Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com
PN 52289:B1 6/5/07 ECN 06-612
HPTV2416UL
Power Supply
Product Installation Document
The Honeywell Power Products HPTV2416UL Power supply provides 16 individually fused 24VAC outputs with a total of 8 amperes.
2 Specifications
UL/ULC Listed Power Supply
Sixteen individually fused 24 VAC outputs
AC Power and 16 Individual Output Indicator LEDs
LED Indicator Lights: – Input Power LED (Green) – ON indicates incoming input voltage – Output Power LEDs (Red) – ON indicates blown output fuse
•Fuses – Incoming Safety Fuse Blocks (2) 3.15A, 250V – Load Output Fuses (16), 1A, 250V – Secondary Fuse, 4A, 250V
AC cord and spare fuses included
Power ON/OFF switch
Dimensions: 9.25 in. x 8.25 in. x 3.5 in. (23.3 cm x 21 cm x 9 cm)
NOTE:
A readily accessible switched circuit breaker must be available to disconnect mains power as required.Do not expose to rain or moisture.Replace fuses with fuses of same type and rating.Refer servicing to qualified personnel.
3 Installation Instructions
1. Pre-drill holes where HPTV2416UL enclosure is to be mounted.
If the included AC cord is used, mount the enclosure in a secure location where the unit cannot be accidentally unplugged.
2. Secure HPTV2416UL enclosure to the desired location (indoor installation only) as shown in Figure 1.
3. Disconnect power to the branch circuit to which the HPTV2416UL will be connected.
4. Place both SW1 switches to the OFF position.
5. Connect incoming AC (120 VAC, 60Hz) into the incoming Fuse block input observing polarities (see Figure 2). Connect ground leads as shown in diagram.
NOTE: All 120V wiring should be routed so that it cannot touch 24V wiring to be installed later.
6. Connect CCTV cameras (or other external loads) to appropriate terminals (example output 1 = 1P, 1N). Route all 24V wiring at least
7. Power the branch circuit and place SW1 to the ON position. The green LED should illuminate indicating 24V is reaching the PCB.
3
/8 in. (0.953 cm) from 120V mains wiring (indoor installations only).
Continued on next page...
8. The red LEDs illuminate only if a camera (load) is installed and the fuse is open. Remove a camera out put fuse to verify LED operation.
9. Secure the cabinet cover with metal screws to prevent access by unauthorized personnel.
Wall
HPTV2408UL-mount.wmf
Mounting
Screws
(4)
(typ.)
Cabinet
Figure 1
HPTV2408UL.wmf
For additional information:
Visit our website: http://www.honeywellpower.com
Contact Technical Support: (877) HPP_POWR
Email us: hpp_techserv@honeywell.com
2 HPTV2416UL Installation Instructions — P/N 52289:B1 6/5/07
Figure 2
Loading...