Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notification capability—can provide early warn ing of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of
an automatic fire alarm system (as described above) and a life
safety communication system that may include an autonomous
control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication met hods—can broadcast a mass notification message. Such a
system, however, does not assure protection against property
damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premises following
the recommendations of the National Fire Protection Asso ciation
Standard 72-2002 (NFPA 72-2002), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of
System Smoke Detectors, which is made available at no charge
to all installing dealers. This document can be found at http: //
www.systemsensor.com/appguides/. A study by the Federal
Emergency Management Agency (an agency of the United
States governme nt) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-floor
or basement fire.
Particles of combustion or “smok e ” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, chimneys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown aw a y from de tectors by air
outlets, such as air conditioning vent s.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designe d to ala rm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires,
which have little visible smoke. Detectors that have ionizing-type
sensing chambers tend to detect fast-flaming fires better than
smoldering fires. Because fires develop in different ways and
are often unpredictable in their growt h, neither type of detector i s
necessarily best and a given type of detector may not provide
adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches
(especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and al arm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector shoul d be tested
at least once per year by a qualified fire protection specialist .
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for
the connection of alarm transmission wiring, communications,
signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes,
speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device
may fail to alert people with a disability or those who have
recently consumed drugs, alcohol, or medication. Please note
that:
• An emergency communication system may take priority over
a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be desi gned to meet intelligibility requirements as defined by NFPA, local codes, and
Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly disseminated on any local displays.
• Strobes can, under c ertain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have sh own that certain people, even when they he ar
a fire alarm signal, do not respond to or comprehend the
meaning of the signal. Audible devices, such as horns and
bells, can have different tonal patterns and frequencies. It is
the property owner's responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm
signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment
l
is
ted for service with your control panel.
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line
failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep t he entire life safety sys tem in
excellent working order , ongoing mai ntenance is required per the
manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72-2002 shall
be followed. Environments with large amounts of dust, dirt, or
high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional life safety system installers only. Adequate written records of all inspections
should be kept.
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All components, circuits, system operations, or sof tware functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indicating device loops. Most devices cannot tol erate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subject ed to li ght ning induced transients. Although no system is completely
immune from lightning transients and interf erence, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal
contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the
body . Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the inst al lati on, ope rati ng, and programming manuals. These instructions must be followed to
avoid damage to the control panel and a ssociated equipment.
FACP operation and rel iability depend upon proper inst allat ion.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi oelectriques depassant les limites applic ables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edict e p ar l e
ministere des Communications du Canada.
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a
specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our
online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
General Information................................................................................................................14
Related Documentation........................................... .................................. ..........................................................14
Important Notices ................................................................. .................................. ............................................14
Section 1: General Description..............................................................................................15
1.1: Architecture of the System ..........................................................................................................................15
1.3: General Features..........................................................................................................................................17
1.5: Safety-Related Modules in the H-S81-HS System......................................................................................20
1.5.1: Central Unit .......................................................................................................................................20
1.5.2: Digital Input Modules........................................................................................................................21
Section 2: Parts of the H-S81-HS System .............................................................................27
2.1: Power Supply Set.........................................................................................................................................27
2.1.1: S81-PU001 Power Supply Set...........................................................................................................27
Technical Features .................................................................................... ...........................................37
2.2: Central Unit Rack ........................................................................................................................................37
3.1: Positioning of the Control Panel................................................................................................................105
3.2: Measures for Installation in Compliance with the EC Standard ................................................................105
3.3: Mounting the H-S81-HS-1R & H-S81-HS-2R Control Panels .................................................................105
3.4: Positioning the H-S81-HS-1/10R Control Panel .......................................................................................106
3.5: Layout of H-S81-HS/1R Internal Parts......................................................................................................107
3.6: Layout of H-S81-HS/2R Internal Parts......................................................................................................108
3.7: Layout of H-S81-HS/1-10R Internal Parts ................................................................................................109
3.10: Connection to AC Main.................................... .................................. .....................................................110
4.2: Management of Faults................................................................................................................................115
4.2.1: Power Supply Set Fault ...................................................................................................................115
4.2.2: Central Unit Fault ............................................................................................................................115
5.3: Field Devices .............................................................................................................................................118
7.2: Fire Alarm Section Menu (Safety) ............................................................................................................131
7.3: Access to Functions...................................................................................................................................131
7.4: Operations at Access Level 1 ....................................................................................................................132
7.4.1: Local Buzzer Silencing....................................................................................................................132
7.7.4: Local Sounder..................................................................................................................................138
Control Panel Test..............................................................................................................................139
Zone Test............................................................................................................................................139
7.9: Operations at Access Level 3 ....................................................................................................................140
7.10.4: Standard Options ................................................................................. ..........................................145
7.13: Access to Operator Functions..................................................................................................................151
7.14: Operations at Access Level 1............................................................ .......................................................152
7.15: Operations at Access Level 2............................................................ .......................................................152
7.17.1: Configured Zones ........................................................... ................................. ..............................153
7.17.2: Zone Status ........................................................................................ ............................................154
7.17.3: Control Panel Tamper Status.........................................................................................................154
7.19.2: Local Sounder............................................................................... .................................................155
7.21.1: Time Slots.................................................................................. ....................................................156
A.2: Power Supply Sets ....................................................................................................................................160
A.3: Central Unit Rack......................................................................................................................................161
B.4: Apollo Addressable Devices.............................................................. .......................................................164
B.5: System Sensor Addressable Devices.........................................................................................................166
B.6: Visual and Audible Alarm Devices...........................................................................................................167
Appendix C: Power Supply Set Dimensions......................................................................168
C.1: H-S81-HS Control Panel Absorption........................................................................................................168
C.2: Absorption of Hochiki Conventional Detectors........................................................................................168
C.3: Absorption of Hochiki Addressable Devices............................................................................................169
C.4: Absorption of Honeywell Addressable Devices .......................................................................................169
C.5: Absorption of Apollo Addressable Devices..............................................................................................170
C.8: Calculation of Total System Absorption...................................................................................................172
C.9: Calculation of Battery Capacity................................................................................................................172
For specific and detailed information on the H-S81-HS panel and system, please refer to following
documents:
Document numberName
ST-058-ITInstallation and user manual (this manual)
ST-071-ITSafety Manual
ED-Cxxxxx-Fyy-RzWiring diagram (specific to each control panel)
ST-015-ITProgramming software PRO-S81
ST-021-ITGraphic supervisory program IRIDE
ST-057-ITHoneywell OPC Server
ST-007-ITModbus RTU protocol
Acronyms
CPUCentral processing unit
EMCElectromagnetic compatibility
I/OInput/output
PSUPower supply unit
TCP/IPNetwork protocol
START-UPSystem start-up
c.c.s.Monitoring & signaling system
d.e.c.Monitoring & automatic delay electronic device
a.d.a.Power supply equipment
Important Notices
Notices throughout this manual inform the reader of practices and conditions, which will affect
physical safety, occupant safety, and equipment performance. Notices appear as:
NOTE: Useful information to help operate the H-S81-HS Panel.
CAUTION:POSSIBLE DAMAGE
INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS,
RUNTIME ERRORS, OR EQUIPMENT DAMAGE.
WARNING: POSSIBLE INJURY
INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE
DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA, OR
PERSONAL INJURY.
This chapter provides a general description of the H-S81-HS control panel, listing the system’s
main technical features.
1.1 Architecture of the System
The H-S81-HS control panel is a high technology product created for controlling safety-related systems and equipment. It is characterized by easy configuration and programming, combined with
excellent reliability and system diagnosis. The H-S81-HS is similar to a “safety PLC” and can be
configured and programmed for carrying out integrated safety functions including fire prevention,
gas detection, burglar alarm and technological control in compliance with applicable standards. The
H-S81-HS can also interact with other control panels of the same type and with supervisory systems via both standard and proprietary protocols such as TCP/IP Ethernet, Modbus RTU, or OPC
Server.
Each system includes a power supply set, a processing unit (which is also the user interface), and
the I/O modules controlling field devices. Both the processing unit and the I/O modules are located
on 19 inch racks. There are two ways of connecting modules and field devices:
•The first solution consists in the use of termination modules equipped with a terminal block
allowing to connect the cables from field device. In this case, I/O modules are connected to the
termination modules by using a 20 way flat cable. The termination module type and the
relevant connections depend on the type of module to be terminated.
•The second solution consists in the use of multi-polar cables directly connected to bus back
through a DIN41618 connector. This solution allows for a redundant module termination. It
also allows for the termination of high current output modules, which is not possible by
adopting the first solution (S81-F5004).
The H-S81-HS system has a modular structure. The processing rack includes two CPUs and an
operator interface panel. Each CPU can be connected to a maximum of 10 racks, with up to 13 I/O
modules each, for a total amount of 130 modules. I/O modules can be installed on the racks without
any limitations, according to the requirements of the specific system under consideration.
The H-S81-HS system is a modular unit consisting of 19” 3-unit high anodized aluminum racks;
they will be installed in a metal cabinet with revolving rack and acrylic glass door. It can include a
variable number of racks (2 to 11), according to the specific needs.
The first rack is always required. It includes the Base with one or two CPUs, the operator interface
display and the keyboard. Modules can be installed from the 2nd rack on. They will be arranged by
type and number according to the requirements of the system to be protected. Besides the versions
designed to the customer's request, 3 versions with certified structure and cabinet are available for
the European market:
•H-S81-HS/10R: Base rack and up to 10 module racks, for ground floor installation W=800,
H=2100, D=800mm
Each module is connected to field devices by a flat cable and an electronic terminal block fitted on
a DIN bar at the bottom of the switchboard; alternatively, modules can be connected to field
devices by pre-wired connectors connected to electromechanical terminal blocks.
NOTE: The operating temperature inside an electronic device significantly affects the duration of
its useful life. High operating temperatures and sharp temperature increases will significantly
reduce electronic device life. It is extremely important that the environmental operating conditions
are within the allowed ranges.
WARNING: REMOVE BATTERIES
SHOULD STORAGE TEMPERATURE BE LOWER THAN -30°C OR EXCEED +60°C, REMOVE
THE LITHIUM BATTERY ON CENTRAL UNITS (S81-U1002-1 MODULES).
1.3.5 Mechanical Conditions
The table below summarizes the type of mechanical tests undergone by the H-S81-HS system.
Standard TestTest Levels
IEC 68-2-6Vibration sinusoidal test (endurance) Frequency range: 10-150Hz
Acceleration amplitude: 0.5g
Number of axis: 3
Number of sweep cycles: 20 per axis
Number of impact per point: 3
Page 19
Safety and Availability of the H-S81-HS SystemGeneral Description
!
Figure 1.3 “Mono” Configuration
1.3.6 Electromagnetic Compatibility (CE)
The H-S81-HS system has been designed and tested for resisting to standard levels of radiated and
conducted electromagnetic interference, and electrostatic discharges. The table below lists the types
and levels of the tests undergone by the H-S81-HS system.
Basic StandardDate TitleNoise Immunity Tests
EN 61000-4-2
A1
A2
EN 61000-4-3
A1
A2
EN 61000-4-4
A1
A2
EN 61000-4-5
A1
ENV 501411994 Conducted disturbances induced by radio-
EN 61000-4-11A11994
1995
1998
Electrostatic discharge immunity test
2001
1996
Radiated, radio-frequency, electromagnetic
1998
field immunity test
2001
1995
2001
Electrical fast transients/bursts immunity test
2001
1995
Surge immunity test
2001
frequency fields immunity test
Voltage dips, short interruptions and voltage
2001
variations immunity test
6 kV contact discharge
8 kV air discharge
10 V/m, 80 MHz-2 GHz, 80% AM
2 kV power supply
1 kV signal lines
2 kV common mode
1 kV differential mode
10 V, 150 kHz-80 MHz, AM
60% 200ms
100% 100ms
CAUTION:ELECTROMAGNETIC COMPATIBILITY
ELECTRICAL DISTURBANCES VARY SIGNIFICANTLY ACCORDING TO THE TYPE OF
INSTALLATION AND WIRING DISTANCE TO AND FROM OTHER DEVICES. THEREFORE, IT IS
IMPORTANT TO MAKE SURE THAT THE ELECTROMAGNETIC INTERFERENCE LEVELS DO
NOT EXCEED THE VALUES REPORTED IN THIS TABLE.
1.4 Safety and Availability of the H-S81-HS System
The H-S81-HS system is intended for use in applications requiring a high safety level, together
with high system availability. According to the required safety and availability levels, different
H-S81-HS system configurations can be provided.
1.4.1 Possible Configurations of the H-S81-HS System
“Mono” Configuration
This solution includes the duplicated central unit and the I/O modules in a single configuration.
General DescriptionSafety-Related Modules in the H-S81-HS System
Figure 1.4 “Duplex” Configuration
“Duplex” Configuration
This solution is characterized by a redundant configuration for both the central unit and the I/O
modules. Module redundancy increases system availability. In case of error or failure of a module
in “duplex” configuration, the broken module is automatically pu t in safety condition (OFF)
whereas the redundant one keeps operating. I/O module redundancy is possible only with safety
related modules.
1.5 Safety-Related Modules in the H-S81-HS System
This paragraph describes the measures undertaken by safety related modules in order to guarantee
the required reliability of the various applications.
1.5.1 Central Unit
The CPU features an external watchdog circuit that activates in case of failure. In standard operating conditions, the CPU cyclically tests the memory, internal voltage values and the status of RAM
lithium batteries. Should it detect any faults, the module would set in safety condition. If there is a
redundant CPU, the new CPU will carry out the monitoring functions without any interruption s.
The broken CPU can be replaced without the need of switching off the system.
Safety-Related Modules in the H-S81-HS SystemGeneral Description
Figure 1.5 Digital Input Test
Figure 1.6 Analog Input Test
1.5.2 Digital Input Modules
Safety-related digital input modules feature a circuit allowing to simulate the opening and closing
of each channel. During operation, channels are cyclically tested. It a redundant module exists, the
control panel keeps operating and gathering data from this module, guaranteeing maximum system
availability. The broken module can be replaced without the need of switching off the system.
1.5.3 4-20mA Input Modules
4-20mA safety-related input modules feature two separated measuring circuits per input channel.
The two measured current values are, hence, compared between them and in case of difference
between the two values the channel is set in failure condition. It a redundant module exists, the control panel keeps operating and gathering data from this module, guaranteeing maximum system
availability. The broken module can be replaced without the need of switching off the system.
1.5.4 Output Modules
Safety-related output modules feature two control drivers connected in series. During operation, the
output channels are cyclically tested by reversal of output status for some hundreds of microseconds. In case of difference between channel set status and the measured one, the whole module is
excluded from operation and its outputs are put in safety condition. (Shut-down) If a redundant
module exists, the control panel keeps operating and gathering data from this module, guaranteeing
maximum system availability. The broken module can be replaced without the need of switching
off the system.
General DescriptionSafety-Related Modules in the H-S81-HS System
Figure 1.7 Digital Output Test
1.5.5 Central Unit Safety Switch-off
During operation, central units cyclically test the main 25V and local 3.3V power supply voltage
values. If one of these values is not within the allowed range, a safety switch-off sequence is carried
out in order to put the whole system in safety condition. During this sequence, the following operations are carried out:
Activation of the main FAULT and SYSTEM FAULT outputs.
Deactivation of the main RUN output.
Deactivation of the RUN LED on the CPU
PANEL SHUT-OFF indication on the display
In this condition, output status is frozen. Restart the system to clear this condition.
•Allowed 25V voltage range: 18.5 - 32VDC (A warning condition is reported with voltage
values <22.5 V and >29.5.)
•Allowed 3.3V local voltage range: 3.15 - 3.6VDC (This function is carried out by an external
reset circuit with voltage values >3.15 V.)
In the configurations with redundant CPU, if the sequence is carried out only by the primary CPU,
the secondary one signals primary CPU failure and starts controlling the system without any interruption of system operation. If, instead, the sequence is carried out only by the secondary CPU, the
primary one signals secondary CPU failure and keeps carrying out its functions.
1.5.6 Central Unit Safety Shut-down
In case of critical failures during operation, the central unit will carry out a safety shut-down
sequence in order to put the whole system in safety condition. The following failures will cause a
safety shut-down:
•Error in checking memory content (Flash/Ram).
•Internal hardware failure
Restart the system to clear this condition.
In the configurations with a redundant CPU, if the sequence is carried out only by the primary
CPU, the secondary one signals primary CPU failure and starts controlling the system without any
interruption of system operation. If, instead, the sequence is carried out only by the secondary CPU,
the primary one signals secondary CPU failure and keeps carrying out its functions.
Communication Network Between Control PanelsGeneral Description
Figure 1.8 Communication Network Between Control Panels
1.6 Communication Network Between Control Panels
By using CPU Ethernet interface, the logic status of the rules (Checked/Not checked) can be
exchanged between several control panels. Control panels are divided into two categories: Master
(receiving) and Slave (transmitting). Each control panel in the network can be indifferently slave
only , master only or slave/master. Slave control panels send to Master ones all the sate changes of
the rules set as remote in master control panel. For every panel can be imported up to 999 remote
rules and can be exported up to 250 local rule. A maximum of 32 control panels can be connected
to each other in a network. Master control panels receive and process the sate changes sent from
slave control panels, and cyclically check the connection with the Slave control panels connected to
them. When the system is switched on, Master control panels request the IP address from the Slave
ones existing in the configuration. Therefore, they send them the message identification code (ID
code). This code is generated random and is dynamically changed every minute and compared with
the one included in the messages from the Slave control panel for message validation. If the code of
a received message is not valid, the message is rejected. Master control panels make a new subscribe to Slave control panels every hour, for checking the existence of any configuration changes.
If Slave control panel response is correct, the Master control panel will wait for the status changes
from Slave control panels. During operation, the Master control panel cyclically tests the efficiency
of the connection to Slave control panels, and, in case of disconnection, signals it on the display.
Signal propagation time between the various control panels may vary according to network traffic.
However, in case of dedicated networks it will not exceed two seconds. Control panel network can
be made of copper or optical fiber by using the proper converters allowing a redundant loop connection able to support a possible failure or fiber break.
General DescriptionCommunication Protocol for Supervisory Systems
Figure 1.9 Control Panel Remote Monitoring
Error Messages of the Communication Network:
The following error messages concerning communication networks can be shown on control panel
displays:
Message TypeControl PanelError Type
ID xxx Communication failure 100MasterThe master cannot communicate with the slave
ID xxx Communication failure 101MasterRemote rule referred to the control panel
ID xxx Communication failure 5SlaveThe slave cannot communicate with the master
ID xxx Remote rule nnn undefinedMasterUndefined remote rule
1.7 Communication Protocol for Supervisory Systems
H-S81-HS systems can be connected to IRIDE supervisory system via LAN network or point-topoint serial connection. A maximum of 2 supervisors per control panel can be configured on the
LAN network, and one on Host serial port. In both cases, a dedicated protocol is used. The connection between control panels and supervisors can be made of copper, optical fiber or copper/fiber
(mixed), for meeting different needs. For using IRIDE supervisory program, please refer to the specific manual ST-021-IT.
Thanks to the program OPC Server, any Windows OPC Client applications (Scada/DCS, supervisors, control or other applications) can communicate to H-S81-HS series control panels featuring
V2.0.0 or higher software version. The OPC Client application can interact with all variables made
available by the control panel following the modes defined by the OPC standard. By using the program OPC Server, clients can access the following data:
•Alarms
•Analog value measurements
•Device status indications
•Control panel status indications
•Communication status indications
For using the program OPC Server, please refer to the specific manual ST-057-IT.
1.9 Programming
H-S81-HS system programming is carried out through a personal computer in OFF-LINE mode by
means of a specific configuration program. After completing the configuration and checking that
the entered data are correct, data can be transferred to the central unit. Once they have been transferred, the central unit replaces the old configuration with the new one and re-initializes the system.
If there are two CPUs, the configuration is transferred to both at the same time. For using the configuration program Pro-S81, please refer to the specific manual ST-015-IT.
This chapter provides a detailed description of all the parts making up the H-S81-HS system.
2.1 Power Supply Set
The H-S81-HS control panel can be equipped with the following power supply sets:
•S81-PU001 power supply set for base plate installation.
•S81-PU002 power supply set for rack installation.
NOTE: The power supply set S81-PU002, for rack installation, can only be used in the version
with ground-floor steelwork.
2.1.1 S81-PU001 Power Supply Set
This is a power supply set to be fitted on a base plate. It consists of a maximum of 4 x 25 Watt
power supply units, PU-A0005-1 model, plus one PU-A0004-1 battery charger module able to supply a 2 or 4 ampere adjustable battery charge current. Power supply units are connected in parallel,
up to a maximum of four units amounting to a total of 16 amperes. Under normal operating conditions, a simplified test is carried out every 30 seconds in order to check the proper presence of the
batteries. A full test, instead, is carried out every hour in order to check electrical connections and
battery efficiency. During battery trickle charge, battery voltage is compensated automatically
according to the temperature. In case of mains voltage failure, batteries are automatically switched
to the load without any interruptions. Should the full charge stage exceed 24 hours, the power supply unit will signal a battery fault. In case of primary power supply failure, the system will shut batteries down when the on-load voltage is lower than 18VDC in order to avoid damaging the
batteries. The set features three open collector outputs for replicating the various types of faults to
the alarm control panel, along with a RS232 port for the connection to a supervisory system.
Technical Features
• Input voltage:110-240V~ (-15% - 10%)
• Free-air operating temperature:-5 °C - 50 °C
• Relative humidity:93% non-condensing
• Protection class:IP20
• Nominal output voltage:25VDC
• Max. output current:4A/8A/16A
• Protections:Line fuse T6.3A H 250V (5x20)
• Battery voltage:26.2 to 28.7 VDC, compensated automatically
• VBAT Ripple:< 100mV pK-pK at maximum current
• Resistance to mains voltage dips: >=20mS at maximum current (with PU-A0005)
• Maximum battery current:4A
• Protections:Over-voltage, short circuit and battery reverse polarity
Technical features of the S81-PU001 power supply set according to the different configurations:
FeaturesS81-PU001-1S81-PU001-2S81-PU001-4
Number of PU-A0005-1 power supply units124
Power supply voltage110-240V~110-240V~110-240V~
Rated frequency50-60Hz50-60Hz50-60Hz
Max. input current at 110V~1.6A3.3A6.4A
Max. input current at 240V~0.79 A1.8 A3.2A
Nominal output voltage25VDC ±2%25VDC ±2%25VDC ±2%
Max. residual ripple266mV704mV704mV
Minimum output voltage
Max. output current
Maximum battery resistance
Max. battery current2A4A4A
Maximum battery capacity26A/h26A/h65A/h
1
2
3
1 Full load output voltage with low batteries in case of main voltage failure
2 Current for the loads plus the current required by the control panel.
3 Internal resistance of the batteries and relevant circuits (Cables, terminals, fuses, etc.)
18.9VDC18.9VDC18.9VDC
4A8A16A
1.5 Ω1.5 Ω1.5 Ω
2.1.2 PU-A0005-1 Power Supply Module
It is a universal switching power supply unit able to provide a maximum current of 4A at 25VDC.
It is used in combination with the PU-A0004-1 battery charger in compliance with EN54-4 standard provisions. The power supply unit features a circuit for load distribution which allows the parallel connection of multiple power supply units, up to a maximum of four units.
Technical Features
• Input voltage:110-240V~ (-15% - 10%)
• Max. absorbed current at 110V~:1.6A
• Max. absorbed current at 240V~:0.79A
• Free-air operating temperature:-5 °C - 50 °C
• Relative humidity:93% non-condensing
• Frequency:50-60 Hz
• Power factor (W/VA):0.6 Typical
• Efficiency:> 80%
• Protection class:IP20
• Dimensions:200mm x 110mm x 60mm
• Insulation between input and output: >2 MΩ (500VDC)
• Insulation between input and ground:>2 MΩ (500VDC)
• Dielectric strength between input and output: 3000 VAC for 1 minute
• Dielectric strength between input and ground: 1500 VAC for 1 minute
• Output voltage:25VDC
• Max. output current:4A
• Ripple:<266mV
• Protections:Line Fuse, over-current, short circuit
THIS MODULE INCLUDES CIRCUITS WITH VOLTAGE AND CURRENT VALUES POTENTIALLY
DANGEROUS FOR PEOPLE.
M2N inputNeutral
M3PEEarth
CURRENT SHARE AND STATUS REPLICATION CONNECTIONS
M1RL-COM1Status relay 1 common
M2RL-NO1Status relay 1 NO
M3RL-COM2Status relay 2 common
M4RL-NO2Status relay 2 NO
M5SHARE (+)Signal for load distribution
OUTPUT POWER SUPPLY CONNECTIONS
M1- V. OUTOutput voltage negative
M2- V. OUTOutput voltage negative
M3+V. OUTOutput voltage positive
M4+V. OUTOutput voltage positive
2.1.3 PU-A0004-1 Battery Charger Module
This is a UPS able to control and charge two 12 Volt batteries with a maximum
capacity of 65Ah. Battery maximum charge current can be set through a dipswitch on the module. Under normal operating conditions, a simplified test is
carried out every 30 seconds in order to check the proper presence of the batteries. A full test, instead, is carried out every hour in order to check electrical connections and battery efficiency. During battery trickle charge, battery voltage is
compensated automatically according to the temperature. In case of mains voltage failure, batteries are automatically switched to the load without any interruptions. Should the full charge stage exceed 24 hours, the power supply unit will
signal a battery fault. In case of primary power supply failure, the system will
shut batteries down when the on-load voltage is lower than 18VDC in order to
avoid damaging the batteries. The set features three open collector outputs for
replicating the faults to the alarm control panel, two inputs for monitoring the
power supply units and one RS232 port for the connection to a supervisory system. It can be used together with one or more PU-A0005-1 power supply units.
In this case, the resulting power supply set will be fully compliant with the
EN54-4:1997/A2:2006 standard.
• Battery voltage26.2 to 28.7 VDC, compensated automatically
• Battery current(1/2/4A) Adjustable through dip switch
• VBAT Ripple< 100mV pK-pK at maximum current
• Resistance to main voltage dips>=20mS at maximum current (with PU-A0005)
• Maximum battery circuit resistance 1.5 ohm
• Maximum battery capacity 65 Ah
• Maximum current to batteries Limited automatically
• Current to the load protected by 20A internal fuse
Internal Connections
CONNECTION OF STATUS OPEN COLLECTOR OUTPUTS
Terminal blockTerminal
M1PSU1 FaultOpen collector output - power supply unit section fault
TB1
Terminal blockTerminalNameFunction
TB2
Terminal blockTerminalNameFunction
TB3
M2PSU2 FaultOpen collector output - battery charger section fault
M3Charge StatusBattery charge status output (energized during the full charge stage).
CONNECTION OF POWER SUPPLY UNIT STATUS INDICATION
M1AND-FailureInput of voltage failure to all power supply sets
M2OR-FailureInpu t of voltage failure to one power supply set
M3-V OutM1 and M2 input common
M1- V. BatBattery negative
M2+V. BatBattery positive
M3- V. LoadNegative of power supply to the Load
M4+V. LoadPositive of power supply to the Load
NameFunction
CONNECTIONS TO THE BATTERIES AND TO THE LOAD
2.1.4 S81-PU002 Power Supply Set
This power supply set is able to supply a maximum current of 32 amperes, duplicated to the load,
and to control and charge two 12 Volt batteries with maximum capacity of 120Ah. Battery maximum charge current is 6 amperes. Under normal operating conditions, a simplified test is carried
out every 30 seconds in order to check the proper presence of the batteries. A full test, instead, is
carried out every hour in order to check electrical connections and battery efficiency. Duri ng battery trickle charge, battery voltage is compensated automatically according to the temperature. In
case of mains voltage failure, batteries are automatically switched to the load without any interruptions. Should the full charge stage exceed 24 hours, the power supply unit will signal a battery fault.
In case of primary power supply failure, the system will shut batteries down when the on-load voltage is lower than 18VDC in order to avoid damaging the batteries. The set features seven open collector outputs for replicating the various types of faults to the alarm control panel, along with a
RS232 port for the connection to the configuration program Test-PUA009. Ho-swapping is possible for both the 4 AC/DC converters and the battery charger (Hot Plug).
Number of PU-A0008-1 power supply units24
Power supply voltage110-240V~110-240V~
Rated frequency50-60Hz50-60Hz
Max. input current at 110V~6A12A
Max. input current at 240V~2.7A5.25A
Nominal output voltage25VDC ±2%25VDC ±2%
Max. residual ripple<115mV<115mV
Minimum output voltage
Min. output current
Max. output current
Maximum battery resistance
Max. battery current6A6A
Maximum battery capacity2x12V 120Ah2x12V 120Ah
1
2
2
3
18.9VDC18.9VDC
8A duplicated20A duplicated
12A duplicated32A duplicated
0.1 Ω 0.05 Ω
1 Full load output voltage with low batteries in case of mains voltage failure
2 Current for the loads plus the current required by the control panel
3 Internal resistance of batteries and relevant circuits. (Cables, terminals, fuses, etc.)
2.1.5 PU-A0007-1 Drawer with Slots
Description
It is a 19 inch rack that can contain a PU-A0009-1 battery charger module and up to four
PU-A0008-1 power supply modules. It features ventilation, consisting in three fans with a diameter
of 120 mm. The terminal blocks for power supply and status replication connection are located on
slot back.
F2N1Primary power supply 1 neutral
F3PE1Primary power supply 1 earth
Line- 2 input voltage
Tag TerminalNameFunction
F1L2Primary power supply 2 phase
2
F2N2Primary power supply 2 neutral
F3PE2Primary power supply 2 earth
NOTE: The PU-A0008-1 modules installed in slot 2 and 3 are connected to line 1
network input. The PU-A0008-1 modules installed in slot 4 and 5 are connected to lin e 2
network input.
Main earth
Tag ScrewNameFunction
3V1PERack earthing
Cooling fans
Tag TerminalNameFunction
M1SFan speedometer signal
4-5-6
M2-VFan power supply negative
M3+VFan power supply positive
Output voltage
Tag TerminalNameFunction
M1+VLOADSupply voltage positive
7
M2-VLOADSupply voltage negative
M3+VBATBattery positive
M4-VBATBattery negative
M1PSU1-FaultPrimary power supply failure
M2PSU2-FaultSecondary power supply failure
M3FaultInternal failure
M4Battery statusBattery status (charge/supply)
8
M5Charge StatusBattery charge status (full charge/trickle charge)
M6Rip.1Programmable output
M7Rip.2Programmable output
M8GNDExternal temperature probe display
M9+SExternal temperature probe positive
M10-SExternal temperature probe negative
RS 232
Tag PinName Function
1N.C.Not used
2TxdRS232 data transmission
3RxdRS232 data reception
4N.C.Not used
9
5GNDRS232 common
6N.C.Not used
7N.C.Not used
8N.C.Not used
9N.C.Not used
2.1.6 PU-A0008-1 Power Supply Module
Description
It is a switching power supply unit with universal input able to provide a maximum current of 20A at 25VDC. It is placed in a 19 inch
rack slot and used in combination with the PU-A0009-1 battery charger in compliance with EN54-4 standard. The power supply unit features a circuit for load distribution which allows the parallel
connection of multiple power supply units, up to a maximum of four
units. Module hot swapping is allowed (Hot Plug). On the front panel
there are: two green LEDs signaling the proper presence of input and
output voltage; a yellow LED that lights up in case of failure; and a
button for shutting the module down before hot-swapping.
• Insulation between input and output:>2 MΩ (500VDC)
• Insulation between input and ground:>2 MΩ (500VDC)
• Dielectric strength between input and output:3000 VAC for 1 minute
• Dielectric strength between inputs and ground: 1500 VAC for 1 minute
• VLOAD voltage:25VDC ±2%
• VLOAD current:20A
• Max. starting current:25A
• VLOAD ripple:< 110mV pK-pK at maximum current
• VLOAD output stability:> 1%
• Line Fuse:T10A H 250V (5x20)
• Protections:Over-voltage, short circuit
WARNING: HIGH VOLTAGE
THIS MODULE INCLUDES CIRCUITS WITH VOLTAGE AND CURRENT VALUES POTENTIALLY
DANGEROUS FOR PEOPLE.
2.1.7 PU-A0009-1 Battery Charger Module
Description
This is a UPS able to control and charge two 12 Volt batteries with a maximum capacity of 120A/h. Battery maximum charge current can be set through
a dip-switch on the module. Under normal operating conditions, a simplified
test is carried out every 30 seconds in order to check the proper presence of
the batteries. A full test, instead, is carried out every hour in order to check
electrical connections and battery efficiency. During battery trickle charge,
battery voltage is compensated automatically according to the measured temperature. During the full charge stage, instead, it is kept at 27.6VDC In case of
mains voltage failure, batteries are automatically switched to the load without
any interruptions. Should the full charge stage last more than 24 hours, the
battery charger will signal a battery fault. In case of primary power supply
failure, the system will shut batteries down when the on-load voltage is lower
than 18VDC in order to avoid damaging the batteries. The set features seven
open collector outputs for replicating the various types of faults, several inputs
for monitoring power supply module and cooling fan status, and one RS232
port for the connection to a supervisory system. It is used together with one or
more PU-A0008-1 power supply units. In this case, the resulting power supply
set is fully compliant with the EN54-4:1997/A2:2006 standard.
• Battery voltage:26.2 to 28.7 VDC, compensated automatically
• Battery current:(4/6A) Adjustable through dip switch
• VBAT Ripple:< 100mV pK-pK at maximum current
• Resistance to mains voltage dips:>=20mS at maximum current (with PU-A0008)
• Maximum battery capacity:120 Ah
• Maximum current to batteries:Limited automatically
• Current to the load:50A External fuse
• Protections:Over-voltage, short circuit, and battery reverse polarity
• CPD reference standards:EN54-4
• EC reference standards:EN50081-2 and EN50082-2 (industrial environment)
2.2 Central Unit Rack
The central unit includes a central processing unit (CPU) with the relevant bus, the display module
and the module for default I/O control. It has the function of processing the data received from the
modules and controlling the operator interface and the communication with supervisory systems.
It is the interface between the two CPUs and the other peripheral devices making up the system.
Technical Features
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95%(RH) non-condensing
Internal connections
TB1 & TB2: +V/-V
These two Faston terminals are used for supply voltage connection
TAGFunctionCable color
TB125VDC power supply positiveRed
TB225VDC power supply negativeBlack
J1: Default I/O
It is a connector for a 14-pole flat cable allowing the connection to the module S81-T8004-1
(default I/O).
J2 & J3: LVDS Bus Loop Link
They are 2 RJ45 connectors for category 5 cable allowing to connect the CPU to the two peripheral
modules. This is a closed loop connection, thus allowing to increase system reliability. The J2 connector (Bus-IN) must be connected to the BUS-OUT terminal of the last rack, whereas the J3 connector (Bus-OUT) must be connected to the BUS-IN terminal of the first rack.
Two connectors for 10-pole flat cable, allowing the connection of a 40 or 80 column serial printer
and of a PC for configuration data transfer. Use the S81-CFT10/2 cable for connecting to the PC.
A connector for 20-pole flat cable, allowing the connection to the S81-U1006 display module.
2.2.2 S81-U1002-1
Description
This module is system central unit. Besides the micro-controller, the module
includes the following elements: Flash memory, buffered static Ram, watchdog
circuit and Ethernet controller. The CPU module can be used in both single and
redundant configuration. In this last case, two CPUs operating in parallel are
used. Both CPUs process the information received from the modules, but only
one of the two CPUs runs the commands. In case of failure of the primary CPU,
the other one keeps on carrying out all the tasks without any interruption of the
machine cycle.
The module front panel includes four LEDs indicating the following conditions:
LEDModeIndication
Link
(Green)
Activity
(Green)
Run
(Green)
Wdo
(Yellow)
Connections
On module front panel there is an 8-pole RJ45 connector, enabling module connection to the Ethernet network. Through this port, connections with maximum length of 100 mm can be carried out
using category 5 cables.
2.2.3 S81-U1006-1
Description
The display module is the interface between the control panel and the operator. It includes a LEDbacklit graphic display with 30 lines of 52 characters each, 19 LEDs, 23 buttons, and one buzzer.
⊗
∅
⊗
∅
⊗
∅ = flashing ⊗ = steady on − = off
Ethernet connection link present
−
No Ethernet connection link
Data transmission/receipt on the Ethernet port
−
No activity on the Ethernet port
Primary CPU
Secondary CPU
Module rear panel includes 5 LEDs with the following functions:
LEDIndication
LD15 (Yellow)Currently not used
LD16 (Yellow)Currently not used
CPU-A Link (Green)Steady on when the communication Link with CPU-A is present
CPU-B Link (Green)Steady on when the communication Link with CPU-B is present
S81-T8004-1 Link Steady on when the communication Link with S81-T8004-1 is present
Buttons
ButtonDescription of buttonsLevelDescription of the function
Local Buzzer Silencing 1-2-3 Deactivates the local buzzer
System sounder silencing2-3Silencing of system fire alarm sounders
Control panel reset 2-3Resets the control panel
Evacuation command2-3Activates system fire alarm sounders
Selection cancel1-2-3 To cancel an operation or to go back to the previous page
Enter key1-2-3 Confirms a selection made when navigating through operator cycle menus
Arrows for selecting menu direction2-3They enable the navigation through operator cycle menus
0-9 key numbers1-2-3 They are used for entering parameters and access passwords
Scroll1-2-3 It allows to view the complete list in operator cycle menu
F1 key1-2-3 It allows to access directly the main page of the active access level
Internal connections
BR1 & BR2: +V/-V
These two Faston terminals are used for supply voltage connection
TAGFunctionCable Color
BR125VDC power supply positiveRed
BR225VDC power supply negative Black
J2
A connector for 20-pole flat cable, allowing the connection to S81-E2003-1 Bus module.
J3
A 4-pole connector supplying power to the LEDs for display backlighting.
J5
A 10-pole connector connecting the membrane keyboard to the display.
2.3 I/O Rack
Up to ten expansion racks can be connected to an H-S81-HS base. Each can include up to thirteen
I/O modules. Position 14 is reserved to the S81-E2002-1 rack controller. Two I/O rack types are
available according to the type of terminations to be used.
This module includes the thirteen modules and the rack controller . Module-field device connections
are carried out using flat cables, with the relevant termination module, from the DIN bar. Using this
bus, systems with redundant I/O modules are not possible.
Technical Features
• Supply voltage:22 - 29VDC
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Maximum number of I/O modules: 13
• Field connections:20-way flat cable
Internal connections
20-pin flat cables are used in this case to connect the rack to the termination module. Flat cable
maximum length is 5 meters. The typ e of termination module and the relevant connections depend
on the type of module to be terminated. Field devices, in this case, can be easily disconnected by
simply disconnecting the flat cables from the termination modules.
This module includes the thirteen modules and the rack controller . Module-field device connections
are carried out by using 3-meter long pre-wired cables. Using this bus, systems with redundant I/O
modules are possible.
Technical features
• Supply voltage:22-29VDC
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
Maximum humidity:
•
• Maximum number of I/O modules: 13
• Field connections:Multi-conductor cables
95% (RH) non-condensing
Internal connections
Pre-wired cables are used in this case to connect the rack to the terminal block. Standard cable
length is 2 meters. The cable type and the relevant connections depend on the type of module to be
terminated.
This module is the rack controller. It allows the information exchange between
CPUs and rack modules. It controls 13 point-to-point links to rack modules and
two closed loop links for the communication to the two CPUs.
Technical features
• Safety rating:applicable up to SIL3
• Supply voltage:22-29VDC
• Quiescent current:20mA
• Operating temperature: -5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
Status Indications
Module front panel includes eight LEDs with the following functions:
LEDIndication
A-IN Link (green)Steady on when CPU-0 loop input link is present
A-OUT Link (green)Steady on when CPU-0 loop output link is present
B-IN Link (green)Steady on when CPU-1 loop input link is present
B-OUT Link (green)Steady on when CPU-1 loop output link is present
Run (green)Flashes during operation
FLT1 (yellow)Steady on in case of local interrupt
FLT2 (yellow)Steady on in case of CPU-A loop interrupt
FLT3 (yellow)Steady on in case of CPU-B loop interrupt
Configuration
Modules are configured by means of a 4-way dip switch used to set the number of racks from 1 to
10, according to the table below:
2.4 I/O modules
The following I/O module types are available:
Part NumberDescriptionNotes
S81-F3002-18 monitored input module for conventional detectorsRedundancy not possible
S81-F3002-28 monitored input module for conventional detectorsRedundancy possible
S81-F4001-1Module with 1 x 4-20mA analog inputRedundancy not possible
S81-F4001-2Module with 1 x 4-20mA analog inputRedundancy possible
S81-F4002-1Module with 2 4-20mA analog inputsRedundancy not possible
S81-F4002-2Module with 2 4-20mA analog inputsRedundancy possible
S81-F4003-1Module with 8 x 4-20mA analog inputsRedundancy not possible
S81-F4003-2Module with 8 x 4-20mA analog inputsRedundancy possible
S81-F5001-1Module with 8 x 500mA monitored outputs for solenoidsRedundancy not possible
S81-F5001-2Module with 8 x 500mA monitored outputs for solenoidsRedundancy possible
S81-F5002-1Module with 16 x 250mA non monitored outputsRedundancy not possible
S81-F5003-1Module with 8 x 250mA monitored outputs for soundersRedundancy not possible
S81-F5004-1Module with 4 x 2A monitored outputs for solenoidsRedundancy not possible
S81-F5004-2Module with 4 x 2A monitored outputs for solenoidsRedundancy possible
S81-F6001-1Module with 8 outputs for fire extinguishing system controlRedundancy not possible
S81-F6002-1Logic moduleRedundancy not possible
S81-F7002-1Loop control module with ESP protocolRedundancy not possible
S81-F7006-1Modbus RTU Master/Slave moduleRedundancy not possible
S81-F7007-1Loop control module with SSP protocolRedundancy not possible
S81-F7008-1Control modules for weighing modulesRedundancy not possible
S81-F7009-1Loop control module with XP95/Discovery protocol Redundancy not possible
S81-F7010-1Loop control module with System Sensor protocol Redundancy not possible
2.4.1 S81-F3002-1 & S81-F3002-2
Description
Eight balanced input module for conventional safety related sensors. All channels can be reset individually and are tested every 30 seconds during operation.
This module is suitable for controlling detection systems with conventio nal
lines and can be used in systems with already existing detection lines for controlling automatic fire extinguishing systems with double enable logic or intrinsically safe systems. It is also used for controlling all the devices typical of fire
extinguishing systems (pressure switches, discharge buttons, etc.). This module
can be duplicated in fault tolerant systems; in this case, the two modules shall
be placed on adjacent racks in the same position. In this configuration, the eight
detection lines are connected to both modules.
Technical Features
• Safety rating:applicable up to SIL3
• Redundancy:S81-F3002-2 model
• Alarm threshold:2 programmable thresholds on 255 levels
Non-Latching-NC,
Alarm verification functionYes/NoDisabled
Pre-alarm threshold10-250Fixed threshold
Alarm threshold10-250Fixed threshold
Channel status with line short circuitTrouble / AlarmTampering
Type of indicationFire, Supervisory, Gas, Trouble , Hidden,
Buzzer Only
Automatic alarm resetYes/NoN0
Enable/Disable channel status export to HostsNo, TCP1, TCP2, RS232No, TCP1, TCP2, RS232
Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232No, TCP1, TCP2, RS232
Allowed values in
SECURITY mode
Latching-NC
Burglar Alarm, Hidden
Field Connection
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
The module is connected to the S81-T8001-1 termination module with 16
terminals by using a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block by the S81-CCT6 16conductor multi-polar cable. For S81-F3002-2 module redundant connection, use the S81-CCT1R cable.
Figure 2.20 Standard Connection Diagram for Burglar Alarm
2.4.2 S81-F4001-1 & S81-F4001-2
Description
Safety related module with 1 x 4-20mA analog input and two programmable
thresholds. It can control the following transducer types: explo sion sensors, air
quality sensors, oxygen sensors, temperature sensors, 4-20mA general sensors.
The channel is continuously tested during operation. The module features a 420mA output that provides the current value measured on the input. This analog
value can be transferred to a DCS by means of the S81-F7006-1 Modbus RTU
module. This module can be duplicated in fault tolerant systems; in this case, the
two modules shall be placed on two adjacent racks in the same position. In this
configuration, the detection lines is connected to both modules.
Technical Features
• Safety rating:applicable up to SIL3
• Redundancy:S81-F4001-2 model
• Alarm threshold:2 programmable thresholds
• Channel test:continuously tested
• Measuring range0-24mA
• Line short circuit condition:with current >23.5mA
• Supply voltage:22-29VDC
• Quiescent current:35mA
• Operating temperature:-5 - 50°C
• Storage temperature:-30 - 80°C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
Module front panel includes three LEDs, a graphic LED bar, and a three-digit display.
Input channel status
Normal−− −
Disabled−− ⊗
Trouble −− ¬
Pre-alarm⊗⊗ −
Alarm⊗− −
Key to symbols: ⊗= steady on LED; − = LED off; ∅= flashing LED
2nd Level1st LevelFault/Disabled
Red LEDRed LEDYellow LED
LED Bar
It indicates the 0-100% percentage of the measured value.
The three-digit display generally shows the measured value in the programmed format. Moreover,
it shows some fault codes according to the following table.
No.Channel Status
---Initialization stage
F00Module/channel not configured
F01Line opening (current <1mA)
F02Over-current (current >23.5mA)
F03Internal test failed
Fx.xDevice trouble
E00Memory data error CRC
+/-999Measured value
1 For current values lower than the set trouble threshold and exceeding 1mA, the
display will show the value of the measured current in mA preceded by letter F. Please
refer to the manual of the connected device for identifying the type of anomaly.
NOTE: The 3-digit display on module front panel does not provide the operator with fundamental
information and does not comply with the standard EN-54-2.
1
Configuration
By using the configuration program ProS81, the following parameters can be set for each input
channel:
FunctionAllowed values
Operating mode Latching/Non latching, UP/Down, NM
Mode of analog value transfer to Hosts Upon request/Automatic in case of change
Unit of measure of the channelPpm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm
Zero Point of the measuring range-999 - 999
End of scale of the measuring range-999 - 999
Pre-alarm threshold-999 - 999
Alarm threshold-999 - 999
Lower trouble threshold1,0 - 3,8mA
Alarm delay0 - 255 seconds
Type of indicationFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm resetYes/No
Enable/Disable status export via ModBus Yes/No
Enable/Disable channel status export to HostsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232
It defines the format of the analog value sent via ModBus,
and automatically via Host
mA, mA tenth, VI, VI tenth, converter points
Threshold Setting
The following parameters can be set for each module through the configuration program or directly
on the control panel in the operator cycle, access level 3:
•Pre-alarm threshold.
•Alarm threshold
•Current value below which a trouble condition is signaled
•Calibration mixture concentration value for end of scale calibration
•Disable the channel of the module to be calibrated from the operator cycle.
•Enter the diagnosis cycle of the module to be calibrated.
•Make sure that no gas is present near the sensor to be calibrated.
•Press the “1” key to calibrate the zero point.
•The new zero value is stored in the memory of the module.
•Press “0” to cancel the operation.
•Exit the module diagnosis cycle and enable the channel.
NOTE: The zero point can be calibrated only with zero values ranging between 3 and 5mA.
End of Scale Calibration
Calibrate the end of scale as follows:
•Disable the channel of the module to be calibrated from the operator cycle.
•Enter the diagnosis cycle of the module to be calibrated.
•Apply gas to the sensor according to the percentage set during configuration.
•Wait for the gas value measured by the module to stabilize.
•Press the key “3” to calibrate the end of scale.
•The new value is stored in the memory of the module.
•Press “2” to cancel the operation.
•Exit the module diagnosis cycle and enable the channel.
NOTE: The end of scale can be calibrated only if the current value measured by the module is
±3mA than the set calibration value.
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 terminals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT2 16conductor multi-polar cable. For S81-F4001-2 module redundant connection ,
use the S81-CCT2R cable.
Safety related module with 2 x 4-20mA analog inputs and two thresholds to be
programmed on the module through the operator cycle. The following transducer
types can be connected to this module: Explosion Sensors, Air Quality Sensors,
Oxygen Sensors, T emperature Sensors, 4-20mA General Sensors. The channel is
continuously tested during operation. The module features 4-20mA outputs that
provide the current value measured on the input. The analog value of each channel can be transferred to a DCS by means of the S81-F7006-1 Modbus RTU
module. This module can be duplicated for fault tolerant systems; in this case,
the two modules shall be placed on two adjacent racks in the same position. In
this configuration, the two detection lines are connected to both modules.
Technical Features
• Safety rating:
• Redundancy:
• Alarm threshold:
• Channel test:
• Measuring range
• Line short circuit condition:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
applicable up to SIL3
S81-F4002-2 model
2 programmable
continuously tested
0-24mA
with current >23.5mA
22-29VDC
60mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
Status Indications
Module front panel includes three LEDs and a three-digit display for each channel.
Input channel status
Normal−− −
Disabled−− ⊗
Trouble −− ¬
Pre-alarm⊗⊗ −
Alarm⊗− −Key to symbols: ⊗= steady on LED; − = LED off; ∅= flashing LED
2nd Level1st LevelFault/Disabled
Red LEDRed LEDYellow LED
Three-Digit Display
The three-digit display generally shows the measured value in the programmed format. Moreover,
it shows some fault codes according to the following table.
No.Channel Status
---Initialization stage
F00Module/channel not configured
F01Line opening (current <1mA)
F02Over current (current >23.5mA)
F03Internal test failed
Fx.xDevice trouble
E00Memory data error CRC
+/-999Measured value
1 For current values lower than the set trouble threshold and exceeding 1mA, the display
will show the value of the measured current in mA preceded by letter F. Please refer to
the manual of the connected device for identifying the type of anomaly.
NOTE: The two 3-digit displays on module front panel do not provide the operator with
fundamental information and do not comply with the standard EN-54-2.
Configuration
By using the configuration program ProS81, the following parameters can be set for each input
channel:
FunctionAllowed values
Operating mode Latching/Non latching, UP/Down, NM
Mode of analog value transfer to Hosts Upon request/Automatic in case of change
Unit of measure of the channelPpm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm
Zero Point of the measuring range-999 - 999
End of scale of the measuring range-999 - 999
Pre-alarm threshold-999 - 999
Alarm threshold-999 - 999
Lower trouble threshold1.0 - 3.8mA
Alarm delay0 - 255 seconds
Type of indicationFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm resetYes/No
Enable/Disable status export via ModBus Yes/No
Enable/Disable channel status export to HostsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232
It defines the format of the analog value sent via ModBus,
and automatically via Host
mA, mA tenth, VI, VI tenth, converter points
Threshold Setting
The following parameters can be set for each module through the configuration program or directly
on the control panel in the operator cycle, access level 3:
•Pre-alarm threshold.
•Alarm threshold.
•Current value below which a trouble condition is signaled.
•Calibration mixture concentration value for end of scale calibration.
Zero Point Calibration
Calibrate the zero point as reported below:
•Disable the channel of the module to be calibrated from the operator cycle.
•Enter the diagnosis cycle of the module to be calibrated.
•Make sure that no gas is present near the sensor to be calibrated.
•Press the “1” key to calibrate the zero point of the channel 1.
•Press “0” to cancel the operation for the channel 1.
•Press the “5” key to calibrate the zero point of the channel 2.
•Press the “4” key to cancel the operation for the channel 2.
•Exit the module diagnosis cycle and enable the channel.
NOTE: The zero point can be calibrated only with zero values ranging between 3 and 5mA.
•Disable the channel of the module to be calibrated from the operator cycle.
•Enter the diagnosis cycle of the module to be calibrated.
•Apply gas to the sensor according to the percentage set during configuration.
•Wait for the gas value measured by the module to stabilize.
•Press the key “3” to calibrate the end of scale for channel 1.
•Press “2” to cancel the operation for channel 1.
•Press the key “7” to calibrate the end of scale for channel 2.
•Press “6” to cancel the operation for channel 2.
•Exit the module diagnosis cycle and enable the channel.
NOTE: The end of scale can be calibrated only if the current value measured by the module is
±3mA than the set calibration value.
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 terminals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT7 16conductor multi-polar cable. For S81-F4002-2 module redundant connection,
use the S81-CCT7R cable.
Safety related module with 8 x 4-20mA analog inputs and two thresholds to be
programmed on the module through the operator cycle. The following transducer types can be connected to this module: Explosion Sensors, Air Quality
Sensors, Oxygen Sensors, Temperature Sensors, 4-20mA General Sensors. The
channels are continuously tested during operation. The analog value of each
channel can be transferred to a DCS by means of the S81-F7006-1 Modbus RTU
module. This module can be duplicated in fault tolerant systems; in this case, the
two modules shall be placed on two adjacent racks in the same position. In this
configuration, the eight detection lines are connected to both modules.
Technical Features
• Safety rating:applicable up to SIL3
• Redundancy:S81-F4003-2 model
• Alarm threshold:2 programmable thresholds for each channel
• Channel test:continuously
• Measuring range0-24mA
• Line short circuit condition: with current >23.5mA
• Supply voltage:22-29VDC
• Quiescent current: 13mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
Module front panel includes two status LEDs for each one of the eight channels.
Input channel status
Normal−−
Disabled−⊗
Trouble −−
Pre-alarm−−
Alarm⊗−
Key to symbols: ⊗= steady on LED; − = LED off; ∅= flashing LED
Indications Line LEDs 1-8
Red LEDYellow LED
Configuration
By using the configuration program ProS81, the following parameters can be set for each input
channel:
FunctionAllowed values
Operating mode Latching/Non latching, UP/Down, NM
Mode of analog value transfer to Hosts Upon request/Automatic in case of change
Unit of measure of the channelPpm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm
Zero Point of the measuring range-999 - 999
End of scale of the measuring range-999 - 999
Pre-alarm threshold-999 - 999
Alarm threshold-999 - 999
Lower trouble threshold1.0 - 3.8mA
Alarm delay0 - 255 seconds
Type of indicationFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm resetYes/No
Enable/Disable status export via ModBus Yes/No
Enable/Disable status export to HostsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232
It defines the format of the analog value sent via ModBus,
The following parameters can be set for each module through the configuration program or directly
on the control panel in the operator cycle, access level 3:
•Pre-alarm threshold.
•Alarm threshold.
•Current value below which a trouble condition is signaled
•Calibration mixture concentration value for end of scale calibration
Zero Point Calibration
Calibrate the zero point as reported below:
•Disable the channel of the module to be calibrated from the operator cycle.
•Enter the diagnosis cycle of the module to be calibrated.
•Disconnect the channel to be calibrated (1-8).
•Make sure that no gas is present near the sensor to be calibrated.
•Press the “1” key to calibrate the zero point of the channel.
•The new zero value is stored in the memory of the module.
•Press “0” to cancel the operation for the channel.
•Exit the module diagnosis cycle and enable the channel.
NOTE: The zero point can be calibrated only with zero values ranging between 3 and 5mA.
End of Scale Calibration
Calibrate the end of scale as follows:
•Disable the channel of the module to be calibrated from the operator cycle.
•Enter the diagnosis cycle of the module to be calibrated.
•Disconnect the channel to be calibrated (1-8).
•Apply gas to the sensor according to the percentage set during configuration.
•Wait for the gas value measured by the module to stabilize.
•Press the key “3” to calibrate the end of scale for the channel.
•Press “2” to cancel the operation for the channel.
•Exit the module diagnosis cycle and enable the channel.
NOTE: The end of scale can be calibrated only if the current value measured by the module is
±3mA than the set calibration value.
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
The module is connected to a S81-T8003-1 termination module with 8 terminals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block by the S81-CCT3 16-conductor multi-polar cable. For S81-F4003-2 module redundant connection, use
the S81-CCT3R1 cable.
FunctionTermination with Flat CableTermination with Multi-conductor Cable
Input signal 1+∅1
Input signal 2+∅22
Input signal 3+∅33
Input signal 4+∅44
Input signal 5+∅55
Input signal 6+∅66
Input signal 7+∅77
Input signal 8+∅88
8 x 500 mA monitored control channel module. This is especially suited to control automatic fire extinguishing systems, and can be used both for controlling
directional and releasing solenoid valves and evacuation visual and audible
alarm devices. During operation, each channel is cyclically tested by the module
through reversal of output signal for approximately 200 hundreds of microseconds. In case of difference between the set signal and the measured one, the control panel promptly signals a fault. Several channels can be connected in parallel
in order to increase the output current. This module can be duplicated in fault
tolerant systems; in this case, the two modules shall be placed on adjacent racks
in the same position. In this configuration, the eight output lines are connected
to both modules.
Technical Features
• Safety rating:applicable up to SIL3
• Redundancy:S81-F5001-2 model
• Channel test:every 2 seconds
• Max. output current:500mA
• Automatic output protection:Yes
• Supply voltage:22-29VDC
• Quiescent current: 35mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
Each one of the eight channels on the front panel includes two status LEDs
Output Channel Status
Off−−
Disabled⊗−
Trouble∅−
Active−⊗Key to symbols ⊗= steady on LED; − = LED off; ∅= flashing LED
Indications 1-8 Out LEDs
Yellow LEDRED LED
Configuration
By using the configuration program ProS81, the following parameters can be set for each output
channel:
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation
Timing1 to 255 seconds/minutes (only for pulsing and intermittent modes)
Output typeNormal / Sounder
Output status in case of CPU faultFrozen in the last status / Off
Enable/Disable status export to HostsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
Thanks to this bus, the module can be terminated by using a S81-T8003-1 termination module with
8 terminals or a S81-T8006-1 8-relay module with a 20-way flat cable.
S81-T8006-1
If this termination type is used, there will be eight relay outputs with one 4A SPDT contact to be
used exclusively for connecting circuits operating with SELV voltage. This solution will guarantee
coil monitoring for the eight relays.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT3 8-conductor
multi-polar cable. For S81-F5001-2 module redundant connection, use the S81CCT3R cable.
FunctionTermination with Flat CableTermination with Multi-conductor Cable
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation
Timing1 to 255 seconds/minutes (only for pulsing and intermittent modes)
Output typeNormal / Sounder
Output status in case of CPU faultFrozen in the last status / Off
Enable/Disable status export to HostsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts on
the channel
No, TCP1, TCP2, RS232
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
Thanks to this bus, the module can be terminated by using a S81-T8001-1 termination module with
16 terminals or a S81-T8007-2 16-relay module.
S81-T8007-2
When this termination type is used, there will be sixteen relay outputs with one 4A SPDT contact to
be used exclusively for connecting circuits operating with SELV voltage.
S81-E2001-2 Bus
Thanks to this bus, the module can be terminated by using a S81-CCT1 16-conductor multi-polar
cable or a S81-T8007-2 16-relay module.
Brown
Green
Yellow
Gray
Pink
Blue
Red
Black
Violet
Gray/Pink
Red/Blue
White/Green
Brown/Green
White/Yellow
Yellow/Brown
White/Gray
S81/CCT1
Figure 2.29 Field Connections
2.4.7 S81-F5003-1
Description
Module with 8 x 250 mA monitored output channels for sounder control. Outputs
are controlled by two virtual channels for allowing both continuous and intermittent output control. Line is monitored by polarity reversal.
Technical Features
• Redundancy:No
• Channel test:No
• Max. output current250mA
• Automatic output protection:Yes
• Supply voltage:22-29VDC
• Quiescent current: 38mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
Each one of the eight channels on the front panel includes two status LEDs.
Output channel status
Off−−
Disabled⊗−
Trouble∅−
Active−⊗Key to symbols ⊗= steady on LED; − = LED off; ∅= flashing LED
Indications 1 - 8 Out LEDs
Yellow LEDRED LED
64H-S81-HS Installation & Operation Manual — Form Number XX-XXXX—X P/N LS10114-000HI-E:A 2/24/2015
Page 65
I/O modulesParts of the H-S81-HS System
Configuration
By using the configuration program ProS81, the following parameters can be set for each output
channel:
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation, ANSI-S3.41, March
Timing1 to 255 seconds
Output typeNormal / Sounder
Output status in case of CPU faultFrozen in the last status / Off
Enable/Disable status export to HostsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts on
the channel
No, TCP1, TCP2, RS232
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
Thanks to this bus, the module can be terminated by using a S81-T8001-1
termination module with 16 terminals.
S81-E2001-2 Bus
Thanks to this bus, the module can be terminated by using a S81-CCT1
16-conductor multi-polar cable or a S81-T8008-1 module.
S81-T8008-1
Should 500 mA per line not be enough, it is possible to connect the optional module S81-T8008-1
to module S81-F5003-1. The former will add 4 x 2A at 24 VDC polarity reversal outputs.
4 x 2A monitored control channel module. This is especially suited to control
automatic fire extinguishing systems, and can be used both for controlling directional and releasing solenoid valves and evacuation visual and audible alarm
devices. During operation, each channel is cyclically tested by the module
through reversal of output signal for approximately 200 hundreds of microseconds. In case of difference between the set signal and the measured one, the control panel promptly signals a fault. Several channels can be connected in parallel
in order to increase the output current. This module can be duplicated in fault tolerant systems; in this case, the two modules shall be placed on adjacent racks in
the same position. In this configuration, the eight output lines are connected to
both modules.
Technical Features
• Safety rating:applicable up to SIL3
• Redundancy:S81-F5004-2 model
• Channel test:every 2 seconds
• Max. output current2A
• Automatic output protection: Yes
• Supply voltage:22-29VDC
• Quiescent current: 20mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
Each one of the eight channels on the front panel includes two status LEDs.
Output channel status
Off−−
Disabled⊗−
Trouble∅−
Active−⊗
Key to symbols ⊗= steady on LED; − = LED off; ∅= flashing LED
Indications 1 - 4 Out LEDs
Yellow LEDRED LED
Configurations
By using the configuration program ProS81, the following parameters can be set for each output
channel:
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation
Timing1 to 255 seconds/minutes (only for pulsing and intermittent modes)
Output typeNormal / Sounder
Output status in case of CPU faultFrozen in the last status / Off
Enable/Disable status export to HostsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts
The module can be connected to field terminal block by using only a multi-conductor cable wi th
the S81-E2001-2 bus.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 8-conductor
multi-polar cable. For S81-F5004-2 module redundant connection, use the
S81-CCT4R cable.
FunctionTermination with Multi-conductor Cable
Output 1+1White
Output 2+2Brown
Output 3+3Green
Output 4+4Yellow
Figure 2.32 Field Connections
NOTE: The module can control resistive or inductive loads with a maximum current of 2A.
Should the module be used for controlling filament lamps, the maximum load power shall not
exceed 10W.
This module is used for controlling the logic and indications of a certain fire
extinguishing zone in compliance with the requirements of the EN12094-1 standard. It controls ten output variables and seven input variables. It controls some
fire extinguishing system typical logics, such as discharge delay and reset inhibit
time. This module checks the status of the inputs and outputs physically located
on other modules by using virtual channels.
Technical Features
• Safety rating:applicable up to SIL3
• Redundancy:Yes
• Max. output current250mA
• Automatic output protection:No
• Supply voltage:22-29VDC
• Quiescent current: 10mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
The front panel includes 8 status LEDs with the following functions:
LEDIndication
Activated (Red LED)Steady on under “activated” condition. It goes out in case of reset.
Relised (Red LED)Steady on under “released” condition. It goes out in case of reset.
Fault (Yellow LED)Flashing in case of trouble in the fire extinguishing zone.
Disabled (Yellow LED)Steady on if a fire extinguishing zone is disabled
Inhibit (Yellow LED)Steady on under “inhibit” condition.
Hold (Yellow LED)Steady on under “Hold” condition.
Aut. Off (Yellow LED)Steady on under “Automatic exclusion” condition
Res. Bank (Yellow LED) Steady on when the reserve bank is selected
By using the ProS81 configuration program, the following parameters can be set for each virtual
channel:
FunctionTypeMode
Operating modeSensorsNO
Activates/alarmed conditionSensorsNon Latching
Type of indicationSensorsFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Operating modeActuatorsContinuous-Normally De-energized
Output typeActuatorsNormal
Enable/Disable status export to HostsSensors/Actuators No, TCP1, TCP2, RS232
Enable/Disable commands from Hosts
on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
The following parameters can be set for each module through the configuration program or directly
on the control panel in the operator cycle, access level 3:
Logic module able to control 100 S-R flip flops, 100 toggles, and 100 timers.
Timers can be configured for two operating modes (Mode-A and Mode-B).
Technical Features
• Redundancy:Yes
• Maximum number of S-R flip flops:100
• Maximum number of logic Toggles: 100
• Maximum number of Timers:100
• Timer range:0-255 seconds
• Supply voltage:22-29VDC
• Quiescent current: 9mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
The front panel includes four LEDs with the following functions:
LEDIndication
F1 (Green LED)Steady on if a logic function input variable is active
F2 (Green LED)Steady on if a logic function output variable is active
F3 (Green LED)Flashing during Timer count.
Disabled (Yellow LED) Steady on if an input or output variable is disabled
Configuration
By using the ProS81 configuration program, the following parameters can be set for each virtual
channel:
ParameterTypeMode
Type SensorsFlip Flop / Toggle / Timer
ModeSensorsA / B (Only for Timer types)
Alarm delaySensors0-255 seconds (Only for Flip Flop and Timer types)
Type of indicationSensorsFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Enable/Disable status export to HostsSensors/ActuatorsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts
on the channel
NOTE: Logic function virtual inputs are set in output zones, whereas logic function virtual
outputs are set in zone sensors.
Sensors/ActuatorsNo, TCP1, TCP2, RS232
Logic Functions
The following time diagrams describe in detail the operation of the various logic functions of the
module.
This module does not feature any field connections, and therefore requires no terminations.
2.4.11 S81-F7002-1
Description
Control module for addressable devices using Hochiki ESP protocol. This module can control up to a maximum of 127 fire detection modules including: smoke,
heat, combined detectors, alarm buttons, control modules, visual and audible
alarm devices.
Technical Features
• Redundancy:No
• Maximum number of devices per loop:127
• Loop maximum current400mA
• Supply voltage:22-29VDC
• Quiescent current: 90mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LEDIndication
Active (Red LED)Steady on if an input is under alarmed/activated condition
Disabled (Yellow LED)Steady on if an input or an output is disabled
Fault (Yellow LED)Flashing in case of Fault condition
Loop Fault (Yellow LED)Flashing in case of loop short circuit or open loop
Log on Fault (Yellow LED) Flashing in case of difference between the detected devices
Service (Yellow LED)Flashing in case of in case of smoke detectors with dirty lenses
TX Pol. (Green LED)It lights up every time data are transmitted from the module to
RX Pol. (Green LED)It lights up every time data from loop devices are received
By using the configuration program ProS81, the following parameters can be set for each point of
the single devices, according to the relevant type:
ParameterTypeMode
Operating mode SensorsLatching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
SensitivitySensors3 sensitivity levels to be selected
Measuring rangeSensorsSee table
Pre-alarm threshold SensorsAccording to the selected measuring range
Alarm threshold SensorsAccording to the selected measuring range
Type of indication SensorsFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm resetSensorsYes/No
Operating modeActuatorsContinuous-Normally Energized, Continuous-Normally De-energized,
TimingActuators1 to 15 seconds (only for pulsing and intermittent modes)
Output typeActuatorsNormal / Sounder
Sounder toneActuators7 selectable tones
Sounder volumeActuators50,55,60,70,78,80,85,88,90,93,94,95,98 decibels
Enable/Disable status export to
Hosts
Enable/Disable commands
from Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Intermittent, Pulsing
The following measuring ranges, with the relevant thresholds, can be selected for the 4-20mA
S81-Mod-AN module:
This module can control the following types of Hochiki Europe addressable devices:
Part NumberDescriptionType Pros-81Notes
ALG-E, ALG-ENPhotoelectric Smoke SensorALG-EPowered by the loop
ATG-EHeat SensorATG-EPowered by the loop
ACB-E, ACB-EWMulti Heat SensorACB-EPowered by the loop
AIE-EIonization Smoke SensorAIE-EPowered by the loop
ACA-ESmoke/Heat Multi SensorACA-EPowered by the loop
S81-Mod-An4-20mA Analog ModuleCHQ-ANRequires external power supply
CHQ-CP, HCP-E, HCP-WManual Call PointCHQ-CPPowered by the loop
CHQ-MZ,CHQ-SZMSingle Zone ModuleCHQ-MZPowered by the loop
CHQ-Z, CHQ-DZMDual Zone ModuleCHQ-ZRequires external power supply
CHQ-SIMSingle Input ModuleCHQ-SIMPowered by the loop
CHQ-S, CHQ-DIMDual Input ModuleCHQ-SPowered by the loop
CHQ-R, CHQ-DRCDual Relay ControllerCHQ-RRequires external power supply
CHQ-B, CHQ-DSCDual Sounder ControllerCHQ-BPowered by the loop
CHQ-PCMPlant Control ModuleCHQ-PCMPowered by the loop
YBO-BSBase Sounder YBO-BSPowered by the loop
CHQ-BSBase Sounder (Old type)CHQ-BSPowered by the loop
YBO-BSBBase Sounder BeaconYBO-BSBPowered by the loop
CHQ-WS2Wall SounderCHQ-WS2Powered by the loop
CHQ-WSBWall Sounder BeaconCHQ-WSBPowered by the loop
CHQ-ABAddressable BeaconCHQ-ABPowered by the loop
CHQ-ARIRemote IndicatorCHQ-ARIPowered by the loop
CHQ-POMPowered Output ModuleCHQ-POMPowered by the loop
CHQ-SOMSingle Output ModuleCHQ-SOMPowered by the loop
FB-1Fire Beam DetectorFB-1Powered by the loop
2.4.12 S81-F7007-1
Description
Control module for addressable devices using the SSP protocol. The module is
able to control up to 127 addressable modules and is mainly used for controlling
technological signals. This type of module shall not be used to connect fire detection devices.
The front panel includes 8 LEDs with the following functions:
LEDIndication
Active (Red LED)Steady on if an input is under alarmed/activated condition
Disabled (Yellow LED)Steady on if an input or an output is disabled
Fault (Yellow LED)Flashing in case of Fault condition
Loop Fault (Yellow LED)Flashing in case of loop short circuit or open loop
Log on Fault (Yellow LED) Flashing in case of difference between the detected devices and the programmed ones.
Service (Yellow LED)Flashing in case of in case of smoke detectors with dirty lenses
TX Pol. (Green LED)It lights up every time data are transmitted from the module to loop devices.
RX Pol. (Green LED)It lights up every time data from loop devices are received
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of
the single devices, according to the relevant type:
ParameterTypeMode
Operating mode SensorsLatching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
Measuring rangeSensorsSee table
Pre-alarm threshold SensorsAccording to the selected measuring range
Alarm threshold SensorsAccording to the selected measuring range
Type of indication SensorsFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm resetSensorsYes/No
Operating modeActuatorsContinuous-Normally Energized, Continuous-Normally De-energized,
TimingActuators1 to 255 seconds (only for pulsing and intermittent modes)
Enable/Disable status export to
Hosts
Enable/Disable commands from
Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Intermittent, Pulsing
The following measuring ranges, with the relevant thresholds, can be programmed for S81-ModAI020, S81-Mod-AV010 analog modules:
Measuring Range Pre-alarm Threshold Alarm Threshold
This module can control the following types of addressable devices:
Part NumberDescriptionType Pros-81 Notes
S81-Mod-DIModule with 8 non monitored inputsDIRequires external power supply
S81-Mod-AITModule with 4 monitored inputsAITRequires external power supply
S81-Mod-AI020Module with 1 x 4-20 mA inputAI020Requires external power supply
S81-Mod-AV010 Module with 1 x 0-10V inputAV010Requires external power supply
S81-Mod-DOModule with 8 open collector outputsDORequires external power supply
S81-Mod-DISP255 message display module DISPRequires external power supply
1 A maximum of 64 modules can be installed in a loop.
1
2.4.13 S81-F7009-1
Description
Control module for addressable devices using XP95/Discovery Apollo protocol.
This module can control up to a maximum of 127 fire detection modules including: smoke, heat, combined detectors, alarm buttons, control modules, visual
and audible alarm devices.
Technical Features
• Redundancy:No
• Number of devices per loop: 127
• Loop maximum current:400mA
• Supply voltage:22-29VDC
• Quiescent current: 90mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LEDIndication
Active (Red LED)Steady on if an input is under alarmed/activated condition
Disabled (Yellow LED)Steady on if an input or an output is disabled
Fault (Yellow LED)Flashing in case of Fault condition
Loop Fault (Yellow LED)Flashing in case of loop short circuit or open loop
Log on Fault (Yellow LED)Flashing in case of difference between the detected devices and the programmed ones.
Service (Yellow LED)Flashing in case of in case of smoke detectors with dirty lenses
TX Pol. (Green LED)It lights up every time data are transmitted from the module to loop devices.
RX Pol. (Green LED)It lights up every time data from loop devices are received
By using the configuration program ProS81, the following parameters can be set for each point of
the single devices, according to the relevant type:
ParameterTypeMode
Operating mode SensorsLatching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
SensitivitySensors5 sensitivity levels to be selected
Type of indication SensorsFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm resetSensorsYes/No
Operating modeActuatorsContinuous-Normally Energized, Continuous-Normally De-energized,
TimingActuators1 to 15 seconds (only for pulsing and intermittent modes)
Output typeActuatorsNormal / Sounder
Sounder toneActuators15 selectable tones
Sounder volumeActuators7 selectable volume levels
Polling LEDSensors/Actuators Enable/Disable LED lighting up during polling
Enable/Disable status export to
Hosts
Enable/Disable commands from
Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Intermittent, Pulsing
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 terminals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 4-conductor
multi-polar cable.
FunctionTermination with Flat CableTermination with Multi-conductor Cable
This module can control the following types of Apollo addressable devices:
Part NumberDescriptionType Pros-81 Notes
55000-600XP95 Optical smoke detectorX-OSDPowered by the loop
55000-500XP95 Ionization smoke detectorX-ISDPowered by the loop
55000-268 /273XP95 Reflective BeamX-RBPowered by the loop
55000-885XP95 Multi-sensor detectorX-HSMPowered by the loop
55000-400XP95 Heat detector (Standard)X-HDPowered by the loop
55000-401XP95 Heat detector (High Temperature)X-HHDPowered by the loop
55100-905XP95 Manual Call PointX-MCPPowered by the loop
XPA-CB-12034-APOXPander Optical smoke detector P-OSDPowered by the loop
XPA-CB-11170-APOXPander Heat detector (Standard)P-HDPowered by the loop
XPA-CB-11171-APOXPander Heat detector (High Temperature)P-HHDPowered by the loop
XPA-CB-13032-APOXPander Multi-sensor detector P-HSMPowered by the loop
XPA-IN-14011-APOXPander Input/Output UnitP-IOUPowered by the loop
XPA-MC-14006-APO XPander Manual Call PointP-MCPPowered by the loop
XPA-CB-14003-APOXPander Sounder/Beacon & Sounder BaseP-SBPowered by the loop
XPA-IN-14007-APOXPander Loop InterfaceP-LIPowered by the loop
55000-640XP95 I.S. Optical smoke detectorX-OSDPowered by the loop
55000-540XP95 I.S. Ionization smoke detectorX-ISDPowered by the loop
55000-440XP95 I.S. Heat detector (Standard)X-HDPowered by the loop
55100-940XP95 I.S. Manual Call PointX-MCPPowered by the loop
55000-847Standard Input/Output UnitX-IOUPowered by the loop
55000-875Standard Mains Input/Output UnitX-MIOPowered by the loop
55000-843Standard Switch Monitor X-SMPowered by the loop
55000-841Standard Switch Monitor PlusX-SMPPowered by the loop
55000-845Standard Zone MonitorX-ZMUPowered by the loop
55000-852Standard Sounder Control UnitX-SCURequires external power supply
55000-803Din Rail Input/Output UnitX-IOUPowered by the loop
55000-797Din Rail Main Input/Output UnitX-MIOPowered by the loop
55000-822Din Rail Switch Monitor X-SMPowered by the loop
55000-821Din Rail Switch Monitor PlusX-SMPPowered by the loop
55000-760Din Rail mini Switch Monitor X-MSMPowered by the loop
55000-812Din Rail Zone MonitorX-ZMUPowered by the loop
55000-182Din Rail Sounder Control UnitX-SCURequires external power supply
55000-773MARMarine Din Rail Zone MonitorX-ZMUPowered by the loop
55000-772MARMarine Din Rail Switch Monitor PlusX-SMPPowered by the loop
55000-181MARMarine Din Rail Sounder Control UnitX-SCURequires external power supply
58000-600MARDiscovery Marine Optical smoke detectorD-OSDPowered by the loop
58000-400MARDiscovery Marine Heat detectorD-HDPowered by the loop
58000-700MARDiscovery Marine Multi-sensor detectorD-HSMPowered by the loop
58100-940MARDiscovery Marine Manual Call PointD-MCPPowered by the loop
58100-975MARDiscovery Marine W.P. Manual Call PointD-MCPPowered by the loop
58000-600Discovery Optical smoke detectorD-OSDPowered by the loop
58000-500Discovery Ionization smoke detectorD-ISDPowered by the loop
58000-700Discovery Multi-sensor detectorD-HSMPowered by the loop
58000-300Discovery Carbon Monoxide detectorD-CMDPowered by the loop
58000-305Discovery Heat/Carbon Monoxide multi-sensorD-HCMPowered by the loop
58000-400Discovery Heat detectorD-HDPowered by the loop
58100-908Discovery Manual call Point RedD-MCPPowered by the loop
58100-950Discovery W.P. Manual call Point RedD-MCPPowered by the loop
45681-393Discovery Sounder/Beacon BaseD-SBBPowered by the loop
58000-005Discovery Open Area Sounder/BeaconD-ASBPowered by the loop
55000-295Intelligent Dual IR Flame detector ATEXX-FDPowered by the loop
55000-021Intelligent Triple IR Flame detector ATEXX-FDPowered by the loop
2.4.14 S81-F7010-1
Description
Control module for addressable devices using System Sensor protocol. This
module can control up to a maximum of 188 fire detection modules including:
smoke, heat, combined detectors, alarm buttons, control modules, visual and
audible alarm devices.
Technical Features
• Redundancy:No
• Operating modes:Configuration via software.
• Number of devices per loop: 99 modules & 99 sensors
• Loop maximum current:500mA
• Supply voltage:22-29VDC
• Quiescent current: 39mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LEDIndication
Active (Red LED)Steady on if an input is under alarmed/activated condition
Disabled (Yellow LED)Steady on if an input or an output is disabled
Fault (Yellow LED)Flashing in case of Fault condition
Loop Fault (Yellow LED)Flashing in case of loop short circuit or open loop
Log on Fault (Yellow LED) Flashing in case of difference between the detected devices and the programmed ones.
Service (Yellow LED)Flashing in case of in case of smoke detectors with dirty lenses
TX Pol. (Green LED)It lights up every time data are transmitted from the module to loop devices.
RX Pol. (Green LED)It lights up every time data from loop devices are received
By using the configuration program ProS81, the following parameters can be set for each point of
the single devices, according to the relevant type:
ParameterTypeMode
Operating mode SensorsLatching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
SensitivitySensors5 or 9 sensitivity levels to be selected
Polling priority for call pointsSensorsNormal, High
Unit of measure of the channel SensorsPpm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm
Zero Point Sensors-500 - 500
End of scale Sensors-500 - 500
Pre-alarm thresholdSensors-500 - 500
Alarm thresholdSensors-500 - 500
Lower trouble thresholdSensors1.0 - 3.8mA
Type of indication SensorsFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm resetSensorsYes/No
Operating modeActuatorsContinuous-Normally Energized, Continuous-Normally De-energized,
Intermittent, Pulsing
TimingActuators1 to 15 seconds (only for pulsing and intermittent modes)
Output typeActuatorsNormal / Sounder
Polling LEDSensors/Actuators Enable/Disable LED lighting up during polling
Enable/Disable status export to
Hosts
Enable/Disable commands
from Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 terminals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 4-conductor
multi-polar cable.
FunctionTermination with Flat CableTermination with Multi-conductor Cable
+Loop Output
-Loop Output
+Loop Input
-Loop Input
---
---
---
---
+∅1
-∅22
+∅33
-∅44
∅55
∅66
∅77
∅88
S81-T8003-1
White
1
Brown
Green
Yellow
S81/CCT4
Figure 2.41 Field Connections
Standard Connection Diagrams
Supported Devices
This module can control the following types of System Sensor addressable devices:
Part NumberDescription
CMA1-IModule with 1 output with isolator 1CON/FORC
M701EModule with 1 output with isolator 1CON/FORC
MMA1-IModule with 1 input with isolator1MON3
M710EModule with 1 input with isolator1MON3
M720EModule with 2 inputs with isolator2MON3
CMA11Module with 1 input & 1 output 2MON3/CON/FORC
M721EModule with 2 inputs & 1 output 3MON3/FORC
CMA22Module with 2 inputs & 2 outputs 4MON3/CON/FORC
CMX-10RMModule with 5 inputs & 5 outputs 10MON3/FORC
MCX-55MModule with 5 inputs & 5 outputs 10MON3/FORC
MMX-10MModule with 10 inputs10MON3
CMX-10RMModule with 10 relay outputs10FORC
M710ECZModule with 1 input for conventional detectors1SCON
M710ECZRModule with 1 input for conventional EExd detectors1SCON
MMTModule for 4-20mA analog interface with 1 channel1TEC2
IIG4NModule for 4-20mA analog interface with 4 channels4TEC2
M700KWOutdoor red alarm button with isolator1PULL
M700KIRed alarm button with isolator1PULL
M700KACI-FG-BBlue alarm button with isolator1PULL
M700KACI-FG-BYellow alarm button with isolator 1PULL
ABS32/PW-IAddressable sounder base with isolator1HORN
ABSB32/PW/RD-IAddressable sounder base & beacon with isolator 1HORN
AWB/RD-IAddressable beacon 1HORN
AWS32/R/RD-IElectronic sounder with beacon with isolator1HORN
AWS32/R-I Electronic sounder with isolator1HORN
NFXI-SS-WAddressable sounder base with isolator 1HORN
NFXI-BSF-WCAddressable sounder base & beacon with isolator1HORN
NFXI-WF-RRAddressable beacon1HORN
NFXI-WS-RElectronic sounder with isolator1HORN
NFXI-WSF-RRElectronic sounder & beacon with isolator1HORN
NFXI-OPTOptical smoke sensor with isolator1PHOT
NFXI-TDIFFRate of rise & fixed 58°C temperature heat detector with isolator1TH58
NFXI-TFIX5858°C heat sensor wi th isolator1TH58
NFXI-TFIX7878°C heat sensor with isolator1TH78
NFXI-SMT2Optical/rate of rise heat detector with isolator1OMNI
NFXI-SMT3Optical smoke, heat and flame IR detector with isolator1OMNI
SDX-751CTEMOptical smoke, heat, CO and flame IR detector with isolator1OMNI
7251 PINNACLELaser smoke detector1PINN
SDX-751MEOptical smoke sensor1PHOT
FDX551REMRate of rise heat detector1TH58
FDX-551HTE78°C heat sensor1TH78
FDX-751-TEMIOptical/rate of rise heat detector1OMNI
IDX751AEIntrinsically safe optical sensor1PHOT
WL-NTMRadio translator--WTR
WL-CM SERIEWireless output modules with one non monitored contact1WFORC
WL-MM SERIEWireless input modules1WMON3
WL-MCPWireless alarm button1WPULL
WL-D100Wireless optical smoke sensor 1WPHOT
WL-D200Wireless optical/rate of rise heat detector 1WTH58
WL-D350Wireless 58°C heat sensor 1WTH58
WL-SDNWireless electronic sounder 1WHORN
Communication module with Modbus RTU Master/slave protocol. It features
two outputs providing independent connections: a RS485 Half Duplex connection, and a RS232 connection. It controls the following Modbus variables:
• 512 Boolean inp ut variabl es (3 2 16-bit words)
• 512 Boolean output variables (32 16-bi t words)
• 1024 16-bit analog variables.
• Analog variables report the values of the 4-20mA analog modules, S81-F4001,
S81-F4002, S81-F4003 types.
Technical Features
• Redundancy:No
• Operating modes:Master/Slave.
• Interface:N°1 RS232 + N°1 RS485
• Supply voltage:22-29VDC
• Quiescent current: 14mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LEDIndication
ACTIVE (Red LED)Steady on if an input variable is active
DISABLED (Yellow LED)Steady on if an input or output variable is disabled
FAULT (Yellow LED)Flashing in case of communication fault. (Master mode only)
MASTER (Green LED)Steady on in Master operating mode.
TX RS232 (Green LED)It lights up every time data are transmitted on the RS232 port
RX RS232 (Green LED)It lights up every time data are received on the RS232 port
TX RS485 (Green LED)It lights up every time data are transmitted on the RS45 port.
RX RS485 (Green LED)It lights up every time data are received on the RS45 port.
Configuration
By using the ProS81 configuration program, the following parameters can be set for each virtual
channel:
ParameterTypeMode
Operating mode SensorsLatching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
Type of indication SensorsFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Operating modeActuatorContinuous-Normally Energized, Continuous-Normally De-energized,
Intermittent, Pulsing
TimingActuator1 to 15 seconds (only for pulsing and intermittent modes)
Output typeActuatorsNormal / Sounder
Enable/Disable status export to Hosts Sensors/Actuators No, TCP1, TCP2, RS232
Enable/Disable commands from
The module includes 2 x 8-way dip switches required for setting the communication parame ters.
SW1: Modbus Address Configuration
SW1 dip switch configures module Modbus address in the 1-255 range. In Slave mode, it defines
module Modbus address, whereas in master mode it defines the address of the Slave peripheral
devices to which commands are to be sent. The address 00 is not allowed.
SW1-1Modbus address Weight 1 (on = Active)
SW1-2Modbus address Weight 2 (on = Active)
SW1-3Modbus address Weight 4 (on = Active)
SW1-4Modbus address Weight 8 (on = Active)
SW1-5Modbus address Weight 16 (on = Active)
SW1-6Modbus address Weight 32 (on = Active)
SW1-7Modbus address Weight 64 (on = Active)
SW1-8Modbus address Weight 128 (on = Active)
SW2: Modbus Parameter Configuration
The 1-2-3 dips of SW2 switch configure the Baud rate according to the table below:
The 6-7-8 dips of the SW2 switch configure the following options:
SW2-6
SW2-7
SW2-8
1 Only for Master mode
On2 stop bits
Off1 stop bit
OnModule in Master mode
OffModule in Slave mode
OnFreezes the last acquired status in case of Slave disconnection
OffPuts all entities in communication fault trouble condition in case of Slave disconnection
1
Moreover, the module includes a Jumper for allowing the 120 ohm termination resistor on the
RS485 line.
OnRS485 primary line termination added
JP1
OffRS485 primary line termination removed
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
This module, used together with S81-MOD-BIL cylinder weighing modules,
allows to monitor cylinder load status and to signal even the slightest extinguishing gas leakage without delay.
Technical Features
• Redundancy:No
• Operating modes:Master/Slave.
• Interface to field devices:RS485
• Load cells on bus:32
• Supply voltage:22-29VDC
• Quiescent current: 14mA
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Hot swap capability:yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LEDIndication
ACTIVEFlashing in case of pre-alarm. On Steady in case of load cell alarm.
DISABLEDSteady on if a load cell is disabled.
FAULTFlashing in case of load cell trouble
MASTERNot used (steady light)
TX RS232Not used (off)
RX RS232Not used (off)
TX RS485It lights up every time data are transmitted on the RS45 port.
RX RS485It lights up every time data are received on the RS45 port.
Configuration
Thanks to the configuration program ProS81, the following parameters can be set for each load
cell:
ParameterTypeMode
Operating mode SensorsLatching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
Pre-alarm thresholdSensors1-3000 hg
Alarm thresholdSensors1-3000 hg
Alarm indication modeSensorsFire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Enable/Disable status export to HostsSensorsNo, TCP1, TCP2, RS232
Enable/Disable commands from Hosts
on the channel
SensorsNo, TCP1, TCP2, RS232
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
The module is connected to a S81-T8003-1 termination module with 8 terminals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT6 6-conductor
multi-polar cable.
FunctionTermination with Flat CableTermination with Multi-conductor Cable
TX DATA RS232TX
RX DATA RS232TX
GNDG
Positive RS485+
Negative RS485-
GNDG
---
---
∅1
∅22
∅33
∅44
∅55
∅66
∅77
∅88
S81-T8003-1
White
1
Brown
Green
Yellow
Gray
Pink
S81-CCT6
Figure 2.45 Field Connections
Standard Connection Diagrams
NOTE: Connect a 120 Ohm, ¼ watt resistor between L+ and L- terminals on the weighing end
module to balance the RS485 bus.
S81-MOD-BIL Weighing Module
The S81-MOD-BIL module, together with the S81-F7008-1 module, allows to monitor cylinder
load status and to signal even the slightest extinguishing gas leakage without delay. The weighing
module communicates with the control module through the RS485 bus that accepts up to 32 modules. Two thresholds, pre-alarm and alarm, can be set per weighing module when programming.
Install the weighing module to the floor with the relevant base by using the four fixing holes on the
lower section of the support. Before tightening the fixing nuts, make sure that cylinder base plate is
perfectly level. Do not install the module outdoor.
Programming the Weighing Module Address
In order to program the address of weighing modules follow the procedure below:
1.Enter the module diagnosis cycle.
2.Select the Program Device Address menu.
3.Set the desired address using the
4.Press Enter.
NOTE: During this stage, only the weighing module to which address has to be
assigned must be connected to the bus.
Weighing Module Reset
In order to reset the weighing modules, follow the procedure below:
1.Enter the module diagnosis cycle.
2.Select the Devices menu.
3.Go to the weighing module to be reset using the arrows.
4.Press Enter.
2.5 Termination modules
I/O modules may be terminated by using termination modules or by directly using a multi-conductor cable, depending on the bus type in use.
Module PNDescription
S81-F3002-1Module with 8 x 22VDC monitored inputsS81-T8001-1S81-CCT1
S81-F3002-2Module with 8 x 22VDC monitored inputsNot availableS81-CCT1R
S81-F3002-3Module with 8 x 12VDC monitored inputsS81-T8001-1S81-CCT1
S81-F4001-1Module with 1 x 4-20mA analog inputS81-T8003-1S81-CCT2
S81-F4001-2Module with 1 x 4-20mA analog inputNot availableS81-CCT2R
S81-F4002-1Module with 2 x 4-20mA analog inputsS81-T8003-1S81-CCT7
S81-F4002-2Module with 2 x 4-20mA analog inputsNot availableS81-CCT7R
S81-F4003-1Module with 8 x 4-20mA analog inputsS81-T8003-1S81-CCT3
S81-F4003-2Module with 8 x 4-20mA analog inputsNot availableS81-CCT3R1
S81-F5001-1Module with 8 x 500mA monitored outputsS81-T8006-1
S81-T8003-1
S81-F5001-2Module with 8 x 500mA monitored outputsNot availableS81-CCT3R
S81-F5002-1Module with 16 x 250mA non monitored outputs S81-T8007-1
S81-T8007-2
S81-T8001-1
S81-F5003-1Module with 8 x 250mA monitored outputs for sounders S81-T8001-1
S81-T8008-1
S81-F5004-1Module with 4 x 2A monitored outputs for solenoidsNot availableS81-CCT4
S81-F5004-2Module with 4 x 2A monitored outputs for solenoidsNot availableS81-CCT4R
S81-F6001-1Module for fire extinguishing systems Not availableNot available
S81-F6002-1Logic moduleNot availableNot available
S81-F7002-1Loop control module with ESP protocolS81-T8003-1S81-CCT4
S81-F7006-1Modbus RTU Master/Slave moduleS81-T8003-1S81-CCT6
S81-F7007-1Loop control module with SSP protocolS81-T8003-1S81-CCT4
S81-F7008-1Control modules for weighing modulesS81-T8003-1S81-CCT6
S81-F7009-1Loop control module with XP95/Discovery protocolS81-T8003-1S81-CCT4
S81-F7010-1Loop control module with System Sensor protocol S81-T8003-1S81-CCT4
2
S81-CCT3
S81-CCT1
S81-T8007-1
S81-T8007-2
S81-CCT1
S81-T8008-1
1
1 Combined with the S81-T8005-1 termin ation module
2 Combined with the S81-T8001-1 termin ation module
2.5.1 S81-T8001-1
Description
16-terminal termination module. It is used with S81-E2001-1 type buses
to terminate the following modules: S81-F3002-1, S81-F5002-1, S81F5003-1
∅1+An. In 1+An. In 1+An. In 1+ Output 1+ Loop OutTX RS232
∅2N.C.N.C.+An. In 2+ Output 2- Loop OutRX RS232
∅3N.C.+An. In 2+An. In 3+ Output 3+ Loop InGND RS232
∅4N.C.N.C.+An. In 4+ Output 4- Loop In+ RS485
∅5+An. Out 1+An. Out 1+An. In 5+ Output 5N.C.- RS485
∅6N.C.N.C.+An. In 6+ Output 6N.C.GND RS485
∅7N.C.+An. Out 2+An. In 7+ Output 7N.C.N.C.
∅8N.C.N.C.+An. In 8+ Output 8N.C.N.C.
S81-F4001-1S81-F4002-1 S81-F4003-1 S81-F5001-1
Description
8-terminal termination module. It is used with S81-E2001-1 type buses
to terminate the following modules: S81-F4001-1, S81-F4002-1,
S81-F4003-1, S81-F5001-1, S81-F7002-1, S81-F7006-1, S81-F7007-1,
S81-F7008-1, S81-F7009-1, S81-F7010-1.
20-terminal termination module. It is used as an adapter with
S81-E2001-2 type buses to connect the S81-F5002-1 modules to the
S81-T8007-1 termination modules by means of a S81-CCT-1 cable.
Technical Features
• Number of terminals: 20
• Assembly:on DIN bar
• Dimensions:W 68 x H 77 x D 50 mm
Interconnection Between S81-CCT1 Cable and S81-T8007-1 Module
TerminalS81-CCT-1 WireRelayNotes
1Not used
2Not used
3WhiteK1Connect to the white wire of cable S81-CCT1
4BrownK2Connect to the brown wire of cable S81-CCT1
5GreenK3Connect to the green wire of cable S81- CCT1
6YellowK4Connect to the yellow wire of cable S81-CCT1
7GrayK5Connect to the gray wire of cable S81-CCT1
8PinkK6Connect to the pink wire of cable S81-CCT1
9BlueK7Connect to the blue wire of cable S81-CCT1
10RedK8Connect to the red wire of cable S81-CCT1
11BlackK9Connect to the black wire of cable S81-CCT1
12VioletK10Connect to the violet wire of cable S81-CCT1
13Gray/PinkK11Connect to the gray/pink wire of cable S81-CCT1
14Red/BlueK12Connect to the red/blue wire of cable S81-CCT1
15White/GreenK13Connect to the white/green wire of cable S81-CCT1
16Brown/GreenK14Connect to the brown/green wire of cable S81-CCT1
17White/YellowK15Connect to the white/yellow wire of cable S81-CCT1
18Yellow/BrownK16Connect to the yellow/brown wire of cable S81-CCT1
19Connect to +25V with a 200mA fuse
20Not used
The S81-T8007-2 module can be connected directly to the S81-E2001-2 bus with cable S81-CCT1
without the need for the S81-T8005-1 interconnection module.
This module transforms the remote Host serial
output signal from RS232 to current loop with
galvanic insulation. The module is passive and
therefore needs an actively operating converter
on the other end. With this module it is possible
to connect a remote Host computer to a maximum
distance of 2,000 meters.
Technical Features
• Supply voltage:22-29VDC
• Quiescent current: 30mA
• Current loop maximum distance: 2,000 meters at 9,600 bps
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Dimensions:W 57 x H 77 x D 50 mm
Status Indications
The module includes 5 x SMD LEDs with the following functions:
LEDIndication
PowerSteady on when supply voltage is detected
RX-232On when data are received on the RS232 port
TX-232On when data are transmitted on the RS232 port
RX-CLOn when data are received on the current loop
TX-CLOn when data are transmitted on the current loop
Internal Connections
J1: RS232
Connection of RS232 serial line. Connect to the J5 connector of module S81-E2003-1 using the
S81-C232/2 cable.
BR1: Power Supply
These 3 terminals connect supply voltage (+25VDC) and earth.
TagFunctionCable Color
∅M125VDC power supply positiveRed
∅M225VDC power supply negativeBlack
∅M3EarthYellow/Green
Field Connections
BR2: Current loop
These 4 terminals connect
TagFunctionCable Color
∅M1RX data input positiveWhite
∅M2RX data input negativeBrown
∅M3TX data output positiveGreen
∅M4TX data output negativeYellow
This module controls 10 digital inputs, 16 open collector outputs and a local sounder 250mA monitored output for Fire alarm functions. Moreover, the
module checks the primary power supply voltage
for any ground fault (earth leakage). It can be combined with module S81-T8001-1 to get 16 x 250mA
open collector outputs, or with modules S81T8007-1 and S81-T8007-2 to get 16 x SPDT contacts.
Technical Features
• Supply voltage:22-29VDC
• Quiescent current: 100mA
• Max. current of open collector outputs 250mA, non protected
• Max. current of local sounder output250mA, protected electronically
• Operating temperature:-5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% (RH) non-condensing
• Dimensions:W 135 x H 77 x D 50 mm
Status Indications
The module includes 2 green LEDs with the following functions:
LEDIndication
Power (Green LED) Steady on when supply voltage is detected
Link (Green LED)Steady on when the link for communication with module S81-U1006-1 is present
Configuration
The module includes a 1-way dip-switch used to enable the ground fault check on the supply voltage.
SW1Description
OnSupply voltage ground fault (earth leakage) check enabled
OffSupply voltage ground fault (earth leakage) check disabled
WARNING: EARTH GROUND
THE SUPPLY VOLTAGE OF THE H-S81-HS CONTROL PANEL IS NOT REFERENCED TO
EARTH. IN SOME DEVICES, SUCH AS PERSONAL COMPUTERS, THE POWER SUPPLY
NEGATIVE IS EARTHED FOR SAFETY REASONS. WHEN THESE DEVICES ARE CONNECTED
TO THE CONTROL PANEL, A GROUND FAULT (EARTH LEAKAGE) TROUBLE IS SIGNALED. TO
PREVENT THIS, MOVE THE SW1 DIP-SWITCH TO THE OFF POSITION.
These three Faston connectors are used to connect supply voltage and earth.
TAGFunctionCable Color
TB125VDC power supply positiveRed
TB225VDC power supply negative Black
TB3Earth Yellow/Green
J1 to J1 on S81-E2003-1
It is a connector for 14-pole flat cable, allowing connection to the S81-E2003-1 Bus module. Connect using S81-CFT14/2 cable.
J2 to J1 on S81-T8001-1, J1 on S81-T8007-1 or J1 on S81- T8007-2
It is a connector for 20-pole flat cable, allowing connection to the S81-T8001-1 termination module
or to the 16-relay modules S81-T8007-1 and S81-T8007-2. Connect using S81-CFT20/05 cable.
∅M11K11Currently not used
∅M12K12Running SystemNormally energized
∅M13K13System faultNormally energized
∅M14K14Power supply fault Normally energized
∅M15K15CPU faultNormally energized
∅M16K16Control panel resetPulsing on reset
System
Normally energized
Field Connections
BR1 Terminal Block
It is a 12-way terminal block to connect the ten default inputs and the local fire alarm sounder.
BR1FunctionTypeNotes
∅M1Remote buzzer silencing inputSafetyN.O.
∅M2Remote sounder silencing inputSafetyN.O.
∅M3Remote control panel reset inputSafetyN.O.
∅M4Remote evacuation control inputSafetyN.O.
∅M5Battery status input (supply/charge)System0V during charge
∅M6PSU1 primary power supply trouble input SystemN.C.
∅M7PSU2 secondary power supply trouble inputSystemN.C.
∅M8Battery charge status (Full charge/Trickle)System0V full charge
∅M9External Fault InputSafetyN.C
∅M10Revolving door tamper inputSecurityN.C
∅M11Local sounder/buzzer output +Safetymax. 250mA
∅M12Local sounder/buzzer output -Safetymax. 250mA
CAUTION:EN-54-2 COMPLIANCE
THE REMOTE EVACUATION CONTROL AND REMOTE CONTROL PANEL RESET INPUTS
MUST NOT BE ACTUATED DIRECTLY THROUGH EXTERNAL MANUAL BUTTONS SINCE THEY
ARE NOT MONITORED. THIS GUARANTEES COMPLIANCE WITH STANDARD EN-54-2.
THE OUTPUTS ABOVE ARE NOT C-, E- OR J-TYPE OUTPUTS (EN 54-1), THEREFORE THEY
MUST NOT BE USED TO CONTROL FIRE ALARM DEVICES OR ALARM, FIRE ALARM OR
FAULT ALARM TRANSMISSION DEVICES. THIS GUARANTEES COMPLIANCE WITH
STANDARD EN-54-2.
2.5.7 S81-T8007-1
Description
It is used with S81-E2001-1
and S81-F5002-1 type
buses. It features 16 x 4A
30VDC SPDT output contacts to be used for the connection of SELV circuits
only. It is also used together
with the S81-T8004-1 module.
Technical Features
• Supply voltage:22-29VDC
• Quiescent current: 0 mA
• Contact type: SPDT
• Contact capacity:4 A 30VDC
• Assembly: on DIN bar
• Operating temperature: -5 - 50 °C
• Storage temperature:-30 - 80 °C
• Maximum humidity:95% non-condensing
• Dimensions: W 170 x H 77 x D 50 mm
Status Indications
The module includes 16 green LEDs for relay status indication:
LEDCondition
LED1 - LED16 (Green LEDs) It lights up when relay coil is active