Honeywell H-S81-HS Operation Manual

Page 1
H-S81-HS
INDUSTRIAL FIRE PANEL
INSTALLATION & OPERATION MANUAL
P/N LS10114-000HI-E:A • ECN 15-xxx • 2/24/2015
Page 2
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu­nication, and other various interoperable communication met h­ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the National Fire Protection Asso ciation Standard 72-2002 (NFPA 72-2002), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http: // www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States governme nt) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smok e ” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown aw a y from de tectors by air outlets, such as air conditioning vent s.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designe d to ala rm at var­ious levels of smoke density. If such density levels are not cre­ated by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing cham­bers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growt h, neither type of detector i s necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn­ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi­als, etc.).
Heat detectors do not sense particles of combustion and al arm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector shoul d be tested at least once per year by a qualified fire protection specialist . Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel­oping fire may damage the alarm system, compromising its abil­ity to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be desi gned to meet intelligi­bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under c ertain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have sh own that certain people, even when they he ar a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig­nals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat­ible with the control panel. It is essential to use only equipment l
is
ted for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem­ises to a central monitoring station may be out of service or tem­porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep t he entire life safety sys tem in excellent working order , ongoing mai ntenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72-2002 shall be followed. Environments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A mainte­nance agreement should be arranged through the local manu­facturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional life safety sys­tem installers only. Adequate written records of all inspections should be kept.
Limit-D-1-2013
2 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to li ght ­ning induced transients. Although no system is completely immune from lightning transients and interf erence, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body . Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, ope rati ng, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and a ssociated equipment. FACP operation and rel iability depend upon proper inst allat ion.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi ­oelectriques depassant les limites applic ables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 3
Page 4
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 5

Table of Contents

General Information................................................................................................................14
Related Documentation........................................... .................................. ..........................................................14
Acronyms............................................................................................................................................................14
Important Notices ................................................................. .................................. ............................................14
Section 1: General Description..............................................................................................15
1.1: Architecture of the System ..........................................................................................................................15
1.2: Mechanical Structure...................................................................................................................................16
1.3: General Features..........................................................................................................................................17
1.3.1: Mechanical Properties .......................................................................................................................17
1.3.2: Electrical Characteristics...................................................................................................................18
1.3.3: Reference Standards..........................................................................................................................18
1.3.4: Climatic Conditions...........................................................................................................................18
1.3.5: Mechanical Conditions......................................................................................................................18
1.3.6: Electromagnetic Compatibility (CE).................................................................................................19
1.4: Safety and Availability of the H-S81-HS System........................................................................................19
1.4.1: Possible Configurations of the H-S81-HS System............................................................................19
“Mono” Configuration................................................................ .................................. ........................19
“Duplex” Configuration .......................................................................................................................20
1.5: Safety-Related Modules in the H-S81-HS System......................................................................................20
1.5.1: Central Unit .......................................................................................................................................20
1.5.2: Digital Input Modules........................................................................................................................21
1.5.3: 4-20mA Input Modules .....................................................................................................................21
1.5.4: Output Modules.................................................................................................................................21
1.5.5: Central Unit Safety Switch-off..........................................................................................................22
1.5.6: Central Unit Safety Shut-down..........................................................................................................22
1.6: Communication Network Between Control Panels.....................................................................................23
1.7: Communication Protocol for Supervisory Systems.....................................................................................24
1.8: OPC Server..................................................................................................................................................25
1.9: Programming ...............................................................................................................................................25
Section 2: Parts of the H-S81-HS System .............................................................................27
2.1: Power Supply Set.........................................................................................................................................27
2.1.1: S81-PU001 Power Supply Set...........................................................................................................27
Technical Features............................................................................................ ....................................27
2.1.2: PU-A0005-1 Power Supply Module..................................................................................................28
Technical Features............................................................................................ ....................................28
Internal Connections.............................................................................................................................29
2.1.3: PU-A0004-1 Battery Charger Module ..............................................................................................29
Technical Features............................................................................................ ....................................30
Internal Connections.............................................................................................................................30
2.1.4: S81-PU002 Power Supply Set...........................................................................................................30
Technical Features............................................................................................ ....................................32
Power Supply Unit Section ..................................................................................................................32
Battery Charger Section .......................................................................................................................32
Cooling Unit...................... .................................. .................................. ...............................................32
Protections............................................................................................................................................32
Reference Standards.............................................................................................................................32
Possible Configurations........................................................................................................................33
2.1.5: PU-A0007-1 Drawer with Slots ........................................................................................................33
Description ...........................................................................................................................................33
Internal connections..............................................................................................................................34
2.1.6: PU-A0008-1 Power Supply Module..................................................................................................35
Description ...........................................................................................................................................35
Technical Features............................................................................................ ....................................36
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 5
Page 6
Table of Contents
2.1.7: PU-A0009-1 Battery Charger Module...............................................................................................36
Description............................................................................................................................................36
Technical Features .................................................................................... ...........................................37
2.2: Central Unit Rack ........................................................................................................................................37
2.2.1: S81-E2003-1......................................................................................................................................38
Description............................................................................................................................................38
Technical Features.................................................................................. ..............................................38
Internal connections..............................................................................................................................38
2.2.2: S81-U1002-1......................................................................................................................................39
Description............................................................................................................................................39
Technical Features.................................................................................. ..............................................39
Status Indications..................................................................................................................................40
Connections ..........................................................................................................................................40
2.2.3: S81-U1006-1......................................................................................................................................40
Description............................................................................................................................................40
Technical features ....................................................................... .........................................................41
Status Indications .................................................................................................................................41
Buttons..................................................................................................................................................41
Internal connections..............................................................................................................................42
2.3: I/O Rack.......................................................................................................................................................42
2.3.1: S81-E2001-1......................................................................................................................................43
Description ...........................................................................................................................................43
Technical Features.................................................................................. ..............................................43
Internal connections..............................................................................................................................43
2.3.2: S81-E2001-2......................................................................................................................................44
Description............................................................................................................................................44
Technical features ....................................................................... .........................................................44
Internal connections..............................................................................................................................44
2.3.3: S81-E2002-1......................................................................................................................................45
Description ...........................................................................................................................................45
Technical features ....................................................................... .........................................................45
Configuration........................................................................................................................................45
2.4: I/O modules..................................................................................................................................................45
2.4.1: S81-F3002-1 & S81-F3002-2............................................................................................................46
Description............................................................................................................................................46
Technical Features .................................................................................... ...........................................46
Status Indications..................................................................................................................................46
Configuration........................................................................................................................................47
Field Connection...................................................................................................................................47
Standard Connection Diagrams............................................................................................................48
2.4.2: S81-F4001-1 & S81-F4001-2...............................................................................................
...........................................................................................................................................49
Description
.
Technical Features.................................................................................. ..............................................49
Status Indications..................................................................................................................................49
Configuration........................................................................................................................................50
Threshold Setting..................................................................................................................................50
Zero Point Calibration ..........................................................................................................................51
End of Scale Calibration.......................................................................................................................51
Field Connections.................................................................................................................................51
Standard Connection Diagrams............................................................................................................52
2.4.3: S81-F4002-1 & S81-F4002-2............................................................................................................53
Description............................................................................................................................................53
Technical Features.................................................................................. ..............................................53
Status Indications..................................................................................................................................53
Three-Digit Display..............................................................................................................................53
Configuration........................................................................................................................................54
Threshold Setting .................................................................................................................................54
.............49
6 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 7
Table of Contents
Zero Point Calibration..........................................................................................................................54
End of Scale Calibration.......................................................................................................................55
Field Connections.................................................................................................................................55
Standard Connection Diagrams............................................................................................................56
2.4.4: S81-F4003-1 & S81-F4003-2............................................................................................................57
Description ...........................................................................................................................................57
Technical Features............................................................................................ ....................................57
Status Indications..................................................................................................................................57
Configuration........................................................................................................................................57
Threshold Setting..................................................................................................................................58
Zero Point Calibration..........................................................................................................................58
End of Scale Calibration.......................................................................................................................58
Field Connections.................................................................................................................................58
Standard Connection Diagrams............................................................................................................59
2.4.5: S81-F5001-1 & S81-F5001-2............................................................................................................60
Description ...........................................................................................................................................60
Technical Features............................................................................................ ....................................60
Status Indications..................................................................................................................................60
Configuration........................................................................................................................................60
Field Connections.................................................................................................................................61
Standard Connection Diagrams............................................................................................................62
2.4.6: S81-F5002-1......................................................................................................................................62
Description ...........................................................................................................................................62
Technical Features............................................................................................ ....................................62
Status Indications..................................................................................................................................62
Configuration........................................................................................................................................63
Field Connections.................................................................................................................................63
2.4.7: S81-F5003-1......................................................................................................................................64
Description ...........................................................................................................................................64
Technical Features............................................................................................ ....................................64
Status Indications .................................................................................................................................64
Configuration........................................................................................................................................65
Field Connections.................................................................................................................................65
S81-T8008-1....................................................................................................................
Standard Connection
Diagrams
............................................................................................................66
.....................65
2.4.8: S81-F5004-1 & S81-F5004-2............................................................................................................67
Description ...........................................................................................................................................67
Technical Features............................................................................................ ....................................67
Status Indications..................................................................................................................................67
Configurations......................................................................................................................................67
Field connections..................................................................................................................................68
2.4.9: S81-F6001-1......................................................................................................................................69
Description ...........................................................................................................................................69
Technical Features............................................................................................ ....................................69
Status Indications..................................................................................................................................69
Virtual channels............................................................................................. .......................................69
Configuration........................................................................................................................................70
Field Connections.................................................................................................................................70
2.4.10: S81-F6002-1....................................................................................................................................71
Description ...........................................................................................................................................71
Technical Features............................................................................................ ....................................71
Configuration........................................................................................................................................71
Logic Functions....................................................................................................................................71
Field Connections.................................................................................................................................73
2.4.11: S81-F7002-1....................................................................................................................................73
Description ...........................................................................................................................................73
Technical Features............................................................................................ ....................................73
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 7
Page 8
Table of Contents
Status Indications..................................................................................................................................73
Configuration........................................................................................................................................74
Field Connections.................................................................................................................................74
Supported Devices.................................................................................. ..............................................76
2.4.12: S81-F7007-1 ....................................................................................................................................76
Description............................................................................................................................................76
Technical Features.................................................................................. ..............................................76
Status Indications..................................................................................................................................77
Configuration........................................................................................................................................77
Field Connections.................................................................................................................................78
Standard Connection Diagrams............................................................................................................78
Supported Devices.................................................................................. ..............................................79
2.4.13: S81-F7009-1 ....................................................................................................................................79
Description............................................................................................................................................79
Technical Features .................................................................................... ...........................................79
Status Indications..................................................................................................................................79
Configuration........................................................................................................................................80
Field Connections.................................................................................................................................80
Standard Connection Diagrams............................................................................................................81
Supported devices..................................................................... ............................................................81
2.4.14: S81-F7010-1 ....................................................................................................................................82
Description............................................................................................................................................82
Technical Features.................................................................................. ..............................................82
Status Indications..................................................................................................................................82
Configuration........................................................................................................................................83
Field Connections.................................................................................................................................83
Standard Connection Diagrams............................................................................................................84
Supported Devices.................................................................................. ..............................................84
2.4.15: S81-F7006-1 ....................................................................................................................................86
Description............................................................................................................................................86
Technical Features.................................................................................. ..............................................86
Status Indications .................................................................................................................................86
Configuration........................................................................................................................................86
Field Connections.................................................................................................................................87
Standard Connection Diagrams...................................................................................................
2.4.16:
S81-F7008
-1 ....................................................................................................................................89
Description............................................................................................................................................89
Technical Features.................................................................................. ..............................................89
Status Indications .................................................................................................................................89
Configuration........................................................................................................................................89
Field Connections.................................................................................................................................89
Standard Connection Diagrams............................................................................................................90
S81-MOD-BIL Weighing Module .......................................................................................................90
Technical Features.................................................................................. ..............................................91
Assembly ..............................................................................................................................................91
Programming the Weighing Module Address......................................................................................91
Weighing Module Reset .......................................................................................................................91
2.5: Termination modules....................................................................................................................................91
2.5.1: S81-T8001-1......................................................................................................................................92
Description............................................................................................................................................92
Technical Features.................................................................................. ..............................................92
Field Connections.................................................................................................................................93
2.5.2: S81-T8003-1......................................................................................................................................93
Description............................................................................................................................................93
Technical Features.................................................................................. ..............................................93
Field Connections.................................................................................................................................93
2.5.3: S81-T8005-1......................................................................................................................................94
.........88
8 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 9
Table of Contents
Description ...........................................................................................................................................94
Technical Features............................................................................................ ....................................94
Interconnection Between S81-CCT1 Cable and S81-T8007-1 Module...............................................94
2.5.4: S81-T8002-1......................................................................................................................................95
Description ...........................................................................................................................................95
Technical Features .............................................................................................. .................................95
Status Indications..................................................................................................................................95
Internal Connections.............................................................................................................................95
Field Connections.................................................................................................................................95
2.5.5: S81-T8004-1......................................................................................................................................96
Description ...........................................................................................................................................96
Technical Features............................................................................................ ....................................96
Status Indications..................................................................................................................................96
Configuration........................................................................................................................................96
Internal Connections.............................................................................................................................97
Field Connections.................................................................................................................................98
Standard Connection Diagrams............................................................................................................99
2.5.6: S81-T8006-1......................................................................................................................................99
Description ...........................................................................................................................................99
Technical Features.............................................................................................. .................................99
Status Indications..................................................................................................................................99
Field Connections...............................................................................................................................100
2.5.7: S81-T8007-1....................................................................................................................................100
Description .........................................................................................................................................100
Technical Features............................................................................................ ..................................100
Status Indications................................................................................................................................100
Field Connections...............................................................................................................................101
2.5.8: S81-T8007-2....................................................................................................................................101
Description .........................................................................................................................................101
Technical Features............................................................................................ ..................................101
Status Indications................................................................................................................................101
Internal Connections...........................................................................................................................101
Field Connections...............................................................................................................................102
Standard Connection Diagrams..........................................................................................................102
2.6: Blank Panels ..............................................................................................................................................103
2.6.1: Description.......................................................................................................................................103
2.7: Cables ........................................................................................................................................................104
Section 3: Installation...........................................................................................................105
3.1: Positioning of the Control Panel................................................................................................................105
3.2: Measures for Installation in Compliance with the EC Standard ................................................................105
3.3: Mounting the H-S81-HS-1R & H-S81-HS-2R Control Panels .................................................................105
3.4: Positioning the H-S81-HS-1/10R Control Panel .......................................................................................106
3.5: Layout of H-S81-HS/1R Internal Parts......................................................................................................107
3.6: Layout of H-S81-HS/2R Internal Parts......................................................................................................108
3.7: Layout of H-S81-HS/1-10R Internal Parts ................................................................................................109
3.8: Cable Entry................................................................................................................................................109
3.9: Earth Grounding Instructions ....................................................................................................................110
3.10: Connection to AC Main.................................... .................................. .....................................................110
3.11: Battery Connection..................................................................................................................................110
3.11.1: Replacement of Battery Fuses.......................................................................................................111
3.12: Instructions for the Connection of Field Devices....................................................................................111
3.12.1: Balanced Input Cables...................................................................................................................111
3.12.2: 4-20 mA Analog Input Cables.......................................................................................................111
3.12.3: Addressable Loop Cables..............................................................................................................112
3.12.4: 25 VDC Power Cables................................................................................. ..................................112
3.12.5: Output Cables..................................................................... .................................. .........................112
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 9
Page 10
Table of Contents
Section 4: Start-Up and Fault Management .......................................................................113
4.1: Start-Up......................................................................................................................................................113
4.1.1: Required Materials...........................................................................................................................113
4.1.2: Preliminary Checks..........................................................................................................................113
4.1.3: Checks on Cables from Field Devices.............................................................................................113
Balanced Input Cables (S81-F3002 Modules)....................................................................................113
Analog Input Cables (S81-F4001, S81-F4002, S81-F4003 Modules)...............................................113
Addressable Loop Cables (S81-F7002, S81-F7007, S81-F7009, S81-F7010 Modules) ...................113
Audible Alarm Device Control Cables (S81-F5003 Modules) ..........................................................114
Solenoid Control Cables (S81-F5001, S81-F5004 Modules).............................................................114
25 VDC Power Cables........................................................................................................................114
4.1.4: Start..................................................................................................................................................114
4.1.5: Functional Tests...............................................................................................................................114
4.2: Management of Faults................................................................................................................................115
4.2.1: Power Supply Set Fault ...................................................................................................................115
4.2.2: Central Unit Fault ............................................................................................................................115
4.2.3: I/O Module Fault .............................................................................................................................115
4.2.4: Replacing One Module of the S81-PU001 Power Supply Set ........................................................115
4.2.5: Replacing One Module of the S81-PU002 Power Supply Set ........................................................115
4.2.6: Battery Replacement........................................................................................................................116
4.2.7: Replacement of the CPU .................................................................................................................116
4.2.8: I/O Module Replacement.................................................................................................................116
4.2.9: Replacement of Fuses......................................................................................................................117
4.2.10: Repair of a Faulty Module.............................................................................................................117
4.2.11: Customer Service and Training.....................................................................................................117
Section 5: Maintenance........................................................................................................118
5.1: Steelwork ...................................................................................................................................................118
5.2: Batteries .....................................................................................................................................................118
5.3: Field Devices .............................................................................................................................................118
5.4: Functional Tests .........................................................................................................................................118
Section 6: Application Notes...............................................................................................120
6.1: Notes for the Development of Systems in Compliance with the EN54-2 / EN54-4 Standard ..................120
6.2: Notes for the Development of Systems in Compliance with the EN12094-1 Standard ............................120
6.2.1: Processing of signals and indicators................................................................................................121
6.2.2: Compulsory Functions.....................................................................................................................121
6.2.3: Optional Functions...........................................................................................................................121
6.2.4: Light Indicators................................................................................................................................122
6.2.5: Monitored Inputs .............................................................................................................................122
6.2.6: Monitored Outputs...........................................................................................................................122
6.2.7: Non-monitored Outputs...................................................................................................................122
6.2.8: Receiving and Processing Inbound Actuation Signals....................................................................123
6.2.9: Transmission of the Release Signal.................................................................................................123
6.2.10: Actuation of Alarm Devices....................................................................... ...................................123
6.2.11: Main Voltage Detection Signal .....................................................................................................123
6.2.12: “Activated” Condition ...................................................................................................................123
6.2.13: “Released” Condition ....................................................... .................................. ...........................123
6.2.14: Resetting the “Activated” and “Released” Conditions..................................................................124
6.2.15: Fault Condition............................. .................................. ................................. ..............................124
6.2.16: Out of Service Condition.............................................................. .................................................124
6.2.17: Release Signal Delay............................... .................................. ....................................................124
6.2.18: Signal Representing Extinguishing Agent Flow............................................................................124
6.2.19: Emergency Hold................................ .................................. .................................. ........................125
Mode-A...............................................................................................................................................125
Mode-B...............................................................................................................................................125
6.2.20: Activation of a Secondary Release Sequence................................................................................125
10 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 11
Table of Contents
6.2.21: Manual Only Mode (Aut-Off).......................................................................................................125
6.2.22: Actuation Commands for System Internal Equipment..................................................................125
6.2.23: Releasing Signals to the Reserve Cylinders..................................................................................126
6.2.24: Actuation Commands to Equipment Outside the System .............................................................126
6.2.25: Emergency Shutdown Devices....................................................................... ...............................126
6.2.26: Activation of Alarm Devices with Different Signals ....................................................................126
6.3: Notes for the Development of Systems in Compliance with the CEI 79-2 Standard................................126
6.4: Notes on I/O Module Redundancy............................................................................................................126
6.4.1: I/O Module Redundancy .................................................................................................................127
6.4.2: I/O Modules for Which Redundancy is Not Possible......................................................................127
6.4.3: I/O Modules for Which Redundancy is Possible With Restrictions ...............................................127
Section 7: Operating Instructions.......................................................................................128
7.1: Operator Interface......................................................................................................................................128
7.1.1: Visual Indicators..............................................................................................................................128
7.1.2: Buttons.............................................................................................................................................129
7.2: Fire Alarm Section Menu (Safety) ............................................................................................................131
7.3: Access to Functions...................................................................................................................................131
7.4: Operations at Access Level 1 ....................................................................................................................132
7.4.1: Local Buzzer Silencing....................................................................................................................132
7.4.2: Delay Override ................................................................................................................................133
7.4.3: Overview of Zones with Ongoing Fire Alarm.................................................................................133
7.4.4: Overview of Zones with Active Fire Pre-alarms.............................................................................134
7.4.5: Overview of Zones Under Supervisory Condition..........................................................................134
7.4.6: Overview of Zones with Active Gas Alarm....................................................................................134
7.4.7: Overview of Trouble Zones ............................................................................................................134
7.4.8: Overview of System Faults..............................................................................................................134
7.5: View...........................................................................................................................................................135
7.5.1: Configured Zones............................................................................................................................135
7.5.2: Disabling..........................................................................................................................................135
7.5.3: Event History...................................................................................................................................135
7.5.4: Alarm History..................................................................................................................................136
7.6: Operations at Access Level 2 ....................................................................................................................136
7.6.1: Sounder Silencing............................................................................................................................137
7.6.2: Control Panel Reset.........................................................................................................................137
7.6.3: Evacuation.......................................................................................................................................137
7.7: Enable/Disable...........................................................................................................................................137
7.7.1: Whole Sensor Zone .........................................................................................................................137
7.7.2: Whole Actuator Zone......................................................................................................................137
7.7.3: Individual Devices...........................................................................................................................137
7.7.4: Local Sounder..................................................................................................................................138
7.8: Management ..............................................................................................................................................138
7.8.1: Loop Reset ......................................................................................................................................138
7.8.2: Date and Time Changing..................................................................................................
..................................................................................................................................................139
7.8.3: Tes
t
Control Panel Test..............................................................................................................................139
Zone Test............................................................................................................................................139
7.9: Operations at Access Level 3 ....................................................................................................................140
7.10: Configuration.............................................. .................................. ...........................................................140
7.10.1: 4-20mA Modules........................................................................ ...................................................140
7.10.2: Fire Extinguishing Modules ................................................................................. .........................141
7.10.3: Communications.................................................................... ........................................................142
Printer.................................................................................................................................................142
Host Computer................................................................ .................................. ..................................143
TCP-IP................................................................................................................................................144
7.10.4: Standard Options ................................................................................. ..........................................145
7.10.5: Change Password............................................... .................................. ..........................................146
...............138
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 11
Page 12
Table of Contents
7.11: Event Displaying......................................................................................................................................146
7.11.1: Disabled Condition.................................. .................................. ....................................................147
7.11.2: Trouble Condition........................................................ .................................. ................................148
7.11.3: Fire Pre-alarm Condition................................. .................................. ............................................149
7.11.4: Fire Alarm Condition.....................................................................................................................149
7.11.5: Supervisory Condition..................... ................................. .................................. ...........................150
7.11.6: Gas Alarm Condition................................................... .................................. ................................150
7.12: Burglar Alarm Section (Security)............................................................................................................151
7.13: Access to Operator Functions..................................................................................................................151
7.14: Operations at Access Level 1............................................................ .......................................................152
7.15: Operations at Access Level 2............................................................ .......................................................152
7.16: Exclude/Include ......................................................................................... ..............................................153
7.16.1: Zone............................................................... .................................. ..............................................153
7.16.2: Individual Devices............................................................ .................................. ...........................153
7.17: View............................................ .................................. .................................. .........................................153
7.17.1: Configured Zones ........................................................... ................................. ..............................153
7.17.2: Zone Status ........................................................................................ ............................................154
7.17.3: Control Panel Tamper Status.........................................................................................................154
7.17.4: Disabling................................. .................................. .....................................................................154
7.17.5: Event History.................... .................................. .................................. .........................................154
7.17.6: Alarm History............................... .................................. ................................. ..............................154
7.18: Operations at Access Level 3............................................................ .......................................................154
7.19: Disable/Enable.............................................................. .................................. .........................................155
7.19.1: Individual Devices............................................................ .................................. ...........................155
7.19.2: Local Sounder............................................................................... .................................................155
7.20: Test................................................. .................................. ........................................................................155
7.21: Configuration............................ ................................. .................................. ............................................156
7.21.1: Time Slots.................................................................................. ....................................................156
7.21.2: Holidays............................................................................... ................................ ..........................157
7.21.3: Standard Options .................................................................... .................................. . ....................158
7.21.4: Change Password..................................... .................................. ....................................................159
7.22: Notes on CPU Redundancy .....................................................................................................................159
Appendix A: Parts List.........................................................................................................160
A.1: Steelwork...................................................................................................................................................160
A.2: Power Supply Sets ....................................................................................................................................160
A.3: Central Unit Rack......................................................................................................................................161
A.4: I/O Rack....................................................................................................................................................161
A.5: I/O Modules ..............................................................................................................................................161
A.6: Termination Modules ................................................................................................................................162
A.7: Blank Panels..............................................................................................................................................162
A.8: Cables........................................................................................................................................................162
Appendix B: Compatible Devices .......................................................................................163
B.1: Hochiki Conventional Detectors...............................................................................................................163
B.2: Hochiki Addressable Devices ........................................................................................ ...........................163
B.3: Honeywell Addressable Devices...............................................................................................................164
B.4: Apollo Addressable Devices.............................................................. .......................................................164
B.5: System Sensor Addressable Devices.........................................................................................................166
B.6: Visual and Audible Alarm Devices...........................................................................................................167
Appendix C: Power Supply Set Dimensions......................................................................168
C.1: H-S81-HS Control Panel Absorption........................................................................................................168
C.2: Absorption of Hochiki Conventional Detectors........................................................................................168
C.3: Absorption of Hochiki Addressable Devices............................................................................................169
C.4: Absorption of Honeywell Addressable Devices .......................................................................................169
C.5: Absorption of Apollo Addressable Devices..............................................................................................170
12 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 13
Table of Contents
C.6: Absorption of System Sensor Addressable Devices.................................................................................171
C.7: External Load Absorption.........................................................................................................................172
C.8: Calculation of Total System Absorption...................................................................................................172
C.9: Calculation of Battery Capacity................................................................................................................172
Appendix D: Adhesive Labels .............................................................................................174
D.1: CPR Adhesive Label........................................................... ................................. .....................................174
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 13
Page 14

General Information

!
!

Related Documentation

For specific and detailed information on the H-S81-HS panel and system, please refer to following documents:
Document number Name
ST-058-IT Installation and user manual (this manual) ST-071-IT Safety Manual ED-Cxxxxx-Fyy-Rz Wiring diagram (specific to each control panel) ST-015-IT Programming software PRO-S81 ST-021-IT Graphic supervisory program IRIDE ST-057-IT Honeywell OPC Server ST-007-IT Modbus RTU protocol

Acronyms

CPU Central processing unit EMC Electromagnetic compatibility I/O Input/output PSU Power supply unit TCP/IP Network protocol START-UP System start-up c.c.s. Monitoring & signaling system d.e.c. Monitoring & automatic delay electronic device a.d.a. Power supply equipment

Important Notices

Notices throughout this manual inform the reader of practices and conditions, which will affect physical safety, occupant safety, and equipment performance. Notices appear as:
NOTE: Useful information to help operate the H-S81-HS Panel.
CAUTION: POSSIBLE DAMAGE
INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS, RUNTIME ERRORS, OR EQUIPMENT DAMAGE.
WARNING: POSSIBLE INJURY
INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA, OR PERSONAL INJURY.
14 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 15

Section 1: General Description

Figure 1.1 System Architecture
This chapter provides a general description of the H-S81-HS control panel, listing the system’s main technical features.

1.1 Architecture of the System

The H-S81-HS control panel is a high technology product created for controlling safety-related sys­tems and equipment. It is characterized by easy configuration and programming, combined with excellent reliability and system diagnosis. The H-S81-HS is similar to a “safety PLC” and can be configured and programmed for carrying out integrated safety functions including fire prevention, gas detection, burglar alarm and technological control in compliance with applicable standards. The H-S81-HS can also interact with other control panels of the same type and with supervisory sys­tems via both standard and proprietary protocols such as TCP/IP Ethernet, Modbus RTU, or OPC Server.
Each system includes a power supply set, a processing unit (which is also the user interface), and the I/O modules controlling field devices. Both the processing unit and the I/O modules are located on 19 inch racks. There are two ways of connecting modules and field devices:
The first solution consists in the use of termination modules equipped with a terminal block allowing to connect the cables from field device. In this case, I/O modules are connected to the termination modules by using a 20 way flat cable. The termination module type and the relevant connections depend on the type of module to be terminated.
The second solution consists in the use of multi-polar cables directly connected to bus back through a DIN41618 connector. This solution allows for a redundant module termination. It also allows for the termination of high current output modules, which is not possible by adopting the first solution (S81-F5004).
The H-S81-HS system has a modular structure. The processing rack includes two CPUs and an operator interface panel. Each CPU can be connected to a maximum of 10 racks, with up to 13 I/O modules each, for a total amount of 130 modules. I/O modules can be installed on the racks without any limitations, according to the requirements of the specific system under consideration.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 15
Page 16
General Description Mechanical Structure
Rear Connections
System Status
LEDs
Display
Keypad
Base Rack
CPU boards and LAN ports.
Module Rack
Rack Controller
13 I/O modules
per each rack
Figure 1.2 Module Rack

1.2 Mechanical Structure

The H-S81-HS system is a modular unit consisting of 19” 3-unit high anodized aluminum racks; they will be installed in a metal cabinet with revolving rack and acrylic glass door. It can include a variable number of racks (2 to 11), according to the specific needs.
The first rack is always required. It includes the Base with one or two CPUs, the operator interface display and the keyboard. Modules can be installed from the 2nd rack on. They will be arranged by type and number according to the requirements of the system to be protected. Besides the versions designed to the customer's request, 3 versions with certified structure and cabinet are available for the European market:
H-S81-HS/1R: Base rack + 1 module rack, wall cabinet W=600, H=700, D=400mm
H-S81-HS/2R: Base rack + 2 module rack, wall cabinet W=600, H=1100, D=400mm
H-S81-HS/10R: Base rack and up to 10 module racks, for ground floor installation W=800, H=2100, D=800mm
Each module is connected to field devices by a flat cable and an electronic terminal block fitted on a DIN bar at the bottom of the switchboard; alternatively, modules can be connected to field devices by pre-wired connectors connected to electromechanical terminal blocks.
16 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 17
General Features General Description

1.3 General Features

• Serial communication interface: 2 x RS232
• Ethernet communication interface: 10/100BaseT with RJ45 connector
• Maximum number of programmable zones: 300 fire alarm zones + 300 burglar alarm zones
• Maximum number of programmable points per zone: 99 inputs 99 outputs 99 links
• Exportable local variables via network: Max. 250
• Importable remote variables via network: Max. 999
• System variables (Local): 64
• Maximum number of modules: 130 (10 rack version)
• Time slots with holiday management: 10 (with 10 intervals each)
• CPU redundancy: Optional
• I/O bus redundancy: Optional
• Module redundancy: Optional only for safety related modules
• Hot swap capability: Available for all modules
• Centralization between control panels: Via LAN network with RCP protocol
• Supervisory system: Max. three supervisors per control panel
• Management of time slots: 10 categories with management of holidays
• Default outputs: 16 SPDT contacts
• Default inputs: 10 opto-isolated inputs
• Available protocols: MODBUS RTU
NOTE: In order to comply with the requirements of EN54-2 standard, a maximum of 32
detectors and/or fire alarm buttons can be set in each zone of the area-1.

1.3.1 Mechanical Properties

H-S81-HS/1R
• Steelwork type Metal, with transparent door and revolving inner door
• Color RAL 7035
• Protection class IP30
• Type of installation Wall installation
• Dimensions H=700mm W=600mm D=400mm
H-S81-HS/2R
• Steelwork type Metal, with transparent door and revolving inner door
• Color RAL 7035
• Protection class IP30
• Type of installation Wall installation
• Dimensions H=1100mm W=600mm D=400mm
H-S81-HS/1-10R
• Steelwork type: Metal, with transparent door and revolving inner door
• Color: RAL 7032
• Protection class: IP30
• Type of installation: Floor ground installation
• Dimensions: H=2100mm W=800mm D=800mm
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 17
Page 18
General Description General Features
!

1.3.2 Electrical Characteristics

• Supply voltage 110-240 V~ (-15% + 10%)
• Nominal frequency of the power supply 50-60Hz
• Power supply set output voltage 25VDC ±2%

1.3.3 Reference Standards

The H-S81-HS system was developed complying with the requirements of the following European standards:
Reference standard Description
EN-54-2:1997 / A1:2006 Fire detection and fire alarm systems
Part 2: Control and indicating equipment
EN-54-4: 1997 / A1:2002 / A2:2006 Fire detection and fire alarm systems
Part 4: Power supply equipment
EN-12094-1:2003 Fixed firefighting systems. Components for gas extinguishing systems.
EN-60950-1:2001 Information technology equipment – Safety - part 1:
CEI 79-2:1998 + Ab2000 Intruder, burglar, hold up and anti-attack alarm systems. Particular requirements
Requirements and test methods for electrical automatic control and delay devices
General requirements
for apparatus.

1.3.4 Climatic Conditions

The table below summarizes the climatic conditions for H-S81-HS system operation and storage. The climatic conditions refer to the whole system.
Parameter Allowed range Notes
Operating temperature -5 - 50°C Storage temperature -40 - 85°C Operating humidity 5 - 95% RH Non-condensing Storage humidity 5 - 95% RH Non-condensing
NOTE: The operating temperature inside an electronic device significantly affects the duration of its useful life. High operating temperatures and sharp temperature increases will significantly reduce electronic device life. It is extremely important that the environmental operating conditions are within the allowed ranges.
WARNING: REMOVE BATTERIES
SHOULD STORAGE TEMPERATURE BE LOWER THAN -30°C OR EXCEED +60°C, REMOVE THE LITHIUM BATTERY ON CENTRAL UNITS (S81-U1002-1 MODULES).

1.3.5 Mechanical Conditions

The table below summarizes the type of mechanical tests undergone by the H-S81-HS system.
Standard Test Test Levels
IEC 68-2-6 Vibration sinusoidal test (endurance) Frequency range: 10-150Hz
IEC 817 Impact test Impact energy: 0.5J
18 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Acceleration amplitude: 0.5g Number of axis: 3 Number of sweep cycles: 20 per axis
Number of impact per point: 3
Page 19
Safety and Availability of the H-S81-HS System General Description
!
Figure 1.3 “Mono” Configuration

1.3.6 Electromagnetic Compatibility (CE)

The H-S81-HS system has been designed and tested for resisting to standard levels of radiated and conducted electromagnetic interference, and electrostatic discharges. The table below lists the types and levels of the tests undergone by the H-S81-HS system.
Basic Standard Date Title Noise Immunity Tests
EN 61000-4-2 A1 A2
EN 61000-4-3 A1 A2
EN 61000-4-4 A1 A2
EN 61000-4-5 A1
ENV 50141 1994 Conducted disturbances induced by radio-
EN 61000-4-11A11994
1995 1998
Electrostatic discharge immunity test
2001 1996
Radiated, radio-frequency, electromagnetic
1998
field immunity test
2001 1995
2001
Electrical fast transients/bursts immunity test
2001 1995
Surge immunity test
2001
frequency fields immunity test Voltage dips, short interruptions and voltage
2001
variations immunity test
6 kV contact discharge 8 kV air discharge
10 V/m, 80 MHz-2 GHz, 80% AM
2 kV power supply 1 kV signal lines
2 kV common mode 1 kV differential mode
10 V, 150 kHz-80 MHz, AM 60% 200ms
100% 100ms
CAUTION: ELECTROMAGNETIC COMPATIBILITY
ELECTRICAL DISTURBANCES VARY SIGNIFICANTLY ACCORDING TO THE TYPE OF INSTALLATION AND WIRING DISTANCE TO AND FROM OTHER DEVICES. THEREFORE, IT IS IMPORTANT TO MAKE SURE THAT THE ELECTROMAGNETIC INTERFERENCE LEVELS DO NOT EXCEED THE VALUES REPORTED IN THIS TABLE.

1.4 Safety and Availability of the H-S81-HS System

The H-S81-HS system is intended for use in applications requiring a high safety level, together with high system availability. According to the required safety and availability levels, different H-S81-HS system configurations can be provided.

1.4.1 Possible Configurations of the H-S81-HS System

“Mono” Configuration
This solution includes the duplicated central unit and the I/O modules in a single configuration.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 19
Page 20
General Description Safety-Related Modules in the H-S81-HS System
Figure 1.4 “Duplex” Configuration
“Duplex” Configuration
This solution is characterized by a redundant configuration for both the central unit and the I/O modules. Module redundancy increases system availability. In case of error or failure of a module in “duplex” configuration, the broken module is automatically pu t in safety condition (OFF) whereas the redundant one keeps operating. I/O module redundancy is possible only with safety related modules.

1.5 Safety-Related Modules in the H-S81-HS System

This paragraph describes the measures undertaken by safety related modules in order to guarantee the required reliability of the various applications.

1.5.1 Central Unit

The CPU features an external watchdog circuit that activates in case of failure. In standard operat­ing conditions, the CPU cyclically tests the memory, internal voltage values and the status of RAM lithium batteries. Should it detect any faults, the module would set in safety condition. If there is a redundant CPU, the new CPU will carry out the monitoring functions without any interruption s. The broken CPU can be replaced without the need of switching off the system.
20 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 21
Safety-Related Modules in the H-S81-HS System General Description
Figure 1.5 Digital Input Test
Figure 1.6 Analog Input Test

1.5.2 Digital Input Modules

Safety-related digital input modules feature a circuit allowing to simulate the opening and closing of each channel. During operation, channels are cyclically tested. It a redundant module exists, the control panel keeps operating and gathering data from this module, guaranteeing maximum system availability. The broken module can be replaced without the need of switching off the system.

1.5.3 4-20mA Input Modules

4-20mA safety-related input modules feature two separated measuring circuits per input channel. The two measured current values are, hence, compared between them and in case of difference between the two values the channel is set in failure condition. It a redundant module exists, the con­trol panel keeps operating and gathering data from this module, guaranteeing maximum system availability. The broken module can be replaced without the need of switching off the system.

1.5.4 Output Modules

Safety-related output modules feature two control drivers connected in series. During operation, the output channels are cyclically tested by reversal of output status for some hundreds of microsec­onds. In case of difference between channel set status and the measured one, the whole module is excluded from operation and its outputs are put in safety condition. (Shut-down) If a redundant module exists, the control panel keeps operating and gathering data from this module, guaranteeing maximum system availability. The broken module can be replaced without the need of switching off the system.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 21
Page 22
General Description Safety-Related Modules in the H-S81-HS System
Figure 1.7 Digital Output Test

1.5.5 Central Unit Safety Switch-off

During operation, central units cyclically test the main 25V and local 3.3V power supply voltage values. If one of these values is not within the allowed range, a safety switch-off sequence is carried out in order to put the whole system in safety condition. During this sequence, the following opera­tions are carried out:
Activation of the main FAULT and SYSTEM FAULT outputs.Deactivation of the main RUN output.Deactivation of the RUN LED on the CPUPANEL SHUT-OFF indication on the display
In this condition, output status is frozen. Restart the system to clear this condition.
Allowed 25V voltage range: 18.5 - 32VDC (A warning condition is reported with voltage values <22.5 V and >29.5.)
Allowed 3.3V local voltage range: 3.15 - 3.6VDC (This function is carried out by an external reset circuit with voltage values >3.15 V.)
In the configurations with redundant CPU, if the sequence is carried out only by the primary CPU, the secondary one signals primary CPU failure and starts controlling the system without any inter­ruption of system operation. If, instead, the sequence is carried out only by the secondary CPU, the primary one signals secondary CPU failure and keeps carrying out its functions.

1.5.6 Central Unit Safety Shut-down

In case of critical failures during operation, the central unit will carry out a safety shut-down sequence in order to put the whole system in safety condition. The following failures will cause a safety shut-down:
Error in checking memory content (Flash/Ram).
Internal hardware failure
Restart the system to clear this condition. In the configurations with a redundant CPU, if the sequence is carried out only by the primary
CPU, the secondary one signals primary CPU failure and starts controlling the system without any interruption of system operation. If, instead, the sequence is carried out only by the secondary CPU, the primary one signals secondary CPU failure and keeps carrying out its functions.
22 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 23
Communication Network Between Control Panels General Description
Figure 1.8 Communication Network Between Control Panels

1.6 Communication Network Between Control Panels

By using CPU Ethernet interface, the logic status of the rules (Checked/Not checked) can be exchanged between several control panels. Control panels are divided into two categories: Master (receiving) and Slave (transmitting). Each control panel in the network can be indifferently slave only , master only or slave/master. Slave control panels send to Master ones all the sate changes of the rules set as remote in master control panel. For every panel can be imported up to 999 remote rules and can be exported up to 250 local rule. A maximum of 32 control panels can be connected to each other in a network. Master control panels receive and process the sate changes sent from slave control panels, and cyclically check the connection with the Slave control panels connected to them. When the system is switched on, Master control panels request the IP address from the Slave ones existing in the configuration. Therefore, they send them the message identification code (ID code). This code is generated random and is dynamically changed every minute and compared with the one included in the messages from the Slave control panel for message validation. If the code of a received message is not valid, the message is rejected. Master control panels make a new sub­scribe to Slave control panels every hour, for checking the existence of any configuration changes. If Slave control panel response is correct, the Master control panel will wait for the status changes from Slave control panels. During operation, the Master control panel cyclically tests the efficiency of the connection to Slave control panels, and, in case of disconnection, signals it on the display. Signal propagation time between the various control panels may vary according to network traffic. However, in case of dedicated networks it will not exceed two seconds. Control panel network can be made of copper or optical fiber by using the proper converters allowing a redundant loop con­nection able to support a possible failure or fiber break.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 23
Page 24
General Description Communication Protocol for Supervisory Systems
Figure 1.9 Control Panel Remote Monitoring
Error Messages of the Communication Network:
The following error messages concerning communication networks can be shown on control panel displays:
Message Type Control Panel Error Type
ID xxx Communication failure 100 Master The master cannot communicate with the slave ID xxx Communication failure 101 Master Remote rule referred to the control panel ID xxx Communication failure 5 Slave The slave cannot communicate with the master ID xxx Remote rule nnn undefined Master Undefined remote rule

1.7 Communication Protocol for Supervisory Systems

H-S81-HS systems can be connected to IRIDE supervisory system via LAN network or point-to­point serial connection. A maximum of 2 supervisors per control panel can be configured on the LAN network, and one on Host serial port. In both cases, a dedicated protocol is used. The connec­tion between control panels and supervisors can be made of copper, optical fiber or copper/fiber (mixed), for meeting different needs. For using IRIDE supervisory program, please refer to the spe­cific manual ST-021-IT.
24 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 25
OPC Server General Description
Figure 1.10 Example of Connection with OPC Server

1.8 OPC Server

Thanks to the program OPC Server, any Windows OPC Client applications (Scada/DCS, supervi­sors, control or other applications) can communicate to H-S81-HS series control panels featuring V2.0.0 or higher software version. The OPC Client application can interact with all variables made available by the control panel following the modes defined by the OPC standard. By using the pro­gram OPC Server, clients can access the following data:
•Alarms
Analog value measurements
Device status indications
Control panel status indications
Communication status indications
For using the program OPC Server, please refer to the specific manual ST-057-IT.

1.9 Programming

H-S81-HS system programming is carried out through a personal computer in OFF-LINE mode by means of a specific configuration program. After completing the configuration and checking that the entered data are correct, data can be transferred to the central unit. Once they have been trans­ferred, the central unit replaces the old configuration with the new one and re-initializes the system. If there are two CPUs, the configuration is transferred to both at the same time. For using the con­figuration program Pro-S81, please refer to the specific manual ST-015-IT.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 25
Page 26
General Description Programming
Figure 1.11 Configuration Program
26 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 27

Section 2: Parts of the H-S81-HS System

Figure 2.1 S81-PU001 Power Supply Set
This chapter provides a detailed description of all the parts making up the H-S81-HS system.

2.1 Power Supply Set

The H-S81-HS control panel can be equipped with the following power supply sets:
S81-PU001 power supply set for base plate installation.
S81-PU002 power supply set for rack installation.
NOTE: The power supply set S81-PU002, for rack installation, can only be used in the version with ground-floor steelwork.

2.1.1 S81-PU001 Power Supply Set

This is a power supply set to be fitted on a base plate. It consists of a maximum of 4 x 25 Watt power supply units, PU-A0005-1 model, plus one PU-A0004-1 battery charger module able to sup­ply a 2 or 4 ampere adjustable battery charge current. Power supply units are connected in parallel, up to a maximum of four units amounting to a total of 16 amperes. Under normal operating condi­tions, a simplified test is carried out every 30 seconds in order to check the proper presence of the batteries. A full test, instead, is carried out every hour in order to check electrical connections and battery efficiency. During battery trickle charge, battery voltage is compensated automatically according to the temperature. In case of mains voltage failure, batteries are automatically switched to the load without any interruptions. Should the full charge stage exceed 24 hours, the power sup­ply unit will signal a battery fault. In case of primary power supply failure, the system will shut bat­teries down when the on-load voltage is lower than 18VDC in order to avoid damaging the batteries. The set features three open collector outputs for replicating the various types of faults to the alarm control panel, along with a RS232 port for the connection to a supervisory system.
Technical Features
• Input voltage: 110-240V~ (-15% - 10%)
• Free-air operating temperature: -5 °C - 50 °C
• Relative humidity: 93% non-condensing
• Protection class: IP20
• Nominal output voltage: 25VDC
• Max. output current: 4A/8A/16A
• Protections: Line fuse T6.3A H 250V (5x20)
• Battery voltage: 26.2 to 28.7 VDC, compensated automatically
• VBAT Ripple: < 100mV pK-pK at maximum current
• Resistance to mains voltage dips: >=20mS at maximum current (with PU-A0005)
• Maximum battery current: 4A
• Protections: Over-voltage, short circuit and battery reverse polarity
• Reference standards: EN54-4
• EC reference standards: EN50081-2 & EN50082-2 (industrial environment)
• Safety: EN60950 (CEI-74-2)
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 27
Page 28
Parts of the H-S81-HS System Power Supply Set
Technical features of the S81-PU001 power supply set according to the different configurations:
Features S81-PU001-1 S81-PU001-2 S81-PU001-4
Number of PU-A0005-1 power supply units 1 2 4 Power supply voltage 110-240V~ 110-240V~ 110-240V~ Rated frequency 50-60Hz 50-60Hz 50-60Hz Max. input current at 110V~ 1.6A 3.3A 6.4A Max. input current at 240V~ 0.79 A 1.8 A 3.2A Nominal output voltage 25VDC ±2% 25VDC ±2% 25VDC ±2% Max. residual ripple 266mV 704mV 704mV Minimum output voltage Max. output current Maximum battery resistance Max. battery current 2A 4A 4A Maximum battery capacity 26A/h 26A/h 65A/h
1
2
3
1 Full load output voltage with low batteries in case of main voltage failure 2 Current for the loads plus the current required by the control panel. 3 Internal resistance of the batteries and relevant circuits (Cables, terminals, fuses, etc.)
18.9VDC 18.9VDC 18.9VDC 4A 8A 16A
1.5 Ω 1.5 Ω 1.5 Ω

2.1.2 PU-A0005-1 Power Supply Module

It is a universal switching power supply unit able to provide a maximum current of 4A at 25VDC. It is used in combination with the PU-A0004-1 battery charger in compliance with EN54-4 stan­dard provisions. The power supply unit features a circuit for load distribution which allows the par­allel connection of multiple power supply units, up to a maximum of four units.
Technical Features
• Input voltage: 110-240V~ (-15% - 10%)
• Max. absorbed current at 110V~: 1.6A
• Max. absorbed current at 240V~: 0.79A
• Free-air operating temperature: -5 °C - 50 °C
• Relative humidity: 93% non-condensing
• Frequency: 50-60 Hz
• Power factor (W/VA): 0.6 Typical
• Efficiency: > 80%
• Protection class: IP20
• Dimensions: 200mm x 110mm x 60mm
• Insulation between input and output: >2 MΩ (500VDC)
• Insulation between input and ground: >2 MΩ (500VDC)
• Dielectric strength between input and output: 3000 VAC for 1 minute
• Dielectric strength between input and ground: 1500 VAC for 1 minute
• Output voltage: 25VDC
• Max. output current: 4A
• Ripple: <266mV
• Protections: Line Fuse, over-current, short circuit
28 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 29
Power Supply Set Parts of the H-S81-HS System
!
Internal Connections
INPUT POWER SUPPLY CONNECTIONS
Tag. Terminal Name Function
M1 L input Phase (protected by internal fuse)
TB1
Tag. Terminal Name Function
TB2
Tag. Terminal Name Function
TB3
WARNING: HIGH VOLTAGE
THIS MODULE INCLUDES CIRCUITS WITH VOLTAGE AND CURRENT VALUES POTENTIALLY DANGEROUS FOR PEOPLE.
M2 N input Neutral M3 PE Earth
CURRENT SHARE AND STATUS REPLICATION CONNECTIONS
M1 RL-COM1 Status relay 1 common M2 RL-NO1 Status relay 1 NO M3 RL-COM2 Status relay 2 common M4 RL-NO2 Status relay 2 NO M5 SHARE (+) Signal for load distribution
OUTPUT POWER SUPPLY CONNECTIONS
M1 - V. OUT Output voltage negative M2 - V. OUT Output voltage negative M3 +V. OUT Output voltage positive M4 +V. OUT Output voltage positive

2.1.3 PU-A0004-1 Battery Charger Module

This is a UPS able to control and charge two 12 Volt batteries with a maximum capacity of 65Ah. Battery maximum charge current can be set through a dip­switch on the module. Under normal operating conditions, a simplified test is carried out every 30 seconds in order to check the proper presence of the batter­ies. A full test, instead, is carried out every hour in order to check electrical con­nections and battery efficiency. During battery trickle charge, battery voltage is compensated automatically according to the temperature. In case of mains volt­age failure, batteries are automatically switched to the load without any interrup­tions. Should the full charge stage exceed 24 hours, the power supply unit will signal a battery fault. In case of primary power supply failure, the system will shut batteries down when the on-load voltage is lower than 18VDC in order to avoid damaging the batteries. The set features three open collector outputs for replicating the faults to the alarm control panel, two inputs for monitoring the power supply units and one RS232 port for the connection to a supervisory sys­tem. It can be used together with one or more PU-A0005-1 power supply units. In this case, the resulting power supply set will be fully compliant with the EN54-4:1997/A2:2006 standard.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 29
Page 30
Parts of the H-S81-HS System Power Supply Set
Technical Features
• Input voltage 22-28 VDC
• Free-air operating temperature -5 °C - 50 °C
• Relative humidity 93% non-condensing
• Efficiency > 83%
• Protection class IP20
• Dimensions 200mm x 110mm x 60mm
• Flammability UL94V2
• Battery voltage 26.2 to 28.7 VDC, compensated automatically
• Battery current (1/2/4A) Adjustable through dip switch
• VBAT Ripple < 100mV pK-pK at maximum current
• Resistance to main voltage dips >=20mS at maximum current (with PU-A0005)
• Maximum battery circuit resistance 1.5 ohm
• Maximum battery capacity 65 Ah
• Maximum current to batteries Limited automatically
• Current to the load protected by 20A internal fuse
Internal Connections
CONNECTION OF STATUS OPEN COLLECTOR OUTPUTS
Terminal block Terminal
M1 PSU1 Fault Open collector output - power supply unit section fault
TB1
Terminal block Terminal Name Function
TB2
Terminal block Terminal Name Function
TB3
M2 PSU2 Fault Open collector output - battery charger section fault M3 Charge Status Battery charge status output (energized during the full charge stage).
CONNECTION OF POWER SUPPLY UNIT STATUS INDICATION
M1 AND-Failure Input of voltage failure to all power supply sets M2 OR-Failure Inpu t of voltage failure to one power supply set M3 -V Out M1 and M2 input common
M1 - V. Bat Battery negative M2 +V. Bat Battery positive M3 - V. Load Negative of power supply to the Load M4 +V. Load Positive of power supply to the Load
Name Function
CONNECTIONS TO THE BATTERIES AND TO THE LOAD

2.1.4 S81-PU002 Power Supply Set

This power supply set is able to supply a maximum current of 32 amperes, duplicated to the load, and to control and charge two 12 Volt batteries with maximum capacity of 120Ah. Battery maxi­mum charge current is 6 amperes. Under normal operating conditions, a simplified test is carried out every 30 seconds in order to check the proper presence of the batteries. A full test, instead, is carried out every hour in order to check electrical connections and battery efficiency. Duri ng bat­tery trickle charge, battery voltage is compensated automatically according to the temperature. In case of mains voltage failure, batteries are automatically switched to the load without any interrup­tions. Should the full charge stage exceed 24 hours, the power supply unit will signal a battery fault. In case of primary power supply failure, the system will shut batteries down when the on-load volt­age is lower than 18VDC in order to avoid damaging the batteries. The set features seven open col­lector outputs for replicating the various types of faults to the alarm control panel, along with a RS232 port for the connection to the configuration program Test-PUA009. Ho-swapping is possi­ble for both the 4 AC/DC converters and the battery charger (Hot Plug).
30 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 31
Power Supply Set Parts of the H-S81-HS System
Figure 2.2 S81-PU002 Power Supply Set - Front View
Figure 2.3 S81-PU002 Power Supply Set - Rear View
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 31
Page 32
Parts of the H-S81-HS System Power Supply Set
Technical Features
• Dimensions (H x W x D): 178 x 482 x 355mm
• Input voltage: 110-240V~ (-15% - 10%)
• Max. input current: See tab.1
• Free-air operating temperature: -5 °C - 50 °C
• Relative humidity: 93% non-condensing
• Input voltage frequency: 50-60 Hz
• Power factor (W/VA): 0.6 Typical
• Protection class: IP20
• Insulation between input and output: >2 M Ω (500VDC)
• Insulation between input and ground: >2 M Ω (500VDC)
Power Supply Unit Section
• VLOAD voltage: 25VDC ±2%
• VLOAD maximum current: 32A duplicated
• VLOAD ripple: < 110mV pK-pK at maximum current
Battery Charger Section
• Battery voltage: 26.2 - 28.7 VDC compensated automatically
• Resistance to mains voltage dips: >=20mS at maximum current
• Maximum battery current: 6A
• Maximum battery resistance:
Internal resistance of the batteries and of the relevant circuits (Cables, terminals, fuses, etc.)
Cooling Unit
• Type of cooling Forced ventilation (3 fans)
• Fan absorption 100mA per fan
• Fan average life at 40° C 80,000 hours
Protections
• Line Fuse: T10A H 250V (5x20)
• Protections: Over-voltage, short circuit and battery reverse polarity
Reference Standards
EN54-4
EN50081-2
EN50082-2
EN60950 (CEI-74-2)
32 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 33
Power Supply Set Parts of the H-S81-HS System
Figure 2.4 S81-PU002 Power Supply Set Slot
Possible Configurations
Features S81-PU002-2 S81-PU002-4
Number of PU-A0008-1 power supply units 2 4 Power supply voltage 110-240V~ 110-240V~ Rated frequency 50-60Hz 50-60Hz Max. input current at 110V~ 6A 12A Max. input current at 240V~ 2.7A 5.25A Nominal output voltage 25VDC ±2% 25VDC ±2% Max. residual ripple <115mV <115mV Minimum output voltage Min. output current Max. output current Maximum battery resistance Max. battery current 6A 6A Maximum battery capacity 2x12V 120Ah 2x12V 120Ah
1
2
2
3
18.9VDC 18.9VDC
8A duplicated 20A duplicated
12A duplicated 32A duplicated
0.1 0.05
1 Full load output voltage with low batteries in case of mains voltage failure 2 Current for the loads plus the current required by the control panel 3 Internal resistance of batteries and relevant circuits. (Cables, terminals, fuses, etc.)

2.1.5 PU-A0007-1 Drawer with Slots

Description
It is a 19 inch rack that can contain a PU-A0009-1 battery charger module and up to four PU-A0008-1 power supply modules. It features ventilation, consisting in three fans with a diameter of 120 mm. The terminal blocks for power supply and status replication connection are located on slot back.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 33
Page 34
Parts of the H-S81-HS System Power Supply Set
Figure 2.5 S81-PU002 Power Supply Set Connections
Internal connections
Line- 1 input voltage
Tag Faston Name Function
F1 L1 Primary power supply 1 phase
1
F2 N1 Primary power supply 1 neutral F3 PE1 Primary power supply 1 earth
Line- 2 input voltage
Tag Terminal Name Function
F1 L2 Primary power supply 2 phase
2
F2 N2 Primary power supply 2 neutral F3 PE2 Primary power supply 2 earth
NOTE: The PU-A0008-1 modules installed in slot 2 and 3 are connected to line 1 network input. The PU-A0008-1 modules installed in slot 4 and 5 are connected to lin e 2 network input.
Main earth
Tag Screw Name Function
3 V1 PE Rack earthing
Cooling fans
Tag Terminal Name Function
M1 S Fan speedometer signal
4-5-6
M2 -V Fan power supply negative M3 +V Fan power supply positive
Output voltage
Tag Terminal Name Function
M1 +VLOAD Supply voltage positive
7
M2 -VLOAD Supply voltage negative M3 +VBAT Battery positive M4 -VBAT Battery negative
34 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 35
Power Supply Set Parts of the H-S81-HS System
Open collector replications
Tag Terminal Name Function
M1 PSU1-Fault Primary power supply failure M2 PSU2-Fault Secondary power supply failure M3 Fault Internal failure M4 Battery status Battery status (charge/supply)
8
M5 Charge Status Battery charge status (full charge/trickle charge) M6 Rip.1 Programmable output M7 Rip.2 Programmable output M8 GND External temperature probe display M9 +S External temperature probe positive
M10 -S External temperature probe negative
RS 232
Tag Pin Name Function
1 N.C. Not used 2 Txd RS232 data transmission 3 Rxd RS232 data reception 4 N.C. Not used
9
5 GND RS232 common 6 N.C. Not used 7 N.C. Not used 8 N.C. Not used 9 N.C. Not used

2.1.6 PU-A0008-1 Power Supply Module

Description
It is a switching power supply unit with universal input able to pro­vide a maximum current of 20A at 25VDC. It is placed in a 19 inch rack slot and used in combination with the PU-A0009-1 battery char­ger in compliance with EN54-4 standard. The power supply unit fea­tures a circuit for load distribution which allows the parallel connection of multiple power supply units, up to a maximum of four units. Module hot swapping is allowed (Hot Plug). On the front panel there are: two green LEDs signaling the proper presence of input and output voltage; a yellow LED that lights up in case of failure; and a button for shutting the module down before hot-swapping.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 35
Page 36
Parts of the H-S81-HS System Power Supply Set
!
Technical Features
• Input voltage: 110-240V~ (-15% -10%)
• Free-air operating temperature: -5 °C - 50 °C
• Relative humidity: 93% non-condensing
• Input voltage frequency: 50-60 Hz
• Power factor (W/VA): 0.6 Typical
• Efficiency: > 80%
• Protection class: IP20
• Dimensions: 128mm x 96mm x 250mm
• Flammability: UL94V2
• Insulation between input and output: >2 MΩ (500VDC)
• Insulation between input and ground: >2 MΩ (500VDC)
• Dielectric strength between input and output: 3000 VAC for 1 minute
• Dielectric strength between inputs and ground: 1500 VAC for 1 minute
• VLOAD voltage: 25VDC ±2%
• VLOAD current: 20A
• Max. starting current: 25A
• VLOAD ripple: < 110mV pK-pK at maximum current
• VLOAD output stability: > 1%
• Line Fuse: T10A H 250V (5x20)
• Protections: Over-voltage, short circuit
WARNING: HIGH VOLTAGE
THIS MODULE INCLUDES CIRCUITS WITH VOLTAGE AND CURRENT VALUES POTENTIALLY DANGEROUS FOR PEOPLE.

2.1.7 PU-A0009-1 Battery Charger Module

Description
This is a UPS able to control and charge two 12 Volt batteries with a maxi­mum capacity of 120A/h. Battery maximum charge current can be set through a dip-switch on the module. Under normal operating conditions, a simplified test is carried out every 30 seconds in order to check the proper presence of the batteries. A full test, instead, is carried out every hour in order to check electrical connections and battery efficiency. During battery trickle charge, battery voltage is compensated automatically according to the measured tem­perature. During the full charge stage, instead, it is kept at 27.6VDC In case of mains voltage failure, batteries are automatically switched to the load without any interruptions. Should the full charge stage last more than 24 hours, the battery charger will signal a battery fault. In case of primary power supply failure, the system will shut batteries down when the on-load voltage is lower than 18VDC in order to avoid damaging the batteries. The set features seven open collector outputs for replicating the various types of faults, several inputs for monitoring power supply module and cooling fan status, and one RS232 port for the connection to a supervisory system. It is used together with one or more PU-A0008-1 power supply units. In this case, the resulting power supply set is fully compliant with the EN54-4:1997/A2:2006 standard.
36 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 37
Central Unit Rack Parts of the H-S81-HS System
Figure 2.6 Central Unit Rack
Technical Features
• Input voltage: 22-28 VDC
• Max. absorbed current: 8A
• Free-air operating temperature: -5 °C - 50 °C
• Relative humidity: 93% non-condensing
• Efficiency: > 83%
• Protection class: IP20
• Dimensions: 128mm x 40mm x 250mm
• Flammability: UL94V2
• Battery voltage: 26.2 to 28.7 VDC, compensated automatically
• Battery current: (4/6A) Adjustable through dip switch
• VBAT Ripple: < 100mV pK-pK at maximum current
• Resistance to mains voltage dips: >=20mS at maximum current (with PU-A0008)
• Maximum battery capacity: 120 Ah
• Maximum current to batteries: Limited automatically
• Current to the load: 50A External fuse
• Protections: Over-voltage, short circuit, and battery reverse polarity
• CPD reference standards: EN54-4
• EC reference standards: EN50081-2 and EN50082-2 (industrial environment)

2.2 Central Unit Rack

The central unit includes a central processing unit (CPU) with the relevant bus, the display module and the module for default I/O control. It has the function of processing the data received from the modules and controlling the operator interface and the communication with supervisory systems.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 37
Page 38
Parts of the H-S81-HS System Central Unit Rack
Figure 2.7 S81-E2003-1 Bus
Figure 2.8 RJ45 UTP Connection Cable

2.2.1 S81-E2003-1

Description
It is the interface between the two CPUs and the other peripheral devices making up the system.
Technical Features
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95%(RH) non-condensing
Internal connections
TB1 & TB2: +V/-V
These two Faston terminals are used for supply voltage connection
TAG Function Cable color
TB1 25VDC power supply positive Red TB2 25VDC power supply negative Black
J1: Default I/O
It is a connector for a 14-pole flat cable allowing the connection to the module S81-T8004-1 (default I/O).
J2 & J3: LVDS Bus Loop Link
They are 2 RJ45 connectors for category 5 cable allowing to connect the CPU to the two peripheral modules. This is a closed loop connection, thus allowing to increase system reliability. The J2 con­nector (Bus-IN) must be connected to the BUS-OUT terminal of the last rack, whereas the J3 con­nector (Bus-OUT) must be connected to the BUS-IN terminal of the first rack.
38 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 39
Central Unit Rack Parts of the H-S81-HS System
Figure 2.9 RS232 Connections
J4 & J5: Printer/Debug / Host Computer
Two connectors for 10-pole flat cable, allowing the connection of a 40 or 80 column serial printer and of a PC for configuration data transfer. Use the S81-CFT10/2 cable for connecting to the PC.
J4 Connector
Pin Signal Signal Pin
1DTR DCD 1 3TXD RXD 2 5RXD TXD 3 7 DCD DTR 4 9GND  GND 5 2DTR DSR 6 4CTS RTS 7 6RTS CTS 8 8RI9
10 NU
Direction
DB9 Female
J6: Display
A connector for 20-pole flat cable, allowing the connection to the S81-U1006 display module.

2.2.2 S81-U1002-1

Description
This module is system central unit. Besides the micro-controller, the module includes the following elements: Flash memory, buffered static Ram, watchdog circuit and Ethernet controller. The CPU module can be used in both single and redundant configuration. In this last case, two CPUs operating in parallel are used. Both CPUs process the information received from the modules, but only one of the two CPUs runs the commands. In case of failure of the primary CPU, the other one keeps on carrying out all the tasks without any interruption of the machine cycle.
Technical Features
• Safety rating: applicable up to SIL3
• Micro-controller: Renesas H8-2318 at 25Mhz
• RAM memory: 4 MB, lithium battery buffered
• FLASH memory: 2 MB
• Ethernet Output: 10/100BaseT with RJ45 connector
• Watch Dog: external
• Redundancy YES
• Supply voltage: 22-29VDC
• Quiescent current: 70mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 39
Page 40
Parts of the H-S81-HS System Central Unit Rack
Figure 2.10 S81-U1006-1
Status Indications
The module front panel includes four LEDs indicating the following conditions:
LED Mode Indication
Link
(Green) Activity
(Green)
Run
(Green)
Wdo
(Yellow)
Connections
On module front panel there is an 8-pole RJ45 connector, enabling module connection to the Ether­net network. Through this port, connections with maximum length of 100 mm can be carried out using category 5 cables.

2.2.3 S81-U1006-1

Description
The display module is the interface between the control panel and the operator. It includes a LED­backlit graphic display with 30 lines of 52 characters each, 19 LEDs, 23 buttons, and one buzzer.
= flashing = steady on = off
Ethernet connection link present
No Ethernet connection link Data transmission/receipt on the Ethernet port
No activity on the Ethernet port Primary CPU Secondary CPU
Blocked CPU
Operating CPU Blocked CPU
40 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 41
Central Unit Rack Parts of the H-S81-HS System
Technical features
• Supply voltage: 22-29VDC
• Quiescent current: 70mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• LCD resolution: 320 x 128 pixels
• Backlighting: LED
• Hot swap capability: yes
Status Indications
The front panel includes 14 LEDs with the following functions:
LED Mode Indication
Alarm (Red)
General Trouble (Yellow) General trouble condition Device Trouble (Yellow) Sensors/actuators trouble Sounder Trouble (Yellow) Alarm sounder trouble PSU1 Trouble (Yellow) Primary power supply trouble PSU2 Trouble (Yellow) Secondary power supply trouble Ground Fault (Yellow) Earth leakage System Trouble (Yellow) System trouble Zone Testing (Yellow) Ongoing zone test General disable (Yellow) General disable condition Device disable (Yellow) Disabled sensors/actuators Sounder disable (Yellow) Disabled alarm sounder Output Delay (Yellow) Activation delay timer on Voltage detection (Green) Primary voltage detection
= flashing = steady on
Non acknowledged alarm condition Acknowledged alarm condition
Module rear panel includes 5 LEDs with the following functions:
LED Indication
LD15 (Yellow) Currently not used LD16 (Yellow) Currently not used
CPU-A Link (Green) Steady on when the communication Link with CPU-A is present CPU-B Link (Green) Steady on when the communication Link with CPU-B is present
S81-T8004-1 Link Steady on when the communication Link with S81-T8004-1 is present
Buttons
Button Description of buttons Level Description of the function
Local Buzzer Silencing 1-2-3 Deactivates the local buzzer
System sounder silencing 2-3 Silencing of system fire alarm sounders
Control panel reset 2-3 Resets the control panel
Evacuation command 2-3 Activates system fire alarm sounders
Delay time reset 1-2-3 Cancels output delay timer
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 41
Page 42
Parts of the H-S81-HS System I/O Rack
Figure 2.11 I/O Rack - Front View
Selection cancel 1-2-3 To cancel an operation or to go back to the previous page
Enter key 1-2-3 Confirms a selection made when navigating through operator cycle menus
Arrows for selecting menu direction 2-3 They enable the navigation through operator cycle menus
0-9 key numbers 1-2-3 They are used for entering parameters and access passwords
Scroll 1-2-3 It allows to view the complete list in operator cycle menu
F1 key 1-2-3 It allows to access directly the main page of the active access level
Internal connections
BR1 & BR2: +V/-V
These two Faston terminals are used for supply voltage connection
TAG Function Cable Color
BR1 25VDC power supply positive Red BR2 25VDC power supply negative Black
J2
A connector for 20-pole flat cable, allowing the connection to S81-E2003-1 Bus module.
J3
A 4-pole connector supplying power to the LEDs for display backlighting.
J5
A 10-pole connector connecting the membrane keyboard to the display.

2.3 I/O Rack

Up to ten expansion racks can be connected to an H-S81-HS base. Each can include up to thirteen I/O modules. Position 14 is reserved to the S81-E2002-1 rack controller. Two I/O rack types are available according to the type of terminations to be used.
42 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 43
I/O Rack Parts of the H-S81-HS System
Figure 2.12 S81-E2001-1 - Rear View
Figure 2.13 Flat Cable Connections
20-Pin Ribbon Cable
Connection on Rear Rack
Termination module on DIN rail

2.3.1 S81-E2001-1

Description
This module includes the thirteen modules and the rack controller . Module-field device connections are carried out using flat cables, with the relevant termination module, from the DIN bar. Using this bus, systems with redundant I/O modules are not possible.
Technical Features
• Supply voltage: 22 - 29VDC
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Maximum number of I/O modules: 13
• Field connections: 20-way flat cable
Internal connections
20-pin flat cables are used in this case to connect the rack to the termination module. Flat cable maximum length is 5 meters. The typ e of termination module and the relevant connections depend on the type of module to be terminated. Field devices, in this case, can be easily disconnected by simply disconnecting the flat cables from the termination modules.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 43
Page 44
Parts of the H-S81-HS System I/O Rack
Figure 2.14 S81-E2001-2 - Rear View
Figure 2.15 Multi-conductor Cable Connections

2.3.2 S81-E2001-2

Description
This module includes the thirteen modules and the rack controller . Module-field device connections are carried out by using 3-meter long pre-wired cables. Using this bus, systems with redundant I/O modules are possible.
Technical features
• Supply voltage: 22-29VDC
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
Maximum humidity:
• Maximum number of I/O modules: 13
• Field connections: Multi-conductor cables
95% (RH) non-condensing
Internal connections
Pre-wired cables are used in this case to connect the rack to the terminal block. Standard cable length is 2 meters. The cable type and the relevant connections depend on the type of module to be terminated.
44 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 45
I/O modules Parts of the H-S81-HS System

2.3.3 S81-E2002-1

Description
This module is the rack controller. It allows the information exchange between CPUs and rack modules. It controls 13 point-to-point links to rack modules and two closed loop links for the communication to the two CPUs.
Technical features
• Safety rating: applicable up to SIL3
• Supply voltage: 22-29VDC
• Quiescent current: 20mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
Status Indications
Module front panel includes eight LEDs with the following functions:
LED Indication
A-IN Link (green) Steady on when CPU-0 loop input link is present
A-OUT Link (green) Steady on when CPU-0 loop output link is present
B-IN Link (green) Steady on when CPU-1 loop input link is present
B-OUT Link (green) Steady on when CPU-1 loop output link is present
Run (green) Flashes during operation FLT1 (yellow) Steady on in case of local interrupt FLT2 (yellow) Steady on in case of CPU-A loop interrupt FLT3 (yellow) Steady on in case of CPU-B loop interrupt
Configuration
Modules are configured by means of a 4-way dip switch used to set the number of racks from 1 to 10, according to the table below:

2.4 I/O modules

The following I/O module types are available:
Part Number Description Notes
S81-F3002-1 8 monitored input module for conventional detectors Redundancy not possible S81-F3002-2 8 monitored input module for conventional detectors Redundancy possible S81-F4001-1 Module with 1 x 4-20mA analog input Redundancy not possible S81-F4001-2 Module with 1 x 4-20mA analog input Redundancy possible S81-F4002-1 Module with 2 4-20mA analog inputs Redundancy not possible S81-F4002-2 Module with 2 4-20mA analog inputs Redundancy possible S81-F4003-1 Module with 8 x 4-20mA analog inputs Redundancy not possible S81-F4003-2 Module with 8 x 4-20mA analog inputs Redundancy possible
SW1-1 SW1-2 SW1-3 SW1-4 Rack No.
OFFOFFOFFOFF 1
ON OFF OFF OFF 2
OFF ON OFF OFF 3
ON ON OFF OFF 4
OFF OFF ON OFF 5
ON OFF ON OFF 6
OFF ON ON OFF 7
ON ON ON OFF 8
OFF OFF OFF ON 9
ON OFF OFF ON 10
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 45
Page 46
Parts of the H-S81-HS System I/O modules
S81-F5001-1 Module with 8 x 500mA monitored outputs for solenoids Redundancy not possible S81-F5001-2 Module with 8 x 500mA monitored outputs for solenoids Redundancy possible S81-F5002-1 Module with 16 x 250mA non monitored outputs Redundancy not possible S81-F5003-1 Module with 8 x 250mA monitored outputs for sounders Redundancy not possible S81-F5004-1 Module with 4 x 2A monitored outputs for solenoids Redundancy not possible S81-F5004-2 Module with 4 x 2A monitored outputs for solenoids Redundancy possible S81-F6001-1 Module with 8 outputs for fire extinguishing system control Redundancy not possible S81-F6002-1 Logic module Redundancy not possible S81-F7002-1 Loop control module with ESP protocol Redundancy not possible S81-F7006-1 Modbus RTU Master/Slave module Redundancy not possible S81-F7007-1 Loop control module with SSP protocol Redundancy not possible S81-F7008-1 Control modules for weighing modules Redundancy not possible S81-F7009-1 Loop control module with XP95/Discovery protocol Redundancy not possible S81-F7010-1 Loop control module with System Sensor protocol Redundancy not possible

2.4.1 S81-F3002-1 & S81-F3002-2

Description
Eight balanced input module for conventional safety related sensors. All chan­nels can be reset individually and are tested every 30 seconds during operation. This module is suitable for controlling detection systems with conventio nal lines and can be used in systems with already existing detection lines for con­trolling automatic fire extinguishing systems with double enable logic or intrin­sically safe systems. It is also used for controlling all the devices typical of fire extinguishing systems (pressure switches, discharge buttons, etc.). This module can be duplicated in fault tolerant systems; in this case, the two modules shall be placed on adjacent racks in the same position. In this configuration, the eight detection lines are connected to both modules.
Technical Features
• Safety rating: applicable up to SIL3
• Redundancy: S81-F3002-2 model
• Alarm threshold: 2 programmable thresholds on 255 levels
• Line short circuit current >115mA
• Channel test: every 30 seconds
• Intrinsic Safety Barriers allowed: uZ680+ Pepperl & Fuchs
• Supply voltage: 22-29VDC
• Quiescent current: 14mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
Each one of the eight channels on the front panel includes two status LEDs providing the following information:
Input channel status
Normal −− − − Disabled ⊗− ⊗ − Trouble ∅− ∅ − Tampering −−− −−− Pre-alarm −∅−−− Alarm −⊗ − ⊗
Key to symbols: = steady on LED; = LED off, = flashing LED, −−−= function not available
Indications Line LEDs 1-8 in SAFETY mode Indications Line LEDs 1-8 in SECURITY mode
Yellow LED Red LED Yellow LED Red LED
46 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 47
I/O modules Parts of the H-S81-HS System
Configuration
By using the configuration program ProS81, the following parameters can be set for each input channel:
Function Allowed values in SAFETY mode
Operating mode: Latching-NO, Latching-NC, Non-Latching-NO,
Non-Latching-NC, Alarm verification function Yes/No Disabled Pre-alarm threshold 10-250 Fixed threshold Alarm threshold 10-250 Fixed threshold Channel status with line short circuit Trouble / Alarm Tampering Type of indication Fire, Supervisory, Gas, Trouble , Hidden,
Buzzer Only Automatic alarm reset Yes/No N0 Enable/Disable channel status export to Hosts No, TCP1, TCP2, RS232 No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232 No, TCP1, TCP2, RS232
Allowed values in
SECURITY mode
Latching-NC
Burglar Alarm, Hidden
Field Connection
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
The module is connected to the S81-T8001-1 termination module with 16 terminals by using a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block by the S81-CCT6 16­conductor multi-polar cable. For S81-F3002-2 module redundant connec­tion, use the S81-CCT1R cable.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 47
Page 48
Parts of the H-S81-HS System I/O modules
S81/CCT1R
S81/CCT1
Figure 2.17 Standard Connection Diagram of NO/NC Contacts
Figure 2.18 Standard Connection Diagram of Conventional Detectors
Figure 2.19 Standard Connection Diagram of the Intrinsic Safety Barrier
Function Termination with Flat Cable Termination with Multi-conductor Cable
detection line 1
detection line 2
detection line 3
detection line 4
detection line 5
detection line 6
detection line 7
detection line 8
+ 1
- 22Brown
+ 3 3 Green
- 44Yellow
+ 55Gray
- 66Pink
+ 77Blue
- 88Red
+ 99Black
- 10 10 Violet
+ 11 11 Gray/pink
- 12 12 Red/blue
+ 13
- 14 14 Brown/green
+ 15 15 White/yellow
- 16 16 Yellow/brown
T8001
terminals
view
Rack - rear
S81-T8001-1
1White
13 White/green
Figure 2.16 Field connections
Standard Connection Diagrams
48 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 49
I/O modules Parts of the H-S81-HS System
Figure 2.20 Standard Connection Diagram for Burglar Alarm

2.4.2 S81-F4001-1 & S81-F4001-2

Description
Safety related module with 1 x 4-20mA analog input and two programmable thresholds. It can control the following transducer types: explo sion sensors, air quality sensors, oxygen sensors, temperature sensors, 4-20mA general sensors. The channel is continuously tested during operation. The module features a 4­20mA output that provides the current value measured on the input. This analog value can be transferred to a DCS by means of the S81-F7006-1 Modbus RTU module. This module can be duplicated in fault tolerant systems; in this case, the two modules shall be placed on two adjacent racks in the same position. In this configuration, the detection lines is connected to both modules.
Technical Features
• Safety rating: applicable up to SIL3
• Redundancy: S81-F4001-2 model
• Alarm threshold: 2 programmable thresholds
• Channel test: continuously tested
• Measuring range 0-24mA
• Line short circuit condition: with current >23.5mA
• Supply voltage: 22-29VDC
• Quiescent current: 35mA
• Operating temperature: -5 - 50°C
• Storage temperature: -30 - 80°C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
Module front panel includes three LEDs, a graphic LED bar, and a three-digit display.
Input channel status
Normal −− − Disabled −− ⊗ Trouble −− ¬ Pre-alarm ⊗⊗ − Alarm ⊗− − Key to symbols: = steady on LED; = LED off; = flashing LED
2nd Level 1st Level Fault/Disabled
Red LED Red LED Yellow LED
LED Bar
It indicates the 0-100% percentage of the measured value.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 49
Page 50
Parts of the H-S81-HS System I/O modules
Three-Digit Display
The three-digit display generally shows the measured value in the programmed format. Moreover, it shows some fault codes according to the following table.
No. Channel Status
--- Initialization stage F00 Module/channel not configured F01 Line opening (current <1mA) F02 Over-current (current >23.5mA) F03 Internal test failed Fx.x Device trouble E00 Memory data error CRC
+/-999 Measured value
1 For current values lower than the set trouble threshold and exceeding 1mA, the
display will show the value of the measured current in mA preceded by letter F. Please refer to the manual of the connected device for identifying the type of anomaly.
NOTE: The 3-digit display on module front panel does not provide the operator with fundamental information and does not comply with the standard EN-54-2.
1
Configuration
By using the configuration program ProS81, the following parameters can be set for each input channel:
Function Allowed values
Operating mode Latching/Non latching, UP/Down, NM Mode of analog value transfer to Hosts Upon request/Automatic in case of change Unit of measure of the channel Ppm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm Zero Point of the measuring range -999 - 999 End of scale of the measuring range -999 - 999 Pre-alarm threshold -999 - 999 Alarm threshold -999 - 999 Lower trouble threshold 1,0 - 3,8mA Alarm delay 0 - 255 seconds Type of indication Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Automatic alarm reset Yes/No Enable/Disable status export via ModBus Yes/No Enable/Disable channel status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232 It defines the format of the analog value sent via ModBus,
and automatically via Host
mA, mA tenth, VI, VI tenth, converter points
Threshold Setting
The following parameters can be set for each module through the configuration program or directly on the control panel in the operator cycle, access level 3:
Pre-alarm threshold.
Alarm threshold
Current value below which a trouble condition is signaled
Calibration mixture concentration value for end of scale calibration
50 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 51
I/O modules Parts of the H-S81-HS System
Zero Point Calibration
Calibrate the zero point as reported below:
Disable the channel of the module to be calibrated from the operator cycle.
Enter the diagnosis cycle of the module to be calibrated.
Make sure that no gas is present near the sensor to be calibrated.
Press the “1” key to calibrate the zero point.
The new zero value is stored in the memory of the module.
Press “0” to cancel the operation.
Exit the module diagnosis cycle and enable the channel.
NOTE: The zero point can be calibrated only with zero values ranging between 3 and 5mA.
End of Scale Calibration
Calibrate the end of scale as follows:
Disable the channel of the module to be calibrated from the operator cycle.
Enter the diagnosis cycle of the module to be calibrated.
Apply gas to the sensor according to the percentage set during configuration.
Wait for the gas value measured by the module to stabilize.
Press the key “3” to calibrate the end of scale.
The new value is stored in the memory of the module.
Press “2” to cancel the operation.
Exit the module diagnosis cycle and enable the channel.
NOTE: The end of scale can be calibrated only if the current value measured by the module is ±3mA than the set calibration value.
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi­nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT2 16­conductor multi-polar cable. For S81-F4001-2 module redundant connection , use the S81-CCT2R cable.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 51
Page 52
Parts of the H-S81-HS System I/O modules
S81/CCT2R
S81/CCT2
Figure 2.22 Standard Connection Diagram
Function Termination with Flat Cable Termination with Multi-conductor Cable
Input signal + 1
--- 22
--- 33
--- 44
Output signal + 55Brown
--- 66
--- 77
1White
--- 88
Figure 2.21 Field Connections
S81-T8003-1
Standard Connection Diagrams
52 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 53
I/O modules Parts of the H-S81-HS System

2.4.3 S81-F4002-1 & S81-F4002-2

Description
Safety related module with 2 x 4-20mA analog inputs and two thresholds to be programmed on the module through the operator cycle. The following transducer types can be connected to this module: Explosion Sensors, Air Quality Sensors, Oxygen Sensors, T emperature Sensors, 4-20mA General Sensors. The channel is continuously tested during operation. The module features 4-20mA outputs that provide the current value measured on the input. The analog value of each chan­nel can be transferred to a DCS by means of the S81-F7006-1 Modbus RTU module. This module can be duplicated for fault tolerant systems; in this case, the two modules shall be placed on two adjacent racks in the same position. In this configuration, the two detection lines are connected to both modules.
Technical Features
• Safety rating:
• Redundancy:
• Alarm threshold:
• Channel test:
• Measuring range
• Line short circuit condition:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
applicable up to SIL3 S81-F4002-2 model 2 programmable continuously tested 0-24mA with current >23.5mA 22-29VDC 60mA
-5 - 50 °C
-30 - 80 °C 95% (RH) non-condensing yes
Status Indications
Module front panel includes three LEDs and a three-digit display for each channel.
Input channel status
Normal −− − Disabled −− ⊗ Trouble −− ¬ Pre-alarm ⊗⊗ − Alarm ⊗− − Key to symbols: = steady on LED; = LED off; = flashing LED
2nd Level 1st Level Fault/Disabled
Red LED Red LED Yellow LED
Three-Digit Display
The three-digit display generally shows the measured value in the programmed format. Moreover, it shows some fault codes according to the following table.
No. Channel Status
--- Initialization stage F00 Module/channel not configured F01 Line opening (current <1mA) F02 Over current (current >23.5mA) F03 Internal test failed
Fx.x Device trouble
E00 Memory data error CRC
+/-999 Measured value
1 For current values lower than the set trouble threshold and exceeding 1mA, the display
will show the value of the measured current in mA preceded by letter F. Please refer to the manual of the connected device for identifying the type of anomaly.
1
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 53
Page 54
Parts of the H-S81-HS System I/O modules
NOTE: The two 3-digit displays on module front panel do not provide the operator with fundamental information and do not comply with the standard EN-54-2.
Configuration
By using the configuration program ProS81, the following parameters can be set for each input channel:
Function Allowed values
Operating mode Latching/Non latching, UP/Down, NM Mode of analog value transfer to Hosts Upon request/Automatic in case of change Unit of measure of the channel Ppm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm Zero Point of the measuring range -999 - 999 End of scale of the measuring range -999 - 999 Pre-alarm threshold -999 - 999 Alarm threshold -999 - 999 Lower trouble threshold 1.0 - 3.8mA Alarm delay 0 - 255 seconds Type of indication Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Automatic alarm reset Yes/No Enable/Disable status export via ModBus Yes/No Enable/Disable channel status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232 It defines the format of the analog value sent via ModBus,
and automatically via Host
mA, mA tenth, VI, VI tenth, converter points
Threshold Setting
The following parameters can be set for each module through the configuration program or directly on the control panel in the operator cycle, access level 3:
Pre-alarm threshold.
Alarm threshold.
Current value below which a trouble condition is signaled.
Calibration mixture concentration value for end of scale calibration.
Zero Point Calibration
Calibrate the zero point as reported below:
Disable the channel of the module to be calibrated from the operator cycle.
Enter the diagnosis cycle of the module to be calibrated.
Make sure that no gas is present near the sensor to be calibrated.
Press the “1” key to calibrate the zero point of the channel 1.
Press “0” to cancel the operation for the channel 1.
Press the “5” key to calibrate the zero point of the channel 2.
Press the “4” key to cancel the operation for the channel 2.
Exit the module diagnosis cycle and enable the channel.
NOTE: The zero point can be calibrated only with zero values ranging between 3 and 5mA.
54 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 55
I/O modules Parts of the H-S81-HS System
End of Scale Calibration
Calibrate the end of scale as follows:
Disable the channel of the module to be calibrated from the operator cycle.
Enter the diagnosis cycle of the module to be calibrated.
Apply gas to the sensor according to the percentage set during configuration.
Wait for the gas value measured by the module to stabilize.
Press the key “3” to calibrate the end of scale for channel 1.
Press “2” to cancel the operation for channel 1.
Press the key “7” to calibrate the end of scale for channel 2.
Press “6” to cancel the operation for channel 2.
Exit the module diagnosis cycle and enable the channel.
NOTE: The end of scale can be calibrated only if the current value measured by the module is ±3mA than the set calibration value.
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi­nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT7 16­conductor multi-polar cable. For S81-F4002-2 module redundant connection, use the S81-CCT7R cable.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 55
Page 56
Parts of the H-S81-HS System I/O modules
S81/CCT7
Figure 2.24 Standard Connection Diagram
Function Termination with Flat Cable Termination with Multi-conductor Cable
Input signal 1 + 1
--- 2 2 ---
Input signal 2 + 33Brown
--- 4 4 ---
Output signal 1 + 5 5 Green
--- 6 6 ---
Output signal 2 + 77Yellow
1White
--- 8 8 --­S81-T8003-1
Figure 2.23 Field Connections
Standard Connection Diagrams
S81/CCT7R
56 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 57
I/O modules Parts of the H-S81-HS System

2.4.4 S81-F4003-1 & S81-F4003-2

Description
Safety related module with 8 x 4-20mA analog inputs and two thresholds to be programmed on the module through the operator cycle. The following trans­ducer types can be connected to this module: Explosion Sensors, Air Quality Sensors, Oxygen Sensors, Temperature Sensors, 4-20mA General Sensors. The channels are continuously tested during operation. The analog value of each channel can be transferred to a DCS by means of the S81-F7006-1 Modbus RTU module. This module can be duplicated in fault tolerant systems; in this case, the two modules shall be placed on two adjacent racks in the same position. In this configuration, the eight detection lines are connected to both modules.
Technical Features
• Safety rating: applicable up to SIL3
• Redundancy: S81-F4003-2 model
• Alarm threshold: 2 programmable thresholds for each channel
• Channel test: continuously
• Measuring range 0-24mA
• Line short circuit condition: with current >23.5mA
• Supply voltage: 22-29VDC
• Quiescent current: 13mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
Module front panel includes two status LEDs for each one of the eight channels.
Input channel status
Normal −− Disabled −⊗ Trouble −− Pre-alarm −− Alarm ⊗− Key to symbols: = steady on LED; = LED off; = flashing LED
Indications Line LEDs 1-8
Red LED Yellow LED
Configuration
By using the configuration program ProS81, the following parameters can be set for each input channel:
Function Allowed values
Operating mode Latching/Non latching, UP/Down, NM Mode of analog value transfer to Hosts Upon request/Automatic in case of change Unit of measure of the channel Ppm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm Zero Point of the measuring range -999 - 999 End of scale of the measuring range -999 - 999 Pre-alarm threshold -999 - 999 Alarm threshold -999 - 999 Lower trouble threshold 1.0 - 3.8mA Alarm delay 0 - 255 seconds Type of indication Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Automatic alarm reset Yes/No Enable/Disable status export via ModBus Yes/No Enable/Disable status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232 It defines the format of the analog value sent via ModBus,
and automatically via Host
mA, mA tenth, VI, VI tenth, converter points
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 57
Page 58
Parts of the H-S81-HS System I/O modules
Threshold Setting
The following parameters can be set for each module through the configuration program or directly on the control panel in the operator cycle, access level 3:
Pre-alarm threshold.
Alarm threshold.
Current value below which a trouble condition is signaled
Calibration mixture concentration value for end of scale calibration
Zero Point Calibration
Calibrate the zero point as reported below:
Disable the channel of the module to be calibrated from the operator cycle.
Enter the diagnosis cycle of the module to be calibrated.
Disconnect the channel to be calibrated (1-8).
Make sure that no gas is present near the sensor to be calibrated.
Press the “1” key to calibrate the zero point of the channel.
The new zero value is stored in the memory of the module.
Press “0” to cancel the operation for the channel.
Exit the module diagnosis cycle and enable the channel.
NOTE: The zero point can be calibrated only with zero values ranging between 3 and 5mA.
End of Scale Calibration
Calibrate the end of scale as follows:
Disable the channel of the module to be calibrated from the operator cycle.
Enter the diagnosis cycle of the module to be calibrated.
Disconnect the channel to be calibrated (1-8).
Apply gas to the sensor according to the percentage set during configuration.
Wait for the gas value measured by the module to stabilize.
Press the key “3” to calibrate the end of scale for the channel.
Press “2” to cancel the operation for the channel.
Exit the module diagnosis cycle and enable the channel.
NOTE: The end of scale can be calibrated only if the current value measured by the module is ±3mA than the set calibration value.
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
58 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 59
I/O modules Parts of the H-S81-HS System
S81/CCT3
Figure 2.26 Standard Connection Diagram
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi­nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block by the S81-CCT3 16-con­ductor multi-polar cable. For S81-F4003-2 module redundant connection, use the S81-CCT3R1 cable.
Function Termination with Flat Cable Termination with Multi-conductor Cable
Input signal 1 + 1 Input signal 2 + 22 Input signal 3 + 33 Input signal 4 + 44 Input signal 5 + 55 Input signal 6 + 66 Input signal 7 + 77 Input signal 8 + 88
S81-T8003-1
White
1
Brown Green Yellow Gray Pink Blue Red
S81/CCT3R
Figure 2.25 Field Connections
Standard Connection Diagrams
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 59
Page 60
Parts of the H-S81-HS System I/O modules

2.4.5 S81-F5001-1 & S81-F5001-2

Description
8 x 500 mA monitored control channel module. This is especially suited to con­trol automatic fire extinguishing systems, and can be used both for controlling directional and releasing solenoid valves and evacuation visual and audible alarm devices. During operation, each channel is cyclically tested by the module through reversal of output signal for approximately 200 hundreds of microsec­onds. In case of difference between the set signal and the measured one, the con­trol panel promptly signals a fault. Several channels can be connected in parallel in order to increase the output current. This module can be duplicated in fault tolerant systems; in this case, the two modules shall be placed on adjacent racks in the same position. In this configuration, the eight output lines are connected to both modules.
Technical Features
• Safety rating: applicable up to SIL3
• Redundancy: S81-F5001-2 model
• Channel test: every 2 seconds
• Max. output current: 500mA
• Automatic output protection: Yes
• Supply voltage: 22-29VDC
• Quiescent current: 35mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
Each one of the eight channels on the front panel includes two status LEDs
Output Channel Status
Off −− Disabled ⊗− Trouble ∅− Active −⊗ Key to symbols ⊗= steady on LED; = LED off; = flashing LED
Indications 1-8 Out LEDs
Yellow LED RED LED
Configuration
By using the configuration program ProS81, the following parameters can be set for each output channel:
Function Mode
Operating mode Continuous-Normally Energized, Continuous-Normally de-energized, Intermittent,
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation Timing 1 to 255 seconds/minutes (only for pulsing and intermittent modes) Output type Normal / Sounder Output status in case of CPU fault Frozen in the last status / Off Enable/Disable status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts
on the channel
No, TCP1, TCP2, RS232
60 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 61
I/O modules Parts of the H-S81-HS System
S81/CCT3
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
Thanks to this bus, the module can be terminated by using a S81-T8003-1 termination module with 8 terminals or a S81-T8006-1 8-relay module with a 20-way flat cable.
S81-T8006-1
If this termination type is used, there will be eight relay outputs with one 4A SPDT contact to be used exclusively for connecting circuits operating with SELV voltage. This solution will guarantee coil monitoring for the eight relays.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT3 8-conductor multi-polar cable. For S81-F5001-2 module redundant connection, use the S81­CCT3R cable.
Function Termination with Flat Cable Termination with Multi-conductor Cable
Output 1 + 1 Output 2 + 22 Output 3 + 33 Output 4 + 44 Output 5 + 55 Output 6 + 66 Output 7 + 77 Output 8 + 88
S81-T8003-1
White
1
Brown Green Yellow Gray Pink Blue Red
S81/CCT3R
Figure 2.27 Field Connections
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 61
Page 62
Parts of the H-S81-HS System I/O modules
Figure 2.28 Standard Connection Diagram
Standard Connection Diagrams
NOTE: The module can control resistive or inductive loads with a maximum current of 500mA. If
the module is used for controlling filament lamps, the maximum load power cannot exceed 4W.

2.4.6 S81-F5002-1

Description
Module with sixteen non monitored 250mA open collector outputs. It is also used together with the S81-T8007-2 16-relay module.
Technical Features
• Redundancy: No
• Channel test: No
• Max. output current 250mA
• Automatic output protection No
• Supply voltage: 22-29VDC
• Quiescent current: 10mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
Each one of the sixteen channels on the front panel includes a status LED.
Indications 1-16
Output Channel Status
Channel under normal condition Enabled channel = steady on LED; = LED off
Out LEDs
RED LED
62 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 63
I/O modules Parts of the H-S81-HS System
Configuration
By using the configuration program ProS81, the following parameters can be set for each output channel:
Function Mode
Operating mode Continuous-Normally Energized, Continuous-Normally de-energized, Intermittent,
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation Timing 1 to 255 seconds/minutes (only for pulsing and intermittent modes) Output type Normal / Sounder Output status in case of CPU fault Frozen in the last status / Off Enable/Disable status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts on
the channel
No, TCP1, TCP2, RS232
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
Thanks to this bus, the module can be terminated by using a S81-T8001-1 termination module with 16 terminals or a S81-T8007-2 16-relay module.
S81-T8007-2
When this termination type is used, there will be sixteen relay outputs with one 4A SPDT contact to be used exclusively for connecting circuits operating with SELV voltage.
S81-E2001-2 Bus
Thanks to this bus, the module can be terminated by using a S81-CCT1 16-conductor multi-polar cable or a S81-T8007-2 16-relay module.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 63
Page 64
Parts of the H-S81-HS System I/O modules
Function Termination with Flat Cable Termination with Multi-conductor Cable
Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8
Output 9 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16
Common Positive
- 1
- 22
- 33
- 44
- 55
- 66
- 77
- 88
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
+
S81-T8001-1
White
1
Brown Green Yellow Gray Pink Blue Red Black Violet Gray/Pink Red/Blue White/Green Brown/Green White/Yellow Yellow/Brown White/Gray
S81/CCT1
Figure 2.29 Field Connections

2.4.7 S81-F5003-1

Description
Module with 8 x 250 mA monitored output channels for sounder control. Outputs are controlled by two virtual channels for allowing both continuous and intermit­tent output control. Line is monitored by polarity reversal.
Technical Features
• Redundancy: No
• Channel test: No
• Max. output current 250mA
• Automatic output protection: Yes
• Supply voltage: 22-29VDC
• Quiescent current: 38mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
Each one of the eight channels on the front panel includes two status LEDs.
Output channel status
Off −− Disabled ⊗− Trouble ∅− Active −⊗ Key to symbols = steady on LED; = LED off; = flashing LED
Indications 1 - 8 Out LEDs
Yellow LED RED LED
64 H-S81-HS Installation & Operation Manual — Form Number XX-XXXX—X P/N LS10114-000HI-E:A 2/24/2015
Page 65
I/O modules Parts of the H-S81-HS System
Configuration
By using the configuration program ProS81, the following parameters can be set for each output channel:
Function Mode
Operating mode Continuous-Normally Energized, Continuous-Normally de-energized, Intermittent,
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation, ANSI-S3.41, March Timing 1 to 255 seconds Output type Normal / Sounder Output status in case of CPU fault Frozen in the last status / Off Enable/Disable status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts on
the channel
No, TCP1, TCP2, RS232
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
Thanks to this bus, the module can be terminated by using a S81-T8001-1 termination module with 16 terminals.
S81-E2001-2 Bus
Thanks to this bus, the module can be terminated by using a S81-CCT1 16-conductor multi-polar cable or a S81-T8008-1 module.
S81-T8008-1
Should 500 mA per line not be enough, it is possible to connect the optional module S81-T8008-1 to module S81-F5003-1. The former will add 4 x 2A at 24 VDC polarity reversal outputs.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 65
Page 66
Parts of the H-S81-HS System I/O modules
Figure 2.31 Standard Connection Diagram
Function Termination with Flat Cable Termination with Multi-conductor Cable
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
+ 1
- 22
+ 33
- 44
+ 55
- 66
+ 77
- 88
+ 9
- 10
+ 11
- 12
+ 13
- 14
+ 15
- 16
S81-T8001-1
White
1
Brown Green Yellow Gray Pink Blue Red Black Violet Gray/Pink Red/Blue White/Green Brown/Green White/Yellow Yellow/Brown
S81/CCT1
Figure 2.30 Field Connections
Standard Connection Diagrams
66 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 67
I/O modules Parts of the H-S81-HS System

2.4.8 S81-F5004-1 & S81-F5004-2

Description
4 x 2A monitored control channel module. This is especially suited to control automatic fire extinguishing systems, and can be used both for controlling direc­tional and releasing solenoid valves and evacuation visual and audible alarm devices. During operation, each channel is cyclically tested by the module through reversal of output signal for approximately 200 hundreds of microsec­onds. In case of difference between the set signal and the measured one, the con­trol panel promptly signals a fault. Several channels can be connected in parallel in order to increase the output current. This module can be duplicated in fault tol­erant systems; in this case, the two modules shall be placed on adjacent racks in the same position. In this configuration, the eight output lines are connected to both modules.
Technical Features
• Safety rating: applicable up to SIL3
• Redundancy: S81-F5004-2 model
• Channel test: every 2 seconds
• Max. output current 2A
• Automatic output protection: Yes
• Supply voltage: 22-29VDC
• Quiescent current: 20mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
Each one of the eight channels on the front panel includes two status LEDs.
Output channel status
Off −− Disabled ⊗− Trouble ∅− Active −⊗ Key to symbols = steady on LED; = LED off; = flashing LED
Indications 1 - 4 Out LEDs
Yellow LED RED LED
Configurations
By using the configuration program ProS81, the following parameters can be set for each output channel:
Function Mode
Operating mode Continuous-Normally Energized, Continuous-Normally de-energized, Intermittent,
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation Timing 1 to 255 seconds/minutes (only for pulsing and intermittent modes) Output type Normal / Sounder Output status in case of CPU fault Frozen in the last status / Off Enable/Disable status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts
on the channel
No, TCP1, TCP2, RS232
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 67
Page 68
Parts of the H-S81-HS System I/O modules
Figure 2.33 Field Connections
Field connections
The module can be connected to field terminal block by using only a multi-conductor cable wi th the S81-E2001-2 bus.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 8-conductor multi-polar cable. For S81-F5004-2 module redundant connection, use the S81-CCT4R cable.
Function Termination with Multi-conductor Cable
Output 1 + 1 White
Output 2 + 2 Brown
Output 3 + 3 Green
Output 4 + 4 Yellow
Figure 2.32 Field Connections
NOTE: The module can control resistive or inductive loads with a maximum current of 2A.
Should the module be used for controlling filament lamps, the maximum load power shall not exceed 10W.
68 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 69
I/O modules Parts of the H-S81-HS System

2.4.9 S81-F6001-1

Description
This module is used for controlling the logic and indications of a certain fire extinguishing zone in compliance with the requirements of the EN12094-1 stan­dard. It controls ten output variables and seven input variables. It controls some fire extinguishing system typical logics, such as discharge delay and reset inhibit time. This module checks the status of the inputs and outputs physically located on other modules by using virtual channels.
Technical Features
• Safety rating: applicable up to SIL3
• Redundancy: Yes
• Max. output current 250mA
• Automatic output protection: No
• Supply voltage: 22-29VDC
• Quiescent current: 10mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
The front panel includes 8 status LEDs with the following functions:
LED Indication
Activated (Red LED) Steady on under “activated” condition. It goes out in case of reset. Relised (Red LED) Steady on under “released” condition. It goes out in case of reset. Fault (Yellow LED) Flashing in case of trouble in the fire extinguishing zone. Disabled (Yellow LED) Steady on if a fire extinguishing zone is disabled Inhibit (Yellow LED) Steady on under “inhibit” condition. Hold (Yellow LED) Steady on under “Hold” condition. Aut. Off (Yellow LED) Steady on under “Automatic exclusion” condition Res. Bank (Yellow LED) Steady on when the reserve bank is selected
Virtual channels
The module controls the following variables:
Variable Type Description
V1 In “Activated” condition V2 In Main primary discharge V3 In Reserve primary discharge V4 In Main secondary discharge V5 In Reserve secondary discharge V6 In Intermittent audible indications V7 In Continuous audible indications V1 Out Manual activation V2 Out Automatic activation V3 Out Automatic exclusion V4 Out Emergency hold V5 Out Release inhibition V6 Out Reserve bank V7 Out Secondary discharge V8 Out Triggered system V9 Out General trouble
V10 Out General disable
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 69
Page 70
Parts of the H-S81-HS System I/O modules
Figure 2.34 Fire Extinguishing System
Configuration
By using the ProS81 configuration program, the following parameters can be set for each virtual channel:
Function Type Mode
Operating mode Sensors NO Activates/alarmed condition Sensors Non Latching Type of indication Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Operating mode Actuators Continuous-Normally De-energized Output type Actuators Normal Enable/Disable status export to Hosts Sensors/Actuators No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts
on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
The following parameters can be set for each module through the configuration program or directly on the control panel in the operator cycle, access level 3:
Parameter Mode
Release delay time 0-60 seconds Reset inhibit time 1-30 minutes Hold operating mode Mode-A / Mode-B
Field Connections
This module does not feature any field connections, and therefore requires no terminations.
70 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 71
I/O modules Parts of the H-S81-HS System

2.4.10 S81-F6002-1

Description
Logic module able to control 100 S-R flip flops, 100 toggles, and 100 timers. Timers can be configured for two operating modes (Mode-A and Mode-B).
Technical Features
• Redundancy: Yes
• Maximum number of S-R flip flops: 100
• Maximum number of logic Toggles: 100
• Maximum number of Timers: 100
• Timer range: 0-255 seconds
• Supply voltage: 22-29VDC
• Quiescent current: 9mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
The front panel includes four LEDs with the following functions:
LED Indication
F1 (Green LED) Steady on if a logic function input variable is active F2 (Green LED) Steady on if a logic function output variable is active F3 (Green LED) Flashing during Timer count. Disabled (Yellow LED) Steady on if an input or output variable is disabled
Configuration
By using the ProS81 configuration program, the following parameters can be set for each virtual channel:
Parameter Type Mode
Type Sensors Flip Flop / Toggle / Timer Mode Sensors A / B (Only for Timer types) Alarm delay Sensors 0-255 seconds (Only for Flip Flop and Timer types) Type of indication Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Enable/Disable status export to Hosts Sensors/Actuators No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts
on the channel
NOTE: Logic function virtual inputs are set in output zones, whereas logic function virtual outputs are set in zone sensors.
Sensors/Actuators No, TCP1, TCP2, RS232
Logic Functions
The following time diagrams describe in detail the operation of the various logic functions of the module.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 71
Page 72
Parts of the H-S81-HS System I/O modules
S-R Flip Flop Function
Toggle Function
Timer Function (Mode-A)
72 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 73
I/O modules Parts of the H-S81-HS System
Timer Function (Mode-B)
Field Connections
This module does not feature any field connections, and therefore requires no terminations.

2.4.11 S81-F7002-1

Description
Control module for addressable devices using Hochiki ESP protocol. This mod­ule can control up to a maximum of 127 fire detection modules including: smoke, heat, combined detectors, alarm buttons, control modules, visual and audible alarm devices.
Technical Features
• Redundancy: No
• Maximum number of devices per loop: 127
• Loop maximum current 400mA
• Supply voltage: 22-29VDC
• Quiescent current: 90mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LED Indication
Active (Red LED) Steady on if an input is under alarmed/activated condition Disabled (Yellow LED) Steady on if an input or an output is disabled Fault (Yellow LED) Flashing in case of Fault condition Loop Fault (Yellow LED) Flashing in case of loop short circuit or open loop Log on Fault (Yellow LED) Flashing in case of difference between the detected devices
Service (Yellow LED) Flashing in case of in case of smoke detectors with dirty lenses TX Pol. (Green LED) It lights up every time data are transmitted from the module to
RX Pol. (Green LED) It lights up every time data from loop devices are received
and the programmed ones.
loop devices.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 73
Page 74
Parts of the H-S81-HS System I/O modules
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of the single devices, according to the relevant type:
Parameter Type Mode
Operating mode Sensors Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC Sensitivity Sensors 3 sensitivity levels to be selected Measuring range Sensors See table Pre-alarm threshold Sensors According to the selected measuring range Alarm threshold Sensors According to the selected measuring range Type of indication Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Automatic alarm reset Sensors Yes/No Operating mode Actuators Continuous-Normally Energized, Continuous-Normally De-energized,
Timing Actuators 1 to 15 seconds (only for pulsing and intermittent modes) Output type Actuators Normal / Sounder Sounder tone Actuators 7 selectable tones Sounder volume Actuators 50,55,60,70,78,80,85,88,90,93,94,95,98 decibels Enable/Disable status export to
Hosts Enable/Disable commands
from Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Intermittent, Pulsing
The following measuring ranges, with the relevant thresholds, can be selected for the 4-20mA S81-Mod-AN module:
Measuring
range
0-10 ppm 0.0-10.0 0.0-10.0 0-20 ppm 0.0-20.0 0.0-20.0
0-50 ppm 0-50 0-50 0-100 ppm 0-100 0-100 0-200 ppm 0-200 0-200
0-100% LEL 0-100 0-100
0-25% O
15-25% O
2
2
4-20 mA 4.0-20.0 4.0-20.0
0-100°C 0-100 0-100
Pre-alarm
Threshold
0.0-25.0 0.0-25.0
15.0-25.0 15.0-25.0
Alarm Threshold
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 terminals with a 20-way flat cable.
74 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 75
I/O modules Parts of the H-S81-HS System
Figure 2.36 Loop standard connection diagram
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 4- conductor multi-polar cable.
Function Termination with Flat Cable Termination with Multi-conductor Cable
+Loop Output
-Loop Output +Loop Input
-Loop Input
---
---
---
---
+ 1
- 22
+ 33
- 44
55 66 77 88
S81-T8003-1
White
1
Brown Green Yellow
S81/CCT4
Figure 2.35 Field Connections
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 75
Page 76
Parts of the H-S81-HS System I/O modules
Supported Devices
This module can control the following types of Hochiki Europe addressable devices:
Part Number Description Type Pros-81 Notes
ALG-E, ALG-EN Photoelectric Smoke Sensor ALG-E Powered by the loop ATG-E Heat Sensor ATG-E Powered by the loop ACB-E, ACB-EW Multi Heat Sensor ACB-E Powered by the loop AIE-E Ionization Smoke Sensor AIE-E Powered by the loop ACA-E Smoke/Heat Multi Sensor ACA-E Powered by the loop S81-Mod-An 4-20mA Analog Module CHQ-AN Requires external power supply CHQ-CP, HCP-E, HCP-W Manual Call Point CHQ-CP Powered by the loop CHQ-MZ,CHQ-SZM Single Zone Module CHQ-MZ Powered by the loop CHQ-Z, CHQ-DZM Dual Zone Module CHQ-Z Requires external power supply CHQ-SIM Single Input Module CHQ-SIM Powered by the loop CHQ-S, CHQ-DIM Dual Input Module CHQ-S Powered by the loop CHQ-R, CHQ-DRC Dual Relay Controller CHQ-R Requires external power supply CHQ-B, CHQ-DSC Dual Sounder Controller CHQ-B Powered by the loop CHQ-PCM Plant Control Module CHQ-PCM Powered by the loop YBO-BS Base Sounder YBO-BS Powered by the loop CHQ-BS Base Sounder (Old type) CHQ-BS Powered by the loop YBO-BSB Base Sounder Beacon YBO-BSB Powered by the loop CHQ-WS2 Wall Sounder CHQ-WS2 Powered by the loop CHQ-WSB Wall Sounder Beacon CHQ-WSB Powered by the loop CHQ-AB Addressable Beacon CHQ-AB Powered by the loop CHQ-ARI Remote Indicator CHQ-ARI Powered by the loop CHQ-POM Powered Output Module CHQ-POM Powered by the loop CHQ-SOM Single Output Module CHQ-SOM Powered by the loop FB-1 Fire Beam Detector FB-1 Powered by the loop

2.4.12 S81-F7007-1

Description
Control module for addressable devices using the SSP protocol. The module is able to control up to 127 addressable modules and is mainly used for controlling technological signals. This type of module shall not be used to connect fire detec­tion devices.
Technical Features
• Redundancy: No
• Number of devices per loop: 127
• Loop maximum current: 250mA
• Supply voltage: 22-29VDC
• Quiescent current: 70mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
76 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 77
I/O modules Parts of the H-S81-HS System
Status Indications
The front panel includes 8 LEDs with the following functions:
LED Indication
Active (Red LED) Steady on if an input is under alarmed/activated condition Disabled (Yellow LED) Steady on if an input or an output is disabled Fault (Yellow LED) Flashing in case of Fault condition Loop Fault (Yellow LED) Flashing in case of loop short circuit or open loop Log on Fault (Yellow LED) Flashing in case of difference between the detected devices and the programmed ones. Service (Yellow LED) Flashing in case of in case of smoke detectors with dirty lenses TX Pol. (Green LED) It lights up every time data are transmitted from the module to loop devices. RX Pol. (Green LED) It lights up every time data from loop devices are received
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of the single devices, according to the relevant type:
Parameter Type Mode
Operating mode Sensors Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC Measuring range Sensors See table Pre-alarm threshold Sensors According to the selected measuring range Alarm threshold Sensors According to the selected measuring range Type of indication Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Automatic alarm reset Sensors Yes/No Operating mode Actuators Continuous-Normally Energized, Continuous-Normally De-energized,
Timing Actuators 1 to 255 seconds (only for pulsing and intermittent modes) Enable/Disable status export to
Hosts Enable/Disable commands from
Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Intermittent, Pulsing
The following measuring ranges, with the relevant thresholds, can be programmed for S81-Mod­AI020, S81-Mod-AV010 analog modules:
Measuring Range Pre-alarm Threshold Alarm Threshold
0-255 Bit 0-255 0-255 0-10 ppm 0.0-10.0 0.0-10.0 0-20 ppm 0.0-20.0 0.0-20.0 0-50 ppm 0.0-50.0 0.0-50.0 0-100 ppm 0-100 0-100 0-200 ppm 0-200 0-200 0-500 ppm 0-500 0-500 0-999 ppm 0-999 0-999 0-100%LEL 0-100 0-100 0-25%O2 0.0-25.0 0.0-25.0 15-25%O2 15.0-25.0 15.0-25.0 4-20 mA 4.0-20.0 4.0-20.0 0-100 °C 0-100 0-100 0-150 °C 0-150 0-150 0-10 V 0.0-10.0 0.0-10.0
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 77
Page 78
Parts of the H-S81-HS System I/O modules
Figure 2.38 Standard Connection Diagram of Technological Controls
Field Connections
The module can be connected to field terminal block by using a flat or a multi­conductor cable, depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi­nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 4-conductor multi-polar cable.
Function Termination with Flat Cable Termination with Multi-conductor Cable
+Loop Output
-Loop Output +Loop Input
-Loop Input
---
---
---
---
+ 1
- 22
+ 33
- 44
55 66 77 88
S81-T8003-1
White
1
Brown Green Yellow
S81/CCT4
Figure 2.37 Field Connections
Standard Connection Diagrams
78 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 79
I/O modules Parts of the H-S81-HS System
Supported Devices
This module can control the following types of addressable devices:
Part Number Description Type Pros-81 Notes
S81-Mod-DI Module with 8 non monitored inputs DI Requires external power supply S81-Mod-AIT Module with 4 monitored inputs AIT Requires external power supply S81-Mod-AI020 Module with 1 x 4-20 mA input AI020 Requires external power supply S81-Mod-AV010 Module with 1 x 0-10V input AV010 Requires external power supply S81-Mod-DO Module with 8 open collector outputs DO Requires external power supply S81-Mod-DISP 255 message display module DISP Requires external power supply
1 A maximum of 64 modules can be installed in a loop.
1

2.4.13 S81-F7009-1

Description
Control module for addressable devices using XP95/Discovery Apollo protocol. This module can control up to a maximum of 127 fire detection modules includ­ing: smoke, heat, combined detectors, alarm buttons, control modules, visual and audible alarm devices.
Technical Features
• Redundancy: No
• Number of devices per loop: 127
• Loop maximum current: 400mA
• Supply voltage: 22-29VDC
• Quiescent current: 90mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LED Indication
Active (Red LED) Steady on if an input is under alarmed/activated condition Disabled (Yellow LED) Steady on if an input or an output is disabled Fault (Yellow LED) Flashing in case of Fault condition Loop Fault (Yellow LED) Flashing in case of loop short circuit or open loop Log on Fault (Yellow LED) Flashing in case of difference between the detected devices and the programmed ones. Service (Yellow LED) Flashing in case of in case of smoke detectors with dirty lenses TX Pol. (Green LED) It lights up every time data are transmitted from the module to loop devices. RX Pol. (Green LED) It lights up every time data from loop devices are received
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 79
Page 80
Parts of the H-S81-HS System I/O modules
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of the single devices, according to the relevant type:
Parameter Type Mode
Operating mode Sensors Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC Sensitivity Sensors 5 sensitivity levels to be selected Type of indication Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Automatic alarm reset Sensors Yes/No Operating mode Actuators Continuous-Normally Energized, Continuous-Normally De-energized,
Timing Actuators 1 to 15 seconds (only for pulsing and intermittent modes) Output type Actuators Normal / Sounder Sounder tone Actuators 15 selectable tones Sounder volume Actuators 7 selectable volume levels Polling LED Sensors/Actuators Enable/Disable LED lighting up during polling Enable/Disable status export to
Hosts Enable/Disable commands from
Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Intermittent, Pulsing
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi­nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 4-conductor multi-polar cable.
Function Termination with Flat Cable Termination with Multi-conductor Cable
+Loop Output
-Loop Output +Loop Input
-Loop Input
---
---
---
---
+ 1
- 22
+ 33
- 44
55 66 77 88
S81-T8003-1
White
1
Brown Green Yellow
S81/CCT4
Figure 2.39 Field Connections
80 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 81
I/O modules Parts of the H-S81-HS System
Figure 2.40 Loop Standard Connection Diagram
Standard Connection Diagrams
Supported devices
This module can control the following types of Apollo addressable devices:
Part Number Description Type Pros-81 Notes
55000-600 XP95 Optical smoke detector X-OSD Powered by the loop 55000-500 XP95 Ionization smoke detector X-ISD Powered by the loop 55000-268 /273 XP95 Reflective Beam X-RB Powered by the loop 55000-885 XP95 Multi-sensor detector X-HSM Powered by the loop 55000-400 XP95 Heat detector (Standard) X-HD Powered by the loop 55000-401 XP95 Heat detector (High Temperature) X-HHD Powered by the loop 55100-905 XP95 Manual Call Point X-MCP Powered by the loop XPA-CB-12034-APO XPander Optical smoke detector P-OSD Powered by the loop XPA-CB-11170-APO XPander Heat detector (Standard) P-HD Powered by the loop XPA-CB-11171-APO XPander Heat detector (High Temperature) P-HHD Powered by the loop XPA-CB-13032-APO XPander Multi-sensor detector P-HSM Powered by the loop XPA-IN-14011-APO XPander Input/Output Unit P-IOU Powered by the loop XPA-MC-14006-APO XPander Manual Call Point P-MCP Powered by the loop XPA-CB-14003-APO XPander Sounder/Beacon & Sounder Base P-SB Powered by the loop XPA-IN-14007-APO XPander Loop Interface P-LI Powered by the loop 55000-640 XP95 I.S. Optical smoke detector X-OSD Powered by the loop 55000-540 XP95 I.S. Ionization smoke detector X-ISD Powered by the loop 55000-440 XP95 I.S. Heat detector (Standard) X-HD Powered by the loop 55100-940 XP95 I.S. Manual Call Point X-MCP Powered by the loop 55000-847 Standard Input/Output Unit X-IOU Powered by the loop 55000-875 Standard Mains Input/Output Unit X-MIO Powered by the loop 55000-843 Standard Switch Monitor X-SM Powered by the loop 55000-841 Standard Switch Monitor Plus X-SMP Powered by the loop 55000-845 Standard Zone Monitor X-ZMU Powered by the loop 55000-852 Standard Sounder Control Unit X-SCU Requires external power supply 55000-803 Din Rail Input/Output Unit X-IOU Powered by the loop 55000-797 Din Rail Main Input/Output Unit X-MIO Powered by the loop 55000-822 Din Rail Switch Monitor X-SM Powered by the loop 55000-821 Din Rail Switch Monitor Plus X-SMP Powered by the loop 55000-760 Din Rail mini Switch Monitor X-MSM Powered by the loop 55000-812 Din Rail Zone Monitor X-ZMU Powered by the loop 55000-182 Din Rail Sounder Control Unit X-SCU Requires external power supply 55000-773MAR Marine Din Rail Zone Monitor X-ZMU Powered by the loop 55000-772MAR Marine Din Rail Switch Monitor Plus X-SMP Powered by the loop 55000-181MAR Marine Din Rail Sounder Control Unit X-SCU Requires external power supply 58000-600MAR Discovery Marine Optical smoke detector D-OSD Powered by the loop
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 81
Page 82
Parts of the H-S81-HS System I/O modules
58000-400MAR Discovery Marine Heat detector D-HD Powered by the loop 58000-700MAR Discovery Marine Multi-sensor detector D-HSM Powered by the loop 58100-940MAR Discovery Marine Manual Call Point D-MCP Powered by the loop 58100-975MAR Discovery Marine W.P. Manual Call Point D-MCP Powered by the loop 58000-600 Discovery Optical smoke detector D-OSD Powered by the loop 58000-500 Discovery Ionization smoke detector D-ISD Powered by the loop 58000-700 Discovery Multi-sensor detector D-HSM Powered by the loop 58000-300 Discovery Carbon Monoxide detector D-CMD Powered by the loop 58000-305 Discovery Heat/Carbon Monoxide multi-sensor D-HCM Powered by the loop 58000-400 Discovery Heat detector D-HD Powered by the loop 58100-908 Discovery Manual call Point Red D-MCP Powered by the loop 58100-950 Discovery W.P. Manual call Point Red D-MCP Powered by the loop 45681-393 Discovery Sounder/Beacon Base D-SBB Powered by the loop 58000-005 Discovery Open Area Sounder/Beacon D-ASB Powered by the loop 55000-295 Intelligent Dual IR Flame detector ATEX X-FD Powered by the loop 55000-021 Intelligent Triple IR Flame detector ATEX X-FD Powered by the loop

2.4.14 S81-F7010-1

Description
Control module for addressable devices using System Sensor protocol. This module can control up to a maximum of 188 fire detection modules including: smoke, heat, combined detectors, alarm buttons, control modules, visual and audible alarm devices.
Technical Features
• Redundancy: No
• Operating modes: Configuration via software.
• Number of devices per loop: 99 modules & 99 sensors
• Loop maximum current: 500mA
• Supply voltage: 22-29VDC
• Quiescent current: 39mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LED Indication
Active (Red LED) Steady on if an input is under alarmed/activated condition Disabled (Yellow LED) Steady on if an input or an output is disabled Fault (Yellow LED) Flashing in case of Fault condition Loop Fault (Yellow LED) Flashing in case of loop short circuit or open loop Log on Fault (Yellow LED) Flashing in case of difference between the detected devices and the programmed ones. Service (Yellow LED) Flashing in case of in case of smoke detectors with dirty lenses TX Pol. (Green LED) It lights up every time data are transmitted from the module to loop devices. RX Pol. (Green LED) It lights up every time data from loop devices are received
82 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 83
I/O modules Parts of the H-S81-HS System
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of the single devices, according to the relevant type:
Parameter Type Mode
Operating mode Sensors Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC Sensitivity Sensors 5 or 9 sensitivity levels to be selected Polling priority for call points Sensors Normal, High Unit of measure of the channel Sensors Ppm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm Zero Point Sensors -500 - 500 End of scale Sensors -500 - 500 Pre-alarm threshold Sensors -500 - 500 Alarm threshold Sensors -500 - 500 Lower trouble threshold Sensors 1.0 - 3.8mA Type of indication Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Automatic alarm reset Sensors Yes/No Operating mode Actuators Continuous-Normally Energized, Continuous-Normally De-energized,
Intermittent, Pulsing Timing Actuators 1 to 15 seconds (only for pulsing and intermittent modes) Output type Actuators Normal / Sounder Polling LED Sensors/Actuators Enable/Disable LED lighting up during polling Enable/Disable status export to
Hosts Enable/Disable commands
from Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi­nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 4-conductor multi-polar cable.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 83
Page 84
Parts of the H-S81-HS System I/O modules
Figure 2.42 Loop standard connection diagram
Function Termination with Flat Cable Termination with Multi-conductor Cable
+Loop Output
-Loop Output +Loop Input
-Loop Input
---
---
---
---
+ 1
- 22
+ 33
- 44
55 66 77 88
S81-T8003-1
White
1
Brown Green Yellow
S81/CCT4
Figure 2.41 Field Connections
Standard Connection Diagrams
Supported Devices
This module can control the following types of System Sensor addressable devices:
Part Number Description
CMA1-I Module with 1 output with isolator 1 CON/FORC M701E Module with 1 output with isolator 1 CON/FORC MMA1-I Module with 1 input with isolator 1 MON3 M710E Module with 1 input with isolator 1 MON3 M720E Module with 2 inputs with isolator 2 MON3 CMA11 Module with 1 input & 1 output 2 MON3/CON/FORC M721E Module with 2 inputs & 1 output 3 MON3/FORC CMA22 Module with 2 inputs & 2 outputs 4 MON3/CON/FORC CMX-10RM Module with 5 inputs & 5 outputs 10 MON3/FORC MCX-55M Module with 5 inputs & 5 outputs 10 MON3/FORC MMX-10M Module with 10 inputs 10 MON3 CMX-10RM Module with 10 relay outputs 10 FORC M710ECZ Module with 1 input for conventional detectors 1 SCON M710ECZR Module with 1 input for conventional EExd detectors 1 SCON MMT Module for 4-20mA analog interface with 1 channel 1 TEC2 IIG4N Module for 4-20mA analog interface with 4 channels 4 TEC2 M700KW Outdoor red alarm button with isolator 1 PULL M700KI Red alarm button with isolator 1 PULL
Addresses
Used
Type
Pro-S81
84 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 85
I/O modules Parts of the H-S81-HS System
M700KACI-FG-B Blue alarm button with isolator 1 PULL M700KACI-FG-B Yellow alarm button with isolator 1 PULL ABS32/PW-I Addressable sounder base with isolator 1 HORN ABSB32/PW/RD-I Addressable sounder base & beacon with isolator 1 HORN AWB/RD-I Addressable beacon 1 HORN AWS32/R/RD-I Electronic sounder with beacon with isolator 1 HORN AWS32/R-I Electronic sounder with isolator 1 HORN NFXI-SS-W Addressable sounder base with isolator 1 HORN NFXI-BSF-WC Addressable sounder base & beacon with isolator 1 HORN NFXI-WF-RR Addressable beacon 1 HORN NFXI-WS-R Electronic sounder with isolator 1 HORN NFXI-WSF-RR Electronic sounder & beacon with isolator 1 HORN NFXI-OPT Optical smoke sensor with isolator 1 PHOT NFXI-TDIFF Rate of rise & fixed 58°C temperature heat detector with isolator 1 TH58 NFXI-TFIX58 58°C heat sensor wi th isolator 1TH58 NFXI-TFIX78 78°C heat sensor with isolator 1TH78 NFXI-SMT2 Optical/rate of rise heat detector with isolator 1 OMNI NFXI-SMT3 Optical smoke, heat and flame IR detector with isolator 1 OMNI SDX-751CTEM Optical smoke, heat, CO and flame IR detector with isolator 1 OMNI 7251 PINNACLE Laser smoke detector 1 PINN SDX-751ME Optical smoke sensor 1 PHOT FDX551REM Rate of rise heat detector 1 TH58 FDX-551HTE 78°C heat sensor 1 TH78 FDX-751-TEMI Optical/rate of rise heat detector 1 OMNI IDX751AE Intrinsically safe optical sensor 1 PHOT WL-NTM Radio translator -- WTR WL-CM SERIE Wireless output modules with one non monitored contact 1 WFORC WL-MM SERIE Wireless input modules 1 WMON3 WL-MCP Wireless alarm button 1 WPULL WL-D100 Wireless optical smoke sensor 1 WPHOT WL-D200 Wireless optical/rate of rise heat detector 1 WTH58 WL-D350 Wireless 58°C heat sensor 1 WTH58 WL-SDN Wireless electronic sounder 1 WHORN
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 85
Page 86
Parts of the H-S81-HS System I/O modules

2.4.15 S81-F7006-1

Description
Communication module with Modbus RTU Master/slave protocol. It features two outputs providing independent connections: a RS485 Half Duplex connec­tion, and a RS232 connection. It controls the following Modbus variables:
• 512 Boolean inp ut variabl es (3 2 16-bit words)
• 512 Boolean output variables (32 16-bi t words)
• 1024 16-bit analog variables.
• Analog variables report the values of the 4-20mA analog modules, S81-F4001, S81-F4002, S81-F4003 types.
Technical Features
• Redundancy: No
• Operating modes: Master/Slave.
• Interface: N°1 RS232 + N°1 RS485
• Supply voltage: 22-29VDC
• Quiescent current: 14mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LED Indication
ACTIVE (Red LED) Steady on if an input variable is active DISABLED (Yellow LED) Steady on if an input or output variable is disabled FAULT (Yellow LED) Flashing in case of communication fault. (Master mode only) MASTER (Green LED) Steady on in Master operating mode. TX RS232 (Green LED) It lights up every time data are transmitted on the RS232 port RX RS232 (Green LED) It lights up every time data are received on the RS232 port TX RS485 (Green LED) It lights up every time data are transmitted on the RS45 port. RX RS485 (Green LED) It lights up every time data are received on the RS45 port.
Configuration
By using the ProS81 configuration program, the following parameters can be set for each virtual channel:
Parameter Type Mode
Operating mode Sensors Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC Type of indication Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Operating mode Actuator Continuous-Normally Energized, Continuous-Normally De-energized,
Intermittent, Pulsing Timing Actuator 1 to 15 seconds (only for pulsing and intermittent modes) Output type Actuators Normal / Sounder Enable/Disable status export to Hosts Sensors/Actuators No, TCP1, TCP2, RS232 Enable/Disable commands from
Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
86 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 87
I/O modules Parts of the H-S81-HS System
The module includes 2 x 8-way dip switches required for setting the communication parame ters.
SW1: Modbus Address Configuration
SW1 dip switch configures module Modbus address in the 1-255 range. In Slave mode, it defines module Modbus address, whereas in master mode it defines the address of the Slave peripheral devices to which commands are to be sent. The address 00 is not allowed.
SW1-1 Modbus address Weight 1 (on = Active) SW1-2 Modbus address Weight 2 (on = Active) SW1-3 Modbus address Weight 4 (on = Active) SW1-4 Modbus address Weight 8 (on = Active) SW1-5 Modbus address Weight 16 (on = Active) SW1-6 Modbus address Weight 32 (on = Active) SW1-7 Modbus address Weight 64 (on = Active) SW1-8 Modbus address Weight 128 (on = Active)
SW2: Modbus Parameter Configuration
The 1-2-3 dips of SW2 switch configure the Baud rate according to the table below:
SW2-1 SW2-2 SW2-3 Baud Rate
Off Off Off 1200 On Off Off 2400 Off On Off 4800 On On Off 9600 Off Off On 19200 On Off On 38400 Off On On 57600 On On On 115200
The 4-5 dips of the SW2 switch configure parity and stop bit number
SW2-4 SW2-5 Parity
Off Off No parity On Off Even Off On Odd On On Not allowed
The 6-7-8 dips of the SW2 switch configure the following options:
SW2-6
SW2-7
SW2-8
1 Only for Master mode
On 2 stop bits Off 1 stop bit On Module in Master mode Off Module in Slave mode On Freezes the last acquired status in case of Slave disconnection Off Puts all entities in communication fault trouble condition in case of Slave disconnection
1
Moreover, the module includes a Jumper for allowing the 120 ohm termination resistor on the RS485 line.
On RS485 primary line termination added
JP1
Off RS485 primary line termination removed
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
1
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 87
Page 88
Parts of the H-S81-HS System I/O modules
Figure 2.44 RS232/RS485 Standard Connection Diagram
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi­nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT6 6-conductor multi-polar cable.
Function Termination with Flat Cable Termination with Multi-conductor Cable
TX DATA RS232 TX RX DATA RS232 TX
GND G
Positive RS485 +
Negative RS485 -
GND G
---
---
1 22 33 44 55 66 77 88
S81-T8003-1
White
1
Brown Green Yellow Gray Pink
S81-CCT6
Figure 2.43 Field Connections
Standard Connection Diagrams
NOTE: For additional details on the use of this module, please refer to the specific document
ST-007-IT-R1 RTU Modbus Protocol.
88 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 89
I/O modules Parts of the H-S81-HS System

2.4.16 S81-F7008-1

Description
This module, used together with S81-MOD-BIL cylinder weighing modules, allows to monitor cylinder load status and to signal even the slightest extinguish­ing gas leakage without delay.
Technical Features
• Redundancy: No
• Operating modes: Master/Slave.
• Interface to field devices: RS485
• Load cells on bus: 32
• Supply voltage: 22-29VDC
• Quiescent current: 14mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LED Indication
ACTIVE Flashing in case of pre-alarm. On Steady in case of load cell alarm. DISABLED Steady on if a load cell is disabled. FAULT Flashing in case of load cell trouble MASTER Not used (steady light) TX RS232 Not used (off) RX RS232 Not used (off) TX RS485 It lights up every time data are transmitted on the RS45 port. RX RS485 It lights up every time data are received on the RS45 port.
Configuration
Thanks to the configuration program ProS81, the following parameters can be set for each load cell:
Parameter Type Mode
Operating mode Sensors Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC Pre-alarm threshold Sensors 1-3000 hg Alarm threshold Sensors 1-3000 hg Alarm indication mode Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only Enable/Disable status export to Hosts Sensors No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts
on the channel
Sensors No, TCP1, TCP2, RS232
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 89
Page 90
Parts of the H-S81-HS System I/O modules
Figure 2.46 RS485 Standard Connection Diagram
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi­nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT6 6-conductor multi-polar cable.
Function Termination with Flat Cable Termination with Multi-conductor Cable
TX DATA RS232 TX RX DATA RS232 TX
GND G
Positive RS485 +
Negative RS485 -
GND G
---
---
1 22 33 44 55 66 77 88
S81-T8003-1
White
1
Brown Green Yellow Gray Pink
S81-CCT6
Figure 2.45 Field Connections
Standard Connection Diagrams
NOTE: Connect a 120 Ohm, ¼ watt resistor between L+ and L- terminals on the weighing end
module to balance the RS485 bus.
S81-MOD-BIL Weighing Module
The S81-MOD-BIL module, together with the S81-F7008-1 module, allows to monitor cylinder load status and to signal even the slightest extinguishing gas leakage without delay. The weighing module communicates with the control module through the RS485 bus that accepts up to 32 mod­ules. Two thresholds, pre-alarm and alarm, can be set per weighing module when programming.
90 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 91
Termination modules Parts of the H-S81-HS System
Technical Features
• Support Material: Steel
• Supply voltage: 22-28VDC
• Typical absorption: 36mA typical
• Protection class: IP 30
• Operating temperature: -5 - 50°C
• Measuring range: 0 - 3000 hg
• Maximum load: 300 Kg
• Compatible control modules: S81-F7008-1
• RS485 bus maximum length: 1000 meters
Assembly
Install the weighing module to the floor with the relevant base by using the four fixing holes on the lower section of the support. Before tightening the fixing nuts, make sure that cylinder base plate is perfectly level. Do not install the module outdoor.
Programming the Weighing Module Address
In order to program the address of weighing modules follow the procedure below:
1. Enter the module diagnosis cycle.
2. Select the Program Device Address menu.
3. Set the desired address using the
4. Press Enter.
NOTE: During this stage, only the weighing module to which address has to be
assigned must be connected to the bus.
Weighing Module Reset
In order to reset the weighing modules, follow the procedure below:
1. Enter the module diagnosis cycle.
2. Select the Devices menu.
3. Go to the weighing module to be reset using the arrows.
4. Press Enter.

2.5 Termination modules

I/O modules may be terminated by using termination modules or by directly using a multi-conduc­tor cable, depending on the bus type in use.
Module PN Description
S81-F3002-1 Module with 8 x 22VDC monitored inputs S81-T8001-1 S81-CCT1 S81-F3002-2 Module with 8 x 22VDC monitored inputs Not available S81-CCT1R S81-F3002-3 Module with 8 x 12VDC monitored inputs S81-T8001-1 S81-CCT1 S81-F4001-1 Module with 1 x 4-20mA analog input S81-T8003-1 S81-CCT2 S81-F4001-2 Module with 1 x 4-20mA analog input Not available S81-CCT2R S81-F4002-1 Module with 2 x 4-20mA analog inputs S81-T8003-1 S81-CCT7 S81-F4002-2 Module with 2 x 4-20mA analog inputs Not available S81-CCT7R S81-F4003-1 Module with 8 x 4-20mA analog inputs S81-T8003-1 S81-CCT3
and keys.
Termination with
Flat Cable
Termination with
Cable
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 91
Page 92
Parts of the H-S81-HS System Termination modules
S81-F4003-2 Module with 8 x 4-20mA analog inputs Not available S81-CCT3R1 S81-F5001-1 Module with 8 x 500mA monitored outputs S81-T8006-1
S81-T8003-1 S81-F5001-2 Module with 8 x 500mA monitored outputs Not available S81-CCT3R S81-F5002-1 Module with 16 x 250mA non monitored outputs S81-T8007-1
S81-T8007-2
S81-T8001-1 S81-F5003-1 Module with 8 x 250mA monitored outputs for sounders S81-T8001-1
S81-T8008-1 S81-F5004-1 Module with 4 x 2A monitored outputs for solenoids Not available S81-CCT4 S81-F5004-2 Module with 4 x 2A monitored outputs for solenoids Not available S81-CCT4R S81-F6001-1 Module for fire extinguishing systems Not available Not available S81-F6002-1 Logic module Not available Not available S81-F7002-1 Loop control module with ESP protocol S81-T8003-1 S81-CCT4 S81-F7006-1 Modbus RTU Master/Slave module S81-T8003-1 S81-CCT6 S81-F7007-1 Loop control module with SSP protocol S81-T8003-1 S81-CCT4 S81-F7008-1 Control modules for weighing modules S81-T8003-1 S81-CCT6 S81-F7009-1 Loop control module with XP95/Discovery protocol S81-T8003-1 S81-CCT4 S81-F7010-1 Loop control module with System Sensor protocol S81-T8003-1 S81-CCT4
2
S81-CCT3
S81-CCT1 S81-T8007-1 S81-T8007-2
S81-CCT1 S81-T8008-1
1
1 Combined with the S81-T8005-1 termin ation module 2 Combined with the S81-T8001-1 termin ation module

2.5.1 S81-T8001-1

Description
16-terminal termination module. It is used with S81-E2001-1 type buses to terminate the following modules: S81-F3002-1, S81-F5002-1, S81­F5003-1
Technical Features
• Number of terminals: 16
• Assembly: on DIN bar
• Dimensions: W 57 x H 77 x D 50 mm
92 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 93
Termination modules Parts of the H-S81-HS System
Field Connections
Terminal
1 + Input 1 - Output 1 + Output 1 2 - Input 1 - Output 2 - Output 1 3 + Input 2 - Output 3 + Output 2 4 - Input 2 - Output 4 - Output 2 5 + Input 3 - Output 5 + Output 3 6 - Input 3 - Output 6 - Output 3 7 + Input 4 - Output 7 + Output 4 8 - Input 4 - Output 8 - Output 4 9 + Input 5 - Output 9 + Output 5 10 - Input 5 - Output 10 - Output 5 11 + Input 6 - Output 11 + Output 6 12 - Input 6 - Output 12 - Output 6 13 + Input 7 - Output 13 + Output 7 14 - Input 7 - Output 14 - Output 7 15 + Input 8 - Output 15 + Output 8 16 - Input 8 - Output 16 - Output 8
S81-F3002-1 S81-F5002-1 S81-F5003-1
Modules that can be terminated

2.5.2 S81-T8003-1

Field Connections
Terminal
1 +An. In 1 +An. In 1 +An. In 1 + Output 1 + Loop Out TX RS232 2 N.C. N.C. +An. In 2 + Output 2 - Loop Out RX RS232 3 N.C. +An. In 2 +An. In 3 + Output 3 + Loop In GND RS232 4 N.C. N.C. +An. In 4 + Output 4 - Loop In + RS485 5 +An. Out 1 +An. Out 1 +An. In 5 + Output 5 N.C. - RS485 6 N.C. N.C. +An. In 6 + Output 6 N.C. GND RS485 7 N.C. +An. Out 2 +An. In 7 + Output 7 N.C. N.C. 8 N.C. N.C. +An. In 8 + Output 8 N.C. N.C.
S81-F4001-1 S81-F4002-1 S81-F4003-1 S81-F5001-1
Description
8-terminal termination module. It is used with S81-E2001-1 type buses to terminate the following modules: S81-F4001-1, S81-F4002-1, S81-F4003-1, S81-F5001-1, S81-F7002-1, S81-F7006-1, S81-F7007-1, S81-F7008-1, S81-F7009-1, S81-F7010-1.
Technical Features
• Number of terminals: 8
• Assembly: on DIN bar
• Dimensions: W 57 x H 77 x D 50 mm
Modules that can be Terminated
S81-F7002-1 S81-F7007-1 S81-F7009-1 S81-F7010-1
S81-F7006-1 S81-F7008-1
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 93
Page 94
Parts of the H-S81-HS System Termination modules

2.5.3 S81-T8005-1

Description
20-terminal termination module. It is used as an adapter with S81-E2001-2 type buses to connect the S81-F5002-1 modules to the S81-T8007-1 termination modules by means of a S81-CCT-1 cable.
Technical Features
• Number of terminals: 20
• Assembly: on DIN bar
• Dimensions: W 68 x H 77 x D 50 mm
Interconnection Between S81-CCT1 Cable and S81-T8007-1 Module
Terminal S81-CCT-1 Wire Relay Notes
1 Not used 2 Not used 3 White K1 Connect to the white wire of cable S81-CCT1 4 Brown K2 Connect to the brown wire of cable S81-CCT1 5 Green K3 Connect to the green wire of cable S81- CCT1 6 Yellow K4 Connect to the yellow wire of cable S81-CCT1 7 Gray K5 Connect to the gray wire of cable S81-CCT1 8 Pink K6 Connect to the pink wire of cable S81-CCT1
9 Blue K7 Connect to the blue wire of cable S81-CCT1 10 Red K8 Connect to the red wire of cable S81-CCT1 11 Black K9 Connect to the black wire of cable S81-CCT1 12 Violet K10 Connect to the violet wire of cable S81-CCT1 13 Gray/Pink K11 Connect to the gray/pink wire of cable S81-CCT1 14 Red/Blue K12 Connect to the red/blue wire of cable S81-CCT1 15 White/Green K13 Connect to the white/green wire of cable S81-CCT1 16 Brown/Green K14 Connect to the brown/green wire of cable S81-CCT1 17 White/Yellow K15 Connect to the white/yellow wire of cable S81-CCT1 18 Yellow/Brown K16 Connect to the yellow/brown wire of cable S81-CCT1 19 Connect to +25V with a 200mA fuse 20 Not used
The S81-T8007-2 module can be connected directly to the S81-E2001-2 bus with cable S81-CCT1 without the need for the S81-T8005-1 interconnection module.
94 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 95
Termination modules Parts of the H-S81-HS System

2.5.4 S81-T8002-1

Description
This module transforms the remote Host serial output signal from RS232 to current loop with galvanic insulation. The module is passive and therefore needs an actively operating converter on the other end. With this module it is possible to connect a remote Host computer to a maximum distance of 2,000 meters.
Technical Features
• Supply voltage: 22-29VDC
• Quiescent current: 30mA
• Current loop maximum distance: 2,000 meters at 9,600 bps
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Dimensions: W 57 x H 77 x D 50 mm
Status Indications
The module includes 5 x SMD LEDs with the following functions:
LED Indication
Power Steady on when supply voltage is detected RX-232 On when data are received on the RS232 port TX-232 On when data are transmitted on the RS232 port RX-CL On when data are received on the current loop TX-CL On when data are transmitted on the current loop
Internal Connections
J1: RS232
Connection of RS232 serial line. Connect to the J5 connector of module S81-E2003-1 using the S81-C232/2 cable.
BR1: Power Supply
These 3 terminals connect supply voltage (+25VDC) and earth.
Tag Function Cable Color
M1 25VDC power supply positive Red M2 25VDC power supply negative Black M3 Earth Yellow/Green
Field Connections
BR2: Current loop
These 4 terminals connect
Tag Function Cable Color
M1 RX data input positive White M2 RX data input negative Brown M3 TX data output positive Green M4 TX data output negative Yellow
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 95
Page 96
Parts of the H-S81-HS System Termination modules
!

2.5.5 S81-T8004-1

Description
This module controls 10 digital inputs, 16 open col­lector outputs and a local sounder 250mA moni­tored output for Fire alarm functions. Moreover, the module checks the primary power supply voltage for any ground fault (earth leakage). It can be com­bined with module S81-T8001-1 to get 16 x 250mA open collector outputs, or with modules S81­T8007-1 and S81-T8007-2 to get 16 x SPDT con­tacts.
Technical Features
• Supply voltage: 22-29VDC
• Quiescent current: 100mA
• Max. current of open collector outputs 250mA, non protected
• Max. current of local sounder output 250mA, protected electronically
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Dimensions: W 135 x H 77 x D 50 mm
Status Indications
The module includes 2 green LEDs with the following functions:
LED Indication
Power (Green LED) Steady on when supply voltage is detected Link (Green LED) Steady on when the link for communication with module S81-U1006-1 is present
Configuration
The module includes a 1-way dip-switch used to enable the ground fault check on the supply volt­age.
SW1 Description
On Supply voltage ground fault (earth leakage) check enabled Off Supply voltage ground fault (earth leakage) check disabled
WARNING: EARTH GROUND
THE SUPPLY VOLTAGE OF THE H-S81-HS CONTROL PANEL IS NOT REFERENCED TO EARTH. IN SOME DEVICES, SUCH AS PERSONAL COMPUTERS, THE POWER SUPPLY NEGATIVE IS EARTHED FOR SAFETY REASONS. WHEN THESE DEVICES ARE CONNECTED TO THE CONTROL PANEL, A GROUND FAULT (EARTH LEAKAGE) TROUBLE IS SIGNALED. TO PREVENT THIS, MOVE THE SW1 DIP-SWITCH TO THE OFF POSITION.
96 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 97
Termination modules Parts of the H-S81-HS System
Figure 2.47 S81-T8004-1 Interconnections
Internal Connections
TB1-TB2-TB3 Power supply
These three Faston connectors are used to connect supply voltage and earth.
TAG Function Cable Color
TB1 25VDC power supply positive Red TB2 25VDC power supply negative Black TB3 Earth Yellow/Green
J1 to J1 on S81-E2003-1
It is a connector for 14-pole flat cable, allowing connection to the S81-E2003-1 Bus module. Con­nect using S81-CFT14/2 cable.
J2 to J1 on S81-T8001-1, J1 on S81-T8007-1 or J1 on S81- T8007-2
It is a connector for 20-pole flat cable, allowing connection to the S81-T8001-1 termination module or to the 16-relay modules S81-T8007-1 and S81-T8007-2. Connect using S81-CFT20/05 cable.
Terminals
S81-T8001-1
M1 K1 Supervisory M2 K2 Alarm Normally de-energized M3 K3 General trouble Normally energized M4 K4 Disabling Normally de-energized M5 K5 External buzzer Normally de-energized M6 K6 Gas Normally de-energized M7 K7 Alarm M8 K8 Tampering Normally energized M9 K9 Trouble Normally energized M10 K10 External sounder Normally energized
Relay S81-T8007-1 S81-T8007-2
Function Type Notes
Normally de-energized
Safety
Normally energized
Security
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 97
Page 98
Parts of the H-S81-HS System Termination modules
!
M11 K11 Currently not used M12 K12 Running System Normally energized M13 K13 System fault Normally energized M14 K14 Power supply fault Normally energized M15 K15 CPU fault Normally energized M16 K16 Control panel reset Pulsing on reset
System
Normally energized
Field Connections
BR1 Terminal Block
It is a 12-way terminal block to connect the ten default inputs and the local fire alarm sounder.
BR1 Function Type Notes
M1 Remote buzzer silencing input Safety N.O. M2 Remote sounder silencing input Safety N.O. M3 Remote control panel reset input Safety N.O. M4 Remote evacuation control input Safety N.O. M5 Battery status input (supply/charge) System 0V during charge M6 PSU1 primary power supply trouble input System N.C. M7 PSU2 secondary power supply trouble input System N.C. M8 Battery charge status (Full charge/Trickle) System 0V full charge M9 External Fault Input Safety N.C M10 Revolving door tamper input Security N.C M11 Local sounder/buzzer output + Safety max. 250mA M12 Local sounder/buzzer output - Safety max. 250mA
CAUTION: EN-54-2 COMPLIANCE
THE REMOTE EVACUATION CONTROL AND REMOTE CONTROL PANEL RESET INPUTS MUST NOT BE ACTUATED DIRECTLY THROUGH EXTERNAL MANUAL BUTTONS SINCE THEY ARE NOT MONITORED. THIS GUARANTEES COMPLIANCE WITH STANDARD EN-54-2.
98 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Page 99
Termination modules Parts of the H-S81-HS System
Figure 2.48 – Inputs and Local Sounder Output Standard Connection Diagram
Standard Connection Diagrams

2.5.6 S81-T8006-1

Description
Technical Features
• Supply voltage: 22-29VDC
• Quiescent current: 0mA
• Contact type: SPDT
• Contact capacity: 4 A 30VDC
• Assembly: on DIN bar
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Dimensions: W 135 x H 77 x D 50 mm
Status Indications
It is used with S81-E2001-1 type buses to terminate S81-F5001-1 mod­ules. It features 8 x SPDT output con­tacts to connect SELV circuits only.
The module includes 8 green LEDs for relay status indication:
LED Condition
LED1 - LED8 (Green LEDs) It lights up when relay coil is active
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 99
Page 100
Parts of the H-S81-HS System Termination modules
!
Field Connections
Relays
NC= Normally Closed NO= Normally Open COM= Common
BR1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
K1 K2 K3 K4 K5 K6 K7 K8
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
CAUTION: EN-54-2 COMPLIANCE
THE OUTPUTS ABOVE ARE NOT C-, E- OR J-TYPE OUTPUTS (EN 54-1), THEREFORE THEY MUST NOT BE USED TO CONTROL FIRE ALARM DEVICES OR ALARM, FIRE ALARM OR FAULT ALARM TRANSMISSION DEVICES. THIS GUARANTEES COMPLIANCE WITH STANDARD EN-54-2.

2.5.7 S81-T8007-1

Description
It is used with S81-E2001-1 and S81-F5002-1 type buses. It features 16 x 4A 30VDC SPDT output con­tacts to be used for the con­nection of SELV circuits only. It is also used together with the S81-T8004-1 mod­ule.
Technical Features
• Supply voltage: 22-29VDC
• Quiescent current: 0 mA
• Contact type: SPDT
• Contact capacity: 4 A 30VDC
• Assembly: on DIN bar
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% non-condensing
• Dimensions: W 170 x H 77 x D 50 mm
Status Indications
The module includes 16 green LEDs for relay status indication:
LED Condition
LED1 - LED16 (Green LEDs) It lights up when relay coil is active
100 H-S81-HS Installation & Operation Manual — P/N LS10114- 000HI-E:A 2/24/2015
Loading...