This product must only be used for the applications outlined in the catalogue and the technical description
and in combination with external components and systems which have been approved or recommended by
Esser by Honeywell.
Warning
In order to ensure correct and safe operation of the product, all guidelines concerning its transport, storage,
installation, and mounting must be observed. This includes the necessary care in operating the product.
Safety-relevant user information
This manual includes all information required for the proper use of the products described.
The term 'qualified personnel' in the context of the safety information included in this manual or on the
product itself designates:
project engineers who are familiar with the safety guidelines concerning fire alarm and extinguishing
systems.
trained service engineers who are familiar with the components of fire alarm and extinguishing systems
and the information on their operation as included in this manual.
trained installation or service personnel with the necessary qualification for carrying out repairs on fire
alarm and extinguishing systems or who are authorised to operate, ground and label electrical circuits
and/or safety equipment/systems.
Safety warnings
The following information is given in the interest of your personal safety and to prevent damage to the
product described in this manual and all equipment connected to it.
Safety information and warnings for the prevention of dangers putting at risk the life and health of user and
maintenance personnel as well as causing damage to the equipment itself are marked by the following
pictograms. Within the context of this manual, these pictograms have the following meanings:
Dismantling
In accordance with Directive 2002/96/EG (WEEE), after being dismantled, electrical and
electronic equipment is taken back by the manufacturer for proper disposal.
Designates risks for man and/or machine. Non-compliance will create risks to man and/or
machine. The level of risk is indicated by the word of warning.
Important information on a topic or a procedure and other important information!
This is an important guideline issued by VdS Schadenverhütung GmbH, Cologne.
If the hazard alarm system is programmed in compliance with VdS, this section must be read very
carefully and all instructions must be adhered to.
2 System overview........................................................................................................................................................ 7
3.4 Definition of the Primary loop number.............................................................................................................. 17
3.5 Central housing.................................................................................................................................................. 19
4.3.4 Serial interface ............................................................................................................................. 41
5.1 Analog loop modules......................................................................................................................................... 62
6.2.1 Technical Data Relay module...................................................................................................... 83
6.3 Serial interface module......................................................................................................................................84
10 Meaning of the three digit error codes / test mode.............................................................................................. 115
11 Functionality for fire alarm control panels............................................................................................................. 126
11.1.1 Use of the analog loop module in door control systems.................................................... 126
15.1 Extension housing for two batteries (Part No. 789300 / -01) ................................................................... 134
16 Power supply for the built-in printer ...................................................................................................................... 135
17 Mounting / Replacing of the Panel front + Printer................................................................................................ 136
17.1 Heat transfer Printer without paper take-up unit (Part No. 7868xx / 7869xx)........................................ 136
17.2 Printer with paper take-up reel (Part No. 7863xx) .................................................................................... 139
18 Fire protection housing (F30)................................................................................................................................ 141
Danger – Electrical shock !
Remove all power from the panel before carrying out any installation work!
ESD protection
While handling electronic assemblies, the necessary precautions against electrostatic discharge
must be taken.
Protective and functional earth
The PE conductor must be connected to the corresponding terminal at the mains supply. Connect
the FE terminal of the panel’s cabinet with the PE rail of the power distributor panel from which the
fire alarm system will be powered.
Commissioning
A complete system check must be carried out after commissioning and for each modification of the
customer data programming!
Additional and updated Informations
The described features, specifications and product related informations in this manual correspond
to the date of issue (refer to date on the front page) and may differ due to modifications and/or
amended Standards and Regulations of the System design, Installation and Commissioning.
Updated informations and declaration of conformity are available for comparison on the
www.esser-systems.de homepage.
®
esserbus
and essernet® are registered trademarks in Germany.
4 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
1 Installation Instruction
Operation of the Fire Alarm Control Panel IQ8Control is governed by the national version of the operating
system software used and the country version programmed in the customer data. The terminal assignment and
wiring illustrated in these installation instructions refer exclusively to the facilities of the operating system
D
software for the Federal Republic of Germany
The fire alarm panel may only be installed in a dry, clean room with controlled access and appropriate
lighting. The environmental conditions must comply with DIN EN 60721-3-3, class 3k5.
The panel must be mounted on a flat surface using appropriate hardware (screws and dowels). Avoid
mechanical stressing. It may only be commissioned after correct mounting on a wall or other mounting
surface of sufficient strength to support the weight of the unit.
Avoid strong electric or magnetic fields as well as mechanical influences. This applies especially to the
presence of fluorescent lighting or energy cabling in the close vicinity of the panel, its components and the
associated cabling. Do not mount on vibrating, unstable surfaces such as light partitioning walls.
Do not install the system in places where adverse conditions prevail. Parts and components of the system
may only be installed in or led through locations which allow compliance with DIN VDE 0800.
Control panels and visual indicators mounted on a wall should be installed at a height of 800 to 1800 mm
above the floor.
.
The fire alarm system is not suitable for connection to IT power supply systems.
It is highly recommended for correct ESD protection that the dummy plug (factory supplement) of the
programming interface plug is inserted into the front of the operation panel.
This documentation applies to the following products:
Fire Alarm Control Panel IQ8Control C/M
Standard system software (without special customer-dependent functionality)
Country function >Germany<
Configuration and Commissioning
For the configuration and commissioning of the system, the programming software tools 8000 is required in
each case in the current program version.
Installer / Installation Specialist
The fire alarm control panel must be installed by a skilled electrician (according to DIN VDE 0833), who, as a
result of the appropriate training and experience, can evaluate the work to be carried out and recognise
potential dangers. In addition to the specialist qualifications, knowledge of the validity and application of the
relevant standards and their use and compliance with is required.
Operator of the Fire Alarm System / Trained Person
For the operation of the fire alarm control panel, a qualified person must be trained in the basic functioning of
the system and its technical requirements. A trained person (according to DIN VDE 0833) must be able to
operate the fire alarm control panel and to recognise faults. If a fault signal occurs or the functionality is limited,
arrangements must be made for the checking and rectification of the cause of the fault.
Maintenance / Service
Maintenance is necessary for the proper operation of the fire alarm control panel. The function of the system
parts can be affected by environmental conditions and ageing. For an application within the area of validity of
the European Union (EU) the maintenance is defined in EN 54. In addition to the safety directives and notes in
this documentation, the country-specific requirements for the operational location of the fire alarm control panel
must be observed.
FB 798951.GB0 / 01.09
5
Fire Alarm Control Panel IQ8Control C/M
1.1 Standards and guidelines
The general technical rules must be observed when installing fire alarm systems. Any deviation from those rules
is only admissible if the same degree of safety can be ensured with different means. Installations within the
European Community are primarily subject to all EU regulations defining the current standards for security
systems.
In Germany, systems are considered to be in compliance with the general technical rules or the standards of the
EU for security systems if they meet the technical guidelines of the VDE (Verband Deutscher Elektrotechniker,
Association of German Electrical Engineers). They may also be considered to be in compliance with the
standards of the EU for security systems if they meet the technical guidelines of another comparable institution
within the European Community which have been accepted in accordance with directive 73/23 EEC of the
Council dd. 19 February 1973 – directive on low-voltage systems- (ABL. EG No. L 77 page 29). The same must
be applied for all applications of additional, product relating guidelines, e.g. EMI-Guideline 2004/108/EC and the
Construction Products Directive (CPD) 89/106/CE.
These are examples:
Standards of the DIN EN 54 “Fire alarm systems“, particulary DIN EN 54-2 „Fire alarm control panels" and
DIN EN 54-4 „Power supply units".
Standards of the DIN VDE 0100 issue, particulary DIN EN 0100-410 „Installation of high-voltage sytems with
rated voltage up to 1000 V“, DIN VDE 0105-100 „Operation of electrical system: General commitments“ and
DIN VDE 0108 „Installation and Operation of high-voltage systems in buildings for public gathering“.
Standards of the DIN EN 62305 or DIN VDE 0185 issue, particulary DIN VDE 0185-1 „Lightning protection:
General standards. DIN VDE 0185-2 „Risk-Management“, DIN VDE 0185-3 „Protection of buildings and
persons“ and DIN VDE 0185-4 „Eletrical and electronic systems in buildings“.
DIN VDE 0701-1 „Maintenance, Modification and Test of electrical devices: General commitments“.
Standards of the DlN VDE 0800 issue, particulary DIN VDE 0800-1 „General commitments, Requirements
and Tests for system security“, DIN VDE 0800-1 „Communication systems, Earthing and potential
compensation“, DIN VDE 0800-174-2 .Information systems – design and installation of communication
cabling in buildings“.
DIN VDE 0815 „Cables for communication and information systems“.
Standards of the DIN VDE 0833 issue Hazard alarm systems for Fire, Intruder and Hold-up, particulary DIN
VDE 0833-1 „General commitments“, DIN VDE 0833-2 „Commitments for fire alarm systems (FAS)“, DIN
VDE 0833-3 „Commitments for Intruder and Hold-up systems“ and DIN VDE 0833-4 „Commitments for
Voice alarm systems within fire protection“.
Standards of the DIN VDE 0845 issue, particulary DIN VDE 0845-1 „Protection of Communication systems
against Lightning, electrostatic charge and overvoltage from high-voltage systems; Actions to avoid overvoltage“.
DIN 14675 Fire alarm systems – Design and Commissioning.
Standards of the DIN EN 120094 issue, localized fire fighting systems – components of extinguishing
systems with gaseous extinguishing agents“, particulary DIN EN 120094-1 „Requirements and test
procedures for automatic electrical Control- and Delay systems“ and DIN EN 12094-3 „ Requirements and
test procedures for Manual release systems and Stop units.
DIN 14675 Fire alarm systems – mounting and operation.
These technical guidelines must be observed within the European Community. The VDE guidelines must be
observed within Germany. In other countries (e.g. U.S.A.: NFPA and UL requirements), the relevant national
standards, guidelines and legislation must be observed.
In addition to the above, the guidelines of the German VdS Schadenverhütung GmbH (VdS) may apply for
systems installed in Germany.
VdS 2046 Safety rules for electrical power systems with voltages up to 1000 V
VdS 2015 Electrical appliances and systems – rules for damage prevention
VdS 2095 Design and installation of fire alarm systems
VdS 2833 Overvoltage protection measures for Hazard Alarm Systems
6 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
2 System overview
The modular design with different micro modules and individual extension concepts allow the Fire Alarm
Computer IQ8Control C and IQ8Control M to be easily adapted to special requirements. This provides the range
from a stand-alone panel up to 31 Fire Alarm Control Panels Computer or other network subscribers such as
supervising system WINMAG, Fire department indicator panel or Intruder Alarm Panels Series 5000 by using
the essernet
The Field device modules required in order to configure a stand-alone FACP in accordance to the appropriate
standards and guidelines. The connections for the Fire Alarm Control Panel, the master box and the three freely
programmable relays are integrated on the Field device module. If several Fire Alarm Control Panels are
connected together in the essernet
®
safety network.
WINMAG
®
LCD
display panel
MFAB
, the master box can be connected to one of the other FACPs.
FDOP
Fire dept.
key box
TAL
module
Fire department
indicator panel
Fibre optical cable
LWL
Fire alarm and extinguishing
computer 8010
essernet
Serial
®
-Interface
essernet
LWL
max. 1 km
®
max. 1 km
max. 1 km
Repeater
esserbus
Fig. 1: System overview
®
-PLus
Additional extensions
The FACP panel configuration may be extended to suit requirements by adding supplementary input/ output
modules, esserbus
®
transponders. Transponders may be installed at special integrated slots or on standard
C-Top rails in the housing. Optional plastic housings conforming to protection class IP 40 are available for the
decentralized installation of transponders on the analog loop.
FB 798951.GB0 / 01.09
7
Fire Alarm Control Panel IQ8Control C/M
3 Configuration options
The operating module front (7860xx) is available in various language versions. The language is defined with the
2-digits of the part number, e.g. 786002
= English lettering.
IQ8Control C IQ8Control M
Operating module
7860_ _
7861_ _
7868_ _
7864_ _
7865_ _
7869_ _
9 9
9 9
9 9
9 9
9 9
9 9
---
---
---
---
---
---
742100
786000
9 9 9
9
1)
---
9
2)
9
1)
7863_ _
Fig. 2: Configuration options
1)
Extension housing required
2)
Not available for operating module 7861 _ _ or 7865 _ _
9
8 FB 798951.GB0 / 01.09
Extension housing 789304
Fire Alarm Control Panel IQ8Control C/M
3.1 Special configuration – Swiss option CH
IQ8Control C IQ8Control M
Operating module
786261
786262
786263
Fig. 3: Operating module – Swiss CH with integrated Fire department operating panel (FBA)
For country-specific displays and labels as well as further information
instructions FACP IQ8Control C/M (Part No. 798950.GB0).
9 9
9 9
9 9
CH
refer to operating
---
---
---
FB 798951.GB0 / 01.09
9
Fire Alarm Control Panel IQ8Control C/M
3.2 FACP IQ8Control C
The configuration of the FACP IQ8Control C includes:
1 Basic module
1 Power supply module
1 Field device module or 1 Extension module
In the full configuration, two freely selectable micro modules
can be employed.
On the Basic module only the upper slot (slot 1) of can be
used for a Field device or Extension module.
The lower slot (slot 2) of the FACP IQ8Control C is not used.
Micro module
c
ABC
Power supply module Part No. 802426
d
1
Field device module Part No. 772479
A
Connector 1
Field device module
B
with one micro module slot
Part No. 772477
2
Fig. 4: Configuration FACP IQ8Control C
Extension module
C
with one micro module slot
Part No. 772478
10 FB 798951.GB0 / 01.09
Configuration of FACP IQ8Control C
Fire Alarm Control Panel IQ8Control C/M
MM 1
MM 1
MM 2
A
B
Connector 1
Example 1:
Basic module with a micro module and a Field device module
(Part No.772479 without micro module slot) on slot 1 of the
Basic module.
Application:
With this configuration, for example, a single control panel
with an analog loop and max. 127 bus devices can be
implemented.
Example 2:
Basic module with a micro module and a Field device module
(Part No.772477 with micro module slot) on slot 1 of the Basic
module
Application:
MM 1
MM 2
C
Connector 1
Connector 1
With this configuration, for example, a single control panel
with two analog loops and max. 254 bus devices can be
implemented
or
This configuration is usually employed in essernet
with an analog loop and max. 127 bus devices.
Example 3:
Basic module with a micro module and a Extension module
(Part No.772478 ) on slot 1 of the Basic module.
Application:
This configuration is usually employed in essernet
with an analog loop and max. 127 bus devices.
Without the Field device module, no connection is
available for the fire department key pad and the
master box. These devices can be connected to a
different control panel of the essernet
®
networks
®
networks
®
.
Fig. 5: Configuration FACP IQ8Control C
FB 798951.GB0 / 01.09
11
Fire Alarm Control Panel IQ8Control C/M
3.3 FACP IQ8Control M
The configuration of the FACP IQ8Control C includes:
1 Basic module
1 Power supply module
1 Field device module or 1 Extension module 1
or
max. 2 Extension modules - each with three micro
module slots
In this full configuration, a total number of slots for 7
(3 + 3 + 1) freely selectable micro module are available.
ABC
1
Slot 1
On the Basic module only the upper slot (slot 1) can be
used for a Field device or Extension module.
The Field device module must be installed in Slot 1 of
the Basic module.
Slot 2
The lower slot (slot 2) can be used for a Extension
D
module only.
Field device module Part No.772479
A
Field device module with one
B
additional micro module slots
Extension module with one
C
additional micro module slots
Extension module with three
D
additional micro module slots
Part No.772477
Part No.772478
Part No.772476
Connector 1Connector 2
2
D
Fig. 6: Configuration FACP IQ8Control M
12 FB 798951.GB0 / 01.09
Example: Configuration of FACP IQ8Control M
Fire Alarm Control Panel IQ8Control C/M
Example 1:
MM 1
MM 2
A
Basic module with a Field device module
MM 4
(without micro module slot) on slot 1 and one
Extension module (with 3 micro module slots)
MM 3
on slot 2.
MM 2
Connector 1
Application:
With this configuration, e.g. a single control
panel with 4 analog loops and max. 508 bus
D
Connector 2
devices can be implemented.
Field device module (Part No.772479)
A
Extension module with three additional micro
D
module slots (Part No.772476)
Example 2:
MM 1
B
D
Connector 2 Connector 1
Fig. 7: Configuration FACP IQ8Control M
MM 3
MM 4
MM 5
Basic module with a Field device module
(without micro module slot) on slot 1 and one
Extension module (with 3 micro module slots)
on slot 2.
Application:
With this configuration, e.g. a single control
panel with 5 analog loops and max. 635 bus
devices can be implemented
Field device module with 1 additional micro
B
module slot (Part No.772477)
Extension module with three additional micro
D
module slots (Part No.772476)
FB 798951.GB0 / 01.09
13
Fire Alarm Control Panel IQ8Control C/M
Example: Configuration of FACP IQ8Control M
MM 2
MM 1
C
MM 4
MM 3
D
Connector 2 Connector 1
MM 5
Example 3:
Basic module with a Field device module
(without micro module slot) on slot 1 and
one Extension module (with 3 micro module
slots) on slot 2.
Application:
With this configuration, e.g. a security
network panel with 4 analog loops and max.
508 bus devices can be implemented.
Extension module with one additional micro
C
module slot (Part No.772478)
MM 1
Extension module with three additional micro
D
module slots (Part No.772476)
MM 4
MM 3
MM 2
Example 4:
Basic module with two Extension modules
(with 3 micro module slots) on slot 1 + 2.
Application:
With this configuration, e.g. a security
network panel with 6 analog loops and max.
D
762 bus devices can be implemented.
Extension module with three additional micro
D
module slots (Part No.772476)
D
Connector 2 Connector 1
MM 5
MM 6
MM 7
Fig. 8: Configuration FACP IQ8Control M
install Field device and Extension modules series 01 FACP 8000 C/M (Part No. 772418, 772419,
Do not
772420, 772421) at FACP IQ8Control C/M.
14 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Three part housing with integrated printer
The integrated printer and the operating module front are mounted in the upper housing. Due to the depth of the
printer, the Basic module and all of the plug-in cards are integrated into a separate housing beneath. The
emergency power supply with max. two 24Ah batteries can be installed into the lowest housings.
Extension housing 789304
or
Extension housing 789303
Fig. 9: Three part housing with integrated printer
Assembly area for esserbus® transponders
1
1
2
Fig. 10: Location of the components in a three part housing
Ensure that the arrangement of the assemblies corresponds with the presentation shown here during
this configuration. Another distribution is not
front, the integrated printer and the battery connection cable.
3
4
c
Basic module / power supply module /
d
slot for micro module
Alternatively Field device module
e
(without micro module slot)
or Field device module (with 1 micro module slot)
or Extension module (with 1 micro module slot)
or Extension module (with 3 micro module slots)
on slot 1
Extension module (with 3 micro module slots)
f
on slot 2
Part No. 772479
Part No. 772477
Part No. 772478
Part No. 772476
Part No. 772476
possible due to the cable length of the operating module
FB 798951.GB0 / 01.09
15
Fire Alarm Control Panel IQ8Control C/M
Location of the components in a three part FACP housing IQ8Control M
Fig. 11: Location of the components in a three part housing
Mounting plate for master boxes DS 7500 / DS 8800
The mounting plate (Part No. 057633) allows installation of two esserbus
®
transponders or one master box Type
DS 7500 / DS 8800 in the extension housing (Part No. 789303).
Protect the devices against short circuits with the metal mounting plate with the plastic spacers and the
insulation foil.
Mounting plate
Insulation foil
Fig. 12: Mounting plate (Part No. 057633)
16 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
3.4 Definition of the Primary loop number
Individual assemblies of the FACP IQ8Control can be switched on/off with the internal primary loop number
through the control panel keyboard or programmed with programming software . This internal primary loop
number is composed of the control panel number, the slot and the assembly number.
Example: Stand-alone FACP (= Panel No. 01)
011301230133
0132
0131
Fig. 13: FACP IQ8Control
0 1XX
2
1
3
Subassembly number of the Basic-, Field device or Extension module
(ref. follow pages)
no module available
no module available
Micro module slot
no module available
Position of modules
Connector 1Connector 2
Connector 1
Extension module
(only IQ8Control M)
0121
0122
0123
Extension module
(only IQ8Control M)
0131
0132
0133
The Field device module (if available) must be installed in >Slot 1< of the Basic module.
>Slot 2< of the Basic module is unused on the FACP IQ8Control C.
1. Remove the central housing of the FACP IQ8Control from the box.
The cover contact and both connecting cables for the rechargeable batteries have already been attached to
the Basic module.
2. Pull the ribbon cable of the operating module and of the built-in printer (if present) off the connectors of the
Basic module.
3. Remove the four connecting screws between the base plate and the housing frame which were screwed in
for transport.
4. The housing door (operating module and variants) has already been connected to the housing frame at the
factory. To detach the housing door from the housing frame, pull out both retaining pins of the housing door
holder.
5. The housing must be mounted on a stable, clean and dry wall surface without mechanical stress. The
function of the snap-type connection for the housing door can be impaired if the housing is not correctly
mounted.
Only flat-head screws and dowels with a diameter of 8 mm should be used to secure the central unit’s
housing. Here, make sure that the screw head fits into the hole of the wall compensation element and does
not project.
6. To compensate for slight wall unevenness, you can screw the four wall compensation pieces of the base
plate in or out. The central unit’s additional pack contains a special spanner for the adjusting the wall
compensation elements.
The three unused fastening points between the base plate and the housing frame are not necessary on the
FACP IQ8Control C/M. This fastening is intended for a different housing use.
Danger - Electrical shock !
Disconnect all power from the panel before carrying out any installation work. The panel may only be
operated while the cabinet is closed. Operation is not allowed while the cabinet is open.
Risk of short circuit
All voltage and signal lines connected to the Basic module must be secured to prevent slipping by
using a suitable attachment materials such as plastic cable binders. Make sure the voltage cable will
not move and touch the signal lines (SELV). Work on the FACP IQ8Control may only be carried out
when it is de-energised (mains and emergency power supply).
FB 798951.GB0 / 01.09
19
Fire Alarm Control Panel IQ8Control C/M
3.6 Assembly
The housing is pre-assembled by factory delivery. To ease the further assembling and mounting please observe
the given mounting sequence.
1
2
3
Fig. 14: Exploded illustration
c
d
e
f
g
h
i
4x wall compensation pieces
1 x Metal sheet of the base plate for shielding and the PE connection (functional earth)
1x rear panel
1x back box
1x housing contact (up to four contacts possible)
1x front frame with operating module and housing door
4x connecting screws
The Basic module is connected to the central housing’s rear metal panel via the metal spacers and
the metal screws. Without this electrically conductive connection between the Basic module and the
rear metal panel, sufficient EMC protection for the FACP IQ8Control is not guaranteed.
4
5
7
6
20 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Operating module / Housing door
The operating module/the housing door is installed by the manufacturer on the front housing part. If required for
dismantling, loosen the 4 fixing screws and remove the front part of the housing.
Depending on the panel configuration, e.g. with or without an installed printer or an individual zone display,
deviation from the illustration here is possible.
For correct ESD protection it is highly
recommended to insert the dummy plug
123
456
789
0
(insert pack) of the programming interface
plug into front of the operation panel.
8
Fig. 15: Operating module / Housing doo
The operating module is not required for programming the FACP IQ8Control. The service PC can
also be directly connected to the programming connector of the Basic module. Using the service
program TEDIS (optional) enables the operating module to be completely simulated on the service
PC with all functions.
Opening
The front door key is always required to open the housing front.
It can be opened with the key vertical
Closing
To close the front door, the lock must be in the horizontal position. The key is not
required. The front door can
simply be pushed closed and engaged in the snap-type fastener.
Example: Housing IQ8Control C
1. Place front frame with integrated door carefully onto the back box.
Take care to ensure that no cables are pinched or damaged when installing or removing the assembly.
2. Insert the four screws between the back box and the front frame and tighten carefully.
3. Insert housing contact in the upper place of the housing with the contact tab downwards. The contact is
connected to the Basic module by factory settings and may be removed for service or maintenance work.
4. Connect the ribbon cable of the operation panel to the corresponding connector on the Basic module.
5. This completes assembly of the housing
FB 798951.GB0 / 01.09
21
Fire Alarm Control Panel IQ8Control C/M
Housing contact
The housing contact provides the monitoring of the panels housing and may be used additionally for control
function by means of service or maintenance work, e.g. to disconnect devices whilst the contact is open.
Max. 2 contacts per housing
(1 integrated contact by factory configuration)
11
Max. 4 contacts per FACP
Select contact operation via the panels data
configuration, e.g.
- Disconnect master box whilst open contact
- Access of Service-PC whilst open contact
- und additional features
11
The housing contact must be place to the appropriate
insert on the top corner of the housing.
Housing contact / contact tab points downwards
Housi ng
open
V2
8
7
6
5
X7 X8
1
2
3
4
Housing contact
Connect to Basic module
(refer to section “Basic module”)
Fig. 16: Housing contact
22 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Connection between the central housing and the extension housing
1
1. Remove the appropriate 2 plastic plates from
panels and extension housing
2. Push the plastic connector bracket in each
originated gap. Observe the arrows on the bracket
for the right direction.
1
1
2x connection pieces
with cable glands
Fig. 17: Knockouts for battery cable
Damage to the system!
Take care to ensure that no cables are pinched or damaged.
Each housing part must be separately fixed to the mounting place. The plastic connection brackets are
not suited to carry the weight of the lower housing alone.
3. Push the upper housing via the guide way of the
brackets towards the wall.
4. Align both connection brackets to ensure that the
cables between the housings may be lead through
the openings of the brackets.
5. Each housing must be fixed with suited screws
(4x) and dowels without twisting stress.
FB 798951.GB0 / 01.09
23
Fire Alarm Control Panel IQ8Control C/M
Wall mounting
The panel must be mounted on a flat surface using appropriate hardware (screws and dowels). Avoid
mechanical stressing. It may only be commissioned after correct mounting on a wall or other mounting surface
of sufficient strength to support the weight of the unit. Minor unevenness of the mounting surface may be
adjusted by the wall compensation device. Apply the delivered key tool from the inside of the housing to adjust
the wall compensation devices.
1
Fig. 18: Rear side of the Standard back box
Fig. 19: Wall compensation element for adjusting and key tool
Damage to the system !
Please note that depending on the rechargeable batteries used, a significant weight must be
supported by the fastening screws of the extension housing.
Plastic key is enclosed.
24 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
3.7 Cable glands
Lead the 230V main power cord through the wall and the cable entry c provided in the rear of the unit (see
illustration). Fasten it using appropriate devices, e.g. plastic cable straps.
Make sure that the mains and signal cables don’t interfere with the rear panel of the cabinet or the cabinet frame
which is mounted on the rear panel.
Signal cables must only be led through the other cable entries
IQ8Control C
d.
IQ8Control M
1
Fig. 20: Cable glands
Danger - Electrical shock !
Disconnect all power from the panel before carrying out any installation work. The panel may only be
operated while the cabinet is closed. Operation is not allowed while the cabinet is open.
Risk of short circuit
All voltage and signal lines connected to the Basic module must be secured to prevent slipping by
using a suitable attachment materials such as plastic cable binders. Make sure the voltage cable will
not move and touch the signal lines (SELV). Work on the FACP IQ8Control may only be carried out
when it is de-energised (mains and emergency power supply).
Insulation of connecting cable
Make sure to lead all cables complete with their outer sheaths intact into the cabinet. Only remove the
insulation from those sections which are inside the cabinet.
3.8 Panel buzzer
2
1
2
If required the internal panel buzzer may be disabled with the solder jumper BR2 on the rear side of the
operating panel PCB.
BR2
BR2
closed, buzzer enabled (factory setting)
BR2
open, buzzer disabled
If the buzzer is permanently disabled (BR2 open), the transmission of this audible warning signal to
must be ensured (e.g. by indicating this condition at a panel within the network)!
FB 798951.GB0 / 01.09 25
Fire Alarm Control Panel IQ8Control C/M
4 Module
The FACP IQ8Control C / M has a modular design so that modules can be replaced/extended at any time.
Only remove or insert modules when the FACP is voltage free.
Switch off the power and battery supply.
Wait for at least 10 seconds before the modules are replaced or supplemented.
Take suitable measures to discharge static electricity.
Check correct installation (modules and connection cables).
Switch on the power and battery supply.
If necessary, check/supplement the customer data using the programming software tools
8000.
4.1 Power supply module (Part No. 802426 index G or higher)
The power supply module is installed on the Basic module of the FACP. This module accommodates the entire
voltage supply for the Fire Alarm Control Panel and the +12 V DC supply voltage for external devices. Maximum
current load from external users will depend on control panel configuration. If necessary, additional supply is
possible from a monitored external power supply unit. The power supply module is suited to connect 2 batteries
(2 x 12 V / 24 Ah). In case of an AC power (230 V DC) loss the panel operation will be supplied without
discontinuation (refer chapter 4.1.3).
Fig. 21: Power supply module (Part No. 802426 from index G)
X1
X 2/3
F1
F2
R 2
Plug connector for transformer (secondary)
Basic module connector
Fuse for the FACP internal power supply: T 4 A
to the analog loop 27,5 V (esserbus
Fuse for secondary side: T 5 A
Potentiometer for adjusting the battery charging voltage to +13.65 V DC (@ 25 °C)
The power supply module must only be installed or removed with the Fire Alarm Control Panel in a
de-energised state.
When you are installing or replacing the power supply module, observe the BR5 solder
bridge/jumper (on the rear side of the circuit board). This jumper is used to set whether the power
supply unit is installed in an FACP 8000C/M or
this could damage the Fire Alarm Control Panel or the power supply unit.
The battery charging voltage is set to the abovementioned values by the manufacturer. If the FACP
is used at other ambient temperatures (refer to technical data), then the battery charging voltage
must be adjusted accordingly using potentiometer R2.
®
) or 42 V (esserbus® PLus)
an IQ8Control C/M. If the jumper is set incorrectly,
<" will be displayed for each analog loop. In the alarm condition, the zone voltage
zone
is lower than the required 42 V. The audible alarm loop device may not sound an alarm at full
volume.
Undervoltage protection (U
BR2
Undervoltage protection activated (factory setting = ON)
The panel switches off automatically if, in case of charging, the
battery voltage is
Under voltage protection disabled
< 9,5 V DC)
Batt
9.5 DC.
ON
1 2 3
OFF
1 2 3
a ground fault message occurs and additionally the fault
zone
1
ON
2
3
1
2
OFF
3
Selection of the analog loop voltage
BR 4
esserbus® System with 27,5 V analog loop voltage
esserbus® PLus System with 42 V analog loop voltage
esserbus
devices with Part No.
®
PLus module Part No. 804382 and appropriate loop
80xxxx required
Damage to the system !
Mixed operation with esserbus® and esserbus® PLus functionality is not possible!
Selection of the Fire Alarm Control Panel
Solder jumper on the rear side of the PCP to select the CPU power supply voltage.
BR5
Factory default of a separately delivered power supply module
(Prepared for mounting in the FACP 8000 C / M)
3 2 1
3 2 1
BR5
Operation in FACP IQ8Control C/M ÎJumper BR 5 closed
BR5
FB 798951.GB0 / 01.09 27
Fire Alarm Control Panel IQ8Control C/M
4.1.1 Mains connection and earth connections
L1
F1
T1.25A
H/230V~
X2
N
U
Main
230V~
N
Housing mantle
terminal
PE
L1
FE
Fig. 22: Connection of the rated voltage (230 V AC) and earth connections on the basic module
The mains supply must be installed in accordance with local regulations by a qualified technician. The AC
connection terminals are located on the Basic module.
Requirements
Use an appropriate mains cable, e.g. NYM 3 x 1.5 mm2 or a cable type with similar specifications.
The installation must comply with local regulations on electrical safety.
Overvoltage fine protection is integrated into the FACP according to EN 54 and the VdS guidelines. Should
coarse protection be required this should be installed by the installer for the specific object.
The fire alarm system must be supplied from the 230 V mains through a separate isolator or an
appropriately labelled safety switch. The required mains voltage (230 V AC) is given on the panels
nameplate.
In buildings fitted with earth fault devices (FI protection), a separate device must be installed for the fire
alarm system.
The fuse for the power supply of the fire alarm system must be clearly labelled with the red marking ‘FACP’.
Observe national standards and guidelines.
The protective earth conductor of the mains cable must be connected to the corresponding screw terminal
at the fire alarm panel (ref. to section Protective and Functional earth).
AC mains voltage
Cable corss section at least
> 4mm² to PE rail
The required mains voltage (230 V AC) is given on the panels nameplate.
Cable insulation
Make sure to lead all cables complete with their outer sheaths intact into the cabinet. Only remove the
insulation from those sections which are inside the cabinet!
Power supply
The fuses of the panel or external power supply units cannot prevent an unexpected fault in electrical
modules; rather, these fuses are intended to protect users and their surroundings from damage.
Therefore, never repair or bridge the fuse that is installed (e.g. T1A H/250V) or replace it with anything
other than the stated type!
28 FB 798951.GB0 / 01.09
4.1.2 Protective and Functional earth
Fire Alarm Control Panel IQ8Control C/M
Wiring FACP IQ8Control C
rear wall plate of the central unit's housing
Battery bag 2
Battery bag 1
Housing mantle terminal
Basic
module
N
Cable cross section at least > 4mm² to PE rail
Wiring FACP IQ8Control M
Metal screws to the
rear wall plate of the central unit's housing
Metal screws to the
L1
U
L1
PE
N
FE
The primary PE-connection (protective
earth) of the mains supply must be
connected to the appropriate terminal of
the FACP to ensure a proper operation of
the system.
The FE (functional earth) and PE
(protective earth) terminals of the panel’s
housing must be connected with the PE
rail of the power distributor panel from
which the fire alarm system will be
powered.
Use copper cable with a cross section of
at least ≥ 4 mm
2
depending on the length
of the cable run.
The FACP IQ8Control is a protection
>class I DIN EN 60950< device.
Basic
module
L1
U
N
Battery bag 1
Fig. 23: Protective and Functional earth
The base module is connected to the rear panel of the cabinet by means of metal spacers and
screws. This electrically conducting connection between base module and rear panel is essential
for correct functional earthing of the FACP IQ8Control C/M.
Battery bag 2
Housing mantle terminal
Cable cross section at least
> 4mm² to PE rail
L1
PE
N
FE
FB 798951.GB0 / 01.09 29
Fire Alarm Control Panel IQ8Control C/M
Several alarm circuits on one power supply unit
If several visual/acoustic alarm devices are switched on e.g. via the 3 relay micro module (part no.
787531), 4 relay micro module (part no. 787530), the 4 zone/2 relay esserbus
no. 808613/808613.10) or the 12 relay esserbus
their power supply is provided by a joint power supply unit
®
transponder (part no. 808610/808610.10) and
, then the installer must ensure that there
®
transponder (part
is a staggered backup concept.
As a rule, several fuses with different fuse values and different response characteristics are
connected in series. The response behaviour also always depends on the preload of the fuses.
In order to carry out this wiring according to the standard, it must be ensured that in the case of a
short circuit, it is not the power supply unit fuse that responds but instead a fuse for the respective
alarm area.
It is thefore paramount
that every single alarm area is protected via a separate external fuse. The
8-fold fuse card (part no. 382040), for example, can be used for this purpose.
The fuse values depend on the number and type of the devices used and must always be
determined for the specific object.
Recommendation: Small fuse value
¼ quick response behaviour.
4.1.3 Emergency power supply
In case of loss of the mains voltage the control panel will be powered without a interruption by the connected
battery. Depending on the capacity of the battery a backup time of up to 72 hours can be realised. After that
time the external alarm devices must be still operable in an alarm condition. The activation of these devices
must be still possible with a minimum battery voltage of 10.5V DC.
First Commissioning
New batteries must be charged at least 24 hours before operation. If the date of manufacturing is dated back
about more than 9 month a battery charge time of min. 48 hours is required.
Deep discharging
The power supply unit periodically monitors the charge of the batteries connected. If this battery test reveals a
battery voltage of below 10.0 V DC under load, battery trouble will be signalled. The battery charge is controlled
by means of a temperature-dependent resistor (NTC). As soon as the voltage of the batteries goes below 9.5V
the battery backup will get disconnected to protect the control panel. The control panel is no longer operational!
Eliminate the trouble condition of the mains power supply and turn/switch on the control panel. The connected
batteries will get charged automatically if the voltage of the batteries during the battery test without external load
is higher than 10.5V DC. A battery failure will be indicated if the voltage of the batteries does not exceed this
level. Discharged batteries have to be recharged with an external power supply or need to be replaced. This
Function can be enabled / disabled with the
jumper BR2 on the basic circuit board.
Exhausted batteries (off-load voltage U
< 10,0V DC) will not charge correctly!
battery
Only the battery types approved by the Esser by Honeywell Fire Alarm Control Panel may be used
for supplying the Fire Alarm Control Panels with backup power. Observe the information and
technical specifications of the battery manufacturer and the VdS-guidelines for deep charged
batteries.
30 FB 798951.GB0 / 01.09
Connection of two batteries
Fx
+
Battery 1
-
+
Fx
Battery 2
-
Fig. 24: Connection of two batteries
Battery 1
max. 12 V DC / 24 Ah
Battery 1
Battery 2
Fire Alarm Control Panel IQ8Control C/M
+
-
+
-
F2 battery 1
T2.5A
BR2
F3 battery 2
T2.5A
Battery 2
BR2
F2
F3
Fx
max. 12 V DC / 24 Ah
Open Î battery 1 + 2 monitoring enabled (factory setting)
Fit usual battery fuse 12 V DC / 10 A (delivered with sub-package)
If a single battery is connected without
an internal control panel battery test is performed.
closing jumper BR2, a battery fault will occur next time and
FB 798951.GB0 / 01.09 31
Fire Alarm Control Panel IQ8Control C/M
Mechanical battery fasteners
1
Up to 2 batteries may be place inside the compact
housing. The required batteries fastener (plastic
device) is delivered with the panels equipment.
Place batteries as shown and insert fastener.
Fig. 26: Mechanical battery fasteners e.g. compact housing IQ8Control C
1
Fig. 27: Mechanical battery in the housing of the IQ8Control M or in the extension housing
Fix the mechanical battery fastener by inserting
the two screws
Up to 2 batteries 12 V / 24 Ah may be placed inside
the lower housing part of the IQ8 Control M or in the
extension housing (part no. 783000 / 01). The
required battery fastener (plastic device) is delivered
with the panel equipment.
Place batteries as shown and insert fastener.
Assemble the additional battery mount by
pushing in.
.
Damage to the system!
Please note that depending on the rechargeable batteries used, a significant weight must be
supported by the fastening screws of the extension housing. It is not permissible to install the
rechargeable batteries without these fastening clamps.
32 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
4.1.4 Specification Power supply module (Part No. 802426)
Main voltage : 230 V AC (+10% / -15%),
Rated current : 0,7 A
Rated frequency range : 50 to 60 Hz (ref. to nameplate)
Rated frequency : 50 Hz
Output voltage : 12 V DC
Current for ext. devices : max. 2A
Permissible current consumption with
2 x 24 Ah batteries and 72 hour
emergency power supply
Battery capacity : max. 2 x 12 V DC / 24 Ah (= 48 Ah)
: max. 650 mA
Battery charge voltage
Undervoltage protection
Ambient temperature : -5 °C to +45°C
Storage temperature : -5 °C to +50°C
Ambient conditions : class 3k5 according to DIN EN 60721-3-3
Protection class : I according to DIN EN 6050
Compatibility : Part No. 802426 Index G or higher
: : 13,65 V DC @ 25 °C
9,5 V DC (with jumper BR2 switch-on / off)
The power supply module is suited for the Fire Alarm Control
Panels IQ8Control C/M with the required Basic module (Part No.
772481/-82).
The required loop voltage (27,5 V or 42 V for esserbus
must be selected on the power supply module with jumper BR4!
For IQ8Control C/M fire alarm control panels it is possible to use
the power supply module from hardware version Index G as a
replacement module. Pay attention to the settings on the power
supply module of FACP IQ8Control C/M and the Index of the
hardware that is used!
®
PLus)
FB 798951.GB0 / 01.09 33
Damage to the system!
Before connecting the alternating voltage (230V AC) read the
panel’s identification plate. It is not
other than that shown on the identification plate (sticker in the
panel housing).
permitted to connect a voltage
Fire Alarm Control Panel IQ8Control C/M
4.2 Basic module
The power supply module and a free selectable micro module may be installed on the appropriate Basic
module connectors. >System connector 1< provides the connection of a Field device module or Extension
module. The slot >System connector 2< is only available for the FACP IQ8Control M.
Housing
open
V2
8
7
6
5
Housing contact
Link data
V1
X7 X8
1
2
3
4
V3
Ethernet
Phone box
X13
HW FAILSAFE USL
Battery 1
+
-
Battery 2
+
-
Power supply module
X9 - A
X10 - B
X2
Fig. 28: Basic module
Part No. 772481
micro module
S1
Reset
X11 - A
X12 - B
USB
V46
F2 battery 1
T2.5A
X1
F1
X3
1 2 3 4 5 6 7 8
BR2
X27 X28 X29
micro module
Î Basic module IQ8Control C
Printer
X23
X31
S2
F3 battery 2
T2.5A
X30
F4
+UBext T2A
GND
V50
+UBext.
BR7
Printer
X24
V62 V63
polarity
A B A B A B
Printer
RxD TxD
TxDreversed
TTY
MMI
RS485
1
D21
NO
Fault
NC
X45
X33
1
2
3
X34X32
C
X35
12
IN
X46
RS485
1
2
3
A B
2
System connector 1
ISB
System connector 2
Part No. 772482
Î Basic module IQ8Control M
Risk of short circuit!
All voltage and signal cables connected to the Basic module must be secured to prevent slipping by
using a suitable attachment materials such as plastic cable binders. Make sure the voltage cable will
not move and touch the signal lines (SELV). Work on the FACP IQ8Control may only be carried out
when it is de-energised (mains and emergency power supply).
34 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
BR2 Solder jumper to set whether the two batteries are connected and the monitoring for the free
battery connection should be switched off.
Open (default)
closed
(The power charge and monitoring of >Battery 2< is disabled)
BR 3 / BR 4
BR7
D21
F1
F2
F3
F4
V46
S2
Solder/jumper for wiring the LCD indicator panel via the RS 485 interface
Solder jumper for enabling an internal printer
Integrated circuit, replacement not required
Mains fuse T1.25A H / 230 V DC
Fuse T2,5A Î battery charge current, battery 1
Fuse T2,5A Î battery charge current, battery 2
Fuse T2A Î 12 V DC supply voltage +Ub
lights during emergency operation Î Limited functionality of the Panel
DIL switch Î Operating mode "OFF" (factory default)
V62 / V63 LED V62 lits red Î Reversed polarity of the connected TTY cable
LED V63 lits green
X1
X2
Transformer connection (primary site)
AC mains connector terminal L1/U, N, PE; for cable with 1,5 - 2,5 mm2 (#12-14 AWG)
X3 Connector for the micro module slot, the internal serial interface TTY / RS 485-1, the common
trouble relay, inputs
(12 V DC, Ub
The RS 485-2 interface connection is not supplied!
X7/X8 (LED V2)
X9-A, 10-B
X11-A, 12-B
Cover contact connection (FACP housing). LED V2 lights while the cover is open.
Connector for the power supply module (Part No. 802426 from Index G)
Micro module slot for a selectable micro module
X23 Connector for the built-in printer via a 26 pole ribbon cable
(For 19” racks the ribbon cable Part No. 750756 max. 50 cm or 750757 max. 120 cm is required)
X24
Connector for the operation panel via a 40 pole ribbon cable
X27, 28, 29, 30 Jumpers to configure the EMI protection for the terminals if an essernet
connected.
X31
X32
X34
X33/35
X45, X46
USB
Connector for the Service-PC (optional panel interface required)
1
2
Pos 1/2
3
1
2
Pos 2/3
3
1
Pos 1/2
2
(do not alter factory default)
3
1
2
Pos 2/3
3
Jumper for the RS 485-2 interface (do not alter position)
Jumper for factory settings only ( do not alter ISB)
Connector for the service-PC and USB-Interface for a System software update.
Internal devices and terminals for future system developments
Î Connection of two batteries >Battery 1+2<
Î Connection of a single battery only to connector >Battery 1<.
for external devices
ext
Î Service mode ”ON“ (software update via USB interface)
Î to check data communication if the TTY-interface is enabled
I1 and I2, the control voltage for the built-in printer and the supply voltage
) for external equipment
ext
®
micro module is
Î RS485-1 terminating resistance activated
Î RS485-1 terminating resistance not activated
Î RS485-2 End of line resistor activated
The RS485-2 interface is
not supplied for this panel
Î RS485-2 terminating resistance not activated
version.
FB 798951.GB0 / 01.09 35
Fire Alarm Control Panel IQ8Control C/M
Connection of the AC mains voltage and batteries
The AC mains voltage must be connected to this terminals of the Basic module. Refer to section “power supply
module” for detailed information.
N
L1
U
X2
Mains
230V~
Fig. 29: Connection of the AC mains voltage and batteries
Danger - Electrical shock !
Disconnect all power from the panel before carrying out any installation work! Observe before
connecting the AC mains voltage (230 V AC) the specifications given on the panels nameplate
(adhesive label) inside the housing.
Connection terminals
Connector: removable, max. 1.5mm
Fig. 30: Connection terminals removable
DIL Switch S2
2
removable
S2
Normal operation
OFF
S2
ON
Reset Button
S1
Reset
Service mode
The LED V50 lits for an optical indication
The service mode will be activated after a panel reset and displayed at
the operation panel.
Press the RESET button to restart the panel. Alarm and fault messages are reset, all
detector zones and primary loops are switched on and all changed switch settings are
read in.
A panel cold start using the RESET button is only possible when the housing contact
(panel housing) is open. If the panel interface was connected to the USB input, the
connection is detected only after a reset.
36 FB 798951.GB0 / 01.09
Î Position "OFF" (factory setting)
Î Position "ON“
Fire Alarm Control Panel IQ8Control C/M
4.3 Software
System requirements:
Firmware: Version V3.01R000 or higher
Programming software tools 8000: Version V1.06R001 or higher
4.3.1 Firmware Update
The system software (Firmware) of the FACP IQ8Control may be updated directly at the panel via the integrated
USB interface. Therewith the FACP IQ8Control may be detected from the Service-PC it is required to install the
appropriate USB driver <usbcf.inf> (MS-Windows 98, 2000, XP) first.
Connect the Service-PC via the USB cable to the USB connector on the Basic module. Switch on the ServicePC
Î the USB connection will be detected automatically and corresponding USB driver requested. The driver
<usbcf.inf> is delivered on the CD-ROM tools 8000 from version V1.06.
USB
Fig. 31: System software (Firmware)
Always save Customer data on Service-PC.
The programmed customer data will not be affected by the firmware update. Depending on the
complexity of the firmware update it might be necessary to reload the customer data with tools
8000 from the Service PC in a compatible data format to the updated FACP.
The description of the programming software relates to tools 8000 version V 1.09. Irrespective of
this a panel configuration with a former programming software from version V1.06 is possible.
Details of the configuration procedure may be differ from the given programming examples.
S2
ON
S1
Reset
Servicemode
FB 798951.GB0 / 01.09 37
Fire Alarm Control Panel IQ8Control C/M
1. Open panel housing
2. Set DIL switch S2 (1+2) on the Basic module in Pos. ON (LED V50 lits).
3. Press reset button
4. Wait until FACP is resetted and the display message „Servicemode“ appears.
5. Connect USB cable (Part No. 789863) to the USB-connector of the FACP IQ8Control an.
6. Start tools 8000 software on the Service PC and select >Tools / actualize panel software<.
7. After the firmware update the message >Update successful< appears on the Service-PC
Î FACP reset
8. Remove USB-plug from the Basic module and set DIL-switch in position OFF
be automatically resetted and returns to the normal operation mode.
Î the FACP IQ8Control will
38 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
4.3.2 Customer data programming
The Fieldbus- und panel interface (Part No. 789863) or panel interface (Part No. 769828) is required to
configure the panels Customer data.
The software tools 8000 from Version V1.06 provides the configuration of the FACP IQ8Control functions and
customizing the system to all requirements. A detailed guideline to the configuration of the FACP IQ8Control is
given in the Online-Help file in tools 8000.
4.3.2.1 Fieldbus- und panel interface (Part No. 789862.10), USB
Therewith the interface may be detected from the Service-PC it is required to install the appropriate USB driver
>usbefi.inf< (MS-Windows 98, 2000, XP). Connect Service-PC and the interface with the USB-cable. Switch ON
the Service-PC
The driver >usbcf.inf< is delivered on the CD-ROM tools 8000 from version V1.06.
Î the USB connection will be detected automatically and corresponding USB driver requested.
USB
Fig. 32: Fieldbus- und panel interface (Part No. 789862.10), USB
4.3.2.2 Panel interface (Part No. 769828), serial
serial
Fig. 33: Panel interface (Part No. 769828), serial
For safety, always
The saved customer data can then be transferred quickly and easily from the service PC to the
FACP IQ8Control.
save your data on the hard disk of the service PC.
FB 798951.GB0 / 01.09 39
Fire Alarm Control Panel IQ8Control C/M
4.3.3 Housing contact
Housi ng
open
V2
X7 X8
8
7
6
5
Housing contact
1
2
3
4
Depending on the panel housing used, up to four cover contacts can
be connected to the connection terminals of the Basic module.
A single contact per housing is integrated by factory settings.
The opened housing contact is indicated by the illuminated LED V2.
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
Fig. 34: Housing contact
4 3 2 1
set
jumper
4 3 2 1
4 3 2 1
4 3 2 1
The cover contact must be opened when the service PC is connected, otherwise connection of the
PC is not recognised by the central unit.
set
jumper
Connection of one housing contact
Connection of two housing contacts
Connection of three housing contacts
Connection of four housing contacts
40 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
4.3.4 Serial interface
The serial interface on the Basic module may be configured as a TTY interface (20 mA) or as an RS485
interface.
The required interface to connect external devices is selected by the Service software tools 8000
from Version V1.06.
TTY interface
V62 V63
TxDreversed
Polarit y
AB A
RxDTxD
receive
TTY
receive
These four terminals may be used for connecting an
external device, e.g. a protocol printer or the kit for a
redundant transmission path (Part No. 784749*), via the
TTY interface (20 mA).
The cable length between external device and interface
must not exceed 1000m.
In operation (green LED)
If wired correctly, the green LED (TxD) will blink at the
transmission frequency to provide visual indication of proper
interface wiring.
B
transmitt
transmitt
Rx +Rx -Tx +Tx -
Reverse polarity indicator (red LED)
If the connection cables are transposed at the terminals, red
LED (Reversed polarity) will light up.
* This option may be installed inside the FACP housing with the Top-hat
An external device, such as an LCD display panel, can be connected to the A/B terminals via the RS485
interface.
The RS485 BUS must be connected with an
EOL resistor at both
If the FACP incl. basic module is the last
device on a loop end, the integrated EOL
resistor can be activated with the X32 jumper.
ends of the loop.
X32
1
2
3
X33
1
2
3
X34
1
2
3
X35
1
2
3
GND
+UBext.
-
Fig. 36: RS485 interface
RS 485-1
A/B
X32
+
external device
Connection of the interface cable – total length max. 1000m
closed Î RS 485 termination resistance activated
open
AB
RS485
1
AB
RS485
2
BA
Î RS 485 termination not activated
RS 485-2
A/B
Do not alter position of the jumpers!
X33/35
Do not connect terminals!
X34
42 FB 798951.GB0 / 01.09
Common trouble relay
SaS-Relay
FAULT
Fire Alarm Control Panel IQ8Control C/M
Contact : change-over (EMI protected)
Breaking capacity : 30 V DC / 1A
Function : Common trouble (SaS-relay FAULT)
If the control panel detects at least one trouble incident,
relay activation will be interrupted and the relay will change
its control status.
Normally energized mode of the relay contact
The relay is activated when the Fire Alarm Control Panel is
in the normal mode. This application provides a fault
CNCNO
message even in the emergency operation of the panel. In
case of a total power loss, a fault message can be
transmitted via the dry relay contact.
exteral device
Fig. 37: Common trouble relay
Do not connect relays (AE) of the FACP with alternating voltage. Even in the case of a >dry relay
contact< it is not possible to switch an external AC-voltage.
Inputs IN1 and IN2
GND
12
IN
Monitored inputs IN1 and IN2 allow you to monitor two
external devices, such as an external power supply for
feeding the control panel components.
An external contact is required for activating an input and
will be open in the normal mode. This contact is used to
switch input IN1 or IN2 to GND in order to send a trouble
message to the Fire Alarm Control Panel.
For each input, Programming software may be used for
entering specific additional text of 25 characters in length
that will be shown on the alphanumeric display and protocol
printer in the event of an incident.
e. g. external power supply
Fig. 38: Inputs IN1 and IN2
FB 798951.GB0 / 01.09 43
Fire Alarm Control Panel IQ8Control C/M
4.3.5 Micro module slot
Eight connection terminals are provided at the micro module slot on the Basic module for connecting the freely
selectable micro module. Assignment of the eight screw terminals will depend on the micro module type used.
micro module
X11 - A
X12 - B
X1
X27X28
X29X30
X2
Fig. 39: Micro module slot, connection terminals and Location of Jumpers
F1
X3
1 2 3 4 5 6 7 8
micro module
All jumpers in horizontal position
X27 X28
X29 X30
Required configuration for all micro modules apart from
essernet
EMC protection for this micro module connection terminal is
activated
All jumpers in vertical position
X27
X28 X29 X30
Only required for essernet® micro module.
The EMC protection is activated on the micro module for
essernet
basic module.
The micro module must be configured with the appropriate jumper and DIL-switches and additionally
programmed in the panels customer data.
®
(factory setting)
®
and therefore switched off on the
44 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
4.3.6 Technical data Basic module
Operating voltage : Internal via the power supply module, +5 V DC / + 12 V DC
Quiescent current : approx 215 mA @ 12 V DC without operating module
approx 230 mA @ 12 V DC incl. operating module
approx 295 mA @ 12 V DC incl. operating module ¼ VGA
Emergency mode operation : available
Fuses : F1 = T1,25A H/230 V AC
F2 = T2,5A
F3 = T2,5A
F4 = T2A / 12 V DC
Î mains voltage, primary
Î battery 1
Î battery 2
Î supply voltage
for external devices
Supply voltage for external devices : max. 12 V DC/ 2A (terminal +Ubext / GND)
Common fault relay : 1 dry change-over contact
Contact rating max. 30 V DC / 1A
Relay operation with common fault programmable in the customer
data
Terminals
- Mains connection
- Communication cables
TTY -interface
or
RS485-1 interface
:
1,5mm
:
removable, max. 1,5mm2
:
20 mA, max. 1000m cable length
:
max. 1000m cable length
2
up to max. 2,5mm
2
Do not connect relays (AE) of the FACP with alternating voltage. Even in the case of a >dry relay
contact< it is not possible to switch an external AC-voltage.
Compatibility : Part No. 772481
Part No. 772482
Î Basic module IQ8Control C
Î Basic module IQ8Control M
The Basic module is suited for the Fire Alarm Control Panels
IQ8Control C/M with the required power supply module
(Part No. 802426 from index G).
The required loop voltage (27,5 V or 42 V for esserbus
®
PLus)
must be selected on the power supply module.
For the Fire Alarm Control Panel system 8000 the basic module
may be used as replacement device. This requires the power
supply module (Part No. 802426 from index G).
FB 798951.GB0 / 01.09 45
Fire Alarm Control Panel IQ8Control C/M
1.2 Field device module
The Field device module required in order to configure a stand-alone FACP in accordance to the appropriate
standards and guidelines. The Field device module integrates all of the input and output modules that are
necessary in addition to the modules on the Basic module to operate as a Fire Alarm Control Panel to DIN VDE
0833. This are e.g. terminals to connect a Fire department notifying system, a master box and programmable
relays.
There are two different kinds of Field device module available for the FACP IQ8Control:
1) Part No.772477 - Field device module with one micro module slot
2) Part No.772479 - Field device module without micro module slot
The FACP must not be operated with series 01 Field device modules.
Features
Terminals for a Fire Department Notifying System (8 Inputs / 8 Outputs)
Terminals for a Master box (manned centre link) incl. relay to switch the required supply voltage and
monitored input to indicate the triggered master box.
Three freely programmable relays – alternatively
- monitored und positive switching,
- positive switching
- or dry change-over contact
Emergency operation for all four relays available
Do not use the relays for the monitored activation of alarm devices.
Monitoring of the relays is only used to detect interruptions and short circuits.
If a control panel is required to function in accordance with DIN 0833, you should program the
relays with the >common fire< (K2), >common alarm< (K3) and >common disconnection< (K4) in
the customer data of the control panel. In the emergency mode the relays will be triggered with the
assigned function.
If several Fire Alarm Control Panels are connected together in the essernet
be connected to one of the other FACPs.
Do not connect relays (AE) of the FACP IQ8Control with alternating voltage. Even in the case of a
>potential free relay< mode it is not possible to switch an external AC-voltage.
®
, the master box can
46 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Field device module (Part No.772479) without micro module slot
GR1
-
+
X8
K4K2
3
2
1
BR19
BR18
BR17
BR20
Field device module
Fig. 40:Field device module (Part No.772479)
K4
2A
K3K2K1
CNCNOCNCNOCNCNOCNCNO
2A2A1A
K3
3
2
1
BR15
BR14
BR13
BR11
BR10
BR16
BR12
BACK
GND
X5X6X7
F1F2F3F4
BR21
V8V10V41V42
3
2
X4
1
K1
3
2
1
BR 9
3
2
1
BR 8
BR 7
BR 6
BR2
V20V21V22
3
2
1
BR 5
BR 4
BR 3
BR1
Field device module (Part No.772477) with micro module slot
MM2
8
X10
GR1
1
-
K4K2
K4
NO
+
2A
3
2
1
BR19
BR18
BR17
BR20
K3K2K1
CNC
K3
3
2
1
BR15
BR14
BR13
BR16
CNCNOCNCNOCNCNO
X5X6X7X8X9
2A2A1A
V8V10V41V42
K1
3
2
1
BR11
BR10
BR 9
BR12
3
2
1
BR 8
BR 7
BR 6
BR2
Field device module
Fig. 41: Field device module (Part No.772477)
The Field device module (if available) must always
Basic module.
be placed on the >System connector 1< of the
BACK
GND
F1F2F3F4
BR 5
BR 4
V20V21V22
BR21
BR 3
X4
3
2
1
3
2
1
BR1
FB 798951.GB0 / 01.09 47
Fire Alarm Control Panel IQ8Control C/M
Relay K1
Relay for connecting a master box. May also be used as a freely programmable relay.
Selection of operating mode and emergency function by means of jumpers.
(Monitoring range 50
Contact rating when used as a >non-monitored change-over contact<
< 30 V DC/ max.1 A
to 1 k)
Relay K2,3,4
X4
X5
X6
X7
X8
X9 / X10
Relay with common function. May also be used as a freely programmable relay.
Selection of operating mode and emergency function by means of jumpers.
Contact rating when used as a >non-monitored change-over contact<
< 30 V DC/ max. 2A
8 inputs for connecting a fire department operating panel – top – IN 1-8
8 outputs for connecting a fire department operating panel – bottom – OUT 1-8
Connection terminals for (master box relay, K1)
for connecting the master box supply voltage, incl. confirmation input for verifying master
box activation
Connection terminal for relay K2
Connection terminal for relay K3
Connection terminal for relay K4
GR1 = Internal primary loop input (primary line no. XX
Normal operation
Fire alarm
Trouble « R = 1 k
Terminals for the micro module slot (only Field device module Part No. 772477)
« R = 10 k
« R 5 k
24, XX= FACP no.)
F1
F2 to F4
V8, V10,
V11, V12
V20 to V22
BR1 and BR2
BR3 to BR5
BR6 to BR20
BR21
Do not connect relays (AE) of the FACP IQ8Control with alternating voltage. Even in the case of a
>potential free relay< mode it is not possible to switch an external AC-voltage.
T1A – Fuse for Relay K1
T2A – Fuse for Relay K2, K3, K4
The LED lights while the corresponding relay is activated or when is has been programmed
for inverse control in the customer data programming
yellow LED V 20 will light up when the Fire Alarm Control Panel is operating in
CPU failure mode
green LED V 21 will light up when the cover contact (control panel housing) is
open
red LED V 22 will light up if a fire alarm is detected while the control panel is
operating in CPU failure mode
Solder bridges for setting the master box control in emergency operation
Jumpers for setting the CPU failure mode function for relays K2, K3, K4
Jumper to select the operation mode of relay K1 and relays K2, K3, K4
Coding jumpers for fire department operating panel with >fire control off / revision< function
(Terminals X4/IN8)
Jumper in position 2-3 >fire control off / revision<
not active / off (factory setting)
Jumper in position 1-2 >fire control off / revision<
active / on
Fig.42: Connection terminals Connection terminals fire department operating panel
Connection of the micro module
Eight connecting terminals are provided for the micro module slot of the Field device module. The actual
connection of the eight terminals depends on the type of module used.
If an essernet
of the basis module. The essernet
basis module. The EMI protection must be implemented by external EMI-protection devices.
®
micro module is used, this module may only be inserted into the micro module slot
®
micro module requires adaptation of the terminal card on the
Primary loop input Pri+/Pri-
Monitored primary loop input Pri+/Pri- (terminal X8) has the purpose of monitoring CPU failure in the essernet
Network. These terminals are used, for example, to connect the common fire relay of another Fire Alarm Control
Panel. In the event of trouble in the essernet
®
micro module, a fire alarm signal may still be sent via the relay
contact to the primary loop input of this control panel. The alphanumeric display at this Fire Alarm Control Panel
will then show the message >Prim. loop fire< in the event of an incident occurring.
The primary loop input can be switched off or on and reset via the corresponding primary loop number.
R*
10K
GR1
R* = monitored end-of-line resistor R =10 k
R= 10 k
R= 5 k
R= 1 k
« Normal status
« Fire alarm, display >Prim. loop fire<
« Trouble
Primary loop no.: xx24 (xx = Panel no. 01-31)
Fig. 43: Primary loop input Pri+/Pri-
®
FB 798951.GB0 / 01.09 49
Fire Alarm Control Panel IQ8Control C/M
4.3.7 Connecting a fire department operating panel
Wiring differs from area to area and is
bottom - terminals
top - terminals
X4
A 12 V DC voltage is required for
governed by the requirements of the
regional fire department.
operation.
top
terminals
X4
FD call LED on
IN8
IN7
IN5
IN6
IN3
IN4
IN1
IN2
If the terminal IN8 (fire control off / revision) is not used, jumper BR21 must always be fitted at
position 2-3 !
Current load per output (OUT1 to OUT 8) max. 25 mA.
(IN1 on GND)
(closer)
do not use
do not use
MB disconnected
acoustic signals off
check MB
reset FACP
fire control off / revision
do not use
fire control off (revision)
MB activation prevent
acoustic signals off
MB disconnected
common fire
extinguishing system activated
MB activated
OUT1
OUT2
bottom
terminals
OUT8
OUT7
OUT5
OUT6
OUT3
OUT4
X4
Fig. 44: Connection terminals fire department operating panel
50 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
4.3.8 Connecting the master box (Relay K1)
Relay K1 for the connection of a master box is part of the peripheral module.
The control configuration of relay K1 can be set to
monitored and switching the positive potential
switching the positive potential
or as a non-monitored change-over contact
by means of jumpers.
K1
BACK
GND
CNCNO
K1
3
2
1
BR 8
BR 7
BR 6
Fig. 45: Location of the master box relay K1 and the jumpers BR 6 to 8 on the Field device module
Setting the operating mode for relay K1
Jumpers Function
BR 1
BR 1
Activation of master box relay (K1) also in the event of a fire alarm with the control panel in
the CPU failure mode (factory setting)
No activation of the master box in the event of CPU failure-fire
BR1BR2
BR 2
No activation of the master box in the event of a fire alarm when the cover contact on the
control panel housing is open (factory setting)
BR 2
Activation of master box even with cover contact open (outer housing)
FB 798951.GB0 / 01.09 51
Fire Alarm Control Panel IQ8Control C/M
Operating mode 1 Î Relay K1 positive switching and monitored
K1
V
*
R *
680
K1
S*
CNCNO
GND
BACK
Panel internal
+monitoring
Fig. 46: Terminal of the master box relay K1
BR8BR7BR6
3
3
2
2
1
1
R*
S*
Diode V*
From Hardware index B the diode V* is integrated in the Field device module.
3
2
1
Relay K1
positive switching (+12 V DC
Monitored end-of-line resistor R = 680 (factory setting) Monitoring capability of
internal resistor in master box 50 to 1000
Dry confirmation contact in master box
+12V DC Ub int.
/ max. 1A) and monitored
intern
(refer to customer data programming)
52 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Wiring example:
Operating mode 1 Î Relay K1 – positive switching and monitored
FACP IQ8
Field device module
Control C/M
Master box
(schematic circuit diagram)
MFAB
acknowledge
Relay
common fire
Relay
MFAB activated
BACK
GND
ÜE -
ÜE +
+ UB ext.
NO
C
acknowledge
alarm
+UB
10987
+UB
R*
680
S*
fire dept. key box
Fig. 47: Schematic circuit diagram master box with FDKB adapter
FB 798951.GB0 / 01.09 53
Fire Alarm Control Panel IQ8Control C/M
Operating mode 2 Î Relay K1 positive switching, not monitored
K1
CNCNO
BACK
GND
BR8BR7BR6
K1
3
2
1
3
2
1
3
2
1
Relay K1
Positive switching (+12 V DC
1A), not monitored
intern
/ max.
+12V DC Ub int.
Fig. 48: Terminal of the master box relay K1
Operating mode 3 Î Relay K1 not monitored change-over contact
K1
BACK
GND
CNCNO
Relay K1
Potential-free, not monitored change
over contact
External voltage
< 30 V DC, max. 1 A
K1
Fig. 49: Terminal of the master box relay K1
The IQ8Control FACP's relays may only be connected to DC voltages. No AC voltage may be
applied, not even when a relay is programmed as a >non-monitored change-over contact<.
BR8BR7BR6
3
2
1
3
2
1
3
2
1
54 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
4.3.9 Connecting the Relays K2, K3, K4
Location of the relay K2,K3,K4 and the jumpers BR9 to 20 on the Field device module
K4K3K2
CNCNOCNCNOCNCNO
Jumpers are used for adjusting the three relays K2, K3
and K4 to a variety of requirements.
K3K4K2
3
3
3
2
1
BR19
BR18
BR17
BR15
BR14
BR16
BR20
2
2
1
1
BR13
BR11
BR10
BR 9
BR12
The three relays may be coded independently of each
other as >positive-switching< and >monitored, positiveswitching< or as >potential-free change-over contact<.
Fig.50: Connecting the Relays K2,K3,K4
K2 K3 K4 Relay
Positive switching / monitored
Signale in operation
R *
-
+
10 K
NO
n. c.
+12V DC
Ub int.
UMess
CNC
+
monitoring
K
Positive switching / not monitored
-
+
NO
n. c.
+12V DC
Ub int.
CNC
K
BR 12
3
2
1
3
2
1
3
2
2
2
1
1
1
3
3
2
2
1
1
BR 9BR 10BR 11BR 12
3
2
1
3
3
2
2
1
1
3
3
2
2
1
1
BR 9BR 10BR 11
3
3
BR 13BR 14BR 15BR 16
3
3
2
2
1
1
3
2
1
BR 13BR 14BR 15BR 16
3
2
1
3
3
2
2
1
1
3
3
2
2
1
1
BR 17BR 18BR 19BR 20
3
3
2
2
1
1
3
2
1
BR 17BR 18BR 19BR 20
3
2
1
Change-over contact / not monitored
NO
CNC
3
2
2
2
2
1
1
1
1
K
3
3
2
2
1
1
BR 9BR 10BR 11BR 12
3
3
3
BR 13BR 14BR 15BR 16
3
3
2
2
1
1
3
3
2
2
1
1
BR 17BR 18BR 19BR 20
3
3
2
2
1
1
FB 798951.GB0 / 01.09 55
Fire Alarm Control Panel IQ8Control C/M
CPU failure mode function of relays K2, K3 and K4
K3K4K2
3
2
1
BR 5
BR 4
BR 3
Fig.51: Location of the emergency mode jumpers BR3 to 5 on the Field device module
K2
3
2
1
BR 4
K3 K4
3
2
1
BR 3
3
2
1
Jumper X in position 1/2
No activation of the relay while the Fire Alarm Control
Panel is in CPU failure mode (state on leaving factory).
BR 5
3
2
1
BR 4
3
2
1
BR 3
3
2
1
Jumper X in position 2/3
Relay also activated while the Fire Alarm Control Panel is
in CPU failure mode.
Used if a common function is programmed for the relays,
BR 5
such as >common fire<, >common alarm< and >common
disconnection<.
56 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
4.3.10 Technical data Field device module
Operating voltage : Internal via the power supply module, +5 V DC / + 12V DC
Quiescent current : approx. 15 mA @ 12 V DC
Fuse F1
Fuse F2, F3, F4
Relay K1
: : T1A – slow blow (relay K1)
T2A - slow blow (relays K2 to K4)
: Max. 1,5 mm
Relay for connecting a master box. May also be used as a freely
:
programmable relay.
2
Selection of operating mode and emergency function by means of
jumpers.
Contact rating when used as a >non-monitored change-over
contact< contact rating < 30 V DC/ max.1 A.
No dry contact cause of the integrated EMI protection.
Relay with common function. May also be used as a freely
Relay K2, K3, K4
:
programmable relay.
Selection of operating mode and emergency function by means of
jumpers.
Contact rating when used as a >non-monitored change-over
contact<, contact rating < 30 V DC/ max.2A
No dry contact cause of the integrated EMI protection.
Fire department operating panel : 8 digital inputs
8 outputs - max. 12 V DC / 20 mA per output
wire gauge , removable terminals
Internal primary loop :
monitored 10 k
Application e.g. for essernet
(normal) / 5 k (FIRE) / 1 k (fault)
®
-emergency operation
Compatibility : Part No.772479
Part No.772477
« Field device module without micro module slot
« Field device module with micro module slot
The IQ8Control FACP's relays may only be connected to DC voltages. No AC voltage may be
applied, not even when a relay is programmed as a >non-monitored change-over contact<!
FB 798951.GB0 / 01.09 57
Fire Alarm Control Panel IQ8Control C/M
4.4 Extension module
Depending on the module type up to three slots for micro modules are integrated on the Extension module.
Connections are available for each micro module. The pin assignment of the eight screw terminals depends on
the employed type of micro module. The pin assignment of the connectors is described for each micro module.
MM2
X11a
X12b
8
X 10
1
X3c
X2b
X1a
Extension module 772478
Fig.52: Extension module (Part No.772478) with one micro module slot
Extension module 772476
X 6
X 5
X 4
Place 1
Place 2
Place 3
X 22
12345678 12345678 12345678
Fig.53: Extension module (Part No.772476) with three micro module slots (only IQ8Control M)
V1
V2
Place 1Place 2Place 3
X 23X 24
58 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
IQ8Control C
The Field device module with a single micro module slot (Part No. 772478) must be placed on the >System
connector 1< of the Basic module. This connector is normally used by the Field device module. Without the field
device module a system configuration in accordance to the standards is not possible (refer to section „Panel
configuration IQ8Control C“).
IQ8Control M
Up to two connectors are available for Extension modules (Field device and or Extension module). Normally the
lower >connector 2< is used to connect an Extension module. If required the upper >connector 1< may be used
too for an Extension module. In this case the integration of an Field device module is impossible. In this case
mounting of the field device is not possible anymore (refer to section „Panel configuration IQ8Control C“).
Extension module with a single micro module slot (Part No. 772478)
This Extension module must be configured in the panels data programming as a Field device module.
X 1a/2b/3c
connector
>System connector 1 or 2< of the Basic modules
X11a/12b
X 10
Connector for a micro module
(Do not connect an essernet
®
micro module)
Terminals for the micro module wiring (refer to the I-text at the bottom)
Extension module with three micro module slots (Part No.772476)
Only FACP IQ8Control M configurable.
LED V1
LED V2
place 1
place 2
place 3
X22
X23
X24
X 4/5/6
ON – Common fire alarm
ON – CPU failure
Micro module slot only for micro module
Micro module slot only for micro module
Micro module slot only for micro module
terminal for micro module slot 1
terminal for micro module slot 2
terminal for micro module slot 3
Plug contact of
>System connector 1 or 2< of the Basic module
If an essernet
slot of the Basic module.
®
micro module is installed, this module can only be operated on the micro module
Refer to note!
Do not connect an
essernet
®
micro module,
Refer to note!
Refer to note!
4.4.1 Technical Data Extension module
Operating voltage : Internal via the power supply module, +5 V DC
Quiescent current : approx. 10 mA
: max. 1,5 mm
Compatibility : Part No.772478
Part No.772476
FB 798951.GB0 / 01.09 59
2
wire gauge, removable Terminals
Î Extension module with one micro module slot
Î Extension module with three micro module slots
Fire Alarm Control Panel IQ8Control C/M
Notes
60 FB 798951.GB0 / 01.09
Installation Instruction
Fire Alarm Control Panel IQ8Control C/M
Micro modules
The FACP IQ8Control C / M has a modular design, so that micro modules can be replaced/extended at any
time.
Only remove or insert micro modules when the FACP is voltage free.
Switch off the power and battery supply.
Wait at least 10 seconds before the micro modules are replaced or supplemented.
Take suitable measures to discharge static electricity.
Check correct installation (micro modules and connection cables).
Switch on the power and battery supply.
If necessary, check/supplement the customer data using the programming software tools
8000.
5.1 Analog loop modules
The following two analog loop modules are available for the Fire Alarm Control Panel IQ8Control C/M:
esserbus® analog loop module (Part No.784382 / 784382.10 / 784382.D0)
To connect fire detectors series 9200 and FACP esserbus® transponders. For the analog loop module operation
the power supply module (Part No.802426) must be configured with the appropriate jumper to 27,5V loop
voltage.
esserbus® PLus analog loop module (Part No.804382 / 804382.10 / 804382.D0)
Fire Alarm Control Panels IQ8Control C/M with esserbus® PLus are based on the standard esserbus®
functionality with the additional function to connect and power audible alarm devices directly to the analog loop.
For this operation of the analog loop module it is necessary to set the loop voltage of the Power supply module
(Part No.802426) with the appropriate jumper to 42 V
are supplied by the loop voltage and do not need an external power supply
Basic data on analog loop of esserbus® and esserbus® PLus
Less than 127 loop devices or 127 zone isolators per analog loop
Analog loop may be divided into 127 individual detector zones (customer data programming)
No more than 32 analog detectors per detector zone
Capability of combining loop and spur loop operation. No sub-spur branching!
Recommended type of cable for analog loop:
Use clearly identified communications cable I-Y (St) Y n x 2 x 0.8 mm or fire alarm cable!
Max. impedance of the analog loop incl. spur measured with respect to the load factor for IQ8Quad
detectors: max. 3500 m
For cable diameter with 0,8 mm and a max. Loop resistance of 130
1)
.
Max. 8 communications transponder per analog loop
max. 16 communications transponder per FACP
max. 8 Smoke aspirating systems LRS compact/eb or LaserFocus per analog loop
max. 16 Smoke aspirating systems LRS compact/eb or LaserFocus per FACP
max. 25 Smoke aspirating systems LRS 100 or LRS-S 700 per analog loop,
max. 50 per FACP (System software from Version V3.01 required).
max. 32 esserbus
max. 100 esserbus
OR
®
transponders per analog loop
®
transponders per FACP
max. 32 Smoke aspirating systems TITANUS PRO / TOP SENS
max. 100 Smoke aspirating systems per FACP.
1)
refer table chapter 5.1.3.
. The audible alarm devices connected to esserbus® PLus
.
(measured from terminal A+ to B+).
®
EB per analog loop.
Damage to the system!
It is only possible to operate the esserbus® PLus devices compatible with the higher loop
voltage (42 V DC). Mixed operation of Standard and esserbus
is not possible ! Loop devices compatible with esserbus
etc.) are identified by the Part No.
These 80xxxx devices are also fully compatible to the existing devices with Part No. 78xxxx
and may be used in standard esserbus
80xxxx.
®
installations.
®
®
PLus function within one panel
PLus (transponders, detectors MCP´s
62 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Mode of analog loop operation
The esserbus
®
/esserbus® PLus
The use of zone isolators allows you to combine ring and spur loops as well as divide the analog loop into 127
detector zones with a total of 127 loop devices. All esserbus
interruption (break in wire) in the analog loop. If a short circuit occurs, only the faulty element between two zone
isolators will be disconnected. Even during this malfunction all other loop devices remain operational.
On the esserbus
®
it is possible to group special fire detectors and manual call points or manual release devices
in separate detector zones. You may also simultaneously operate esserbus
zones on the analog loop. The esserbus
installed as loop devices on the esserbus
Commissioning a wired and functional analog loop requires use of the service PC and the software tools 8000
This Service software initiates an automatic wiring recognition function on the analog loop and addresses all
esserbus
®
loop devices automatically. There is no longer any need to set addresses manually. For further
information on programming, please refer the online help for the programming software tools 8000.
To indicate a data communication between FACP and detectors the corresponding LED on the basic module
flashes. The green LED of the IQ8Quad fire detector flashes each 30 seconds.
Operation of zone isolators
A short circuit on the analog loop will cause the cut-off relays to open in the relevant zone isolator and
disconnect the faulty segment (e.g., a detector zone) from the analog loop. The disconnected detectors will be
shown on the alphanumeric display with trouble message Com.trbl (communication trouble). All other loop
devices on the analog loop, as well as the fire detectors or esserbus
triggered, will remain operational. The zone isolators do not work on an open circuit, e.g. break in wire.
Bi-directional ring interrogation keeps all loop devices on the analog loop functional.
All Fire detectors series IQ8Quad provides an integrated loop isolator. For additional loop devices optional
isolators are available.
is a monitored two-wire loop fed from two sides and exhibiting loop topology.
®
loop devices remain functional in the event of
®
®
transponders are decentralised input/output modules capable of being
®
.
transponders in separate detector
®
transponders whose zone isolator has
Use of zone isolators
1. Always upstream of the point where the analog loop crosses into another fire compartment
2. On changing from special fire detectors to manual call points (and vice versa)
3. At least in the 32nd fire detector of a detector zone
Fire alarm systems in accordance to the German VdS-Guidelines (VdS Schadenverhütung
GmbH, Köln) must not be installed with more than 512 automatic fire alarm detectors per
panel.
In VdS approved systems, failure of a maximum of 32 detectors on the analog loop, e.g., a
detector zone, is permissible in the event of a trouble incident. A zone isolator must be installed
in at least the 32nd detector in a detector zone.
The analog loop module enables you to connect the analog loop - the esserbus®. The analog loop is configured
with Programming software tools 8000 from index V1.06R001.
Connect cable shielding of the analog loop only at one side.
When using the module in door control systems, place the enclosed labels on or in the FACP
housing (see chapter 11.1).
X 1
K1, K2
LED 1
LED 2
LED 3
LED 4
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
Released cable
terminal: Press
in upper tab and
fit cable below.
X 1/2 64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
K1,K 2 Bi-directional loop interrogation by loop isolators
(K1 = A+, A- / K2 = B+, B-)
LED 1 (SMD) red, flashing « +42V supply voltage failure or communication to
control panel processor interrupted
(SMD) red, lit
« Module in CPU failure mode
(control panel CPU failure)
LED 2 (SMD) yellow, flashing « Processor program running – normal mode
(SMD) yellow, flashing rapidly
LED 3 (SMD) red, lit « esserbus
« Module in test mode
®
PLus Mode activated
+42 V loop voltage
LED 4 (SMD) yellow, flashing « Module reset
(SMD) yellow, lit
« Module defect
LED 5 (SMD) red, flashing « in normal mode in time with communication on the loop
(SMD) red, lit
« Short circuit on analog loop
FB 798951.GB0 / 01.09 65
Fire Alarm Control Panel IQ8Control C/M
The esserbus® PLus cable is directly connected to the terminals on analog loop module (Part No. 804382 /
804382.10 / 804382.D0)
Example:
1
esserbus® PLus cable
terminal
module (Part No. 804382 /
804382.10 / 804382.D0)
The cable screen must be
connected to the mantle
terminal (panel housing)..
Fig. 58: esserbus® PLus cable terminal Analog loop module (Part No.804382 / 804382.10 / 804382.D0)
Requirements components for the esserbus
®
-PLus analog loop:
Part No Description
802426 Power supply module with selectable 27.5 V / 42 V analog loop voltage
27,5 V
or
42 V
« for esserbus
« for esserbus
®
®
PLus
Analog loop
804382 /
Analog loop module for esserbus® PLus connection.
804382.10 /
804382.D0
max. 4 analog loop modules per Fire Alarm Control Panel
It is only permitted to connect suitable devices for the higher loop voltage 42 V e.g.
Damage to the system !
esserbus® PLus must be installed with the appropriate loop devices. Mixed operation of standard
esserbus
loop voltage of 42 V. The loop devices compatible with esserbus
Part No.
1)
refer table chapter 5.1.3.
1)
transponders or fire detectors with Part No.
®
and esserbus® PLus with one control panel is not possible because the higher analog
80xxxx to the esserbus
®
PLus are indicated by the
®
PLus loop
80xxxx.
66 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
5.1.2.1 esserbus® PLus alarm devices
Available loop alarm devices for directly connection to the esserbus® PLus analog loop.
Part No. Name Load factor (LF)
Fire detector IQ8Quad
up to 700 m 91 to 96 91 to 96 91 to 96 91 to 96 X X
800 m 85 to 90 85 to 90 85 to 90 85 to 90 X X
1000 m 73 to 78 73 to 78 73 to 78 73 to 78 X X
1100 m 67 to 72 67 to 72 67 to 72 67 to 72 X X
1300 m 61 to 66 61 to 66 61 to 66 61 to 66 X X
1500 m 55 to 60 55 to 60 55 to 60 55 to 60 X X
1600 m 49 to 54 49 to 54 49 to 54 49 to 54 X X
up to 4 loops
IQ8Control M
2000 m 1 to 48 1 to 48 1 to 48 1 to 48 X X
up to 3500 m 0 0 0 0 X X
up to 700 m 46 to 48 46 to 48 46 to 48 46 to 48 46 to 48 46 to 48
800 m 40 to 45 40 to 45 40 to 45 40 to 45 40 to 45 40 to 45
1000 m 35 to 39 35 to 39 35 to 39 35 to 39 35 to 39 35 to 39
1100 m 34 to 36 34 to 36 34 to 36 34 to 36 34 to 36 34 to 36
1300 m 31 to 33 31 to 33 31 to 33 31 to 33 31 to 33 31 to 33
1500 m 28 to 30 28 to 30 28 to 30 28 to 30 28 to 30 28 to 30
1600 m 25 to 27 25 to 27 25 to 27 25 to 27 25 to 27 25 to 27
up to 6 loops
IQ8Control M
2000 m 1 to 24 1 to 24 1 to 24 1 to 24 1 to 24 1 to 24
up to 3500 m 0 0 0 0 0 0
68 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
5.2 essernet® module
The essernet® module permits networking up to 31 essernet® devices, such as e.g. Fire Alarm Control Panel
System 8000 and IQ8Control, Intruder alarm panel system 5000 and WINMAG supervisor system software.
Additionally optional gateways are available to connect standard devices to the network. Two essernet
module are available with a standard and high transmission rate.
Fire alarm control panel
IQ8Control M
Indicating and operating panel
Fire alarm control panel
IQ8Control M
Fire alarm control panel
IQ8Control C
®
micro
essernet
Intruder alarm panel 5008
Fig. 59: Example - essernet® network with different devices
Terminal card assignment
1
2
3
4
5
6
7
8
Fig. 60: Terminal card assignment
not used !
not used !
not used !
not used !
In a essernet
The EMI-protection / the extended EMI-protection of the LAN network must be implemented by
external EMI protection devices.
L1 +
L1 -
L2 +
L2 -
®
network you may only use essernet® modules with the same transmission speed.
The essernet® micro module must be placed on the micro module slot of the Basic module. There for it is
required to set the corresponding jumpers on the Basic module to configure the terminals for the essernet
Rotary address switch to select panel address factor x1
S2
X1
X4 / X5
LED
red
green
yellow
Rotary address switch to select panel address factor x10
64 pin connector for the micro module slot inside the FACP
jumpers for configuration of the terminals IN/OUT (terminal 1+2 and 3+4)
X4
X4
34
12
If data is transferred via fibre optic, two fibre optic fibre converters are always required for a data path
between the devices.
The documentation 798636 and 798963 contains more information about fibre optic converters.
Status and error indication
on - communication error between essernet® micro module and FACP
flashing - communication with other network devices
on - communication error (A/B mode)
All other LED display combinations mean that there is a fault in the essernet
measuring operation is active.
Connect cable shielding to the appropriate terminals !
The data signalling rate and connection cable to be used is governed by the module type
installed. In a network you may only use essernet® modules with the same data signalling rate.
78
56
unidirectional communication
copper cable
connected
fibre optics converter
terminal card
12 34
X5
X5
5678
fibre optic cable
connected
fibre optics converter
terminal card
®
module or that
FB 798951.GB0 / 01.09 71
Fire Alarm Control Panel IQ8Control C/M
5.2.2 Technical data essernet® micro module
essernet® micro module 62.5 k
(Part No. 784840 / 784840.10)
Operating voltage : Internal via the power supply module,
essernet
(Part No. 784841 / 784841.10)
Internal via the power supply module,
+ 5 V DC
Current consumption approx. 150 mA @ 12 V DC
Emergency operation : yes
®
Connector :
A single essernet
micro module may be connected per FACP on the appropriate
micro module slot on the Basic module.
Observe jumper X4 / X5!
max. 1,5 mm
Required cable Transmission speed 62.5 kBd
Telephone cable
I-Y (ST) Y n x 2 x 0.8 mm,
Cable length max. 1000 m.
Other cable types such as paperwrapped cables, control lines (NYM) or
smaller cross-sections are not suitable
transmission : Token-Passing protocol similar to DIN 19245 - 1 (Profi BUS)
Topology : loop topology (wire-breakage und short circuit tolerance)
®
Compatibility essernet
micro module 62.5 kBd (Part No. 784840) :
Do not operate hardware with index up to B2
B3 in a common panel.
with hardware from index
Important Note!
The essernet
®
micro modules are class A information devices (ITE) as per DIN EN 55022: 1999-05.
This device may cause radio interference in a residential environment. The user may be legally
obliged to take appropriate action in any case of interference. A residential area is defined as an area
in which the operation of broadcast radio or television receivers must to be anticipated in a range of
10 m from the device in question In this case the operator of the system is responsible for all action
needed.
72 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Setting the essernet® address
The address of Network Micro Modules type 1 and 2 with hardware revision E and higher is set as a decimal
number by means of two rotary switches. Use an appropriate screwdriver for setting switches
(x10). The actual address is represented by the total of both values.
Adressing example e.g. Panel, address 9 or 21
S1 (x1) and S2
address
9
21
0
2
S2
8
7
8
7
Schalterstellung Micro module
S1
0
1
9
9
2
3
4
6
5
0
1
9
2
8
3
7
4
6
5
0
1
9
6
5
1
2
3
4
0
1
9
2
8
3
7
4
6
5
Address factor
Value
Σ = S1 x 1 + S2 x 10
S1 = X 1
9 x 1 + 0 x 10 = 9
S2 = X 10
S1 = X 1
1 x 1 + 2 x 10 = 21
S2 = X 10
Jumper configuration for the essernet® micro module type
If an essernet® micro module is used in the micro module slot, the integrated EMC filter must be set with
jumpers
X27 to X30.
All jumpers in horizontal position
X27 X28
X29 X30
Required configuration for all micro modules apart from
essernet
®
(factory setting)
EMC protection for this micro module connection terminal is
activated
All jumpers in vertical position
X27
X28 X29 X30
Only required for essernet
The EMC protection is activated on the micro module for
essernet
®
and therefore switched off on the
basic module.
®
micro module.
EMC protection of the essernet
®
cabling has to be ensured by appropriate external devices.
FB 798951.GB0 / 01.09 73
Fire Alarm Control Panel IQ8Control C/M
Important installation instructions of essernet® micromodules
The outgoing and return line of the essernet® link must always be installed separately, i.e. not in a multiple-
pair cable or cable duct. Installing them together may impair operation or, in the event of irreparable damage
to the cable/cable duct, lead to failure of the connection because of a break in the outgoing and return line.
Different over voltage protection modules have been insert for the two essernet
Always avoid installing an essernet
®
line together with lines from the power supply, motor control lines,
phase control lines or other live switch cables. Observe corresponding standards and guidelines.
Possible fault causes
Breaks or twists in the essernet® connection line.
Damage to the LAN cable (for the essernet
®
micro module 500 kBd) as a result of inadmissible bending
radi.
The eight coding bridges incorrectly set for the essernet
®
micro module terminal card in the Fire Alarm
Control Panel
essernet
essernet
®
address incorrectly set on the DIL switch of the essernet® micro module (display: SYS fault
®
control panel: xx), red LED lights up on the essernet® micro module.
®
micro module types.
Line too long or attenuation too high. Typical loop resistances in relation to line length: IBM cable type 1
approx. 100 ohms/km, or telephone cable I-Y (ST) n x 2 x 0.8mm approx. 70 ohms/km.
The control panel or non-identified user is in failure mode or in the process of starting, e.g. after a reset.
Control panel or essernet
See chapter “the essernet
®
user dead or connection line open at both ends.
®
Diagnostic line”.
Fault messages
The messages are only shown after switching on the essernet® micro module and these indications will
remain until the module is re-started.
- incorrect address setting
- hardware failure
- test mode
The messages communication error, short circuit/open line, and normal operation are only shown while the
relevant state persists
EMC fine protection
When using the essernet® micro module attention should be paid to the setting of the jumpers
which is required for the essernet
®
adjustment.
The overvoltage protection/the extended EMC protection must be produced using special
protection modules for the LAN cable. See fire detection technology product group catalogue.
74 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
FOC converter (Part No. 784763 / 784764)
The FOC converter is used to convert electrical into optical signals for reliable data communication under
difficult conditions e.g. where conventional copper cables are not suitable. Mixed operation of fibre optical and
conventional wiring within a common network is possible. The mixed operation of Fibre optics cable (FOC) and
conventional copper cables within a common network is possible. For networking Fire Alarm Control Panels via
fibre optic cables, at least one FOC converter and an essernet
required. Depending on the optical cable type, the distance between two FACPs may be up to 3000 m. The
FOC converter is available with type F-ST (Part No. 784763) or type F-SMA (Part No. 784764) optical
connectors.
Installation
The FOC converter must be mounted inside the FACP housing or in the same control cabinet. It is mounted
directly on a standard 35 mm top hat rail (C mounting) (Part No. 788602 / 788652).
Requirements / limitations
two multi-mode fibres are required per network section
the fibres must be connected directly to each other (not via a multiplexer)
fibre optics type G50 / 125 µm Î max. attenuation 6dB corresponding to a length of ca. 2000 m or
fibre type G62.5 / 125 µm
max. 16 FOC connections per essernet
max. 31 connections per essernet
Îmax. attenuation 9dB corresponding to a length of ca. 3000 m
®
network at a transfer rate of 62.5 kBd
®
network at a transfer rate of 500 kBd
®
micro module from hardware revision E are
Fibre Optics Link
FOC
essernet
Fibre Optics Link
FOC
Fig. 63: Schematic wiring of an fibre optics cable
Please refer to the manual (Part No. 798636 and 798963) for detailed information about fibre optic
wirings.
FOC
®
FOC
FB 798951.GB0 / 01.09 75
Fire Alarm Control Panel IQ8Control C/M
6 Relay module
6.1 3-relay module / 3-relay common trouble module
Micro module for activating external devices (not potential free) such as a flashing lamp or siren, with monitoring
capability. You may connect up to three external devices to this micro module.
Relay assignment is programmed with the service PC and Programming software tools 8000 from version
V1.06R001 software. For each relay, you may enter a specific additional text comprising 25 characters per line
for output on the alphanumeric display and protocol printer.
Wi t h t h e 3 - r e l a y m o d u l e ( 7 8 7 5 3 2 ) , r e l a y K 1 i s c o n n e c t e d
a s c o m m o n t r o u b l e r e l a y , t h a t i s , i n t h e n o r m a l a c t i v a t e d .
123 4 5 6 7 8 9 1 0
12
N O
N C
N O
N C
F 5F 3
K 3
S 1
S 2
3 - r e l a y m o d u l e / 3 r e l a y c o m m o n t r o u b l e m o d u l e
L E D
Fig. 64: 3-relay module / 3-relay common trouble module
X 1
K1, K2, K3
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
K 1 (for 3-relay common trouble module type used as common trouble relay)
K 2 and K 3 freely programmable, max. contact rating 30 V DC /1 A
7 8 7 5 3 13 R Ü7 8 7 5 3 23 R Ü S
K 2
F 1
K 1
T E S T
X 1
S1, S2
TEST
LED
F1, F3, F5
coding switch for selecting monitored / non- monitored setting, or for special application
Test socket for in-factory adjustments only!
No indicator function (in-factory testing purposes)
Electronic fuse (multifuse): to reset, de-energise for approx. 30 seconds at the relevant screw
terminals on the terminal card
76 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Adjustment of the relays
Relay Status Contacts switch S 1 Contact
21
K 1
K 2
10 k monitored
not monitored
monitored
10 k
not monitored
closed
S 1
12
open
S 1
43
closed
S 1
34
open
S 1
65
closed
open
K3
monitored
10 k
not monitored
S 1
56
S 1
No AC voltages may be applied to the relays built-into the Fire Alarm Control Panel. This applies
also to those relays operated in the >non-monitored< mode.
The >monitored / non-monitored< mode for individual relays must be programmed in addition to the
setting on the micro module using the service PC.
FB 798951.GB0 / 01.09 77
Fire Alarm Control Panel IQ8Control C/M
Wiring an external signalling device without loop monitoring
Example with relay K2 (terminal 5 and 6), non-monitored mode
34
K 2
S 1
4
5
alarm
6
7
Fig. 65: Schematic wiring of an external signalling device without loop monitoring
D
1
+
relay
D
L
2
-
Fig. 66: Schematic wiring of inductive loads
L = inductive load
D
= series diode BY251 (notice relays current max. 2 A)
1
D
= recovery diode e.g. 1N4007 o.ä.
2
-
+
78 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
Connecting an external signalling device with loop monitoring
Monitored activation of external devices involves monitoring the loop for an end-of-line resistor of 10 k. In the
event of an incident, polarity changes between monitoring and activation voltage at the (relay) connection
terminals. The relay switches over from monitoring the loop to activating the external device, such as a
signalling device.
It is imperative to fit a protective diode (e.g. 1N4004 / 1A) in order to prevent the monitoring current, for
example, from activating external signalling devices while monitoring is in progress.
Example using relay K2 (terminal 5 and 6), monitored mode
34
K 2
S 1
4
5
+
monitoring
-
6
R
7
4
5
-
alarm
+
6
R
7
Fig. 67: Schematic wiring of an external signalling device with loop monitoring
Three relays with a common external voltage (default setting).
This application involves feeding an external voltage (e.g. +12V) to terminals 3 and 4 on the terminal card, this
voltage then being switched via the relay to the external device for activation in the event of an incident
occurring.
78910
S 1
S 2
S 1
12
NONCNO
NC
S 2
closed
n.o.
1
2
3
4
5
6
7
8
ext. device at relay K1
+
+
ext. voltage,e.g. +12
-
ext. device at relay K2
+
ext. device at relay K3
+
Fig. 68: Application examples (A)
Application examples (B)
Two relays with two differing external voltages
This application permits the switching of two different external voltages (e.g., +12V and +24V). This involves
relays K1 and K2 on the micro modules!
Relay K3 is not used!
78910
NC
open
n.c.
1
2
3
4
5
6
7
8
ext. device for relay K1
+
+
ext. Voltage for external device
at relay K1, e.g. +12 V
-
ext. device for relay K2
+
+
ext. Voltage for external device
at relay K1, e.g. +24 V
-
S 1
S 1
12
NONCNO
S 2
S 2
Fig. 69: Application examples (B)
80 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
6.2 4- Relay module
This micro module accommodates four freely programmable, non-monitorable, potential-free relays for
activating external devices and system components.
Relay assignment is programmed with the service PC and programming software tools 8000 from version
V1.06R001 software. For each relay, you may enter a specific additional text comprising 25 characters per line
for output on the alphanumeric display and protocol printer.
S 4S 3
K 4
Example of switch position
n.o.
NO contactNC contact
Fig. 70: 4- Relay module
X 1
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
Switch for setting the NC or NO contact function for each relay.
Electronic fuse (multifuse): to reset, de-energise for approx. 30 seconds at the relevant screw
terminals on the terminal card.
No AC voltages may be applied to the relays built-into the Fire Alarm Control Panel. This applies
also to those relays operated in the >non-monitored< mode.
FB 798951.GB0 / 01.09 81
Fire Alarm Control Panel IQ8Control C/M
Terminal card assignment
1
2
3
4
5
6
7
8
Fig. 71: Terminal card assignment
Schematic circuit diagram (example using relay K1)
ext. device at relay K1
ext. device at relay K2
ext. device at relay K3
ext. device at relay K4
Power supply
F1
S1
1
2
3
K1
Fig. 72: Schematic wiring
D
4
1
+
relay
D
L
2
-
Fig. 73: Schematic wiring of inductive loads
+-
-
+
L = inductive load
D
= series diode BY251 (notice relays current max. 2 A)
1
D
= recovery diode e.g. 1N4007 o.ä.
2
82 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
6.2.1 Technical Data Relay module
4-relay module (Part No. 787530)
Operating voltage : Internal via the power supply module, + 5 V DC / +12 V DC
Quiescent current : approx. 10 mA @ 12 V DC
Fuse (F1, F2, F3, F4) : Multifuse 1 A (for Relay K1 to K4)
Relay (K1, K2, K3, K4) : 4 programmable contacts - normally Open or normally close
(not monitored)
Contact rating : max. 30 V DC / 1 A per output
2
Terminals : max. 1,5mm
wire gauge, removable
3-relay module
(Part No. 787531)
Voltage : Internal via the power supply
module, + 5 V DC / +12 V DC
Quiescent current
: 5 mA@ 12 V DC 15 mA@ 12 V DC
3-relay common fault module
(Part No. 787532)
Internal via the power supply module,
+ 5 V DC / +12 V DC
consumption
Relay : 3 monitored, normally open or
normally close contacts
2 monitored, normally open or
normally close contacts plus a
common fault relay (energized in
normal operation)
Contact rating : max. 30 V DC / 1 A per output max. 30 V DC / 1 A per output
Fuse : Multifuse 1 A (per relay) Multifuse 1 A (per relay)
Terminals max. 1,5mm2 wire gauge, removable
Compatibility : The Relay modules may be operated on a free selectable micro module
slot of the FACP IQ8Control.
For System 8000 fire alarm control panels the relay module may be used
as a replacement devices.
Damage to the system!
No AC voltages may be applied to the relays built-into the FACP IQ8Control. This applies also
to those relays operated in the >non-monitored< mode!
Observe Schematic wiring of inductive loads!
FB 798951.GB0 / 01.09 83
Fire Alarm Control Panel IQ8Control C/M
Y
6.3 Serial interface module
6.3.1 RS 232 / TTY module
This module provides either a serial RS 232 or TTY interface (20mA) for exchanging data with external devices
connected.
Assignment of the serial interface type is programmed with the service PC and software tools 8000 from version
V1.06R001 software. You may enter a specific additional text comprising 25 characters per line for output on the
alphanumeric display and protocol printer.
RS 232 / TTY module
Fig. 74: RS 232 / TTY module
X 1
BR 3
BR 4
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
open – do not alter factory settings
Solder jumper for activating control LED D16 to D19. Factory setting (jumper = open)
should only be altered for testing the interface as a result of the higher level of current
required by the LED
BR 3
X1
BR 4
D 16
D 17
D 18
D 19
RxD
TxD
Tx
Rx
V24
TT
D 16, D 17
D 18, D 19
Control LED for data communication with RS 232 interface (observe BR 4)
Control LED for date communication with TTY interface (observe BR 4)
84 FB 798951.GB0 / 01.09
Assignment of terminal card RS232 module
Fire Alarm Control Panel IQ8Control C/M
external device
1
2
3
4
5
6
7
8
Fig. 75: Assignment of terminal card RS232 module
Assignment for terminal card TTY module
1
not used
TxD (transmitt)
RxD (receive)
not used
not used
not used
Data GND (potential free)
not used
Max. cable length for RS 232 is 15 m, recommended cable: I-Y (St) Y x 2 x 0.8mm
Tx -
transmitt
RxD
TxD
Data
GND
external device
Rx 2
3
4
5
6
7
8
Fig. 76: Assignment for terminal card TTY module
If solder jumper BR3 is closed on the module, TTY interface may not be used.
not used
not used
Tx +
transmitt
Rx +
not used
Rx +
receive
Tx +
not used
Rx -
Max. cable length for TTY is 1000 m, recommended cable: I-Y (St) Y x 2 x 0.8mm
receive
Tx -
FB 798951.GB0 / 01.09 85
Fire Alarm Control Panel IQ8Control C/M
6.3.2 Technical data interface modules
RS 232/TTY module (Part No. 784842)
Operating voltage : Internal via the power supply module, + 5 V DC / +12 V DC
Quiescent current : TTY-mode approx. 55 mA @ 12 V DC
RS232-mode approx. 35 mA @ 12 V DC
Interface type : TTY (20mA) or RS232
selectable in panels date configuration
Transmission speed : max. 19200 bit/s
2
Terminals : max. 1,5 mm
wire gauge, removable
Interface cable length : TTY
RS 232
Î max. 1000 m
Î max. 15 m
86 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
7 Master box activation module
Micro module for activating a master box (MFAB) and alerting the relevant emergency services, such as the fire
department. With the Fire Alarm Control Panel, a connection for a master box module is integrated in the Field
device module. If a Field device module is not fitted, an MFAB control module can be used for the connection of
a master box. Up to 10 MFAB may be operated within a common fire alarm system.
The required operation must be programmed with the service PC and Programming software tools 8000 from
version V1.06R001 software. For the MFAB relay, an individual additional text with 25 characters per line can be
entered for the clear text display and the protocol printer.
MFAB activation module
S 1
BR1 BR2 BR3 BR4 BR5 BR6
K 1
F 1
Fig. 77: Master box activation module
X1
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
K1
Relay for switching the MFAB supply voltage, e.g., +12 V or +24 V (DC)
max. contact rating max. 30 V DC / 1 A
F1
Electronic fuse (multifuse): to reset, de-energise for approx. 30 seconds at the relevant screw
terminals on the terminal card
X1
S 2
ON
1234
S1
S2
BR1, BR3
Setting the master box activation mode:
Switch set to left
Switch set to right
« Activation intermittent
« Activation continuous
DIL switch to select the activation time of the MFAB (see table next Page)
Hardware adjustment of MFAB activation (see following pages).
FB 798951.GB0 / 01.09 87
Fire Alarm Control Panel IQ8Control C/M
DIL switch S2
The time for the duration of the activation of the MFAB can be selected using DIL switch S2.
Selecting the activation time for the MFAB
ON
1234
activation for approx. 6 seconds
ON
1234
activation for approx. 2,5 seconds
ON
This selection only becomes active when
"intermittent activation"
is selected on switch S1!
1234
activation for approx. 1,5 seconds
ON
1234
activation for approx. 0,25 seconds
CPU failure mode function
Even when the Fire Alarm Control Panel is in the CPU failure mode the master box will still be activated in the
event of a fire alarm. It is not possible to reset the master box while the Fire Alarm Control Panel is in the CPU
failure mode!
Switching off the master box
The activation of the MFAB can be inhibited, for example for service or maintenance work, on the control panel
keyboard of the Fire Alarm Control Panel.
An automatic switch-off of activation can be programmed in the customer data. When the Fire Alarm Control
Panel is opened (cover contact), the master box will not be activated in the case of an event.
A switched off master box will not transmit an alarm message to assisting organisations (e.g. fire
department) in the case of an event.
88 FB 798951.GB0 / 01.09
Wiring of the terminal card
1
2
monitoring
3
4
F1
MFABrelay
5
6
7
8
Fire Alarm Control Panel IQ8Control C/M
+ MFAB
supply
voltage
not use
MFAB reset (+12 V or +24 V / 300 mA)
primary loop to MFAB (+MFAB)
GND
unlock fire department box (switched to GND max. 300 mA)
MFAB
acknowiedgment
MFAB
(schematic circuit diagram)
acknowiedgment
contact
+UBext.
+
K
FDKB
unlock
K
fire dept. key box
(schematic circuit diagram)
Fig. 78: Wiring of the terminal card
he signal to enable the fire service key box (FDKB) is activated when the master box acknowledge signal
T
(terminal 8 = MFAB acknowledge) from the Fire Alarm Control Panel is detected.
ptical displays of the master box
O
An activated master box can be identi
fied by a steadily lit red LED Main Detector (MFAB) on the control panel of
the Fire Alarm Control Panel. Intervening personnel such as the fire department have been notified.
it has been impossible to activate a master box due to an event, possibly because the MFAB was switched
If
off, this is indicated on the control panel by the steadily lit red LED Notify fire department.
FB 798951.GB0 / 01.09 89
Fire Alarm Control Panel IQ8Control C/M
Inhibiting MFAB activation
The master box or master box relay will not be activated if,
the cover contact (lock on outer hosing) is open. (factory setting of solder jumper on module: BR2 = open ;
BR3 = closed). The customer data of the Fire Alarm Control Panel must be programmed under menu point
Functional designation of the MFAB control module to suppress the activation of the master box when the
cover contact is open.
the operating panel keyboard has been enabled for operation (key-operated switch).
the master box is disconnected.
there is trouble with the master box.
Activation of the MFAB in dependency on the cover contact (BR2 and BR3)
The hardware adjustment of the activation of the master box is determined by the two solder bridges BR2 and
BR3 on the MFAB control module.
D
Factory setting Germany
BR2 = open The activation of the MFAB occurs in dependency on the customer data
BR3 = closed
Configuration for the Netherlands
BR2 = closed
BR3 = open
configuration
programming. If, for BR3 = closed example, activation has been suppressed in the
menu point Functional designation of the MFAB control module when the cover
contact is open, the master box will not be activated in the case of an event when
the cover contact is open.
NL
The activation of the MFAB occurs
programming. If, for example, activation has been suppressed in the menu point
Functional designation of the MFAB control module when the cover contact is
open, the master box will still be activated in the case of an event by hardware
when the cover contact is open.
independently of the customer data
90 FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
7.1 Technical Data Master box activation module (Part No. 784385)
Operating voltage : Internal via the power supply module, + 5 V DC / +12 V DC
Quiescent current consumption : approx. 10 mA @ 12 V DC (without monitoring)
or max. 127 loop devices, e.g. Fire detectors IQ8Quad,
series 9200, esserbus
®
-transponders and loop compatible
alarm devices, dividable in 127 individual zones
Quiescent current: approx. 25 mA.
Total current for loop devices max. 180 mA
12 345 6
A +
not used
A -
not used
B +
not used
B -
not used
B-B
78
B B +
A -
A +
not used!
A-A
+
+
78
Master box activation module (Part No. 784385)
To connect and control the MFAB operation.
Quiescent current: approx. 15 mA.
12 345 6
not used
MFAB reset (+12V oder +24V/300mA)
+MFAB supply voltage
PPrimary loop to MFAB (+MFAB)
GND
unlock fire dept. box (max. 300mA)
MFAB acknowiedgment
92 FB 798951.GB0 / 01.09
RS232 / TTY module (Part No. 784842)
Serial interface, alternatively RS232- or TTY
(20 mA) to connect external devices e.g. WINMAG,
Printers, Remote indicator panels etc.
Quiescent current: approx. 35 mA @i RS232 approx. 55 mA @i TTY
Fire Alarm Control Panel IQ8Control C/M
78
not used
TxD (transmitt)
RxD (receive)
not used
not used
not used
Data GND (potential free)
not used
12 345 6
3 Relay module (Part No. 787531)
Three bistable relay (monitoring possible) with
programmable operation mode normally open or normally
close.
Contact rating: max. 30 V DC / 1A
Quiescent current: approx. 5 mA
Tx - (transmitt)
Tx +
(transmitt)
Rx + (receive)
(receive)
Rx -
ext. device to relay K 1
ext. voltage e. g. +12 V
ext. device to relay K 2
ext. device to relay K 2
not used
not used
not used
not used
+
+
-
+
+
12 345 6
12 3 45 6
12 3 45 6
78
78
78
3 Relay common fault module (Part No. 787532)
Three bistable relay (monitoring possible) with
K 2
+
+
-
+
+
-
programmable operation mode normally open or normally
close and an additional common fault relay (energized in
normal mode).
Contact rating: max. 30 V DC / 1A
Quiescent current: approx. 15 mA
ext. device to relay K 1
ext. voltage for ext. device
to Relay K 1 e. g. +12 V
ext. device to relay
ext. voltage for ext. device
to Relay K 2 e. g. +24 V
FB 798951.GB0 / 01.09 93
Fire Alarm Control Panel IQ8Control C/M
4 Relay module (Part No. 787536)
Four dry relay contacts (not monitored) with programmable
operation mode normally open or normally close.
Contact rating: max. 30 V DC / 1A
The Commissioning / Maintenance as well as Operations and Fire Alarm Control Panel functions which should
only be performed by specialised installers or authorised persons are integrated under the menu options
>Installer< in the Fire Alarm Control Panel IQ8Control C/M. The service level is protected from unauthorised
access by a numeric authorisation code. This authorisation code is dependent on the >country function<
programmed in the customer data. Pressing the Installer function key moved from the service level to the
installer level. Before entry to the installer level, the authorisation code must be entered. (Exception
requirement of the authorisation code has been deleted by the programming of the Customer data). The
authorisation for operations in the Installer level remains active until the keyboard cover (key switch) is closed or
no keyboard operation is carried out in the installer level for more than ten minutes. During this period, access is
possible to the various display levels without further authorisation.
The menu options >Installer< is only displayed in the service level !
Indicated Display messages may differ due to object related programming.
A complete system check must be carried out after commissioning and for each modification of the
customer data programming!
Authorisation code (by factory default)
The authorisation code programmed at works level through the Country function can be changed individually in
the Customer data programming.
: The
Code: 123 for programmes Country functions for
(Germany, Great Britain, Switzerland and others)
20290 for programmed Country function for The Netherlands (NL)
--- for programmed Country function for Austria
(no works programmed authorisation code)
Accsess Installer level
Code: * * * *
EscapeDeleteSelect
Fig. 80: Entry of the authorisation code
Press the function key >Service< (The display changes to the service level)
Press the function key >Installer<
Enter the authorisation code (e.g. -123- for the Country function Germany on the keyboard)
Press function key >Select<
The Function menu of the installer level appears
Correcting an input error
An incorrect entry can be corrected with the >Delete< function key. Following the fourth incorrect entry, the
keyboard is blocked for approx. 60 seconds.
Installer code unknown
If the installer code is unknown or has been forgotten, it can be easily queried with the service PC. For this
purpose, the Customer data is obtained from the control panel by the tools 8000 software. The max. 8-digit
authorisation code is then displayed under menu options >Customer data - installer code< . Storage of the
Customer data which has only been queried to obtain the installer code is not necessary.
96FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
The function menu of the installer level appears with four menu points:
The function menu of the installer level with its four menu points appears after the successful entry of the
authorisation code:
Installer
1 Primary loop functions
2 Detector simulation
3 Control simulation
4 Printer function
EscapeEvent mem.Select
Fig. 81: Function menu
Pressing the
1. Primary loop function
Switching on/resetting a primary loop
Switching off a primary loop
Test operation of an analog loop
Detector replacement in an analog loop
Escape function key exits the installer level to the status display.
2. Detector simulation
Alarm simulation of a fire detector
Pre-alarm simulation of a fire detector
Trouble simulation of a fire detector
End test (simulation)
3. Control simulation
Activate simulation of a control (relay/open collector output)
Trouble simulation of a control (relay/open collector output)
End test (simulation)
4. Printer functions
Switching off the internal or external protocol printer
Switching on the internal or external protocol printer
Print out the event memory / repeat printout
Display event memory
FB 798951.GB0 / 01.09 97
Fire Alarm Control Panel IQ8Control C/M
8.1 Primary loop function
Primary loop function
Under this menu point, the internal primary loops of this Fire Alarm Control Panel or other Fire Alarm Control in
an essernet
possible to replace single detectors in operative analog loops e.g. during maintenance work.
Primary loops are:
all analog ring modules included in this FACP
(including the analog loop connected to this module with all bus devices)
all four-zone-modules included in this FACP
(including all detector zones and detectors connected to this module)
certain modules, such as relays or the interface on the basis/peripheral module
Connector and corresponding Primary loop number
Individual assemblies of the Panel can be switched on/off with the internal primary loop number through the
control panel keyboard or programmed with programming software. This internal primary loop number is
composed of the control panel number, the slot and the assembly number (ref to Chapter 3.4).
Primary loop / transfer route
Primary loop : 121
®
network can be switched on or off and checked by a manual test function. Additionally, it is
1 Switch on / reset
2 Switch off
3 Test
4 Replace detector
EscapeFunction
Fig. 82: Switching on / resetting a primary loop
N Enter the number of the primary loop to be switched on and press the Select function key
Enter the number of the desired function (1 = Switching on/reset) or select the menu options >Switching
on/Reset< with the cursor keys and press the >Function key<
The primary loop is switched on and indicated on the display with a alphanumeric message.
Switching off a primary loop
Enter the number of the primary loop to be switched off and press the Select function key
Enter the number of the desired function (2 = Switching off) or select the menu options >Switching off< with
the cursor keys and press the >Function< key
The primary loop is switched off and indicated on the display with a alphanumeric message. In the switched off
state of a primary loop, the yellow LED >Collective switch-off< lights in addition to the display message. The
displays and controls programmed in the Customer data of the Fire Alarm Control Panel for the function
Switch-off are activated.
When a primary loop is switched off, all detector zones and fire detectors connected to this module are
also switched off.
Switched off fire detectors will not signal an alarm in the case of an event !
98 FB 798951.GB0 / 01.09
8.2 Testing (the analog loop)
Fire Alarm Control Panel IQ8Control C/M
Primary loop / transfer route
Primary loop : 121
1 Switch on / reset
2 Switch off
3 Test
4 Replace detector
EscapeFunction
Fig. 83: Testing the analog loop
Enter the number of the analog loop to be tested and press the Select function key.
Enter the number of the desired function (3 = Testing) or select the menu options >Test operation< with the
cursor keys and press the >Function< key.
An analog loop in test operation will not signal an alarm in the case of an event!
The Function >Testing< is not carried out when ...
the analog loop module is defective.
the analog loop is switched off.
Testing an analog loop
The test operation must be carried out individually for each analog loop or detector zone. The simultaneous
testing of several analog loops/detector zones is impossible.
By this menu point, the selected analog loop (including all detectors and esserbus
detector zones in the analog loop are tested for the following functions:
Malfunctions of one or more detectors / esserbus
Malfunction of the switch-on control (SOC) by automatic detectors.
Conformance of the addresses with the Customer data programming
(if necessary, the detector data is automatically updated).
Conformance of the analog loop wiring with the Customer data programming.
Conformance of detector types and external wiring with the Customer data programming.
®
transponders.
®
transponders) or single
FB 798951.GB0 / 01.09 99
Fire Alarm Control Panel IQ8Control C/M
8.3 Detector replacement
Replacement of fire and diagnostic detectors (4-zone module)
Diagnostic fire detectors can be replaced without adjustment of the detector address on the base circuit board
or overwriting data with the service PC. The menu options >Detector replacement< is inoperable for these
detectors.
Replacement of intelligent detectors Series 9200 (Analog loop)
Any number of detectors series 9200 / IQ8Quad or esserbus® transponders in an analog loop can be replaced.
The replacement of detectors can be carried out in many cases without the service PC. (See table)
At the control panel
find out whether the replacement can be carried out
Enter the installer code, select primary loop function,
At the location
of the detector
Using the table on next page,
without the service PC.
yes
enter the primary loop number and
select function 2 "swich off"
no
connect service-PC and
carry out automatic wiring
analog ring loop.
Exchange all detectors which are to be replaced in the
analog ring loop. Screw the new detectors tightly into
the detector bases, do not damage connecting cables.
At the control panel
Enter the installation code, select primary loop
function, enter the primary loop number and select
On the primary loop all zones and the Primary loop
function 4 "replace detector".
are indicated on the display with "TEST"
Wait until the display "TEST"
for the primary loop go out.
Have malfunctions occurred?
no
yes
Which trouble code appears
see section 11 (detector malfunctions).
in the display ?
Is this malfuntion
due to the replacement
of detectors?
no
Check the execution of the
replacement and reactivate
Replace detector function.
yes
Switch the primary loop, detector
Replacement of detectors is completed.
zone or detector. Replacement
of detectors is completed.
Fig. 84: Flow diagram of detector replacement
100FB 798951.GB0 / 01.09
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.