Adherence to the following will aid in problem-free installation with long-term reliability:
Installation Precautions - Adherence to the following will aid in problem-free installation
with long-term reliability: WARNING - Several different sources of power can be connected
to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit
and associated equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt to install, service, or operate
this unit until manuals are read and understood. CAUTION - System Re-acceptance T est after
Software Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or change in site-specific
software. Re-acceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or wiring. All
components, circuits, system operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified. This
system meets NFP A requirements for operation wi thin the range of 0°C-49°C (32°F-120°F) or
humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful
life of the system's standby batteries and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it is recommended that this system
and its peripherals be installed in an environment with a normal room temperature of 15-27º
C/60-80º F. V erify that wir e sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged
when subjected to lightning induced transients. Although no system is completely immune
from lightning transients and interference, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical Services Department if any problems are
anticipated or encountered. Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits. Remove all electronic
assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible,
make all cable entries from the sides or rear. Before making modifications, verify that they
will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with screw terminal removal. Silent Knight
fire alarm control panels contain static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic assemblies removed from the
unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated equipment.
Installation Manual
FACP operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a
substitute for fire insurance! An automatic fire alarm system - typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm
control with remote notification capability - can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or loss of life
resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke
detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in
walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire
on another level or floor of a building. A second floor detector, for example, may not sense a
first floor or basement fire. Furthermore, all types of smoke detectors, including ionization
and photoelectric types, have sensing limitations. No type of smoke detector can sense every
kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical circuits, children
playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and
in rooms used by the system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are not so located, a developing fire
may damage the alarm system, crippling its ability to report a fire. Audible warning devices
such as bells may not alert people if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building. A fire alarm system will not
operate without any electrical power. If AC power fails, the system will operate from standby
batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist. Equipment used in the system
may not be technically compatible with the control. It is essential to use only equipment listed
for service with your control panel. Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All
devices and system wiring should be tested and maintained by professional fire alarm
installers following written procedures supplied with each device. System inspection and
testing should be scheduled monthly or as required by National and/or local fire codes.
Adequate written records of all inspections should be kept.
1.1Overview of Basic System ....................................................................................................................... 1-1
1.1.1 Hardware Features ............................ ................................................................................................ 1-1
1.1.2 Software Features ............................................................................................................................. 1-2
1.2About this Manual .................................................................................................................................... 1-2
1.2.1 Terms Used in this Manual ............................................................................................................... 1-2
2.2.1 Requirements for All Installations .................................................................................................... 2-2
2.2.2 Requirements for Central Station Fire Alarm Systems .................................................................... 2-3
2.2.3 Requirements for Local Protected Fire Alarm Systems ...................................................................2-3
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems - Digital Alarm Communicator
Transmitter (DACT) 2-3
Section 3
Before You Begin Installing ...............................................................................................3-1
3.1What’s in the Box? ................................................................................................................................... 3-1
4.15.3.1 Using the 5220 Module ........................................................................................................4-43
4.15.3.2 Using the 7644 Module ........................................................................................................4-44
4.15.4 Using the SD500-ARM Addressable Relay Module ...................................................................... 4-45
4.15.5 Using a MR-201/T Control Relay From Air Products ................................................................... 4-46
4.15.6 Transmitter Activated by Dry Contacts .......................................................................................... 4-47
Section 5
Hochiki and SK SLC Device Installation ...........................................................5-1
5.1List of SK SLC Devices ...........................................................................................................................5-1
5.2List of Hochiki SLC Devices ................................................................................................................... 5-2
5.3Maximum Number of Devices ................................................................................................................. 5-3
5.4Wiring Requirements for SLC Devices ..................................... .............................................................. 5-3
5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration ......................................................................... 5-3
5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration .................................................................. 5-5
5.5Wiring SK SLC Detectors ........................................................................................................................ 5-6
5.6Addressing SK SLC Devices ...................................................................................................................5-7
7.2SLC Family ..............................................................................................................................................7-2
Response with System-Wide Conditions ............................................................................. 7-16
7.5.2 Add Group ...................................................... ................................................................................ 7-17
7.5.3 Delete Group ...................................................................................................................................7-17
7.5.4 View Group Points .......................................................................................................................... 7-18
7.5.5 Edit Output Group Templates .........................................................................................................7-18
8.4Menu System ............................................................................................................................................8-3
8.4.1 Main Menu Overview ....................................................................................................................... 8-3
8.4.2 Using the Menus ............................... ................................................................................................ 8-4
8.5.1 Setting Time and Date ...................................................................................................................... 8-4
8.5.2 Disable / Enable a Point .................................................................................................................... 8-4
8.5.3 Disable / Enable NACs by Group .....................................................................................................8-4
8.5.4 View Event History ..................................... ... .................................................................................. 8-5
8.5.4.1 To clear the event history ....................................................................................................... 8-5
8.5.5 Conduct a Fire Drill .......................................................................................................................... 8-5
8.5.6 Conduct an Indicator Test .................................................................................................................8-5
8.5.7 Conduct a Walk Test ......................................................................................................................... 8-6
8.5.8 Conduct a Dialer Test ....................................................................................................................... 8-6
8.5.9 Silence alarms or troubles .................................................................................................................8-7
8.5.11 Check Detector Through Point Status ..............................................................................................8-7
8.5.12 View Status of a Point ..................................................... ................................................................. 8-8
8.5.13 View Alarms or Troubles ................................................................................................................. 8-8
8.5.14 View System Information .................................................................................................................8-8
10.2 Common Problems ................................................................................................................................. 10-1
10.2.2 Event History .................................................................................................................................. 10-3
10.3 Built-in Troubleshooting and Testing Tools ..........................................................................................10-4
10.3.2 SLC Multi Locator .......................................................................................................................... 10-5
10.3.3 I/O Point Control ............................................................................................................................ 10-6
Installation Records ....................................................................................................................11-1
11.1 SLC Point Record .................................................................................................................................. 11-1
11.2 Conventional Output Point Record ........................................................................................................11-8
Special Characters Lists .........................................................................................................B-1
B.1Characters used for Naming .....................................................................................................................B-1
Silent Knight Fire Product Warranty and Return Policy
1512097
IntelliKnight 5820XL Installation Manual
8151209
Section 1
Introduction
The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control
system that meets the requirements of UL 864.
1.1Overview of Basic System
The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit boards
mounted to an aluminum housing.
1.1.1Hardware Features
•The IntelliKnight 5820XL panel has one signaling line circuit (SLC). Up to three
additional SLC loops can be added using the 5815XL SLC expander. The SLC(s) support
the SK series addressable detectors and modules or Hochiki protocol detectors and
modules.
•Each SLC supports up to 99 detectors and 99 modules for a total of 396 detectors and 396
modules per 5820XL panel when using SK series devices. Alternatively, each SLC
supports up to 127 Hochiki devices for a total of 508 devices per 5820XL panel.
•6.0A of output power is available through 6 sets of terminals for notification and auxiliary
applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total
output power for all 6 circuits must not exceed 6.0A).
•Built-in dual phone line, digital alarm communicator/transmitter (DACT).
•Reports events to central station by point or by zone.
•UL Listed for pre-action and deluge releasing systems.
•Dedicated Form C trouble relay and two general purpose Form C programmable relays.
•Basic system operation can be performed using a key or a user code.
•Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).
•Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on
one control panel. See sections 4.8 and 4.9 for additional information on these models.
•Printing of detector status, event history, and real time event log available through the
Model 5824 Serial/Parallel Printer Interface Module (sold separately).
•Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.
•Add 6 Flexput™ circuits with each 5895XL Intelligent Power Module (up to 8 5895XLs
per system). See note below.
•Add 4 notification/auxiliary power circuits with each 5496 Intelligent Power Module. See
note below.
Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any
combination.
1512091-1
IntelliKnight 5820XL Installation Manual
1.1.2Software Features
•125 software zones, 250 output groups.
•Advanced smoke detector features:
Automatic drift compensation
Maintenance alert region
Point status eliminates calibrated smoke test requirements for NFPA 72
•“JumpStart” feature for easy programming
•Non-volatile event history stores 1000 events
•A choice of output patterns available for notification outputs, including ANSI 3.41
temporal signal
•Built-in synchronization appliance support for AMSECO, Faraday, Gentex
Sensor
®
, and Wheelock®.
1.2About this Manual
®
, System
This manual is intended to be a complete reference for all installation and operation tasks for
the 5820XL. Please let us know if the manual does not meet your needs in any way. We value
your feedback!
1.2.1Terms Used in this Manual
The following terminology is used with the IntelliKnight 5820XL system:
Table 1-1 Manual Terminology
TermDescription
SLCSignaling line circuit
ModuleThe term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the 5820XL
panel itself and the built-in 5897 power supply. It also ref ers to any
(optional) 5815XL SLC expansion modules.
Input PointAn addressable sensing device, such as a smoke or heat detector or a contact
monitor device.
Input ZoneA protected area made up of input points.
Output Point
(or Output Circuit)
Group (or “Output Group”)A group of output points. Operating characteristics are common to all
Output (or “Cadence”) PatternThe pattern that the output will use, for example, Constant, March Code,
MappingMapping is the process of specifying which outputs are activated when
A notification point or circuit for notification appliances. Relay circuits and
auxiliary power circuits are also considered output points.
output points in the group.
ANSI 3.41. Applies to zones and special system events. See Section 7.7.3.2
for additional information.
certain events occur in the system. Section 6.2 explains mapping in detail.
1-2151209
Introduction
1.3Compatible Products
Table 1-2 lists the products available from Silent Knight for use with the IntelliKnight
5820XL.
Table 1-2: 5820XL Compatible Products
Ty pe of
Device
Addressable
SLC Devices
Other
Modules
Misc.7860 Telephone CordRJ31X cord for connecting phone line to the 5820XL.
See Section 5.2 for a list of compatible devices.
5815XL SLC ExpanderAllows an additional 127 Hochiki SLC devices, or 99 SK detectors and 99 SK modules
5211 Ground Start RelayFor use with ground start telephone network. (Do not use in UL installations.)
5824 Serial/Parallel Printer
Interface Module
5895XL Intelligent Power
Module
5496 Intelligent Power
Module
5860 and 5860R Remote Fire
Alarm Annunciator
5860TG and 5860TR Trim
Ring Kit
5865-3 and 5865-4 LED
Annunciator
5880 LED I/O ModuleDriver for up to 40 LEDs. Interfaces with customized
5883 General Purpose Relay
Module
5660 Silent Knight Software
Suite (SKSS)
5670 Silent Knight Software
Suite (SKSS)
RBBRemote Battery Box for mounting backup batteries that are too large to fit into the main
ModelDescription
to be added to the system. Up to three 5815XLs per system.
Allows a printer to be attached for the system for on-site event logging, detector status
and event history reports. Two maximum per system.
Provides additional power, six Flexput™ circuits, and two
Form C relays. Max. 8 per system see Model 5895 Installation Instructions P/N 151024.
Provides 4 additional Notification Appliance Circuits/
Auxiliary power. (Up to 8 per system.)
Same operation, similar appearance as on-board
annunciator. Up to 8 5860s per system. 5860 is gray; 5860R
is red.
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray; 5860TR is
red.
LED annunciator can display up to 30 LEDs (15 red and 15
yellow). 5865-4 has key switches for silence and reset, and
a system trouble LED.
annunciator boards. In addition the 5880 has eight generic
switch input points.
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be
used with each 5880 module.
For communication and panel programming with a Windows-based computer and
*modem (not sold by Silent Knight, see Table 1-3 for compatible modems). Enables
remote viewing of detector status and event history.
Facility management software. For remote viewing of detector status and event history.
Requires a modem (not sold by Silent Knight).
control panel cabinet.
Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
5895XLs and 5496s can be
used in any combination,
up to a total of eight
devices on one system.
5865-3, 5865-4, and 5880
can be used in any
combination, up to a total
of eight devices on one
panel.
Note: Models SD500-FRCM, and SD500-FRCM-4 are no longer manufactured, but they are still compatible with
the IntelliKnight system. Contact Silent Knight if you need information about these modules.
1512091-3
IntelliKnight 5820XL Installation Manual
The following modems have been tested by Silent Knight for compatibility with the 5820XL
and the Silent Knight Software Suite software packages:
Table 1-3: Compatible Modems
ManufacturerModel
US Robotics28.8
LifeStyle
Motorola
MultiTechMT19321ZDX
28.8, 3400 series
Premier 33.6
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent
Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Customer Service at 800-328-0103 or in Connecticut
203-484-7161.
IntelliKnight® is a registered trademarks of Silent Knight. Flexput™ is a trademark of Silent
Knight.
1-4151209
Introduction
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected
premise following the recommendations of the current edition of the National Fire Protection
Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes,
and the recommendations contained in Guide for the Proper Use of System Smoke Detectors,
which is made available at no charge to all installing dealers. A study by the Federal
Emergency Management Agency (an agency of the United States government) indicated that
smoke detectors may not go off or give early warning in as many as 35% of all fires. While
fire alarm systems are designed to provide warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons. For example:
•Particles of combustion or smoke from a developing fire may not reach the sensing
chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or
smoke flow.
Smoke particles may become cold, stratify , and not reach the ceiling or upper walls where
detectors are located.
Smoke particles may be blown away from detectors by air outlets
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires
developing on another level.
•The amount of smoke present may be insufficient to alarm smoke detectors. Smoke
detectors are designed to alarm at various levels of smoke density. If such density levels
are not created by a developing fire at the location of detectors, the detectors will not go
into alarm.
•Smoke detectors, even when working properly, have sensing limitations. Detectors that
have photoelectronic sensing chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers
tend to detect fast flaming fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide adequate warning of a fire.
•Smoke detectors are subject to false alarms and nuisance alarms and may have been
disconnected by users. For example, a smoke detector located in or near a kitchen may go
into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or
steamy environments may cause a smoke detector to falsely alarm. If the location of a
smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect
the smoke detector; call a professional to analyze the situation and recommend a solution.
•Smoke detectors cannot be expected to provide adequate warning of fires caused by arson,
children playing with matches (especially within bedrooms), smoking in bed, violent
explosions (caused by escaping gas, improper storage of flammable materials, etc.).
1512091-5
IntelliKnight 5820XL Installation Manual
•Heat detectors do not sense particles of combustion and are designed to alarm only when
heat on their sensors increases at a predetermined rate or reaches a predetermined level.
Heat detectors are designed to protect property, not life.
•Warning devices (including horns, sirens, and bells) may not alert people or wake up
sleepers who are located on the other side of closed or partially open doors. A warning
device that activates on a different floor or level of a dwelling or structure is less likely to
awaken or alert people. Even persons who are awake may not notice the warning if the
alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by
passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or
other devices should be provided to warn these people). Any warning device may fail to
alert people with a disability, deep sleepers, people who have recently used alcohol or
drugs, or people on medication or sleeping pills.
Please note that:
i)Strobes can, under certain circumstances, cause seizures in people with conditions
such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not
respond or comprehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercises to make people aware of fire
alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent
hearing loss.
•Telephone lines needed to transmit alarm signals from a premises to a central station may
be out of service or temporarily out of service. For added protection against telephone line
failure, backup radio transmission systems are recommended.
•System components, though designed to last many years, can fail at any time. As a
precautionary measure, it is recommended that smoke detectors be checked, maintained,
and replaced per manufacturer’s recommendations.
•System components will not work without electrical power. If system batteries are not
serviced or replaced regularly , they may not provide battery backup when AC power fails.
•Environments with high air velocity or that are dusty or dirty require more frequent
maintenance.
In general, fire alarm systems and devices will not work without power and will not function
properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate,
an alarm system is not a substitute for insurance.
Property owners should continue to act
prudently in protecting the premises and the people in their premises and should properly
insure life and property and buy sufficient amounts of liability insurance to meet their needs.
1-6151209
Introduction
Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection
equipment in all rooms and areas of the house or building in accordance with the requirements
and recommendations of the current edition of the National Fire Protection Association
Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations,
State and local codes and the recommendations contained in Guide for the Proper Use of
System Smoke Detectors, which is made available at no charge to all installing dealers. For
specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for
fire protection systems.
Requirements and Recommendations include:
•Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing construction.
•It is recommended that more than one smoke detector shall be installed in a hallway if it is
more than 30 feet long.
•It is recommended that there shall never be less then two smoke detectors per apartment or
residence.
•It is recommended that smoke detectors be located in any room where an alarm control is
located, or in any room where alarm control connections to an AC source or phone lines
are made. If detectors are not so located, a fire within the room could prevent the control
from reporting a fire.
•All fire alarm systems require notification devices, including sirens, bells, horns, and/or
strobes. In residential applications, each automatic alarm initiating device when activated
shall cause the operation of an alarm notification device that shall be clearly audible in all
bedrooms over ambient or background noise levels (at least 15dB above noise) with all
intervening doors closed.
•It is recommended that a smoke detector with an integral sounder (smoke alarm) be
located in every bedroom and an additional notification device be located on each level of
a residence.
•To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards. At a
minimum the requirements of Chapter 7 of NFPA 72 shall be followed. A maintenance
agreement should be arranged through the local manufacturer’s representative.
Maintenance should be performed annually by authorized personnel only.
•The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to make sure
all sensors and transmitters are working properly.
1512091-7
IntelliKnight 5820XL Installation Manual
1-8151209
Section 2
Agency Listings, Approvals, and Requirements
2.1Federal Communications Commission (FCC)
1. The following information must be provided to the telephone company before the
IntelliKnight 5820XL can be connected to the phone lines:
Ringer equivalence:0.8B
DType of jack:RJ31X
EFacility Interface Codes:Loop Start: 02LS2
Ground Start: 02GS2
FService Order Code:9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted by
ACTA. On the inside cover of this equipment is a label that contains, among other
information, a product identifier. If requested, this information must be provided to the
telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network
must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA.
A compliant telephone cord (not provided) and modular jack must be utilized with this
product. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine
the number of devices that may be connected to the public switched telephone network. This
number must not exceed 5.0. Since this product has an REN of 1.0, the number of devices is
limited. The REN number is imbedded in the FCC registration number as 10B.
If the 5820XL causes harm to the telephone network, the telephone company will notify you
in advance that the temporarily discontinuance of service may be required. But if advance
notice is not practical, the telephone company will notify the customer as soon as possible.
Also, you will be advised of your right to file a complaint with the FCC if you believe it is
necessary.
The telephone company may make changes in its facilities, equipment, operations or
procedures that could affect the operation of the equipment. If this happens the telephone
company will provide advance notice in order for you to make necessary modifications to
maintain uninterrupted service.
If trouble is experienced with the 5820XL, for repair or warranty information, please contact
Silent Knight at 1-800-328-0103 or www.silentknight.com. If the equipment is causing harm
to the telephone network, the telephone company may request that you disconnect the
5820XL until the problem has been resolved.
1512092-1
IntelliKnight 5820XL Installation Manual
This product cannot be adjusted or repaired in the field. It must be returned to the factory for
service.
This equipment is not designed for use with party line service. Connection to party line
service is subject to state tariffs. You may contact the state public utility commission, public
service commission or corporation commission for information.
Since the 5820XL is a commercial fire alarm panel, it must be connected upstream of all other
equipment utilizing the phone lines. If you have questions about the installation, contact your
telephone company or a qualified installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions:
(1) This device may not cause radio interference, and (2) This device must accept any interference received,
including interference that may cause undesired operation.
2.2Underwriters Laboratories (UL)
2.2.1Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer
to the specific section of the manual for additional requirements. The following subsections
list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 8.7 for
information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 5.2 of this manual and or conventional detectors listed in the compatibility chart. (See Appendix A.)
3. Use UL listed notification appliances compatible with the 5820XL from those specified in
the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
2-2151209
Agency Listings, Approvals, and Requirements
Restricted Options:
•The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 30 hours. For UL certified installations this number must be set from 1 to 3 hours.
•The system allows the use of non-latching spot type smoke detectors. This feature may not
be used in commercial applications whereby a general alarm is sounded. It is intended for
elevator recall, door holding applications, and hotel/motel room applications.
•The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL
certified installations the setting must be a minimum of 60 seconds.
•Call forwarding shall not be used.
•When two count is used detector spacing shall be cut in half, you shall not use the alarm
verification feature, and no delay shall be used.
•P.A.S feature shall be used only with automatic detectors.
2.2.2Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. Y ou must program a phone number and a test time so that the 5820XL sends an automatic
daily test to the central station.
3. Do not use the ground start option.
4. The AC Loss Hours option must be set from 1-3 hours.
5. The Attempts to Report option must be set for 5.
2.2.3Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4Requirements for Remote Station Protected Fire
Alarm Systems - Digital Alarm Communicator
Transmitter (DACT)
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 15-30 hours.
1512092-3
IntelliKnight 5820XL Installation Manual
2-4151209
Section 3
Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth
installation. Please read this section thoroughly, especially if you are installing a 5820XL
panel for the first time.
3.1What’s in the Box?
The IntelliKnight 5820XL ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Two keys for user operation of the on-board annunciator (installer operations require the
Installer’s Code)
•Ten 4.7K ohm end-of-line resistors
•A battery cable for batteries wired in series
3.2Environmental Specifications
It is important to protect the 5820XL control panel from water. To prevent water damage, the
following conditions should be AVOIDED when installing the units:
•Intended for indoor use in dry locations only
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the 5820XL control panel, the unit should be mounted
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity not exceeding 93% noncondensing.
4X
5O100 mA for initiation circuits
6X
7O100 mA for initiation circuits
8X
9O100 mA for initiation circuits
10X
11O100 mA for initiation circuits
12X
13O100 mA for initiation circuits
14X
15O100 mA for initiation circuits
16B
17A
18+
1920B
21A
22+
2324N.C.
26N.O.
27N.C.
29N.O.
30N.C.
32N.O.
33SC-L1
34SC+
35SC-L2
36SC+
*I/O 6Flexput™ Circuits24 VDC
*I/O 5Flexput™ Circuits24 VDC
*I/O 4Flexput™ Circuits24 VDC
*I/O 3Flexput™ Circuits24 VDC
*I/O 2Flexput™ Circuits24 VDC
*I/O 1Flexput™ Circuits24 VDC
SBUS communication5 VDC100 mA
SBUS OUT
SBUS power24 VDC1.0 A
SBUS INUsed for Class A installations0Ω
RELAY 2General Purpose Relay 224 VDC2.5 A, resistiveN/A25C
RELAY 1General Purpose Relay 124 VDC2.5 A, resistiveN/A28C
TROUBLE Trouble Relay24 VDC2.5 A, resistiveN/A31C
SLC OUT
SLC IN
SLC terminals32 VDC150 mA0Ω
Used for Class A installations0Ω
VoltageCurrent
Rating
3.0 Amp Notification and
Aux power Circuits
3.0 Amp Notification and
Aux power Circuits
3.0 Amp Notification and
Aux power Circuits
3.0 Amp Notification and
Aux power Circuits
3.0 Amp Notification and
Aux power Circuits
3.0 Amp Notification and
Aux power Circuits
Earth Ground
Faults
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
*Regulated/Special application when used for releasing.
3-2151209
Before You Begin Installing
Terminal # and LabelDescription
37RingPhone Line 1 Telco Ring
38TipPhone Line 1 Telco Tip
39RingPhone Line 1 Premises Ring
40TipPhone Line 1 Premises Tip
41RingPhone Line 2 Telco Ring
42TipPhone Line 2 Telco Tip
43RingPhone Line 2 Premises Ring
44TipPhone Line 2 Premises Tip
45SC-SLC Programming Terminal ( - ) 32 VDC150 mA
46SC+SLC Programming Te rminal ( + ) 32 VDC150 mA
VoltageCurrent
N/A0Ω
N/A0Ω
Rating
3.4Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with
telephone communication or cause false alarms. To avoid induced noise, follow these
guidelines:
•Isolate input wiring from high current output and power wiring. Do not pull one multiconductor cable for the entire panel. Instead, separate the wiring as follows:
Earth Ground
Faults
0Ω
High voltageAC power, Terminals 1-3
SLC loopsTerminals 33-36
Audio input/output Phone line circuits, Terminals
•Do not pull wires from different groups through the same conduit. If you must run them
together, do so for as short a distance as possible or use shielded cable. Connect the shield
to earth ground at the panel. You must route high and low voltages separately.
•Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit
board where it could induce noise into the sensitive microelectronics or pick up unwanted
RF noise from the high speed circuits. See Figure 3-1 for an example.
•High frequency noise, such as that produced by the inductive reactance of a speaker or
bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it
around a ferrite toroid.
1512093-3
IntelliKnight 5820XL Installation Manual
Figure 3-1 Wire Routing Example
3-4151209
3.5Board Assembly Diagram
Ground Start
Relay Socket
Chassis
Mounting
Nuts
Chassis
Mounting
Nuts
To ACOn-board Annunciator
Key Switch
Input
Programming
Ports
Before You Begin Installing
Figure 3-2 Model 5820XL Assembly
Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL
assembly to the cabinet. If you should need to remove the board assembly for repair, remove
the four mounting nuts which hold the assembly in the cabinet. Then lift the entire assembly
out of the cabinet. Do not attempt to remove the circuit boards from the metal bracket.
1512093-5
IntelliKnight 5820XL Installation Manual
3.6Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs for your
installation.
3.6.1Current Draw Worksheet Requirements
The following steps must be taken when determining 5820XL current draw and standby
battery requirements.
1. You will use the Current Draw Worksheet to determine current draw and standby battery
requirements. Use Table 3-1 if installing SK SLC Devices and Table 3-2 if installing
Hochiki SLC Devices. For the 5820XL, the worst case current draw is listed for the panel,
addressable devices, and all SBUS expanders. Fill in the number of addressable devices
and expanders that will be used in the system and compute the current draw requirements
for alarm and standby. Record this information in the Current Draw Wo rkshe et on Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the
device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself,
does not exceed 6.0 A. This is the maximum alarm current for the 5820XL control panel.
If the current is above 6.0 A you will need to use a notification power expander(s) such as
the Silent Knight 5495 or the 5895XL intelligent power expander, to distribute the power
loads so that the 5820XL or the power expanders do not exceed their power rating. Refer
to the current draw worksheets provided with the 5495 or the 5895XL manuals so you do
not exceed their power requirements.
6. Complete the remaining instructions in the appropriate Current Draw Worksheet for determining battery size requirements.
3-6151209
Loading...
+ 198 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.