAG THERMOSTAT
M8828
Fig. 20. L8124E multizone system with circulator connections and internal schematic.
60-2061—10 12
Page 13
9
LOW VOLTAGE
R
H S
A
THERMOSTAT ZONE 1
1
L1 (HOT)
TO ADDITIONAL R845A RELAYS
L2
FOR OTHER ZONES
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
L8124L
T
1K
W
LOW LIMIT/ CIRCULATOR
1K2
Z
1K1
R
B
ZR
ZC
B HIGH LIMIT
3
B1R
B2 C2
C1
TV
G
1
2
2
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
LINE VOLTAGE CIRCULATOR ZONE 1
R845A RELAY ZONE 2
6
5
3
4
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH
2
GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
ZONE 2 CIRCULATO
ZONE 2 LOW VOLTAGE THERMOSTAT
M882
Fig. 21. L8124L multizone system with circulator connections and internal schematic.
To install the setting stop:
1. Turn the knob to the setting that is to be established as
the limit.
2. Place the setting stop over the knob in the position
where the arm of the setting stop strikes (after the stop is pressed into place) projection A and prevents turning the knob beyond the desired limit setting.
3. Press the setting stop tightly onto the knob so its inner
teeth securely engage the knob.
4. Turn the knob back and forth several times to make
IGH LIMIT ETTING
SWITCH BREAKS ON TEMPERATURE RISE. BURNER TURNS OFF. CIRCULATOR OPERATES ON A CALL FOR HEAT.
SWITCH MAKES ON TEMPERATURE FALL. BURNER OPERATES ON CALL FOR HEAT.
sure the stop functions properly.
5. n all the settings are made, replace the cover.
LOW LIMIT AND CIRCULATOR SETTING
1
WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).
SWITCH MAKES R-W AND BREAKS R-B ON TEMPERATURE RISE.
SWITCH MAKES R-W AND BREAKS R-B ON TEMPERATURE RISE.
SWITCH MAKES R-B AND BREAKS R-W ON TEMPERATURE FALL. BURNER IS ON TO MAINTAIN MINIMUM WATER TEMPERATURE. CIRCULATOR IS OFF.
1
M1523
Fig. 22. Relationship of set points and differential.
13 60-2061—10
Page 14
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
P
KNOB SET AT 180°F (82°C)
Material Safety Data Sheet (MSDS) for heat-conductive compound, which is included with TRADELINE Aquastat Relay models.
SETTING STOP
SETTING STOP ARM
ROJECTION "A"
1
SCALE MARKINGS IN FAHRENHEIT ONLY.
Fig. 23. Setting stop in position to limit
the high limit setting to 200°F (93°C).
220
200
1
180
160
140
M2844

Heat Anticipator

The thermostat heat anticipator should be set at 0.2A.

CHECKOUT

Put the system into operation and observe each function through at least one complete cycle. Be sure the control operates as intended.

MATERIAL SAFETY DATA SHEET (MSDS)

SECTION 1. PRODUCT AND COMPANY IDENTIFICATION.

Product Name: Heat conductive compound.
MSDS ID: DS9021.
Synonyms: MS1699.
Product Use: Heat conductive material used to enhance contact and heat transfer in temperature sensor applications.
Manufacturer: Honeywell Inc., 1985 Douglas Drive North, Minneapolis, MN 55422.
Date Released: October 8, 1999.
NFPA Ratings:
Health 0; Flammability 1; Reactivity 0; Personal Protection B.
60-2061—10 14
Page 15
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS

Section 2. Composition, Information on Ingredients (Table 3).

Table 3. Ingredients of Heat Conductive Compounda.
Ingredients CAS Number Percent PEL TLV
No. 2 Lithium Complex Grease (70%):
Mineral Oil 64742-65-0 35-50
Mineral Oil 64742-62-7 20-25
Lithium Hydrostearate/Sebacate Complex 68815-49-6 4-9
Zinc Alkyldithiophosphate 68649-42-3 0-2
Aluminum Paste (30%):
Aluminum, as Al 7429-90-5 20-25
Aliphatic Petroleum Distillates 8052-41-3 10-15
Stearic Acid 57-11-4 1-2
Aromatic Petroleum Distillates 64742-95-6 1-2
a
Additional Information: Part No. 120650 (0.5 oz. tube); Part No. 107408 (4 oz. can); Part number 197007 (5 gallon container).
May also contain minute amounts of lithium and molybdenum lubricant compounds.
3
5 mg/m
3
5 mg/m
15 mg/m
2900 mg/m
5 mg/m
3
3
5 mg/m
5 mg/m
10 mg/m
3
525 mg/m
5 mg/m
3
3
3
3
3

Section 3. Hazard Identification

Acute Health Effects:
Skin—Excessive contact can cause skin irritation and dermatitis.
Eye—Direct contact with eye will cause irritation.
Inhalation—No adverse effects are expected.
Ingestion—Ingestion of product may cause nausea, vomiting and diarrhea.
Chronic Health Effects:
Existing skin rash or dermatitis may be aggravated by repeated contact.
OSHA Hazard Classifications:
None.
Carcinogenicity:
Not considered to be a carcinogen by either OSHA, NTP, IARC, or ACGIH.
Target Organs:
None known.

Section 4. First Aid Measures

Skin Contact:
Remove excess with cloth or paper. Wash thoroughly with mild soap and water. Obtain medical attention if irritation develops and persists.
Ingestion:
Contact physician or local poison control center immediately.
Inhalation:
Remove patient to fresh air and obtain medical attention if symptoms develop.

Section 5. Fire Fighting Measures

Flash Point:
>383°F (195°C). Will burn if exposed to flame.
Extinguishing Media:
Carbon dioxide, dry chemical or foam.
Special Fire Fighting Procedures:
None.
Explosion Hazards:
None. Aluminum powder can react with water to release flammable hydrogen gas. In the form of this product, this reaction is not expected.
Eye Contact:
Flush eyes with water for 15 minutes. Remove any contact lenses and continue to flush. Obtain medical attention if irritation develops and persists.

Section 6. Accidental Release Measures

Scrape up and dispose as solid waste in accordance with state and federal regulations.
15 60-2061—10
Page 16
L8124A,B,C,E,G,L,M AQUASTAT® RELAYS

Section 7. Handling and Storage

Store in dry place. Keep container closed when not in use.

Section 8. Exposure Controls and Personal Protection

Ventilation:
No special ventilation is required when working with this product.
Respiratory Protection:
None required.
Eye Protection:
Not normally required. However, use chemical safety goggles or faceshield if potential for eye contact exists, especially if material is heated.
Hand/Clothing Protection:
Not normally required. Protective gloves and clothing are recommended, as material is difficult to remove from skin and clothing.
Other Protective Equipment:
None required.
Incompatibilities:
Strong oxidizing agents and halogens.
Hazardous Decomposition Products:
Carbon dioxide, carbon monoxide.

Section 11. Toxicology Information

No data available.

Section 12. Ecological Information

Chemical Fate Information:
Hydrocarbon components will biodegrade in soil; relatively persistent in water.

Section 13. Disposal Consideration

Dispose of as solid waste in accordance with Local, State and Federal regulations.

Section 14. Transportation Information

DOT Classification:
Not classified as hazardous.

Section 9. Physical and Chemical Properties

Appearance/Odor:
Aluminum color, semi-solid material, pleasant odor.
Solubility in Water:
Negligible.
Specific Gravity:
0.86.

Section 10. Stability and Reactivity

Stability:
Stable.
Reactivity:
Hazardous polymerization will not occur.

Section 15. Regulatory Information

SARA Title III Supplier Notification:
Include in Section 311/312 inventory reports if amounts exceed 10,000 pounds. Aluminum compounds are subject to the reporting requirements under Section 313 of Emergency Planning and Community Right-to-Know Act of 1986 (40 CFR
372). Ingredients listed in TSCA Inventory.

Section 16. Other Information

This information is furnished without warranty, expressed or implied, except that it is accurate to the best of our knowledge.
Prepared By:
PROSAR, 1295 Bandana Boulevard, Suite 335, St. Paul, MN 55108 (651-917-6100).
Automation and Control Solutions Automation and Control Solutions
Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
60-2061—10 G.R. Rev. 12-01 www.honeywell.com
M1V 4Z9