Honeywell Power Products
12 Clintonville Road
Northford, CT 06472-1653
A
Honeywell
Power Products
HPF602ULADA
HPF602ULADA
6 Amp NAC Expander
US
INSTALLATION & OPERATION MANUAL
Document 151341
10/14/10 Rev:
P/N 151341:L1 ECN: 10-0642
L1
Installation Precautions
FCC Warning
Maintenance
Adherence to these statements will aid in problem-free installation and enhance long-term
reliability.
Unit should be inspected at least once per year for proper operation as follows:
WARNING
book prior to starting the installation.
Follow the instructions
Disconnect AC power and batteries
Remove all electronic assemblies
Verify that wire sizes are adequate
Install this equipment in the proper environment.
Tighten screw terminals adequately
Like all solid state electronic devices,
Though designed to last many years,
W
This device may not cause radio interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
in all installation, operating, and programming manuals. These instructions must be followed to avoid
proper installation by qualified personnel.
prior to servicing. Failure to do so can damage circuits. Fuses are one time use devices and
he
same type and rating (see markings on the boards). Replace any fuse covers before energizing.
prior to any drilling, filing, reaming, or p unc hing of the enc lo sure . W hen po ss ible, ma ke a ll cable
entries from the sides or rear. Before making a ny mo d ifications , verify that they will not interfere with battery, transformer, and
printed circuit board location.
DC output, AC input). Use 18 AWG to 14 AWG for power limited circuits (AC Fail/Low Battery signal). Assure proper output voltage
by measurem ent before connecting devices. This helps avoid potential damage. Keep power limited wiring separate from nonpower limited wiring (120VAC / 60Hz Input, Battery Wires). Minimum .25” spacing must be provided. Use 75 C or higher rated UL
insulated wire for connecting the unit to the electrical mains.
may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all
peripherals be installed in an environment with a nominal room temperature of 0-49° C/32-120° F. To reduce the risk of fire or
electric shock, do not expose to rain or excessive moisture. Do not block any ventilation openings. Upon completion of wiring,
secure enclosure door with screws (supplied) or a key lock. Installation hardware and method must be adequate to support the
weight of the unit and foreseeable mechanical loadings. Clean only with a dry cloth.
. Over-tightening may damage threads, resulting in reduced terminal contact pressure and
difficulty with screw terminal removal. Use only accessories and replacement parts specified by the manufacturer.
this system may operate erratically or can be damaged when subjected to lightning-induced
suppressive d evices will re duc e susceptibility. Consu lt the Technical Services Departmen t shou ld pro blems be anticipated or
encountered.
system components can fail at any time. This system contains static-sensitive components.
static-suppressive packaging to protect electronic assemblies removed from the unit.
Under normal load conditions, the DC output voltage should be checked for proper voltage level.
Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals
5 years, however it is recommended to change batteries within 4 years or less as necessary.
Honeywell is not responsible for any typographical errors.
to contain voltage drop
Output Voltage Test:
Battery Test:
: This unit should be installed by qualified service personnel and in accordance with The National Electrical
Code, as well as NFPA 72 and all applicable Local Regulations. It is recommended to first review this complete instruction
damage to the product and minimize hazard. Keep them in a safe place for periodic review. Operation and reliability depend upon
must be replaced when they blow. For continued protection against risk of electric shock and fire hazard replace all fuses with t
in all circuits. Use 18 AWG or larger for all power connections (Battery,
transients. Although no system is completely immune from lightning transients and interferences, proper grounding and use of surge
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use
ARNING: This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1)
and at the board terminals marked [+ BAT-- ] to insure that there is no break in the battery connection wires. Expected battery life is
The useful life of the system's standby batteries and the electronic components
The HPF602ULADA is a notification appliance circuit and auxiliary power expander that
provides up to 6 amps of filtered, 24 volt power for powering notification appliances and
auxiliary devices. The HPF602ULADA provides its own AC power connection, battery
charging circuit, and battery connections. Used with security and fire alarm control panels, the
HPF602ULADA enables you to connect and distribute power to many more devices than your
panel may normally allow.
•Input Configurations
The HPF602ULADA has two optically isolated signaling inputs that provide the signal
connection from the main control panel to the HPF602ULADA (see Section 3.2 for more
details).
•Output Configurations
The HPF602ULADA has four power-limited notification appliance circuits that can be
configured in various combinations of Class A and Class B circuits (see Section 3.3 for
details).
•Auxiliary Power Configurations
The HPF602ULADA has a dedicated, power-limited, auxiliary output that can be
configured in two different ways. The auxiliary output can either be non-resettable
(always on), or configured to switch off during the AC power failure to conserve the
battery standby power . When the auxiliary power is configured to switch off, there is a 30
second delay before the auxiliary power is turned off after the AC power fails (see Section
4.8.4 for details).
•Form C Trouble Relay
The HPF602ULADA includes a general trouble relay that will de-energize for any trouble
situation. (see Section 4.4.1 for details).
•Earth Fault Detection
The HPF602ULADA monitors for earth faults to the system power or system ground.
When detected, the system de-energizes the trouble relay and the input supervision relays
(see Section 5.2 for details).
•ANSI Temporal Code
The HPF602ULADA provides two configuration options that will drive outputs with the
ANSI temporal code if the inputs are on constantly (see Section 4.8.1 for details).
•Supports Synchronized appliances
The HPF602ULADA provides configuration options that will eliminate the need for
synchronized modules when using AMSECO, Faraday, Gentex, System Sensor, or
Wheelock synchronization appliances.
1513411
HPF602ULADA Distributed Power Module Installation Manual
Section 2
UL Requirements
When installed in accordance with NFPA 70 and NFPA 72 standards, the HPF602ULADA
can be connected to UL Listed devices.
The HPF602ULADA is also listed to meet UL Standard 864 and power limiting requirements.
The HPF602ULADA is compatible with any UL listed control unit utilizing reverse polarity
supervised notification appliance circuits, using 24 VDC regulated outputs.
2.1ULC Requirements
Install in accordance with CE 22.1 and ULC S524. For the installation to comply with ULC,
the Silent Knight 5612 module must be installed between the battery and control as describe
in Section 4.8.
2151341
System Overview
Section 3
System Overview
CAUTION
Each output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will cause it to shut down
(power limit). The circuit will automatically reset once you remove the overload condition.
3.1Terminal Descriptions and Electrical Ratings
Terminal #DescriptionRatings
TB1
1AC (black–“hot”)
120 VAC 60 Hz, A2Earth Ground
3AC (white–“neutral”)
TB2
1Auxiliary Power (-)
2Auxiliary Power (+)
3Notification 4 Output (-)
4Notification 4 Output (+)Although each output
5Notification 3 Output (-)
6Notification 3 Output (+)total current draw from
7Notification 2 Output (-)
8Notification 2 Output (+)auxiliary power must
HPF602ULADA Distributed Power Module Installation Manual
3.2Signal Input Terminals
Terminals 14 through 19 are polarized signal input terminals. They provide the signaling
connection from the main panel to the HPF602ULADA. See Figure 4-2 for more details.
The main panel supervises its notification appliance circuits used for communicating with the
HPF602ULADA the same way it supervises ordinary notification appliance circuits. The
signal inputs on the HPF602ULADA monitor the polarity of the voltage coming from the
main panel’s notification appliance circuits to determine when to operate the notification
appliance circuits on the HPF602ULADA. The HPF602ULADA emulates the trouble
behavior of a normal notification appliance circuit by interrupting the EOL supervision
current for internal or output trouble conditions on the HPF602ULADA.
Note that the HPF602ULADA will accurately sense the polarity of the main panel’s
notification appliance circuits to drive the outputs whether or not the supervision connection
is intact. The following situations will disconnect the EOL supervision at the signal inputs and
indicate a trouble condition:
•Low AC power
•Low Battery condition
•Earth ground fault to the system power or system ground
•Auxiliary output power-limited condition
•EOL supervision trouble or power-limited condition at an output
Trouble conditions will not necessarily occur for both inputs when the trouble is specific to a
particular output. Only the signal input controlling the output circuit that is in trouble will
indicate a trouble condition. Below are examples where both inputs do NOT indicate trouble
for a trouble occurring at only one output circuit.
Example 1:If input 1 controls all four outputs, a fault on any output will cause input 1
to indicate trouble. The fault does not affect input 2.
Example 2:If input 1 controls outputs 1 and 2, and input 2 controls outputs 3 and 4, a
fault condition on output 3 or 4 will cause input 2 to indicate trouble. The
fault does not affect input 1.
Note:Once the inputs are driven with forward polarity to activate the outputs, the main control panel will not be
able to sense trouble conditions through its notification appliance circuit connected to the HPF602ULADA
input circuits. Use the HPF602ULADA trouble relay when it is necessary to monitor trouble conditions
and active alarm conditions at the same time.
Section 6 explains the significance of each trouble condition in more detail.
4151341
System Overview
3.3Notification Appliance Circuit Terminals
T erminals 3 through 10 are the notification appliance circuit output terminals. Each of the four
circuits are rated at 3 amps, although you can only draw a total of 6 amps from the
HPF602ULADA. The HPF602ULADA outputs are short-circuit protected (power limited)
according to UL 864 standards. Overcurrent indicators are yellow LEDs. The output voltage
can vary depending on the load and input voltage.
The four power-limited NAC outputs can be configured as follows:
•Four Class B circuits•Faraday synchronized outputs
•Two Class A circuits•Gentex synchronized outputs
•One Class A and two Class B circuits•System Sensor synchronized outputs
One or both HPF602ULADA signal inputs control the NAC outputs, depending on the
specific configuration setup. Possible configurations for the HPF602ULADA are:
For Option:These Inputs:Control These Outputs:As:
1Input 1All outputsClass B circuits
2
3
4
5Input 1Outputs 1-2 and 3-4Class A circuit pairs
6
7
8
9
10
11
12
13
Input 1 or
Input 2coded circuits
Input 1Outputs 1 and 2Class B circuits
Input 2Outputs 3 and 4Class B circuits
Input 1Output 1Class B circuits
Input 2Outputs 2, 3, and 4Class B circuits
You can select which input controls which output, and which inputs are Class A and Class B
using the 7-position DIP switch on the printed circuit board. Section 4.8 for DIP switch
settings.
1513415
HPF602ULADA Distributed Power Module Installation Manual
Section 4
Installation
Before installing the HPF602ULADA, the AC input must first be wired into the building’s
main electrical power through the TB1 terminals (see Figure 4-2). Shut off the electrical
power to the HPF602ULADA, and then complete the general installation of the
HPF602ULADA using the information in this section.
4.1Mounting
Mount the HPF602ULADA in locations that meet the following temperature and humidity
requirements. Do not expose the panel to conditions outside these ranges. For use in indoor,
dry environments.
Temperature
Humidity
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting
on concrete, especially when moisture is expected, first attach a piece of 3/4-inch plywood to
the concrete surface. Attach the HPF602ULADA to the plywood.
o
C-49o C (32o F-120o F)
0
10%-93% at 30o C (86o F) noncondensing
4.1.1Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the
conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause
water problems. Installers should take reasonable precautions to prevent water from entering
the cabinet. Water damage is not covered under warranty.
6151341
Installation
Note: The use of
this knock out will
reduce the number
and/or size of
batteries this cabinet can
contain. Evaluation of space is
important before using.
4.2Wire Routing
To avoid induced noise (transfer of electrical energy from one wire to another), keep input
wiring isolated from high current output and power-limited wiring. Induced noise can
interfere with telephone communication or even cause false alarms. Avoid pulling a single
multiconductor cable for the entire system. Instead, separate high current input/output from
low current. Separate power-limited from non-power-limited wiring. Non-power-limited
wiring must be enclosed in conduit.
Wiring within the cabinet should be routed around the perimeter of the cabinet. It should not
cross the printed circuit board where it could induce noise into the sensitive microelectronics
or pick up unwanted RF noise from the switching power supply circuit.
Figure 4-1 Sample Wire Routing
1513417
HPF602ULADA Distributed Power Module Installation Manual
4.3Current Requirements (Standby and Alarm)
4.3.1Current Drawn From Host Panel
Table 4-1 shows the HPF602ULADA current draw requirements from the main control panel
when the panel’s notification appliance circuit is in alarm. The current draw from the main
panel when it is supervising the HPF602ULADA is the same current draw that would be
present when the main panel supervises an ordinary notification appliance circuit.
Table 4-1: Alarm Current Drawn From Main Control Panel
Panel VoltageCurrent
Alarm Current (for typical voltages)
drawn from main panel’s notification
appliance
circuits.
4.3.2Current Drawn from Battery
12 VDC6.5 mA
24 VDCOne input circuit: 15 mA
Both input circuits: 30 mA
Batteries used with the HPF602ULADA must not exceed 35AH. (33AH max. for FM
(Factory Mutual) Installations). Batteries larger than 7 AH will not fit into the
HPF602ULADA cabinet and must be housed in the RBB Remote Battery Box. See Section
4.7 for battery installation.
The following is the maximum current draw from the auxiliary power terminals for standby
calculations. These currents assume 24 or 60 hours of standby time, followed by 5 minutes of
maximum alarm current.
•195 mA for 24 Hour Standby Current
•39 mA for 60 Hours of Auxiliary Standby Current
The above numbers were calculated assuming the use of 7 AH batteries at 100% of rated
capacity.
The total current of the HPF602ULADA, plus all items powered from it, must not exceed 6 A
when the panel is in alarm. Use Table 4-2 to ensure that the current does not exceed 6 A and,
that the desired amount of standby is possible for the battery intended for use with the
HPF602ULADA.
4.3.2.1CAN/ULC-S527
Per CAN/ULC-S527, the maximum current draw from the auxiliary power terminals for
standby calculations is 39 mA for 24 hours standby current. The current assumes 24 hours of
standby time, followed by 30 minutes of maximum alarm current.
8151341
Table 4-2: Battery Calculation Worksheet
Installation
Device
For each device use this formula:This column X This column= Current per number of devices.
HPF602ULADA Distributed Power
Module
(Current draw from battery)
A
Auxiliary DevicesRefer to device manual for current ratings.
B
Notification appliancesRefer to device manual for current ratings.
C
Total current ratings of all devices in system (line A + line B + line C)
D
Total current ratings converted to amperes (line D x .001):
E
Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5). 24 Hrs. for NBC,
F
section 3.2.7.8
Multiply lines E and F. Total standby AH
G
Alarm sounding period in hours. In accordance with NBC and ULC.
H
(For example, 5 minutes = .0833 hours, or for ULC installations 30 minutes = 0.5 hours.)
Multiply lines E and H.Total alarm AH
I
Add lines G and I.Total standby and alarm AH
J
Multiply line J by 1.20.
K
(20% extra insurance to meet desired performance) Total ampere-hours required
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Alarm:mA0 mAmA
Notification Appliance Current
Standby
Current
0 mAmA
mAmA
AA
H
AH
AH
AH
Alarm
Current
H
AH
1513419
HPF602ULADA Distributed Power Module Installation Manual
4.4Connecting the HPF602ULADA to a FACP
Figure 4-2 shows the general layout of the HPF602ULADA PC board. This section also
provides specific wiring details for accessories.
Figure 4-2 The Model HPF602ULADA PC Board Layout
Consult the installation manual for specific wiring information for the control panel being
used.
10151341
Installation
Must be connected to
a power limited source
4.4.1Common Trouble Relay
The HPF602ULADA has a Form C trouble relay built into Terminals 11-13. The relay
provides a normally open and a normally closed contact, both of which are rated at 2.5A. The
trouble relay will deactivate under any trouble condition.
A typical application of the trouble relay is to connect the HPF602ULADA normally closed
(N.C.) contacts in series with the EOL supplied with the fire alarm control panel. This will
cause a trouble on the fire alarm control panel when the HPF602ULADA opens its trouble
contacts.
Note:The N.C. contact is the contact that is closed when the HPF602ULADA has power and there are no trouble
conditions.
Figure 4-3 Trouble Relay Connection Example
15134111
HPF602ULADA Distributed Power Module Installation Manual
4.5Notification Appliance Wiring
Note:Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device you have chosen
will work with this feature.
Important!
For all synchronization options, input 1 is the strobe input and input 2 is the audible input. The signals to input 1 and input 2
must be DC signals for the synchronization patterns to work properly. When it is desired to activate both strobes and audibles,
input 1 and input 2 must be active. If it is desired to only activate strobes, then input 1 must be active and input 2 must be
inactive. The audible can be deactivated and reactivated at any time by changing the signal at input 2 as long as input 1
remains active. If input 1 is not active, then input 2 is ignored.
4.5.1Class A Supervised Wiring
Figure 4-4 shows how to wire for Class A input and output supervision. Use in/out wiring
methods for proper supervision. (Refer to Appendix A for notification appliances compatible
with the HPF602ULADA.)
Class A Output Notification Circuits
The configuration shown in Figure 4-4 shows two, 3 A devices wired as Class A. When using
the outputs as Class A circuits, loop the wiring back to the corresponding circuit pair. For
Class A wiring, no external EOL is necessary since it is built into the HPF602ULADA board.
Class A Supervised Input Circuits
The configuration shown in Figure 4-4 shows Class A supervised wiring from a fire alarm
control panel to the HPF602ULADA board. Pay close attention to the polarities when wiring a
panel to the HPF602ULADA and follow these requirements:
•When wiring to Terminal 18 on the HPF602ULADA, you must use two separate wires.
Do not loop a single wire or twist two conductors together.
•Do not use notification appliances on Class A circuits connected to a HPF602ULADA for
input. The HPF602ULADA will detect voltage across the input circuits, but is not
12151341
designed to pass the added current load from notification appliances.
Installation
Figure 4-4 Class A Supervised Input/Output Connections
4.5.2Class B Supervised Wiring
Figure 4-5 shows how to wire for Class B input and output supervision. Use in/out wiring
methods for proper supervision (Refer to the Appendix for notification appliances approved
for use with the HPF602ULADA.)
Class B Output Notification Circuits
Figure 4-5 shows four, 1.5 A devices wired as Class B.
Place a 4.7k ohm EOL resistor (provided) at the end of each circuit to enable supervision
when using all outputs as Class B notification appliance circuits. The 4.7k EOLs must be
wired to the terminals whether or not you are using all output terminals.
15134113
HPF602ULADA Distributed Power Module Installation Manual
Class B Supervised Input Circuits
Figure 4-5 shows Class B supervised wiring from a fire alarm control panel to the
HPF602ULADA.
Use an EOL resistor as shown to enable notification appliance circuit input supervision. Some
panels use EOLs that have a different value from the 4.7k ohm EOL resistor used by the
HPF602ULADA. In this case, the EOL must be UL listed for the fire alarm control panel (not
the HPF602ULADA).
Figure 4-5 Class B Supervised Input/Output Connections
4.6Ground Fault Detection Enable/Disable Jumper
In some cases the ground fault detection feature on the HPF602ULADA may interfere with
the ground fault detection feature of the main control panel in the system. To disable the
ground fault detection feature on the HPF602ULADA, place the jumper block on J1, across
Pins 1 and 2 (see Figure 4-2).
14151341
Installation
Model 6712
(Supervised)
Jumper
(P/N140694)
4.7Battery Connection
Use two 12 VDC, 7 AH gel cell batteries inside the HPF602ULADA cabinet. For batteries
larger than 7 AH (not to exceed 35 AH) use the RBB Remote Battery Box. It is recommended
that you replace the batteries every five years. The following steps and diagram explain how
to connect the batteries.
1. Connect the black wire to the negative (-) side of Battery #1.
2. Connect the jumper wire provided (PN 140694) from the positive (+) side of Battery #1 to
the negative side of Battery #2.
3. Connect the red wire to the positive (+) side of Battery #2.
Figure 4-6 Battery Connection
4.8DIP Switch Settings
A 7-position DIP switch on the HPF602ULADA board allows you to select the following:
•How long the HPF602ULADA will wait before indicating a loss of AC.
•Which input (Input 1 or Input 2) will control the NACs.
•Which NACs to wire as Class A and Class B.
•Auxiliary power state.
•Which NACs to operate as steady, ANSI temporal, or sync. outputs
Refer to Figure 4-2 for the location of the DIP switch on the HPF602ULADA board.
15134115
HPF602ULADA Distributed Power Module Installation Manual
4.8.1Selecting the Standard Input/Output Configurations
Figure 4-7 and Figure 4-8 show the position of each switch for the non-synchronized input
and output configurations. The position of Switches 4 and 5 does not affect the relationship of
inputs to outputs.
Note:The HPF602ULADA checks switches 1, 2, 3, and 6 only when powering up the HPF602ULADA. If you
change these switch settings, you must remove both the AC power and the battery to make the
HPF602ULADA recognize the new settings.
Figure 4-7 Setting DIP Switches 1-3
Figure 4-8 Setting DIP Switches 1-3 (Continued)
Note:For 100 mS input signal debounce with no synchronization DIP switches 6 and 7 must be turned On.
16151341
Installation
4.8.1.1Input/Output Configurations That Select ANSI
Temporal-Coded Outputs
The DIP switch settings marked with an asterisk (*) in Figure 4-7 and Figure 4-8 are designed
to produce ANSI temporal-coded outputs from a constant input. The figures shown below
compare the output patterns of configurations before and after the addition of this feature.
Standard HPF602ULADA Input to Output Relationship
Input/Output Relationship for ANSI
Temporal-coded Options
With this new feature, a steady signal can produce the pattern shown above for panels not
previously able to do so.
Note:The HPF602ULADA can also produce temporal patterns if the inputs are non-ANSI temporal configura-
tions.
15134117
HPF602ULADA Distributed Power Module Installation Manual
4.8.2Selecting Synchronized Output Configurations
The following sections describe how to configure the HPF602ULADA as a synchronization
power expander for Amseco, Faraday, Gentex, System Sensor, or Wheelock synchronized
horn/strobe appliances.
Note:In order for the synchronization feature to operate properly, make sure you have set the DIP switches for
the proper manufacturer. See Sections 4.8.2.1, 4.8.2.2, or 4.8.2.3.
Important!
For all synchronization options, input 1 is the strobe input and input 2 is the audible input. The signals to input 1 and input 2
must be DC signals for the synchronization patterns to work properly. When it is desired to activate both strobes and audibles,
input 1 and input 2 must be active. If it is desired to only activate strobes, then input 1 must be active and input 2 must be
inactive. The audible can be deactivated and reactivated at any time by changing the signal at input 2 as long as input 1
remains active. If input 1 is not active, then input 2 is ignored.
To select the input/outputs for AMSECO synchronized appliances, set the DIP switches as
shown in Figure 4-13.
Figure 4-13 AMSECO Synchronized Configurations
15134119
HPF602ULADA Distributed Power Module Installation Manual
4.8.3Setting the Loss of AC Delay
Normal selection for reporting loss of AC is 3 hours.
The ON position is for test purposes only and the normal position for Switch 4 is OFF. For
testing the Low AC reporting, you can temporarily turn Switch 4 ON without removing
power.
Note:Remember to turn the switch OFF when testing is complete.
Figure 4-14 Setting DIP Switch 4
4.8.4Setting the Auxiliary Output
Switch 5 on the DIP switch determines how the auxiliary power operates on the
HPF602ULADA.
The HPF602ULADA checks Switch 5 only when powering up the HPF602ULADA. If you
change this switch, you must remove both the AC power and the battery to force the
HPF602ULADA to recognize the new switch setting.
Figure 4-15 Setting DIP Switch 5
20151341
Sample Applications
HPF602ULADA
Local Fire Alarm
Control Panel
Local Fire Alarm
Control Panel
HPF602ULADA
Section 5
Sample Applications
The drawings in this section show various HPF602ULADA configurations, including
“daisy-chaining”.
5.1Notification Power Applications
Figure 5-1 Input 1 Activates All Four Outputs
Figure 5-2 Input 1 Activates NACs 1 and 2; Input 2 Activates NACs 3 and 4
15134121
HPF602ULADA Distributed Power Module Installation Manual
HPF602ULADA
HPF602ULADA
Local Fire Alarm
Control Panel
HPF602ULADA
HPF602ULADA
HPF602ULADA
Local Fire Alarm
Control Panel
Note:When multiple power supplies are used with one control unit they will not sync with each other
Figure 5-3 One Control Activating Two HPF602ULADAs
22151341
Figure 5-4 One Control Activating Three HPF602ULADAs in Series
Sample Applications
HPF602ULADA
HPF602ULADA
HPF602ULADA
Local Fire Alarm
Control Panel
Figure 5-5 Each Control NAC Activates Five Output NACs
5.2Non-Resettable Power Application
The HPF602ULADA provides a dedicated 3 A auxiliary power output that you can select as
non-resettable (output is always on). See Section 4.8.4 for setting the auxiliary power. If you
need more than 3 A, wire the inputs as shown in Figure 5-6.
Figure 5-6 Auxiliary Output Wiring for Non-Resettable Power
15134123
HPF602ULADA Distributed Power Module Installation Manual
HPF602ULADA
Fire Alarm Panel
ESL DHX 1224
5.3Door Holder Application
In a typical door holder application, the door holder power must be interrupted to close all fire
doors under the following conditions:
•Any active alarm condition.
•AC power failure (to conserve battery power).
T o close the fire doors in these situations, wire an N.C. programmable relay from the FACP in
series with the auxiliary power to the door holders as shown in Figure 5-7.
The circuit shown in Figure 5-7 will provide up to 3 amps of door holder power. (See Section
5.2 if you need more than 3 amps of auxiliary power.) The power in this example is released
when AC power is off for 30 seconds or more, or when the relay from the fire alarm control
panel becomes open. You would have to use the equivalent of a programmable relay from a
fire alarm control panel that is programmed to open under alarm conditions. See Section 4.8.4
for selecting auxiliary power options.
Figure 5-7 Door Holder Wiring Example
24151341
Troubleshooting
Section 6
Troubleshooting
Light-emitting diodes (LEDs) indicate fault conditions. This section describes the LED states.
6.1LEDs
The eight LEDs indicate a fault in one of the circuits (either NACs 1 through 4, auxiliary
power, earth fault, low AC, or battery). A fault in the LED's corresponding circuit will light
the LED (labeled on the board). Their functions are as follows:
LEDColorDescription
OUT1YellowWhen ON, output circuit 1 is in trouble or in an overcurrent state.
OUT2YellowWhen ON, output circuit 2 is in trouble or in an overcurrent state.
OUT3YellowWhen ON, output circuit 3 is in trouble or in an overcurrent state.
OUT4YellowWhen ON, output circuit 4 is in trouble or in an overcurrent state.
AUXYellowWhen ON, the auxiliary power output is in an overcurrent state.
FLTYellowWhen ON, an earth ground fault on the unit exists.
BATTYellowWhen ON, a low battery condition exists.
ACGreenWhen OFF , there is no AC power to the unit. Under normal conditions, this LED is ON
to indicate the presence of AC power.
See Figure 4-2 for locations of LEDs.
15134125
HPF602ULADA Distributed Power Module Installation Manual
6.2Trouble Conditions
Trouble ConditionWhat Happens
Low AC
(AC input voltage is low or off
for 6 hours or longer.)
Low Battery
(Battery voltage is less than
21.4 VDC.)
Earth Ground Fault
(The earth terminal is connected
to one of the positive or
negative terminals on the output
or auxiliary output circuits.)
Power Limit At AUX
(Current draw at the auxiliary
power terminals is exceeding
3.0 amps.)
Power-limited OUTPUT
(Current draw at an output
terminal is exceeding 3.0
amps.)
EOL supervision trouble
(Equivalent resistance of the
EOL resistor is outside the
range 2k - 10k.)
Input 1 and Input 2 supervision circuits open after a 6 hour delay.
The green AC LED turns off as soon as low AC or loss of AC occurs (does not wait 6 hours).
The trouble relay is de-energized after a 6 hour delay.
The trouble restores within 1 minute of the AC voltage restoring to a normal level.
Input 1 and Input 2 supervision circuits open. The yellow “BATT” LED lights.
The trouble relay is de-energized.
The trouble restores when battery voltage is greater than 22.4 VDC.
Input 1 and Input 2 supervision circuits open. The yellow “FLT” LED lights.
The trouble relay is de-energized.
The trouble restores when the fault between the earth ground and one of the output circuit
terminals is removed.
Power disconnects at the AUX terminal. Input 1 and Input 2 supervision circuits open. The
yellow “AUX” LED lights. The trouble relay is de-energized.
The trouble restores when the overcurrent condition no longer exists. When a circuit goes into
a power limited state, it will reverse the polarity of the voltage at the terminals and verify the
load. If it is more than 1k ohms, the power limit will self-restore.
This does not automatically occur for some devices typically connected to auxiliary power.
Power limit conditions do not restore in reverse polarity monitoring if the devices are not
polarized (for example, some door holder devices). To allow automatic restores for
power-limited auxiliary circuits, it is recommended that all non-polarized devices be polarized
using a diode in series with each device.
Power at the OUTPUT is disconnected. Input 1 and Input 2 supervision circuits open. The
corresponding yellow LED lights. The trouble relay is de-energized.
The trouble restores when the overcurrent condition no longer exists.
Input 1 and Input 2 supervision circuits open. Corresponding yellow LED lights.
The trouble relay is de-energized.
Trouble restores if an EOL within (2k-10k) appears at the output terminals.
Note: While Input 1 & 2 are activated, Input 1 & 2 will not open to indicate a trouble or supervisory condition.
Once the circuit is deactivated it will open to indicate a trouble or supervisory condition.
26151341
Troubleshooting
6.3Earth Fault Resistance
Table 6-1 lists the earth fault resistance detection for each applicable terminal on the FACP.
Table 6-1: Earth Fault Resistance Values by Terminal
HPF602ULADA Distributed Power Module Installation Manual
6.4Removing and Replacing the Control Panel
This section provides instruction on how to remove and replace the control panel if it is
determined that the control panel needs to be repaired or replaced.
6.4.1Removing the Control Panel
Follow these step to properly remove the control panel:
1. Remove the two heat sink screws. The heat sink screws are located on the top of the
cabinet. See Figure 6-1.
Figure 6-1 Mounting Screw Locations
2. Remove the four chassis mounting screws. See Figure 6-1 for chassis screw locations.
3. Carefully remove the control panel.
6.4.2Replacing the Control Panel
Follow these steps to replace the control panel:
Note:Use a grounding strap when working with static sensitive components.
1. Align the control panel with the chassis mounting stand-offs. See Figure 6-1.
2. Insert the four chassis mounting screws (see Figure 6-1). Do not over tighten the chassis
mounting screws.
3. Insert the two heat sink screws (see Figure 6-1). Do not over tighten the heat sink screws.
Note:The heat sink screws must be installed for proper heat dispersion of the power module’s power supply.
28151341
Appendix A
UL Listed Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL
resistor on each circuit. All supervised notification appliances used with the HPF602ULADA
must be polarized.
Note:Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen
will work with this feature. Synchronization is UL listed for multi-circuit operation.
A.1Notification Appliances
Table A-1 below lists notification appliances compatible with the HPF602ULADA.
Appliances which can be synchronized indicate the type of sync available in the
columns marked Audio and/or Visual
P2RH-P2-Wire Horn/Strobe High Candela
PC2RH2-Wire Horn/Strobe High Candela
PC2RH-P2-Wire Horn/Strobe High Candela
P2W2-Wire Horn/Strobe
P2W-P2-Wire Horn/Strobe
PC2W2-Wire Horn/S trobe
PC2W-P2-Wire Horn/Strobe
P2WH2-Wire Horn/Strobe High Candela
P2WH-P2-Wire Horn/Strobe High Candela
PC2WH2-Wire Horn/Strobe High Candela
PC2WH-P2-Wire Horn/Strobe High Candela
P2RK2-Wire Horn/Strobe
PC2RK2-Wire Horn/Strobe
P2RHK2-Wire Horn/Strobe High Candela
PC2RHK2-Wire Horn/Strobe High Candela
P4R4-Wire Horn/Strobe
PC4R4-Wire Horn/Strobe
P4RH4-Wire Horn/Strobe High Candela
P4W4-Wire Horn/Strobe
36151341
UL Listed Notification Appliances
Table A-1: Compatible Notification Appliances
ManufacturerModelAudioVisualType
PC4W4-Wire Horn/Strobe
P4WH4-Wire Horn/Strobe High Candela
PC4WH4-Wire Horn/Strobe High Candela
P4RK4-Wire Horn/Strobe
PC4RK4-Wire Horn/Strobe
P4RHK4-Wire Horn/Strobe High Candela
PC4RHK4-Wire Horn/Strobe High Candela
PC4RH4-Wire Horn/Strobe High Candela
SRStrobe
SR-PStrobe
SCRStrobe
SCR-PStrobe
System Sensor
con’t
SRHStrobe High Candela
SRH-PStrobe High Candela
SCRHStrobe High Candela
SCRH-PStrobe High Candela
SWStrobe
SW-PStrobe
SCWStrobe
SCW-PStrobe
SWHStrobe High Candela
SWH-PStrobe High Candela
SCWHStrobe High Candela
SCWH-PStrobe High Candela
SRKStrobe
SCRKStrobe
SRHKStrobe High Candela
SCRHKStrobe High Candela
15134137
HPF602ULADA Distributed Power Module Installation Manual
RSSWP-24MCWHStrobe Weatherproof
ZRS-MCWHStrobe
ZRS-24MCCStrobe
ZRS-24MCCHStrobe
MB-G6-24 Motor Bell
MB-G10-24 Motor Bell
MB-G6-12 Motor Bell
MB-G10-12 Motor Bell
MIZ-24-R Mini-Horn