Honeywell HVAC232-2P2-20, HVAC232-1P1-20, HVAC232-1P5-20, HVAC232-P55-20, HVAC232-P37-20 Applications Manual

...
HVAC232/402
APPLICATION MANUAL
27 652 _ENG 0 6
Content
0 DOCUMENT HYSTORY .............................................................................................................................. 5
1 SAFETY ............................................................................................................................................................ 6
1.1 Warnings ...............................................................................................................................................................................................................................................................7
1.2 Safety instructions............................................................................................................................................................................................................................................8
1.3 Earthing and earth fault protection ......................................................................................................................................................................................................... 9
1.4 Before running the motor .............................................................................................................................................................................................................................10
2.1 Storage ................................................................................................................................................................................................................................................................... 10
2.2 Maintenance .......................................................................................................................................................................................................................................................10
2.3 Warranty .................................................................................................................................................................................................................................................................11
3.1 Mechanical installation ................................................................................................................................................................................................................................. 11
3.2 HVAC232/402 dimensions  ........................................................................................................................................................................................................................14
3.3 Cooling ...................................................................................................................................................................................................................................................................17
3.4 Power losses ........................................................................................................................................................................................................................................................18
3.5 EMC levels ............................................................................................................................................................................................................................................................ 21
3.6 Changing the EMC protection class from C2 to C4 ........................................................................................................................................................................22
3.7 Cabling and connections .............................................................................................................................................................................................................................. 23
3.8 Screw of cables ...................................................................................................................................................................................................................................................28
3.9 Stripping lengths of motor and mains cables .................................................................................................................................................................................... 31
3.10 Cable installation .............................................................................................................................................................................................................................................. 32
3.11 Cable and motor insulation checks ......................................................................................................................................................................................................... 32
4 COMMISSIONING AND
STARTUP WIZARD ..................................................................................................................................... 32
4.1 Commissioning steps of HVAC232/402 ..............................................................................................................................................................................................32
4.2 Startup Wizard .................................................................................................................................................................................................................................................... 34
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 2
6.1 Introduction ......................................................................................................................................................................................................................................................... 41
6.2 Control I/O ............................................................................................................................................................................................................................................................ 42
7.1 General ................................................................................................................................................................................................................................................................... 44
7.2 Display .................................................................................................................................................................................................................................................................... 44
7.3 Keypad .................................................................................................................................................................................................................................................................... 46
8.1 Main menu ...........................................................................................................................................................................................................................................................47
8.2 Reference menu .................................................................................................................................................................................................................................................49
8.3 Monitoring menu .............................................................................................................................................................................................................................................. 50
8.4 Parameter menu ................................................................................................................................................................................................................................................ 53
8.5 System menu .......................................................................................................................................................................................................................................................54
9.1 Quick setup parameters (Virtual menu, shows when par. 16.2  1) ................................................................................................................................... 56
9.2 Easy usage menu (Control panel: Menu PAR  P16).................................................................................................................................................................89
9.3
Fire mode (Control panel: Menu PAR
P18) ............................................................................................................................................................................................... 90
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 3
10.1 Motor settings (Control panel: Menu PAR  P1) .......................................................................................................................................................................... 96
10.2 Start / stop setup (Control panel: Menu PAR  P2) .................................................................................................................................................................... 101
10.3 Frequency references (Control panel: Menu PAR  P3) ........................................................................................................................................................... 112
10.4 Ramps & brakes setup (Control panel: Menu PAR  P4) ......................................................................................................................................................... 114
10.5 Digital inputs (Control panel: Menu PAR  P5) .............................................................................................................................................................................117
10.6 Analogue inputs (Control panel: Menu PAR  P6) ...................................................................................................................................................................... 118
10.7 Digital outputs (Control panel: Menu PAR  P7) .........................................................................................................................................................................119
10.8 Analogue outputs (Control panel: Menu PAR  P8) ...................................................................................................................................................................120
10.9 Fieldbus DataMapping (Control panel: Menu PAR  P9) ...................................................................................................................................................... 120
10.10 Prohibited Frequencies (Control panel: Menu PAR  P10) ....................................................................................................................................................121
10.11 Protections (Control panel: Menu Par  P12) ...............................................................................................................................................................................122
10.12 Automatic reset (Control panel: Menu PAR  P13) .....................................................................................................................................................................127
10.13 PID control parameters (Control panel: Menu PAR  P14).....................................................................................................................................................128
10.14 Application setting (Control panel: Menu PAR  P15) .............................................................................................................................................................. 130
10.15 Application setting (Control panel: Menu PAR  P16) .............................................................................................................................................................. 131
10.16 System parameter  ............................................................................................................................................................................................................................................132
10.17 Modbus RTU  .......................................................................................................................................................................................................................................................133
10.18 Termination resistor  ........................................................................................................................................................................................................................................ 134
10.19 Modbus address area  ....................................................................................................................................................................................................................................134
10.20 Modbus process data  .................................................................................................................................................................................................................................... 134
11 Technical data ............................................................................................................................................... 138
11.1 HVAC232/402 technical data .................................................................................................................................................................................................................... 138
12 PART NUMBERS, POWER RATINGS, SIZE, AND WEIGHT ............................................................. 141
12.1 Part Number Options ...................................................................................................................................................................................................................................... 141
12.2 Low overload ........................................................................................................................................................................................................................................................142
12.3 High overload ...................................................................................................................................................................................................................................................... 142
12.4 HVAC232/402 – Mains voltage 208240 V ........................................................................................................................................................................................ 143
13 ACCESSORIES .............................................................................................................................................. 145
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 4

0 DOCUMENT HYSTORY

Version Date Modifications
ENG06 20190807 Table 54 : Modbus: Input process data: ID2003
new Name "Frequency reference" and new Type "0…10'000"
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 5

1 SAFETY

Please read the information included in cautions and warnings carefully:
CAUTION
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY OUT THE ELECTRICAL INSTALLATION!
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 6

1.1 Warnings

WARNING
The components of the power unit of the frequency converter are live when HVAC232/402 is connected to mains. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The control unit is isolated from the mains potential.
WARNING
The motor terminals U, V, W (T1, T2, T3) and the possible brake resistor terminals / + are live when HVAC232/402 is connected to mains, even if the motor is not running.
WARNING
The control I/O-terminals are isolated from the mains potential. However, the relay output terminals may have a dangerous control voltage present even when HVAC232/402 is disconnected from mains.
WARNING
If the frequency converter is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a main switch (EN 602041).
WARNING
If HVAC232/402 is disconnected from mains while running the motor, it remains live if the motor is energized by the process. In this case the motor functions as a generator feeding energy to the frequency converter.
WARNING
After disconnecting the frequency converter from the mains, wait until the fan stops and the indicators on the display go out. Wait 5 more minutes before doing any work on HVAC232/402 connections.
WARNING
The earth leakage current of HVAC232/402 frequency converters exceeds 3.5 mA AC. According to standard EN61800 51, a reinforced protective ground connection must be ensured.
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 7
WARNING
The motor can start automatically after a fault situation, if the autoreset function has been activated.

1.2 Safety instructions

CAUTION
The HVAC232/402 frequency converter has been designed for fixed installations only.
CAUTION
Do not perform any measurements when the frequency converter is connected to the mains.
CAUTION
Do not perform any voltage withstand tests on any part of HVAC232/4 02. The product safety is fully tested at factory.
CAUTION
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the frequency converter.
CAUTION
Do not open the cover of HVAC232/402. Static voltage discharge from your fingers may damage the components. Opening the cover may also damage the device. If the cover of HVAC232/402 is opened, warranty becomes void.
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 8

1.3 Earthing and earth fault protection

MCR36497
MCR36498
The Smart HVAC232/402 frequency converter must always be earthed with an earthing conductor connected to the earthing terminal. See figure below:
MCR36496
Fig. 2. MI4
Fig. 1. MI1 - MI3
Fig. 3. MI5
1. The earth fault protection inside the frequency converter protects only the converter itself against earth faults.
2. If residual current devices are used they must be tested with the drive with earth fault currents that are possible to arise in fault situations.
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 9

1.4 Before running the motor

2.2 Maintenance

Checklist:

Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.

Set the maximum motor speed(frequency) according to the motor and the machine connected to it.

Before reversing the motor shaft rotation direction make sure that this can be done safely.

Make sure that no power correction capacitors are connected to the motor cable.

2 RECEIPT OF DELIVERY

After unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (compare the type designation of the product to the code: see chapter 12).
Should the drive have been damaged during the shipping, please contact primarily the cargo insurance company or the carrier.
In normal operating conditions, HVAC232/402 frequency converters are maintenance- free. However, regular maintenance is recommended to ensure a trouble-free operating and along lifetime of the drive. We recom­mended to follow the table below for maintenance intervals.
Table 1.
Maintenance interval Maintenance action
Whenever necessary Clean heat sink* Regular Check tightening torques of terminals 12 months (If stored) Check input and output terminals and control
I/O terminals. Clean cooling tunnel.* Check operation of cooling fan. Check for corrosion on terminals, bus bars
and other surfaces.*
6 - 24 months (depending on environment)
* Only for frame 4 and frame 5
Check and clean cooling fans:
• Main fan*
• Internal fan*
If the delivery does not correspond to your order, contact the supplier imme­diately.

2.1 Storage

If the frequency converter is to be kept in store before use make sure that the ambient conditions are acceptable:
Storing temperature –40 °F (–40 °C)…+70 °F (21 °C) Relative humidity < 95%, no condensation
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 10
Capacitor recharge
M36500
After a longer storage time the capacitors need to be recharge in order to avoid capacitor damage. Possible high leakage current through the capac­itors must be limited. The best way to achieve this is to use a DC-power supply with adjustable current limit.
1. Set the current limit to 300…800 mA according to the size of the drive.
2. Then connect the DC-power supply to the input phase L1 and L2.

3 INSTALLATION

3.1 Mechanical installation

There are two possible ways to mount HVAC232/402 in the wall. For MI1MI3, either screw or DIN-rail mounting; For MI4MI5, screw or flange mounting.
3. Then set the DC-voltage to the nominal DC voltage level of the (1.35 × Un AC) and supply the converter for at least 1h.If DC-voltage is not available and the unit has been stored much longer than 12 months de-energized, consult the factory before connecting power.

2.3 Warranty

Only manufacturing defects are covered by the warranty. The manufacturer assumes no responsibility for damages caused during or resulting from transport, receipt of the delivery, installation, commissioning or use.
The manufacturer shall in no event and under no circumstances be held responsible for damages and failures resulting from misuse, wrong installation, unacceptable ambient temperature, dust, corrosive substances or operation outside the rated specifications. Neither can the manufacturer be held responsible for consequential damages.
Variable frequency drive devices (VFD) and accessories: new products for thirty-six (30) months from the date of production.
MI2
MI1
BACK RESET
=M4
OK
LOC REM
=M5
LOC
BACK
REM
RESET
OK
Fig. 4. Screw mounting, MI1 - MI3
MI3
BACK RESET
=
M5
LOC REM
OK
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 11
MI4
MI5
M36501
1 2
M36502
=M 6
=M 6
LOC
BACK RESET
REM
OK
LOC
BACK RESET
REM
OK
Fig. 5. Screw mounting, MI4 - MI5
Fig. 6. DIN-rail mounting, MI1 - MI3
NOTE:
See the mounting dimensions on the back of the drive.
LOC
BACK RESET
REM
OK
M36503
Fig. 7. Flange mounting, MI4 - MI5
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 12
Ø 1/4 (7)
TOP
(153)
14-1/2 (370)
DRIVE OUTLINE
13/64 (6)
51/64
(20)
OPENING OUTLINE
6
14-19/64 (362)
6-1/2 (166)
6-51/64
(173)
7-13/32
(189)
MI4
1-3/32
(29)
5/8
(16)
MI5
1-3/32
(29)
14 (356)
15-7/64 (384)
M36504
Fig. 8. Flange mounting cutout dimensions for MI4
[Unit: inches (mm)]
Ø 1/4 (7)
TOP
6
(153)
DRIVE OUTLINE
OPENING OUTLINE
16 (407)
14 (356)
15-45/64 (400)
17 (431)
13/64 (6)
6-1/2 (166)
6-51/64
(173)
7-13/32
(189)
M36505
13
(332)
15/32
(12)
29/32
(23)
3
(77)
6-1/2 (165)
3-1/2
(89)
15
(379)
19/32
(15)
29/32
(23)
3-45/64
(95)
4-7/32
(107)
8 (202)
M36507
Fig. 10. Flange mounting depth dimensions
for MI4 and MI5 [Unit: inches (mm)]
Fig. 9. Flange mounting cutout dimensions for MI5
[Unit: inches (mm)]
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 13

3.2 HVAC232/402 dimensions

W2
W3
W2
W3
D2
H (H1)
H2
D (D1)
W (W1)
Fig. 11. HVAC232/402 dimensions,
MI1 - MI3
H3
H (H1)
H2
W (W1)
H3
D (D1)
Fig. 12. HVAC232/402 dimensions,
MI4 MI5
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 14
Table 2. HVAC232/402 dimensions in inches (mm).
Type H1 H2 H3 W1 W2 W3 D1 D2
MI1 6.3 (160.1) 5.8 (147) 5. 4 (137. 3) 2.6 (65.5) 1.5 (37.8) .18 (4.5) 3.9 (98.5) .28 (7) MI2 7.7 (1 95 ) 7. 2 ( 18 3) 6.7 (170) 3.5 (90) 2.5 (62.5) .22(5.5) 4 (101.5) .28 (7) MI3 10 (254.3) 9.6 (244) 9.0 (229.3) 3.9 (100) 3.0 (75) .22 (5.5) 4.3 (108.5) .28 (7) MI4 14.6 (370) 13.8 (350.5) 13.2 (336.5) 6.5 (165) 5.5 (140) .28 (7) 6.5 (165) ­MI5 16.3 (414) 15.7 (398) 15.1 (383) 6.5 (165) 5.5 (140) .28 (7) 8.0 (202) -
Table 3. HVAC232/402 frame dimensions (mm) and weights in lbs (kg)
Dimensions in inches (mm) Weight in lbs (kg.)*
Frame
MI1 2.6 (66) 6.3 (160) 3.9 (98) 1.1 (0.5) MI2 3.5 (90) 7.7 (19 5) 4 (102) 1.6 (0.7) MI3 3.9 (100) 10 (254.3) 4.3 (109) 2.2 (1) MI4 6.5 (165) 14.6 (370) 6.5 (165) 17.7 (8) MI5 6.5 (165) 16.3 (414) 8 (202) 22 (10)
* without shipping package
W H D
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 15
Fig. 13. HVAC232/402 dimensions,
MI23 - Display Location
Fig. 14. HVAC232/402 dimensions,
MI45 - Display Location
Dimensions in inches (mm)
A .7 (17) .9 (22.3) B 1.7 (44) 4 (102)
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 16
Frame MI2 MI3
Dimensions in inches (mm)
A 8 (205) 9.8 (248.5)
B 3.4 (87) 3.4 (87)
Frame MI2 MI3

3.3 Cooling

B
C
B
A
D
A
Enough free space shall be left above and below the frequency converter to ensure sufficient air circulation and cooling. You will find the required dimensions for free space in the table below.
If several units are mounted above each other, the required free space equals C + D (see figure below). Moreover, the outlet air used for cooling by the lower unit must be directed away from the air intake of the upper unit.
The amount of cooling air required is indicated below. Also make sure that the temperature of the cooling air does not exceed the maximum ambient temperature of the converter.
Table 4. Min. clearances around AC drive
Min clearance in inches (mm)
Type A* B* C D
MI1 .8 (20) .8 (20) 3.9 (100) 2 (50) MI2 .8 (20) .8 (20) 3.9 (100) 2 (50) MI3 .8 (20) .8 (20) 3.9 (100) 2 (50) MI4 .8 (20) .8 (20) 3.9 (100) 3.9 (100) MI5 .8 (20) .8 (20) 4.7 (120) 3.9 (100)
* Min clearance A and B for drives for MI1~MI3 can be 0 inches if the ambient temperature
is below 104 °F (40°C).
A = clearance around the freq. converter (see also B) B = distance from one frequency converter to another or distance to
cabinet wall C = free space above the frequency converter D = free space underneath the frequency converter
Fig. 15. Installation space
NOTE:
See the mounting dimensions on the back of the drive.
Leave free space for cooling above (100 mm),below (50 mm), and on the sides (20 mm) of HVAC232/402! (For MI1 - MI3, side-to-side installation allowed only if the ambient temperature is below 104 °F (40 °C); For MI4MI5, side-to-side installation is not allowed.
Table 5. Required cooling air
Type Cooling air required in cfm (m³/h)
MI1 5.886 (10) MI2 5.886 (10) MI3 17. 65 8 (30 ) MI4 26.487 (45) MI5 44.145 (75)
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 17

3.4 Power losses

If the operator wants to raise the switching frequency of the drive for some reason (typically e.g. in order to reduce the motor noise), this inevitably affects the power losses and cooling requirements, for different motor shaft power, operator can select the switching frequency according to the graphs below.
MI1 - MI3 1P 230 V POWER LOSS
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 18
MI1 - MI5 3P 400 V POWER LOSS
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 19
MI1 - MI5 3P 400 V POWER LOSS
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 20

3.5 EMC levels

EN618003 defines the division of frequency converters into four classes according to the level of electromagnetic disturbances emitted, the require­ments of a power system network and the installation environment (see be­low). The EMC class of each product is defined in the type designation code.
Category C1: Frequency converters of this class comply with the re-
quirements of category C1of the product standard EN 618003(2004). Category C1 ensures the best EMC characteristics and it includes converters the rated voltage of which is less than 1000 V and which are intended for use in the 1st environ­ment.
NOTE:
The requirements of class C are fulfilled only as far as the conducted emissions are concerned.
Category C4: The drives of this class do not provide EMC emission protec-
tion. These kinds of drives are mounted in enclosures.
Environments in product standard EN 618003 (2004)
First environment: Environment that includes domestic premises. It also
includes establishments directly connected without intermediate transformers to a low-voltage power supply network which supplies buildings used for domestic purposes.
NOTE:
Houses, apartments, commercial premises or offices in a residential building are examples of first environment locations.
Category C2: Frequency converters of this class comply with the re-
quirements of category C2of the product standard EN 618003(2004). Category C2 includes converters in fixed installations and the rated voltage of which is less than 1000 V. The class C2 frequency converters can be used both in the 1st and the 2nd environment.
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 21
Second environment: Environment that includes all establishments oth-
er than those directly connected to a low-voltage power supply network which supplies buildings used for domestic purposes.
NOTE:
Industrial areas, technical areas of any building fed from a dedicated transformer are examples of second environment locations.

3.6 Changing the EMC protection class from C2 to C4

The EMC protection class of MI13 frequency converters can be changed from class C2 to class figure below. MI4 & 5 can also be changed by removing the EMC jumpers.
NOTE:
Do not attempt to change the EMC level back to class C2. Even if the procedure above is reversed, the frequency converter will no longer fulfil the EMC requirements of class C2!
Fig. 16. EMC disconnecting screw, MI1 - MI3
C4 by
removing the EMC-capacitor disconnecting screw, see
Fig. 18. EMC jumpers, MI5
Fig. 19. Jumpers
• Remove the main cover and locate the two jumpers.
• Disconnect the RFI-filters from ground by lifting the jumpers up from their default positions. See Figure 19.
Fig. 17. EMC jumpers, MI4
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 22
L1 L 2/N L3 U/T1 V/T2 W/T3R+ R-
1~ (230V) 1~ (115V)

3.7 Cabling and connections

Power cabling
NOTE:
Tightening torque for power cables is 0.5 - 0.6 Nm.
3~ (230 V, 400 V)
1~ (230 V)
Strip the plastic
cable for 360
earthing
MAINS MOTOR
Motor out
Strip the plastic cable for 360 earthing
3~ (230 V, 400 V, 600 V)
MAINS MOTOR
BRAKE RESISTOR
(NOT USED)
External brake resistor 3~ (230 V, 400 V, 600 V)
Motor out
Fig. 20. HVAC232/402
power connections, MI1
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 23
Fig. 21. HVAC232/402
power connections, MI2 - MI3
3~ (380 V, 480 V)
BRAKE
MAINS MOTOR
RESISTOR
Fig. 22. HVAC232/402
power connections, MI4
Control Cabling
Motor out
Attach the support AFTER installing the power cables
3~ (380 V, 480 V)
Motor out
MAINS MOTOR
Fig. 23. HVAC232/402
power connections, MI5
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 24
BRAKE
RESISTOR
Fig. 24. Mount the PE-plate and API cable support,
MI1 - MI3
Attach this plate BEFORE installing the power cables
Attach the support AFTER installing the power cables
Attach this plate BEFORE installing the power cables
Fig. 26. Open the lid, MI1 - MI3
Fig. 25. Mount the PE-plate and API cable support,
Fig. 27. Open the lid, MI4 - MI5
MI4 - MI5
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 25
Control cable tightening torque: 0.4 Nm
Allowed option boards in HVAC232/402
NOTE:
When OPTB1, OPTB2 or OPTB4 are used in HVAC232/402, +24 VDC (±10 %, min. 300 mA) power should be supplied to Terminal 6 (+24_out) and Terminal 3 (GND) in control board.
Strip the plastic cable coating for 560° earthing
Fig.28. Install the control cables MI1MI3.
See Chapter „6.2 Control I/O“ on page 42
Table 6 .
Option boards (all boards are varnished)
OPTB1 6 × inputs/outputs programmable OPTB2 2 × Relay output + Thermistor OPTB4 2 AO & 1 AI mA OPTB5 3 × Relay output OPTB9 1 × RO, 5 × inputs 42…240 V OPTBF 1 AI mA, 1RO, 1DO op. col. OPTBH 3 × temp sensors Pt1000, Ni1000 or Pt100 OPTE9 Modbus TCP Dual port
Fig. 29. Install the control cables MI4 - MI5.
See Chapter „6.2 Control I/O“ on page 42
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 26
Optional board assembly structure:
1
2
4
5
6
3
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 27

3.8 Screw of cables

12 screws M4 × 8
Fig. 30. MI1 screws Fig. 31. MI2 screws
14 Screws M4 × 9
10 screws M4 × 8
10 screws M4 × 8
6 Screws M4 × 17
4 screws M4 × 10
Fig. 32. MI3 screws Fig. 33. MI4 - MI5 screws
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 28
Cable and fuse specifications
Use cables with heat resistance of at least 158 °F (70 °C). The cables and the fuses must be dimensioned according to the tables below.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type and impedance of the supply circuit.
Installation of cables is presented in chapter „3.10 Cable installation“ on page 32.
The fuses function also as cable overload protection. The recommended fuse types are gG/gL (IEC 602691). The fuse voltage rating should be selected according to the supply network. The final selection should be made according to local regulations, cable installation conditions and cable
specification. Bigger fuses than what is recommended below should not be used.
Table 7. Cable types required to meet standards.
EMC categories are described in Chapter „3.5 EMC levels“ on page 21.
EMC category cat. C2 cat. C4
Mains cable types 1 1 Motor cable types 3 1 Control cable types 4 4
Table 8. Cable type descriptions
Consult the factory about faster fuses.
Honeywell offers recommendations also for aR (IEC 602694) and gS (IEC 602694) fuse ranges.
These instructions apply only to cases with one motor and one cable con­nection from the frequency converter to the motor. In any other case, ask the factory for more information.
Cable type Description
1 Power cable intended for fixed installation and the specific mains voltage. Shielded cable not required.
(NKCABLES / MCMK or similar recommended)
2 Power cable equipped with concentric protection wire and intended for the specific mains voltage.
(NKCABLES / MCMK or similar recommended).
3 Power cable equipped with compact low-impedance shield and intended for the specific mains voltage.
(NKCABLES / MCCMK, SAB / ÖZCUYJ or similar recommended). *360º earthing of both motor and FC connection required to meet the standard
4 Screened cable equipped with compact low-impedance shield (NKCABLES /Jamak, SAB / ÖZCuYO or similar).
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 29
Table 9. Cable and fuse sizes for HVAC232/402, 208 - 240 V, 1~
Frame Power
[kW]
MI1 0.25…0.55 10 2×1.5+1.5 3×1.5+1.5 1.5…4 1.5…4 0.5…1.5 0.5…1.5
MI2 0.75…1.50 20 2×2.5+2.5 3×1.5+1.5 1.5…4 1.5…4 0.5…1.5 0.5…1.5
MI3 2.2* 32 2×6+6 3×1.5+1.5 1.5…6 1.5…6 0.5…1.5 0.5…1.5
* The maximum ambient operating temperature of this drive is 40 °C!
Fuse
[A]
Mains cable
Cu [mm2]
Motor cable
Cu [mm2]
Main
terminal
[mm2]
Terminal cable size (min/max)
Earth
terminal
[mm2]
Control
terminal
[mm2]
Table 10. Cable and fuse sizes for HVAC232/402, 380 - 480 V, 3~
Frame Power
[kW]
MI1 0.37…0.75 6 3×1.5+1.5 3×1.5+1.5 1.5…4 1.5…4 0.5…1.5 0.5…1.5
MI2 1.1…2.2 10 3×1.5+1.5 3×1.5+1.5 1.5…4 1.5…4 0.5…1.5 0.5…1.5
Fuse
[A]
Mains cable
Cu [mm2]
Motor cable
Cu [mm2]
Main
terminal
[mm2]
Terminal cable size (min/max)
Earth
terminal
[mm2]
Control
terminal
[mm2]
Relay
terminal
[mm2]
Relay
terminal
[mm2]
MI3 3.0…5.5 20 3×2.5+2.5 3×2.5+2.5 1.5…6 1.5…6 0.5…1.5 0.5…1.5
MI4 7.5…25.5 20 3×6+6 3×6+6 1…10Cu 1…10 0.5…1.5 0.5…1.5
MI5 15…18.5 40 3×10+10 3×10+10 2.5…50 Cu/Al 2.5…35 0.5…1.5 0.5…1.5
NOTE:
To fulfil standard EN6180051, the protective conductor should be at least 10 mm2 Cu or 16 mm2 Al. Another possibility is to use an additional protective conductor of at least the same size as the original one.
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07 30
Loading...
+ 115 hidden pages