Honeywell HPFF12, HPFF12E, HPFF12CME, HPFF12CM Instruction Manual

Power Products
HPFF12(E)/HPFF12CM(E)
Notification Appliance Circuit Expander
Instruction Manual
Document 53576 Rev: B3 10/1/2018 ECN: 18-476
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifica­tion capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication methods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http:// www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or sm
oke
flow.
Smoke particles may become “cold,” stratify, and not reach t
he
c
eiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air out­lets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reachi
ng
t
he detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a devel­oping fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limita­tions. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate­of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signal­ing, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes, speak­ers and displays may not alert people if these devices are located
on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert peo­ple with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligibility requirements as defined by NFPA, local codes, and Authoritie
s
Havi
ng Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meani
ng
of
the signal. Audible devices, such as horns and bells, can hav
e
di
fferent tonal patterns and frequencies. It is the property
owner's responsibility to conduct fire drills and other traini
ng
ex
ercises to make people aware of fire alarm signals an
d
i
nstruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can ca
use
t
emporary or permanent hearing loss
.
A
life safety system will not operate without any electrical power. If
AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backu
p radio transmission systems are recommended.
The most common cause of life safety system malfunction is inad­equate maintenance. To keep the entire life safety system in excel­lent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Envi­ronments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Mainte­nance should be scheduled as required by National and/or local fire codes and should be performed by authorized professional life safety system installers only. Adequate written records of all inspec­tions should be kept.
Limit-D2-2016
2 HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con­nected to the fire alarm control panel. Disconnect all sources of
power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be
tested in accordance with NFPA 72 after any programming opera­tion or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system compo­nents, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadver­tently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/ 32-120º F and at a relative humidity . However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from light­ning transients and interference, proper grounding will reduce sus­ceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Con­sult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tighten­ing may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any cir­cuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interfer­ence to radio communications. It has been tested and found to comply with the limits for class A computing devices pur­suant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart­ment of Communications.
Le present appareil numerique n'emet pas de bruits radio­electriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate®, FlashScan®, Honeywell®. NOTIFIER®, ONYX®, ONYXWorks®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
HPFF12 NAC Expander — P/N 53576:B3 10/1/2018 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
Product name and version number (if applicable)
Printed manual or online Help
Topic Title (for online Help)
Page number (for printed manual)
Brief description of content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 HPFF12 NAC Expander — P/N 53576:B3 10/1/2018

Table of Contents

Section 1: System Overview............................................................................................................................................. 7
1.1: General...............................................................................................................................................................................................................7
1.2: Features..............................................................................................................................................................................................................7
1.3: Start-up Procedure .............................................................................................................................................................................................8
1.4: Jumpers ..............................................................................................................................................................................................................8
1.4.1: Charger Disable Jumper (J1) ..................................................................................................................................................................9
1.4.2: Ground Fault Disable Jumper (J2)..........................................................................................................................................................9
1.5: LED Indicators .................................................................................................................................................................................................. 9
1.6: Specifications ....................................................................................................................................................................................................9
Section 2: Installation ..................................................................................................................................................... 13
2.1: Backbox Mounting ..........................................................................................................................................................................................13
2.2: Chassis-Mounting in FACP Cabinets ..............................................................................................................................................................16
2.3: NAC Circuit Wiring ........................................................................................................................................................................................20
2.3.1: Four NACs Configured for Class B (Style Y)......................................................................................................................................20
2.3.2: Two NACs Configured for Class A (Style Z) ......................................................................................................................................21
2.3.3: Mixing Class B and Class A NACs ......................................................................................................................................................22
2.3.4: HPP31076 Optional Class A (Style Z) Adapter ...................................................................................................................................23
2.4: Mounting Addressable Modules......................................................................................................................................................................23
2.4.1: Mounting Modules from Honeywell Fire Systems ..............................................................................................................................24
2.4.2: Mounting Six-Circuit Modules from Honeywell Fire Systems............................................................................................................25
2.5: Power-Limited Wiring Requirements..............................................................................................................................................................25
2.5.1: Power-Limited Wiring, Standard Chassis ............................................................................................................................................26
2.5.2: Power-Limited Wiring, FACP Cabinet ................................................................................................................................................27
Section 3: Programming Options .................................................................................................................................. 29
3.1: DIP Switch Settings .........................................................................................................................................................................................29
3.2: Programmable Features ...................................................................................................................................................................................30
3.2.1: Input/Output Functions.........................................................................................................................................................................30
3.2.2: Synchronization Type ...........................................................................................................................................................................30
3.2.3: Trouble Reporting Delay with an AC Failure ......................................................................................................................................30
3.2.4: Split Alarm and Silencing ....................................................................................................................................................................31
Section 4: Trouble Supervision...................................................................................................................................... 32
4.1: Supervised Functions and Field Wiring...........................................................................................................................................................32
4.2: Trouble Reporting............................................................................................................................................................................................32
4.2.1: Normal/Standby ...................................................................................................................................................................................32
4.2.2: Alarm ...................................................................................................................................................................................................33
4.2.3: TB2: AC FAIL Contacts.......................................................................................................................................................................33
4.2.4: TB2: TROUBLE Contacts....................................................................................................................................................................33
4.2.5: TB3: Initiating Device Inputs SIGNAL 1 and SIGNAL 2 ...................................................................................................................33
4.2.6: Trouble Memory...................................................................................................................................................................................33
4.2.7: Ground Fault Detection ........................................................................................................................................................................34
4.2.8: NAC Overload Protection and Indication.............................................................................................................................................34
Section 5: Applications................................................................................................................................................... 35
5.1: Controlling Four NAC Circuits from a Single Source ....................................................................................................................................35
5.2: Controlling and Silencing Four NACs ............................................................................................................................................................36
5.3: Split Alarm and Selective Silence....................................................................................................................................................................37
5.3.1: Selective Silence ...................................................................................................................................................................................37
5.3.2: Split Alarm Mode .................................................................................................................................................................................38
5.4: Connecting Multiple Units ..............................................................................................................................................................................39
Section 6: Power Supply Requirements........................................................................................................................ 42
6.1: Overview..........................................................................................................................................................................................................42
6.2: Calculating the AC Branch Circuit Current.....................................................................................................................................................42
6.3: Calculating the System Current Draw .............................................................................................................................................................42
6.3.1: Overview...............................................................................................................................................................................................42
6.3.2: How to Calculate System Current Draw ..............................................................................................................................................43
6.4: Calculating the Battery Size ............................................................................................................................................................................44
6.4.1: NFPA Battery Requirements ................................................................................................................................................................44
6.4.2: Selecting and Locating Batteries ..........................................................................................................................................................44
6.5: NAC Circuit Loop Wiring Requirements........................................................................................................................................................44
HPFF12 NAC Expander — P/N 53576:B3 10/1/2018 5
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the stan-
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Sys­tems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such oper­ation requires the approval of the local Authority Having Jurisdiction (AHJ).
dards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code
Underwriters La
UL 464 Audible Signaling Appliances UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
HPP Documents:
HPP Device Compatibility HPFF8(E)/HPFF8CM(E) NAC Expander HPP31076 Optional Class A (Style Z) Adapter
boratories Documents:
cument #54399
Do Document #53499 Document #53728
6 HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
The Honeywell Power Products FireForce (HPFF) is one of the most innovative fire alarm remote power supplies available that com­plies with UL 864 9th Edition. Designed with advanced switch-mode power supply technology and built with the latest surface-mount electronic manufacturing techniques, they incorporate several new features that demanding installers requested to speed them through installation and servicing.
The HPFF12 is a 12.0 A power supply that provides power for Notification Appliance Circuit (NAC) expansion to support ADA require­ments and strobe synchronization (sync). It provides filtered 24 VDC power to drive four NAC outputs. The four-output circuits may be configured as: four Class B (Style Y); two Class A (Style Z); two Class B and one Class A; or four Class A with the optional HPP31076 Class A adapter installed. The input circuits, which control the power supply operation, are triggered by the reverse polarity of a NAC or by the reverse polarity of a 12 VDC or 24 VDC power source. The power supply is compatible with 12 VDC or 24 VDC control panels. It contains an internal battery charger capable of charging up to 26.0 AH (amp hour) batteries.
The HPFF12 is a wall cabinet unit that can accommodate up to two 18 AH batteries. It can be configured to internally house one address­able control or relay module, a six-circuit relay module, or a six-circuit control module. (Modules available through authorized Honey-
well Fire Systems distributors.)
HPFF12CM is a chassis-mount model that can fit two 12.0 AH batteries. It is used for a multi-pack option that allows up to three HPFF12CM units to be mounted in a compatible Fire Alarm Control Panel (FACP) cabinet; these separately sold cabinets are also referred to as the large equipment enclosure. The addressable control or relay module option is not available on these models. (Equip-
ment enclosures available through authorized Honeywell Fire Systems distributors.)
HPFF12 and HPFF12CM power supply models operate at 120 VAC/60 Hz.
HPFF12E and HPFF12CME power supply models are export units that operate at 240 VAC/50 Hz.
NOTE: When an HPFF12CM unit is mounted in a FACP cabinet, the top row must be left open for proper heat dissipation.

1.1 General

The HPFF power supplies are used as remotely mounted power supplies and battery chargers. The Fire Alarm Control Panel (FACP) or initiating device is connected to the input circuit(s). When the control input circuit activates due to the reverse polarity of the signal from the initiating device, the power supply will activate its NAC outputs.
During the inactive or non-alarm state, the power supply supervises its NAC field wiring independently for short and open conditions. If a NAC fault is detected, the power supply will open the initiating device input signal to notify the FACP and the Normally-Closed Trou­ble contact. If an AC loss is detected, the power supply will open the initiating device input signal, Normally-Closed Trouble, and a ded­icated AC Fail contact.
If an alarm condition occurs and the NAC outputs are activated, the supervision and charger are disabled and the NAC circuit is no lon­ger supervised (except for excessive loading or shorts). Supervision of other power supply faults such as battery voltage, AC loss, and ground fault will continue and may be monitored via Trouble contacts.

Section 1: System Overview

1.2 Features

The enclosures offered are self-contained lockable cabinets – If the local Authority Having Jurisdiction (AHJ) requires the fire protection system to have matching locks, the units’ locks may
be swapped in the field to accommodate Honeywell Fire Systems branded panels: Honeywell, Notifier, Gamewell-FCI, Silent Knight, Farenhyt, and Fire-Lite Alarms
24 VDC remote power supply
Outputs are completely power-limited
Four output circuits: – Fully filtered power – Four 24 VDC Class B (Style Y), or two Class A (Style Z), or two Class B (Style Y) and one Class A (Style Z) NACs (special
application)
– Four 24 VDC Class A (Style Z) NACs (special application) with optional HPP31076 Class A adapter
Status LED indicators on control PCB – Power On LED – Auxiliary Trouble LED – Battery Trouble LED – Ground Fault LED – Individual NAC Trouble LEDs
Maximum current for any one output circuit: 3.0 A
Maximum total continuous current available: 12.0 A for HPFF12, HPFF12E, HPFF12CM, and HPFF12CME
NAC overload protection and indication: – Shorted or excessively loaded NAC outputs automatically protect themselves – Status LEDs will illuminate steady to indicate the circuit affected
Integral supervised battery charger: – Capable of charging 7.0 AH to 26.0 AH batteries – For lead-acid batteries only – Battery Trouble LED blinks to indicate charger fault
Fully supervised power supply, battery, and NACs
HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
System Overview Start-up Procedure
!
Two independent optically-isolated input/control circuits, compatible with 12 VDC and 24 VDC control panel NACs
Selectable strobe synchronization for NACs compatible with System Sensor, Cooper Wheelock, Faraday, Amseco, and Gentex notification appliances
Selectable pass-through or filtered input – Pass-through input of steady, coded audible, and synchronized strobe signals to NAC outputs – Filtered for full-wave-rectified polarity-reversing inputs or reducing spurious noise to generate steady-on NAC outputs
Silenceable with two independent alarm inputs or by passed-through synchronization protocol
Split Alarm mode allows a combination of coded signals outputs and Selectable Silence on NAC pairs
Selectable silence with two independent alarm inputs and the HPFF programmed in Split Alarm mode
End-of-line resistor compare: – Attach a single reference resistor to match value of the NAC end-of-line resistor (ELR) – Provides use of a wide range of ELR resistors’ values: 1.9K ohms to 25K ohms – Eases retrofit installations by matching existing ELR value without having to locate in the field. (ELRs must be UL Listed.)
NAC Trouble memory: – Individual NAC Trouble LEDs blink if past troubles occurred – Aids installer or repair personnel to find the location of past troubles
Fixed, clamp-style terminal blocks to accommodate 12 AWG (3.31 mm²) to 22 AWG (0.326 mm²) wire
Separate Trouble and AC Fail Form-C relay contacts
Initiating device input signal is interrupted for Trouble indication at device or FACP
Optional two-hour delay: – In opening of Trouble contacts upon AC loss (AC Fail contact always transfers immediately upon AC loss) – In interruption of initiating device input signal for Trouble indication at device or FACP – UL 864 9th Edition requires 1-3 hour delay, therefore always programming for the two-hour delay is recommended
Auxiliary output: – Continuous 24 VDC output (even in alarm): 2.0 A – Resettable fuse (PTC) limited
Mounting locations on the Control circuit board for optional addressable relay and control modules

1.3 Start-up Procedure

1. Configure the power supply jumpers as described in Section 1.4, “Jumpers”, on page 8.
2. Install the power supply as described in Section 2, “Installation”, on page 13.
3. Program the power supply as described in Section 3, “Programming Options”, on page 29.
4. Wire the power supply circuits, referring to the options described in Section 4, “Trouble Supervision”, on page 32 and the application examples in Section 5, “Applications”, on page 35.
5. Connect the primary source wiring while observing the following:
• HPFF12 and HPFF12CM: make certain the primary source is 120 VAC, 60 Hz, 5.0 A.
• HPFF12E and HPFF12CME: make certain the primary source is 240 VAC, 50 Hz, 2.80 A.
• Run a pair of wires (with earth ground conductor) from the protected premises’ main breaker box to TB1 on the internal 24 VDC
power supply circuit board.
• For power supplies: use 14 AWG (2.089 mm²) wire with 600 V insulation.
• Connect ground of the protected premise to ground stud of the enclosure using a dedicated nut/lockwasher supplied in the
hardware kit.
WARNING: DISCONNECT POWER
MAKE CERTAIN THAT THE AC CIRCUIT BREAKER IS OFF BEFORE MAKING ANY WIRING CONNECTIONS BETWEEN THE CIRCUIT BREAKER AND THE POWER SUPPLY.
6. Apply power to the power supply using the following procedure: – Apply AC power by turning on the AC mains circuit breaker connected to the power supply. – Connect a properly charged battery to the TB1 on the unit’s internal Control circuit board.

1.4 Jumpers

The HPFF power supplies are comprised internally of two basic components: a 24 VDC power supply and a Control circuit board. The HPFF12 models have an installed 12.0 A power supply. Jumpers are located on the control circuit board; see Figure 1.1, “Control Circuit Board”.
8 HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
LED Indicators System Overview
TB2
LEDs
N/O
N/C
COMM
N/O
N/C
COMM
AC FAIL
TROUBLE
J1
!
J2
1L2 2L1 2L2
3L1 3L2
4L1 4L2

1.4.1 Charger Disable Jumper (J1)

The HPFF power supplies’ battery charger capacity is 26 AH maximum using the integral charger with a maximum charging rate of 0.75 A. The integral charger on the Control circuit board must be disabled in certain situations by removing the charger-disable jumper. One situation is when system requires a common battery set, as is possible in the large equipment enclosure. Another situation is if the system requires a larger battery capacity than the inte­gral charger can charge in the proper time. Larger capacity batteries can be used if they are housed in an external UL-Listed enclosure, along with a UL-Listed battery charger that can restore the full charge to the batteries in the proper time.
CAUTION: BATTERY CHARGER DISABLE
THE BATTERY CHARGER IS AUTOMATICALLY DISABLED DURING ALARM, SO BATTERIES WILL NOT BE CHARGED WHEN THE POWER SUPPLY IS IN THE ALARM STAGE.
Larger capacity batteries can be used if they are housed in an external UL-Listed enclosure, along with a UL-Listed battery charger suit­able for fire alarm service and with sufficient capacity to restore the full charge in the required time. The alternate enclosure and battery charger shall be listed for Fire Protective Signaling use.

1.4.2 Ground Fault Disable Jumper (J2)

The Ground Fault detection circuit on the Control circuit board monitors the impedance from earth ground to any user wiring point, including +24 VDC. An exception is the initiating device signal inputs because they are optically-isolated from the rest of the circuitry and should be detected by the initiating device or FACP. Remove ground-fault disable jumper to disable the ground fault detection.
If the common circuitry of two or more HPFFs are connected together, or if the com­mon of an HPFF is connected to the common of a system, such as a single battery con­nected to multiple units, then the ground fault jumpers must be removed from all but
one of the units. The unit with the jumper installed provides the ground monitoring for the whole system. If two or more units are connected together with ground fault monitoring enabled, then the monitoring circuits inter­fere with each other, and false ground faults will be generated.

1.5 LED Indicators

Indicator Name State Trouble Condition
LED 1, 2, 3, 4 SIG(1, 2, 3, 4) TRBL
LED 5 GF TRBL Steady illumination An earth ground fault is present
LED 6 BAT TRBL
LED 7 AUX TRBL Steady illumination Excessive loading or shorted auxiliary output
LED 8 POWER ON
NOTE: If all four SIG TRBL LEDs are illuminated steady, check if the reference ELR resistor is missing or doesn’t match the ELR resistors used to terminate the Class B circuits. Otherwise, each NAC must have a trouble.

1.6 Specifications

Refer to Section 1.1, “Control Circuit Board”, on page 11 for terminal locations.
Primary AC Power — TB1 (on 24 VDC power-supply circuit board)
HPFF12 and HPFF12CM: 120 VAC, 60 Hz, 5.0 A
HPFF12E and HPFF12CME: 240 VAC, 50 Hz, 2.80 A
Wire size: 14AWG (2.08 mm²) with 600 V insulation
Initiating Device Signal Inputs — TB3 (on Control circuit board); terminals SIGNAL1: +IN, –IN, +OUT, –OUT, and SIGNAL2: +IN, –IN, +OUT, –OUT
Supervised by FACP or initiating device, power-limited
A supervisory relay must be used if initiating device is a power source.
Blinking NAC Trouble Memory
Steady illumination Open or shorted NAC
Blinking Charger Fault
Steady illumination Low or missing battery
Blinking Low (brown-out) or missing AC input
Steady illumination Normal/Standby
Table 1.1 LED Indicators
HPFF12 NAC Expander — P/N 53576:B3 10/1/2018 9
System Overview Specifications
Available for one of the following:
– 4-wire inputs; or – 2-wire inputs and an ELR; or – facilitate multiple unit systems
Trigger input voltage: 12 and 24 VDC
Input trigger draw in alarm polarity:
– 12 VDC, 5.68 mA maximum per input – 24 VDC, 12.26 mA maximum per input
12 AWG (3.31 mm²) to 18 AWG (0.821 mm²)
End-of-line Resistor Reference – TB3 (on Control circuit board); terminals REF+ and REF–
Used for the ELR compare feature
Range: 1.9K ohms to 25K ohms
12 AWG (3.31 mm²) to 22 AWG (0.326 mm²)
NAC Output Circuits — TB4 (on Control circuit board); terminals 1L1(+), 1L2(–), 2L1(+), 2L2(–), 3L1(+), 3L2(–), 4L1(+), and 4L2(–) — alarm polarity in parentheses (See below for other TB4 terminals.)
Supervised, special application, and power-limited
Voltage rating: 24 VDC filtered.
Current:
– Maximum for any one circuit: 3.0 A – Maximum total continuous for all outputs: HPFF12, HPFF12CM, HPFF12E, HPFF12CME: 12.0 A
Output circuit types:
– four Class B (Style Y); or – two Class A (Style Z); – two Class B (Style Y) and one Class A (Style Z) NACs; or – four Class A (Style Z) NACs with optional HPP31076 Class A adapter
12 AWG (3.31 mm²) to 18 AWG (0.75 mm²)
Refer to the HPP Device Compatibility Document #54399. for listed compatible devices.
Trouble Contact Rating — TB2 (on Control circuit board); terminals TROUBLE: N/C, COM, and N/O
Not supervised
Fail-safe Form-C relay
Normally energized, transfers with NAC, battery, charger (in standby), AC loss, ground fault, and auxiliary output trouble
2.0 A @ 30 VDC
AC loss trouble can be delayed for 2 hours (see “Programming Options”)
12 AWG (3.31 mm²) to 18 AWG (0.75 mm²)
AC Fail Contact Rating — TB2 (on Control circuit board); terminals AC FAIL: N/C, COM, N/O (See above for other TB4 termi­nals.)
Not supervised
Fail-safe Form-C relay
Normally energized, always transfers with AC loss
2.0 A @ 30 VDC
12 AWG (3.31 mm²) to 18 AWG (0.75 mm²)
Battery Charging Circuit — TB1 (on Control circuit board); terminals +BATT and –BATT
Supervised, non-power-limited
Supports lead-acid type batteries only
Float charge voltage: 26.6 VDC
Charger disabled if battery voltage falls below 15 VDC
Maximum charge current: 0.75 A
Battery fuse (F1): 15 A, 32 V
Maximum battery capacity: 26.0 AH
Minimum battery capacity: 7.0 AH
Power supply draws a maximum standby current of 75 mA from batteries Auxiliary Output — TB4 (on Control circuit board); terminals +A and –A (See above for other TB4 terminals.)
Voltage checked for excessive loading, power limited (PTC), special application
Voltage rating: 24 VDC continuous (even in alarm)
Current: 2.0 A maximum. (Subtract auxiliary load from total to determine available NAC load.)
12 AWG (3.31 mm²) to 18 AWG (0.75 mm²)
For a list compatible optional modules that can be connected to the Auxiliary output, see the HPP Device Compatibility Document
#54399.
10 HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
Specifications System Overview
TB3
TB4
TB1
TB2
SW2
LEDs
REF+ REF– + IN – IN + OUT – IN + OUT+ OUT + IN – OUT
SIGNAL 1
SIGNAL 2
BATT+ BATT–
A+
N/O
N/C
COMM
N/O
N/C
COMM
AC FAIL
TROUBLE
J1
J2
1L1 1L2 2L1 2L2
3L1 3L2
4L1 4L2A–
REF+
REF–
Signal 1 +IN
Signal 1 –IN
Signal 1 +OUT
Signal 1 –OUT
Signal 2 +IN
Signal 2 –IN
Signal 2 +OUT
Signal 2 –OUT
LEDs:
LED1 (Power On)
LED2 (Auxiliary Trouble)
LED3 (Battery Trouble)
LED4 (Ground Fault Trouble)
LED5 (Signal 4 Trouble) LED6 (Signal 3 Trouble) LED7 (Signal 2 Trouble) LED8 (Signal 1 Trouble)
TB2: AC Fail & Trouble Relays
Trouble N/C
Trouble COMM
Trouble N/O
AC Fail N/C
AC Fail COMM
AC Fail N/O
T
B
1
:
B
a
t
t
e
r
y
+
-
J1: Charger Disable
J2: Ground Fault
Disable
HPFF812PCA2.wmf
S
W
1
(
l
e
f
t
t
o
r
i
g
h
t
)
:
S
I
G
S
E
L
A
C
2
H
R
S
Y
N
S
E
L
B
S
Y
N
S
E
L
A
S
I
G
3
/
4
B
S
I
G
3
/
4
A
S
I
G
1
/
2
B
S
I
G
1
/
2
A
TB3: ELR Reference/ IDC Inputs
Alarm Polarity
Shown
A+ A- 1L1 1L2 2L1 2L2 3L1 3L2 4L1 4L2
TB4: Auxiliary/NAC Outputs
Figure 1.1 Control Circuit Board
SW2: Reset
FF12pca.wmf
Figure 1.2 HPFF12 24 VDC Power Supply Circuit Board
HPFF12 NAC Expander — P/N 53576:B3 10/1/2018 11
Notes
12 HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
The standard cabinet may be either semi-flush or surface mounted. Fire Alarm Control Panel (FACP) cabinets can only be wall mounted.
!
ff8cab.wmf
Figure 2.1 Standard Cabinet: Dimensions
Door = 19.26” (48.92cm) Backbox = 19.0” (48.26cm)
Door = 16.821” (42.73cm) Backbox = 16.65” (42.29cm)
Depth = 5.207” (13.23cm)
Depth =
5.257”
(13.353cm)
Top
Bottom
Left Side Right Side
Each cabinet mounts using two or three key slots and two 0.250" (6.35 mm) diameter holes in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme tem­peratures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems and power supplies.

2.1 Backbox Mounting

CAUTION: STATIC SENSITIVE COMPONENTS
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A STATIC STRAP BEFORE HANDLING ANY BOARDS SO THAT THE STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with the 24 VDC power supply and the Control circuit board can be easily removed. Loosen the two #8-32 nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a safe location until it can be reinstalled in the backbox.
1. Mark and pre-drill a hole in the wall for the center top keyhole mounting bolt using the dimensions illustrated in Figure 2.2 or
Figure 2.3.
NOTE: See the EQ Series Install Sheet PN 53412 for door-mounting details and measurements for B-size and C-size backboxes.
2. Install the center top fastener in the wall with screw head protruding.
3. Place backbox over the top screw, level and secure.
4. Mark and drill the left and right upper and lower mounting holes.
Note: outer holes (closest to sidewall) are used for 16" O.C. stud mounting.
5. Install remaining fasteners.

Section 2: Installation

HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
Installation Backbox Mounting
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
92udlsencl.wmf
Figure 2.2 Standard Cabinet: Dimensions for Wall-mounting
14 HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
Backbox Mounting Installation
(13.097cm)
5.156”
5.93”
(15.062cm)
5.93”
(15.062cm)
7.12”
(18.084cm)
(6.197cm)
2.44”
0.875” (2.223cm)
1.125” (2.858cm)
45-3/4"
(116.21)
24.125” (61.28cm)
24.0” (60.96cm)
1.625”
(4.13cm)
2.06”
(5.24cm)
11. 5”
(29.21cm)
5.16”
(13.1cm)
(10.16cm)
4”
4”
(5.08cm)
1”
(2.54cm)
11”
(27.94cm)
11”
(27.94cm)
2.625”
(6.604cm)
0.875 (2.22cm)
1.125 (2.86cm)
0.875 (2.22cm)
1.125 (2.86cm)
1.875”
(4.7cm)
37.03”
(94.06cm)
0.31”
(0.79cm)
0.31”
(0.79cm)
45.875”
(116.52cm)
2.25”
(5.72cm)
2.25”
(5.72cm)
19.5”
(49.53cm)
16.0” (40.64cm)
1.125”
(2.858 cm)
0.50”
(1.27 cm)
0.50”
(1.27 cm)
0.250” (0.635 cm)
HPFF8LargeEqpt.wmf
Chassis-
mounting
studs
(2 per row of
backbox)
Keyholes
2 places
Mounting holes
2 places
e
q
c
a
b
-
d
2
.
w
m
f
Four rows of
Equipment
c
a
b
t
o
p
.
w
m
f
Top View of Backbox
c
a
b
4
k
e
y
h
o
l
e
.
w
m
f
Keyhole dimensions
Height of
mounting bolt
after installation
NOTE: See CAB-4 Series Install Sheet PN 15330 and EQ Series Install Sheet PN 53412 for door-mounting details and
measurements for A, B, and C size backboxes. This drawing shows EQBB-D4 knockout locations.
Top knockout: Inner: Outer:
Four Lower knockouts: Inner: Outer:
Knockouts: Inner:
Outer:
Figure 2.3 FACP Cabinet-Mounting Details: Backbox-Mounting Holes and Chassis-Mounting Studs (EQBB-D4
shown)
HPFF12 NAC Expander — P/N 53576:B3 10/1/2018 15
Loading...
+ 33 hidden pages