Honeywell IRD 1010, IRD 1020 User Manual

certified Qualitysystem
746e/08/98
ISO 9001 / EN 29001
Reg. Nr. 10529
Infra-red flicker detector
Flame monitoring device for yellow- or blue­burning oil flames
INTRODUCTION
The IRD 1010 is employed to monitor the flame of an oil burner. This flame monitoring device should be connected to a Satronic oil burner control box. Monitoring is based on the infra-red flicker principle, in other words, the flickering infra-red light of the flame is detected. The steady radiation from, for example, the glowing refractory layer on the inside of the boiler, has no effect on the detector. The IRD 1010 replaces the models IRD 910, 911 and 911 vi. If exchanging the units, care must be taken to connect them correctly (see page 3).
TYPES AVAILABLE (also see page 4, Variants)
Item no. Designation
16501 Flicker detector IRD 1010 right 16502 Flicker detector IRD 1010 end-on 16503 Flicker detector IRD 1010 left
The infra-red flicker detector is suitable for use with the following control boxes:
IRD 1010 DKO 970, 972, 974, 976
DKW 974, 976 DMO 976 TF 801, 802.1, 804 TF 830.1, 832.1, 834.1, 834E.1, 834.2, 836 TF 844, TF 974, 976 MMD 900, 900.1, TTO 872, 876 MMO 872, 876 TMO 720-4
A Honeywell Company
TECHNICAL DATA
Supply voltage 220 / 240 V (-15... +10%)
Nominal current input approx. 4 mA Power consumption 1 VA Ambient temperature -20° C to +60° C Insulation standard IP 41 Mounting attitude any Weight 40 g Flame viewing attitude side-on or end-on according
Spectral response 800 - 1100 nm (with daylight filter) maximum 950 nm
Frequency range 15 Hz.... 250 Hz (-12 dB)
Sensitivity adjustment range approx. 1 : 20 (26 dB) Switch-on delay < 3.5 sec. (after connecting operating voltage) Response time < 0.1 sec. Cut-out time < 1 sec.
IRD 1010
50 Hz (50 - 60 Hz)
to type
CONSTRUCTIONAL FEATURES
The infra-red sensor and the pre-amplifier are hermetically sealed in glass and along with the electronics form an integrated unit in the flame detector. Wiring is by way of a plug connection. The sensitivity control and two LED’s for indication of the flame signal are situated on the rear of the flicker detector.
1
TECHNICAL FEATURES
COMMISSIONING AND MAINTENANCE
1. Flame detection
- Yellow- as well as blue-burning oil flames can be monitored.
- The flame detector is suitable for operation where the
ambient temperature is within the range -20° to +60° C.
- The flickering detector IRD 1010 becomes active not before a minimum threshold-level of steady light is exceeded. That guarantees that neither electromagnetic­nor ignition-spark noise are affecting the IRD.
- Sensitivity is adjustable.
- LED 1 is a warning indicator for the pre-purge phase as well as normal operation. LED 2 indicates the actual status of the detector: On or off.
- During pre-purge, LED 1 indicates possible stray light, which may be produced either by a flickering or by a steady light source, before the detector switches on (LED 2).
- When the burner is operating normally, LED 1 acts as a warning indication of the flame signal current sensitivity being set too low - it begins to flicker or extinguishes before the detector switches off.
- The compact dimensions of the detector allow it to be installed on any burner. The detector shaft has the same dimensions as the FZ 711 S. It therefore also fits into the FZ holder M 74.
- Unlike UV tubes, the IRD 1010 flicker detector does not deteriorate with age.
2. Installation instructions
During commissioning and after servicing, the flame monitoring system should be checked for faultless operation as follows:
1. Check that the detector is connected properly. Wrong connections are a risk to safety, and could cause damage to the detector unit or burner system.
2. Adjust to maximum sensitivity and start the burner: If the LED indicator is lit after the start impulse, carefully adjust the sensitivity control until LED 1 extinguishes. No LED should light up during the pre-purge phase.
3. With the system set for normal operation, pull out the detector probe and cover it up to cut off light. Both LED indicators must extinguish. The control box should switch to lockout or attempt to re-start the sequence.
4. Attempt to re-start with the flame detector covered. There must be no indication from the LED’s after the start impulse. The burner control box must switch to lockout at the end of the safety interval.
5. Attempt to start the burner with the detector exposed to stray light e.g. from fluorescent lighting, a cigarette lighter or light bulb (not daylight or an electric torch): Depending on the type of control box, it should switch to lockout either immediately or at the end of the pre-purge, as a result of stray light.
6. When the burner is operating normally, carefully turn back the sensitivity control until LED 1 begins to flicker. Increase the setting again by one or two increments until both LED’s are lit. If LED 1 does not flicker even at po­sition 1: Leave potentiometer at position 1-2. This adjust­ment should be carried out when the flame signal current is weakest (shortly after flame establishment or after stabilisation).
- The detector probe should be fitted so that it receives the light which pulsates most strongly. This can be achieved by positioning the detector as close as possible to the flame or by directing it at a particular zone of the flame (e.g. by using a sighting tube).
- No stray light must be allowed to fall on the detector (e.g. through cracks or from a sight glass). Pulsating stray light (e.g. from fluorescent lighting or light bulbs) could cause the system to switch to lockout. Due to the very high sensitivity of the detector, it should not be exposed directly or indirectly (reflections) to the ignition spark.
- The infra-red flicker detector should be fitted in such a way that the ambient temperature cannot under any circumstances rise above 60 °C. At higher temperatures, there is a risk of incorrect operation and the life expectancy of the unit could be reduced. In addition, care should be taken that the detector is not subjected to unusually harsh vibration and receives no hard knocks.
The flame detection device requires no maintenance of any kind, and as it is classed as safety equipment, no attempt should be made to open the housing.
Because the nature of the flame can change in time due to the accumulation of dirt, the indicators on the detector should be checked periodically.
Please note:
Burner operating normally = both LED’s on Burner in pre-purge phase = both LED’s off
For safety reasons the sensitivity must not be set higher than necessary.
IRD 1010
2
Loading...
+ 2 hidden pages