Note: All nominal ratings based upon LP fuel. Refer to specication sheet for
NG ratings and deration adjustments for ambient temperature and altitude.
6
NATURAL GAS INSTALLATION
BTU and
Pressure Decal
Flex Fuel LineSafety Shut-Off
with Pressure Port
Check Distance with
Gas Provider
Size Meter for Generator Load
Plus ALL Appliances
Size gas pipe with Generator Sizing Guide or to local codes.
For Underground Installations Verify
Piping System for Code Compliance
TABLE 4B
Natural Gas 3.5" to 5"
of Water Column
(Table values are maximum
pipe run in feet.)
Pipe Size (in)
kW0.75"1"1.25"1.5"
1130125200
15–171060125
201060125
Natural Gas
1 cubic foot = 1,000 BTU
1 therm = 100,000 BTU
Gas consumption = 13,000-16,000 BTU per kW/hr
Pressure
1 inch mercury = 13.61 inches water column
1 inch Water Column = 0.036 psi
3.5–7 inches water column = 0.126 psi to 0.252 psi
Note:
– Pipe sizing is based on 0.5" H
– Sizing includes a nominal number of elbows and tees.
– Please verify adequate service and meter sizing.
– Tables based on black pipe.
O pressure drop.
2
7
LP VAPOR INSTALLATION
BTU and
Pressure Decal
Check Distance with
Regulator Manufacturer
Check Distance
with LP Provider
Size Tank Large Enough to Provide
Required BTU's for Generator and ALL
Connected Appliance Loads.
Be Sure to Correct for MIWR (See Table 6)
Primary Regulator
Per LP Provider
Flex Fuel Line
Size gas pipe from secondary regulator with Generator Sizing
Guide or to local codes.
1 inch mercury = 13.61 inches water column
1 inch Water Column = 0.036 psi
11–14 inches water column = 0.396 psi to 0.50 psi
3
/lb., 4.24 lbs./gal., 2500 btu/ft
Sized per LP Provider
3
8
Note:
– Pipe sizing is based on 0.5" H
– Sizing includes a nominal number
of elbows and tees.
– Please verify adequate service and meter sizing.
– Tables based on black pipe.
O pressure drop.
2
TABLE 6
LP VAPOR (LPV) TANK SIZING
Vapor Withdrawal
Tank Capacity
Total (Gal.)
1207240
1509040
25015040
32519540
50030040
Tank Capacity
Useable (Gal.)
Minimum Temp
(°F)
20
0
20
0
20
0
20
0
20
0
Tank Capacity (btu/hr.)Length
(Inches)
246,240
164,160
82,080
293,760
195,840
97,920
507,600
338,400
169,200
642,600
428,400
214,200
792,540
528,360
264,180
572433
682433
943039
1193039
1193746
Diameter
(Inches)
Overall Ht.
(Inches)
Gas Required for Common Appliances
APPLIANCEApproximate Input
Warm Air Furnace
Single Family
Multifamily, per unit
Hydronic Boiler, Space Heating
Single Family
Multifamily, per unit
Hydronic Boiler, Space and Water Heating
Single Family
Multifamily, per unit
Range, Free Standing, Domestic
Built-In Oven or Broiler Unit, Domestic
Built-ln Top Unit, Domestic
Note: Tank BTU capacity and generator run times based upon maintaining a
minimum tank fuel level of 20%. Tanks are typically lled to 80% full.
Note: Typical fuel consumption based on a generator 100% loaded.
BTU / Hr
60,000–120,000
40,000–60,000
80,000–140,000
50,000–80,000
100,000–200,000
50,000–100,000
50,000–90,000
14,000–16,000
40,000–85,000
TABLE 7
Generator
kW Rating
LPNat. GasLP VaporNat. GasLP VaporNat. Gas
87129,000121,00079,00078,000
1110175,000195,000107,000124,000
1313268,000255,000149,000157,000
1414279,000279,000168,000177,000
1515260,000296,000166,000185,000
1716325,000312,000181,000193,000
2018350,000308,000189,000205,000
2222313,000316,000188,000190,000
2525430,000430,000298,000297,000
2725356,000359,000195,000197,000
3030493,000492,000320,000320,000
3635500,000503,000280,000282,000
4545725,000730,000378,000380,000
4848755,000756,000393,000392,000
6060818,000862,000458,000483,000
70671,028,0001,020,000503,000500,000
80801,163,0001,154,000603,000600,000
100941,268,0001,260,000718,000713,000
1301221,798,0001,786,000933,000927,000
1501422,075,0002,061,0001,078,0001,070,000
GENERATOR FUEL CONSUMPTION
Fuel Consumption
at 100% BTU/HR
Fuel Consumption
at 50% BTU/HR
Operating Cost Per Hour
=
NG Therms/HR x Cost of NG Therm
9
UPS - Generator Compatibility
Passive (also referenced as
standby or off-line) and
Line-Interactive
These technologies are most common
for personal workstations and point
of sale applications. They are typically
single phase equipment with size
ranges of 350 VA - 2000 VA for
passive and 500 VA to 5000 VA for
line-interactive.
Passive UPS’s are the simplest type.
Under normal conditions AC power
passes straight through to the UPS
load. When the input power supply
goes outside of specications, the
UPS transfers the load from input
power to the internal DC to AC power
inverter. Passive UPS’s do not correct
for voltage or frequency deviations
under “normal” operation.
Line-interactive is similar to the
passive technology except it has
circuitry that attempts to correct for
standard voltage deviations. Frequency
deviations under “normal” power
operation are not corrected.
Equipment Notes:
These devices tend to be electrically /
harmonically very noisy. A single small
UPS is not a signicant concern, but
applications with multiple UPS’s can
be problematic.
Passive UPS technology typically
has normal tolerances of 10-25% on
voltage and 3 Hertz on frequency.
Minuteman UPS input tolerance is
closer to 10-36%. If the input source
goes outside of these tolerances, the
UPS will switch onto the UPS battery
source. Some line-interactive units
may have frequency tolerances factory
set to 0.5 Hertz. These units will need
to have their frequency tolerance
increased to a minimum of 2 Hertz.
Minuteman UPS products are close to
5 Hertz and not 0.5 Hertz.
Generator Sizing Recommendation:
Limit the total UPS loading to 15% - 20%
of the generator capacity.
Double-Conversion
This technology is most common
for critical load applications. Doubleconversion UPS’s constantly rectify
AC to DC and then invert the DC back
into AC. This conguration results in
an output that corrects for voltage and
frequency deviations.
There are single and three phase
models covering small through large
applications. Most UPS applications
larger than 5000 VA use double
conversion technology. This approach
is also the preferred technology for
generator applications.
Equipment Notes:
Double-conversion UPS’s that are
single phase or unltered three phase
models tend to create a signicant
level of electrical/ harmonic noise.
This is illustrated by harmonic current
distortions that are greater than 35%.
Minuteman UPS products could
have current distortion of 8%. When
three phase models are supplied with
harmonic lters (current distortion less
than 10%), this concern is no longer
an issue.
Generator Sizing Recommendation:
Single phase models: limit the total
UPS loading to 25% of the generator
capacity. Single phase Minuteman
UPS models: limit the total UPS
loading to 50% of the generator
capacity. Three phase models without
lters (current distortion > 30%):
limit the UPS loading to 35% of the
generator capacity. Three phase
models with lters (current distortion <
10%): limit the UPS loading to 80% of
the generator capacity.
UPS Information
2 x kVA rating for a ltered system
3 – 5 x kVA rating for an unltered system
It is recommended you refer to the Honeywell UPS Generator Compatibility sheet
(Pg 10) and contact the manufacturer of the UPS system to assist in your installation.