While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the National Fire Protection Association
Standard 72 (NFPA 72), manufacturer's recommendations,
State and local codes, and the recommendations contained in
the Guides for Proper Use of System Smoke Detectors, which
are made available at no charge to all installing dealers.
These documents can be found at http://www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a firstfloor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Limit-C1-2-2007
2HPFF12 NAC Expander — P/N 53576:B 11/24/2010
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®,
UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a
trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of
the Microsoft Corporation.
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
4HPFF12 NAC Expander — P/N 53576:B 11/24/2010
Table of Contents
Table of Contents
Section 1: System Overview................................................................................................................... 9
1.5: LED Indicators ..................................................................................................................................................... 13
3.2: Programmable Features ........................................................................................................................................36
4.1: Supervised Functions and Field Wiring................................................................................................................39
5.1: Controlling Four NAC Circuits from a Single Source .........................................................................................42
5.2: Controlling and Silencing Four NACs.................................................................................................................. 43
5.3: Split Alarm and Selective Silence ........................................................................................................................44
5.4: Connecting Multiple Units ...................................................................................................................................46
Section 6: Power Supply Requirements.............................................................................................. 48
6.2: Calculating the AC Branch Circuit Current..........................................................................................................48
6.3: Calculating the System Current Draw ..................................................................................................................49
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standards
• NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 464 Audible Signaling Appliances
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
HPFF12 NAC Expander — P/N 53576:B 11/24/20107
8HPFF12 NAC Expander — P/N 53576:B 11/24/2010
Section 1: System Overview
The Honeywell Power Products FireForce (HPFF) is one of the most innovative fire alarm remote
power supplies available that complies with UL 864 9th Edition. Designed with advanced switchmode power supply technology and built with the latest surface-mount electronic manufacturing
techniques, they incorporate several new features that demanding installers requested to speed them
through installation and servicing.
The HPFF12 is a 12.0 A power supply that provides power for Notification Appliance Circuit
(NAC) expansion to support ADA requirements and strobe synchronization (sync). It provides
filtered 24 VDC power to drive four NAC outputs. The four-output circuits may be configured as:
four Class B (Style Y); two Class A (Style Z); two Class B and one Class A; or four Class A with
the optional HPP31076 Class A adapter installed. The input circuits, which control the power
supply operation, are triggered by the reverse polarity of a NAC or by the reverse polarity of a 12
VDC or 24 VDC power source. The power supply is compatible with 12 VDC or 24 VDC control
panels. It contains an internal battery charger capable of charging up to 26.0 AH (amp hour)
batteries.
The HPFF12 is a wall cabinet unit that can accommodate up to two 18 AH batteries. It can be
configured to internally house one addressable control or relay module, a six-circuit relay module,
or a six-circuit control module. (Modules available through authorized Honeywell Fire Systems
distributors.)
HPFF12CM is a chassis-mount model that can fit two 12.0 AH batteries. It is used for a multi-pack
option that allows up to three HPFF12CM units to be mounted in a compatible Fire Alarm Control
Panel (FACP) cabinet; these separately sold cabinets are also referred to as the large equipment
enclosure. The addressable control or relay module option is not available on these models.
(Equipment enclosures available through authorized Honeywell Fire Systems distributors.)
HPFF12, and HPFF12CM power supply models operate at 120 VAC/60 Hz.
HPFF12E, and HPFF12CME power supply models are export units that operate at 240 VAC/50 Hz.
NOTE: When an HPFF12CM unit is mounted in a FACP cabinet, the top row must be left open
for proper heat dissipation.
1.1 General
The HPFF power supplies are used as remotely mounted power supplies and battery chargers. The
Fire Alarm Control Panel (FACP) or initiating device is connected to the input circuit(s). When the
control input circuit activates due to the reverse polarity of the signal from the initiating device, the
power supply will activate its NAC outputs.
During the inactive or non-alarm state, the power supply supervises its NAC field wiring
independently for short and open conditions. If a NAC fault is detected, the power supply will open
the initiating device input signal to notify the FACP and the Normally-Closed Trouble contact. If an
AC loss is detected, the power supply will open the initiating device input signal, Normally-Closed
Trouble, and a dedicated AC Fail contact.
If an alarm condition occurs and the NAC outputs are activated, the supervision and charger are
disabled and the NAC circuit is no longer supervised (except for excessive loading or shorts).
Supervision of other power supply faults such as battery voltage, AC loss, and ground fault will
continue and may be monitored via Trouble contacts.
HPFF12 NAC Expander — P/N 53576:B 11/24/20109
System OverviewFeatures
1.2 Features
•The enclosures offered are self-contained lockable cabinets.
– If the local Authority Having Jurisdiction (AHJ) requires the fire protection system to have
matching locks, the units’ locks may be swapped in the field to accommodate Honeywell
Fire Systems branded panels: Honeywell, Notifier, Gamewell FCI, Silent Knight, and FireLite Alarms.
•24 VDC remote power supply.
•Outputs are completely power-limited.
•Four output circuits:
– Fully filtered power.
– Four 24 VDC Class B (Style Y), or two Class A (Style Z), or two Class B (Style Y) and one
Class A (Style Z) NACs (special application).
– Four 24 VDC Class A (Style Z) NACs (special application) with optional HPP31076 Class
A adaptor.
•Status LED indicators on control PCB:
– Power On LED
– Auxiliary Trouble LED
– Battery Trouble LED
– Ground Fault LED
– Individual NAC Trouble LEDs
•Maximum current for any one output circuit: 3.0 A.
•Maximum total continuous current available: 12.0 A for HPFF12, HPFF12E, HPFF12CM, and
HPFF12CME.
•NAC overload protection and indication:
– Shorted or excessively loaded NAC outputs automatically protect themselves.
– Status LEDs will illuminate steady to indicate the circuit affected.
•Integral supervised battery charger:
– Capable of charging 7.0 AH to 26.0 AH batteries.
– For lead-acid batteries only.
– Battery Trouble LED blinks to indicate charger fault.
•Fully supervised power supply, battery, and NACs.
•Two independent optically-isolated input/control circuits, compatible with 12 VDC and 24
VDC control panel NACs.
•Selectable strobe synchronization for NACs compatible with System Sensor, Cooper
Wheelock, Faraday, Amseco, and Gentex notification appliances.
•Selectable pass-through or filtered input.
– Pass-through input of steady, coded audible, and synchronized strobe signals to NAC
outputs.
– Filtered for full-wave-rectified polarity-reversing inputs or reducing spurious noise to
generate steady-on NAC outputs.
•Silenceable with two independent alarm inputs or by passed-through synchronization protocol.
•Split Alarm mode allows a combination of coded signals outputs and Selectable Silence on
NAC pairs.
•Selectable silence with two independent alarm inputs and the HPFF programmed in Split
Alarm mode.
•End-of-line resistor compare:
– Attach a single reference resistor to match value of the NAC end-of-line resistor (ELR).
10HPFF12 NAC Expander — P/N 53576:B 11/24/2010
Start-up ProcedureSystem Overview
!
– Provides use of a wide range of ELR resistors’ values: 1.9K ohms to 25K ohms.
– Eases retrofit installations by matching existing ELR value without having to locate in the
field. (ELRs must be UL Listed.)
•NAC Trouble memory:
– Individual NAC Trouble LEDs blink if past troubles occurred.
– Aids installer or repair personnel to find the location of past troubles.
•Fixed, clamp-style terminal blocks to accommodate 12 AWG (3.31 mm²) to 22 AWG (0.326
mm²) wire.
•Separate Trouble and AC Fail Form-C relay contacts.
•Initiating device input signal is interrupted for Trouble indication at device or FACP.
•Optional two-hour delay:
– In opening of Trouble contacts upon AC loss (AC Fail contact always transfers immediately
upon AC loss).
– In interruption of initiating device input signal for Trouble indication at device or FACP.
– UL 864 9th Edition requires 1-3 hour delay, therefore always programming for the two-hour
delay is recommended.
•Auxiliary output:
– Continuous 24 VDC output (even in alarm): 2.0 A.
– Resettable fuse (PTC) limited.
•Mounting locations on the Control circuit board for optional addressable relay and control
modules.
1.3 Start-up Procedure
1.Configure the power supply jumpers as described in Section 1.4, “Jumpers”, on page 12.
2.Install the power supply as described in Section 2, “Installation”, on page 17.
3.Program the power supply as described in Section 3, “Programming Options”, on page 35.
4.Wire the power supply circuits, referring to the options described in Section 4, “Trouble
Supervision”, on page 39 and the application examples in Section 5, “Applications”, on page
42.
5.Connect the primary source wiring while observing the following:
• HPFF12 and HPFF12CM: make certain the primary source is 120 VAC, 60 Hz, 5.0 A.
• HPFF12E and HPFF12CME: make certain the primary source is 240 VAC, 50 Hz, 2.80 A.
• Run a pair of wires (with earth ground conductor) from the protected premises’ main
breaker box to TB1 on the internal 24 VDC power supply circuit board.
• For power supplies: use 14 AWG (2.089 mm²) wire with 600 V insulation.
• Connect ground of the protected premise to ground stud of the enclosure using a dedicated
nut/lockwasher supplied in the hardware kit.
WARNING:
MAKE CERTAIN THAT THE AC CIRCUIT BREAKER IS OFF BEFORE MAKING ANY WIRING
CONNECTIONS BETWEEN THE CIRCUIT BREAKER AND THE POWER SUPPLY.
6.Apply power to the power supply using the following procedure:
– Apply AC power by turning on the AC mains circuit breaker connected to the power supply.
– Connect a properly charged battery to the TB1 on the unit’s internal Control circuit board.
HPFF12 NAC Expander — P/N 53576:B 11/24/201011
System OverviewJumpers
!
1.4 Jumpers
The HPFF power supplies are comprised internally of two basic components: a 24 VDC power
supply and a Control circuit board. The HPFF12 models have an installed 12.0 A power supply.
Jumpers are located on the control circuit board; see Figure 1.1, “Control Circuit Board”.
1.4.1 Charger Disable Jumper (J1)
The HPFF power supplies’ battery charger capacity is 26 AH maximum
using the integral charger with a maximum charging rate of 0.75 A. The
integral charger on the Control circuit board must be disabled in certain
situations by removing the charger-disable jumper. One situation is when
system requires a common battery set, as is possible in the large
equipment enclosure. Another situation is if the system requires a larger
battery capacity than the integral charger can charge in the proper time.
Larger capacity batteries can be used if they are housed in an external
UL-Listed enclosure, along with a UL-Listed battery charger that can
restore the full charge to the batteries in the proper time.
CAUTION:
THE BATTERY CHARGER IS AUTOMATICALLY DISABLED DURING ALARM, SO BATTERIES
WILL NOT BE CHARGED WHEN THE POWER SUPPLY IS IN THE ALARM STAGE.
Larger capacity batteries can be used if they are housed in an external UL-Listed enclosure, along
with a UL-Listed battery charger suitable for fire alarm service and with sufficient capacity to
restore the full charge in the required time. The alternate enclosure and battery charger shall be
listed for Fire Protective Signaling use.
1.4.2 Ground Fault Disable Jumper (J2)
The Ground Fault detection circuit on the Control
circuit board monitors the impedance from earth
ground to any user wiring point, including +24 VDC.
An exception is the initiating device signal inputs
because they are optically-isolated from the rest of the
circuitry and should be detected by the initiating
device or FACP. Remove ground-fault disable jumper
to disable the ground fault detection.
If the common circuitry of two or more HPFFs are connected together, or if the common of an
HPFF is connected to the common of a system, such as a single battery connected to multiple units,
then the ground fault jumpers must be removed from all but one of the units. The unit with the
jumper installed provides the ground monitoring for the whole system. If two or more units are
connected together with ground fault monitoring enabled, then the monitoring circuits interfere
with each other, and false ground faults will be generated.
12HPFF12 NAC Expander — P/N 53576:B 11/24/2010
LED IndicatorsSystem Overview
1.5 LED Indicators
IndicatorNameStateTrouble Condition
BlinkingNAC Trouble Memory
LED 1, 2, 3, 4SIG(1, 2, 3, 4) TRBL
Steady illuminationOpen or shorted NAC
LED 5GF TRBLSteady illuminationAn earth ground fault is present
BlinkingCharger Fault
LED 6BAT TRBL
Steady illuminationLow or missing battery
LED 7AUX TRBLSteady illuminationExcessive loading or shorted auxiliary
LED 8POWER ON
NOTE: If all four SIG TRBL LEDs are illuminated steady, check if the reference ELR resistor is
missing or doesn’t match the ELR resistors used to terminate the Class B circuits. Otherwise,
each NAC must have a trouble.
1.6 Specifications
Refer to Section 1.1, “Control Circuit Board”, on page 15 for terminal locations.
Primary AC Power — TB1 (on 24 VDC power-supply circuit board)
•HPFF12 and HPFF12CM: 120 VAC, 60 Hz, 5.0 A.
•HPFF12E and HPFF12CME: 240 VAC, 50 Hz, 2.80 A.
•Wire size: 14AWG (2.08 mm²) with 600 V insulation.
Initiating Device Signal Inputs — TB3 (on Control circuit board); terminals SIGNAL1: +IN,
–IN, +OUT, –OUT, and SIGNAL2: +IN, –IN, +OUT, –OUT.
output
BlinkingLow (brown-out) or missing AC input
Steady illuminationNormal/Standby
Table 1.1
•Supervised by FACP or initiating device, power-limited.
•A supervisory relay must be used if initiating device is a power source.
•Available for one of the following:
– 4-wire inputs; or
– 2-wire inputs and an ELR; or
– facilitate multiple unit systems.
•Trigger input voltage: 12 and 24 VDC.
•Input trigger draw in alarm polarity:
– 12 VDC, 5.68 mA maximum per input.
– 24 VDC, 12.26 mA maximum per input.
•12 AWG (3.31 mm²) to 18 AWG (0.821 mm²).
HPFF12 NAC Expander — P/N 53576:B 11/24/201013
System OverviewSpecifications
End-of-line Resistor Reference – TB3 (on Control circuit board); terminals REF+ and REF–.
•Used for the ELR compare feature.
•Range: 1.9K ohms to 25K ohms.
•12 AWG (3.31 mm²) to 22 AWG (0.326 mm²).
NAC Output Circuits — TB4 (on Control circuit board); terminals 1L1(+), 1L2(–), 2L1(+),
2L2(–), 3L1(+), 3L2(–), 4L1(+), and 4L2(–) — alarm polarity in parentheses. (See below for
other TB4 terminals.)
•Supervised, special application, and power-limited.
•Voltage rating: 24 VDC filtered.
•Current:
– Maximum for any one circuit: 3.0 A.
– Maximum total continuous for all outputs: HPFF12, HPFF12CM, HPFF12E, HPFF12CME:
12.0 A
•Output circuit types:
– four Class B (Style Y); or
– two Class A (Style Z);
– two Class B (Style Y) and one Class A (Style Z) NACs; or
– four Class A (Style Z) NACs with optional HPP31076 Class A adaptor.
•12 AWG (3.31 mm²) to 18 AWG (0.75 mm²).
•Refer to Appendix A, “Device Compatibility”, on page 53 for listed compatible devices.
Trouble Contact Rating — TB2 (on Control circuit board); terminals TROUBLE: N/C,
COM, and N/O.
•Not supervised.
•Fail-safe Form-C relay.
•Normally energized, transfers with NAC, battery, charger (in standby), AC loss, ground fault,
and auxiliary output trouble.
•2.0 A @ 30 VDC.
•AC loss trouble can be delayed for 2 hours (see “Programming Options”).
•12 AWG (3.31 mm²) to 18 AWG (0.75 mm²).
AC Fail Contact Rating — TB2 (on Control circuit board); terminals AC FAIL: N/C, COM,
N/O. (See above for other TB4 terminals.)
•Not supervised.
•Fail-safe Form-C relay.
•Normally energized, always transfers with AC loss.
•2.0 A @ 30 VDC.
•12 AWG (3.31 mm²) to 18 AWG (0.75 mm²).
Battery Charging Circuit — TB1 (on Control circuit board); terminals +BATT and –BATT.
•Supervised, non-power-limited.
•Supports lead-acid type batteries only.
•Float charge voltage: 26.6 VDC.
•Charger disabled if battery voltage falls below 15 VDC.
•Maximum charge current: 0.75 A.
•Battery fuse (F1): 15 A, 32 V.
•Maximum battery capacity: 26.0 AH.
•Minimum battery capacity: 7.0 AH.
•Power supply draws a maximum standby current of 75 mA from batteries.
Auxiliary Output — TB4 (on Control circuit board); terminals +A and –A. (See above for
other TB4 terminals.)
•Voltage checked for excessive loading, power limited (PTC), special application.
•Voltage rating: 24 VDC continuous (even in alarm).
•Current: 2.0 A maximum. (Subtract auxiliary load from total to determine available NAC load.)
•12 AWG (3.31 mm²) to 18 AWG (0.75 mm²).
•For a list compatible optional modules that can be connected to the Auxiliary output, see
Appendix A, “Device Compatibility”.
g
HPFF12 NAC Expander — P/N 53576:B 11/24/201015
g
Figure 1.1 Control Circuit Board
System OverviewSpecifications
HPFF12pca.wmf
Figure 1.2 HPFF12 24 VDC Power Supply Circuit Board
16HPFF12 NAC Expander — P/N 53576:B 11/24/2010
Section 2: Installation
!
The standard cabinet may be either semi-flush or surface mounted. Fire Alarm Control Panel
(FACP) cabinets can only be wall mounted. Each cabinet mounts using two or three key slots and
two 0.250" (6.35 mm) diameter holes in the backbox. The key slots are located at the top of the
backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet
approximately 5 feet (1.5 m) above the floor with hinge mounting on the left. Determine the
number of conductors required for the devices to be installed. Sufficient knockouts are provided for
wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All
wiring should be in accordance with the National and/or Local codes for fire alarm systems and
power supplies.
2.1 Backbox Mounting
CAUTION:THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS.
ALWAYS GROUND YOURSELF WITH A STATIC STRAP BEFORE HANDLING ANY BOARDS
SO THAT THE STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC
SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with the
24 VDC power supply and the Control circuit board can be easily removed. Loosen the two #8-32
nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs.
Place the chassis assembly in a safe location until it can be reinstalled in the backbox.
1.Mark and predrill a hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.2, “Standard Cabinet: Dimensions for Wall-mounting”
on page 19 or Figure 2.3, “FACP Cabinet-Mounting Details: Backbox-Mounting Holes
and Chassis-Mounting Studs (EQBB-D4 shown)” on page 20.
NOTE: See EQ Series Install Sheet PN 53412 for door-mounting details and
measurements for B-size and C-size backboxes.
2.Install the center top fastener in the wall with screw head protruding.
3.Place backbox over the top screw, level and secure.
4.Mark and drill the left and right upper and lower mounting holes.
5.Note: outer holes (closest to sidewall) are used for 16" O.C. stud mounting.
6.Install remaining fasteners.
HPFF12 NAC Expander — P/N 53576:B 11/24/201017
InstallationBackbox Mounting
92udlscab.wmf
Figure 2.1 Standard Cabinet: Dimensions
18HPFF12 NAC Expander — P/N 53576:B 11/24/2010
Backbox MountingInstallation
Semi-Flush Mounting
Do not recess box more
than 3.875” into wall to
avoid covering venting
holes on top of box.
92udlsencl.wmf
Figure 2.2 Standard Cabinet: Dimensions for Wall-mounting
HPFF12 NAC Expander — P/N 53576:B 11/24/201019
InstallationBackbox Mounting
HPFF8LargeEqpt.wmf
Chassis-
mounting
studs
(2 per row of
backbox)
Keyholes
2 places
Mounting holes
2 places
45-7/8"
(116.52)
37-1/32"
(94.06)
45-3/4"
(116.21)
24-1/8" (61.28)
16" (40.64)
(10.16)
4"
24" (60.96)
1-5/8"
(4.13)
2-1/4"
(5.72)
2-1/4"
(5.72)
5/16" dia.
(0.79)
5/16" dia.
(0.79)
19-1/2" (49.53)
5-5/32"
(13.1)
2-1/16"
(5.24)
2-5/8"
(6.604)
Top knockout:
Inner 1.375" (3.49)
Outer 1.750" (4.45)
Four lower knockouts
Inner 0.875" (2.22)
Outer 1.125" (2.86)
11-1/2"
)
(29.21
1-7/8”
(4.699)
2"
)
(5.08
1”
)
(2.54
11"
)
(27.94
11"
)
(27.94
eqcab-d.wmf
Four rows of
Equipment
cab4keyhole.wmf
Top View of Backbox
6857ko.wmf
Keyhole dimensions
Height of
mounting bolt
after installation
NOTE: See EQ Series Install Sheet PN 53412 for door-mounting details and measurements
for B and C size backboxes.
Figure 2.3 FACP Cabinet-Mounting Details: Backbox-Mounting Holes and Chassis-
Mounting Studs (EQBB-D4 shown)
20HPFF12 NAC Expander — P/N 53576:B 11/24/2010
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.