Honeywell HPF602ULADA User Manual

6 Amp NAC Expander
Honeywell Power Products 12 Clintonville Road Northford, CT 06472-1653
Honeywell
Power Products
HPF602ULADA
HPF602ULADA
6 Amp NAC Expander
US
INSTALLATION & OPERATION MANUAL
Document 151341 10/14/10 Rev:
P/N 151341:L1 ECN: 10-0642
L1
Installation Precautions
FCC Warning
Maintenance
Adherence to these statements will aid in problem-free installation and enhance long-term
reliability.
Unit should be inspected at least once per year for proper operation as follows:
WARNING
book prior to starting the installation.
Follow the instructions
Disconnect AC power and batteries
Remove all electronic assemblies
Verify that wire sizes are adequate
Install this equipment in the proper environment.
Tighten screw terminals adequately
Like all solid state electronic devices,
Though designed to last many years,
W
This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
in all installation, operating, and programming manuals. These instructions must be followed to avoid
proper installation by qualified personnel.
prior to servicing. Failure to do so can damage circuits. Fuses are one time use devices and
he
same type and rating (see markings on the boards). Replace any fuse covers before energizing.
prior to any drilling, filing, reaming, or p unc hing of the enc lo sure . W hen po ss ible, ma ke a ll cable entries from the sides or rear. Before making a ny mo d ifications , verify that they will not interfere with battery, transformer, and printed circuit board location.
DC output, AC input). Use 18 AWG to 14 AWG for power limited circuits (AC Fail/Low Battery signal). Assure proper output voltage by measurem ent before connecting devices. This helps avoid potential damage. Keep power limited wiring separate from non­power limited wiring (120VAC / 60Hz Input, Battery Wires). Minimum .25” spacing must be provided. Use 75 C or higher rated UL insulated wire for connecting the unit to the electrical mains.
may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 0-49° C/32-120° F. To reduce the risk of fire or electric shock, do not expose to rain or excessive moisture. Do not block any ventilation openings. Upon completion of wiring, secure enclosure door with screws (supplied) or a key lock. Installation hardware and method must be adequate to support the weight of the unit and foreseeable mechanical loadings. Clean only with a dry cloth.
. Over-tightening may damage threads, resulting in reduced terminal contact pressure and
difficulty with screw terminal removal. Use only accessories and replacement parts specified by the manufacturer.
this system may operate erratically or can be damaged when subjected to lightning-induced
suppressive d evices will re duc e susceptibility. Consu lt the Technical Services Departmen t shou ld pro blems be anticipated or encountered.
system components can fail at any time. This system contains static-sensitive components.
static-suppressive packaging to protect electronic assemblies removed from the unit.
Under normal load conditions, the DC output voltage should be checked for proper voltage level.
Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals
5 years, however it is recommended to change batteries within 4 years or less as necessary.
Honeywell is not responsible for any typographical errors.
to contain voltage drop
Output Voltage Test: Battery Test:
: This unit should be installed by qualified service personnel and in accordance with The National Electrical
Code, as well as NFPA 72 and all applicable Local Regulations. It is recommended to first review this complete instruction
damage to the product and minimize hazard. Keep them in a safe place for periodic review. Operation and reliability depend upon
must be replaced when they blow. For continued protection against risk of electric shock and fire hazard replace all fuses with t
in all circuits. Use 18 AWG or larger for all power connections (Battery,
transients. Although no system is completely immune from lightning transients and interferences, proper grounding and use of surge
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use
ARNING: This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1)
and at the board terminals marked [+ BAT-- ] to insure that there is no break in the battery connection wires. Expected battery life is
The useful life of the system's standby batteries and the electronic components

Contents

Section 1
Introduction ..................................................................................................................................................1
Section 2
UL Requirements ..................................................................................................................................2
2.1 ULC Requirements ......................................................................................................................................2
Section 3
System Overview ..................................................................................................................................3
3.1 Terminal Descriptions and Electrical Ratings .............................................................................................3
3.2 Signal Input Terminals ............ .....................................................................................................................4
3.3 Notification Appliance Circuit Terminals ....................................................................................................5
Section 4
Installation .....................................................................................................................................................6
4.1 Mounting ......................................................................................................................................................6
4.1.1 Preventing Water Damage ....................................................................................................................6
4.2 Wire Routing ................ .............................................................. ..................................................................7
4.3 Current Requirements (Standby and Alarm) .............................................. .................................................8
4.3.1 Current Drawn From Host Panel ................. .........................................................................................8
4.3.2 Current Drawn from Battery .................................................................................................................8
4.3.2.1 CAN/ULC-S527 .........................................................................................................................8
4.4 Connecting the HPF602ULADA to a FACP .............................................................................................10
4.4.1 Common Trouble Relay ......................................................................................................................11
4.5 Notification Appliance Wiring ...................................................................................................................12
4.5.1 Class A Supervised Wiring .......................................................................... .......................................12
Class A Output Notification Circuits ..............................................................................................12
Class A Supervised Input Circuits .......................................................................................... ........12
4.5.2 Class B Supervised Wiring ........................................... ......................................................................13
Class B Output Notification Circuits ..............................................................................................13
Class B Supervised Input Circuits .................................................... ...............................................14
4.6 Ground Fault Detection Enable/Disable Jumper .......................................................................................14
4.7 Battery Connection ....................................................................................................................................15
4.8 DIP Switch Settings ................................................................................................................................... 15
151341 i
HPF602ULADA Distributed Power Module Installation Manual
4.8.1 Selecting the Standard Input/Output Configurations ..........................................................................16
4.8.1.1 Input/Output Configurations That Select ANSI Temporal-Coded Outputs .............................17
4.8.2 Selecting Synchronized Output Configurations .................................................................................18
4.8.2.1 Selecting Synchronized Faraday Configurations .....................................................................18
4.8.2.2 Selecting Synchronized Gentex Configurations ......................................................................18
4.8.2.3 Selecting Synchronized System Sensor Configurations .......................................................... 19
4.8.2.4 Selecting Synchronized Wheelock Configurations ..................................................................19
4.8.2.5 Selecting Synchronized AMSECO Configurations .................................................................19
4.8.3 Setting the Loss of AC Delay .............................................................................................................20
4.8.4 Setting the Auxiliary Output ...............................................................................................................20
Section 5
Sample Applications ......................................................................................................................21
5.1 Notification Power Applications ................................................................................................................21
5.2 Non-Resettable Power Application ............................................................................................................23
5.3 Door Holder Application ...........................................................................................................................24
Section 6
Troubleshooting ..................................................................................................................................25
6.1 LEDs ..........................................................................................................................................................25
6.2 Trouble Conditions ....................................................................................................................................26
6.3 Earth Fault Resistance ................................................................................................................................27
6.4 Removing and Replacing the Control Panel ..............................................................................................28
6.4.1 Removing the Control Panel ...............................................................................................................28
6.4.2 Replacing the Control Panel ...............................................................................................................28
Appendix A UL Listed Notification Appliances
A.1 Notification Appliances .............................................................................................................................29
...............................................................................29
ii 151341

Section 1 Introduction

The HPF602ULADA is a notification appliance circuit and auxiliary power expander that provides up to 6 amps of filtered, 24 volt power for powering notification appliances and auxiliary devices. The HPF602ULADA provides its own AC power connection, battery charging circuit, and battery connections. Used with security and fire alarm control panels, the HPF602ULADA enables you to connect and distribute power to many more devices than your panel may normally allow.
Input Configurations The HPF602ULADA has two optically isolated signaling inputs that provide the signal
connection from the main control panel to the HPF602ULADA (see Section 3.2 for more details).
Output Configurations The HPF602ULADA has four power-limited notification appliance circuits that can be
configured in various combinations of Class A and Class B circuits (see Section 3.3 for details).
Auxiliary Power Configurations The HPF602ULADA has a dedicated, power-limited, auxiliary output that can be
configured in two different ways. The auxiliary output can either be non-resettable (always on), or configured to switch off during the AC power failure to conserve the battery standby power . When the auxiliary power is configured to switch off, there is a 30 second delay before the auxiliary power is turned off after the AC power fails (see Section
4.8.4 for details).
Form C Trouble Relay The HPF602ULADA includes a general trouble relay that will de-energize for any trouble
situation. (see Section 4.4.1 for details).
Earth Fault Detection The HPF602ULADA monitors for earth faults to the system power or system ground.
When detected, the system de-energizes the trouble relay and the input supervision relays (see Section 5.2 for details).
ANSI Temporal Code The HPF602ULADA provides two configuration options that will drive outputs with the
ANSI temporal code if the inputs are on constantly (see Section 4.8.1 for details).
Supports Synchronized appliances The HPF602ULADA provides configuration options that will eliminate the need for
synchronized modules when using AMSECO, Faraday, Gentex, System Sensor, or Wheelock synchronization appliances.
151341 1
HPF602ULADA Distributed Power Module Installation Manual

Section 2 UL Requirements

When installed in accordance with NFPA 70 and NFPA 72 standards, the HPF602ULADA can be connected to UL Listed devices.
The HPF602ULADA is also listed to meet UL Standard 864 and power limiting requirements. The HPF602ULADA is compatible with any UL listed control unit utilizing reverse polarity
supervised notification appliance circuits, using 24 VDC regulated outputs.

2.1 ULC Requirements

Install in accordance with CE 22.1 and ULC S524. For the installation to comply with ULC, the Silent Knight 5612 module must be installed between the battery and control as describe in Section 4.8.
2 151341
System Overview

Section 3 System Overview

CAUTION
Each output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will cause it to shut down (power limit). The circuit will automatically reset once you remove the overload condition.

3.1 Terminal Descriptions and Electrical Ratings

Terminal # Description Ratings
TB1
1 AC (black–“hot”)
120 VAC 60 Hz, A2 Earth Ground
3 AC (white–“neutral”)
TB2
1 Auxiliary Power (-) 2 Auxiliary Power (+) 3 Notification 4 Output (-) 4 Notification 4 Output (+) Although each output 5 Notification 3 Output (-) 6 Notification 3 Output (+) total current draw from 7 Notification 2 Output (-) 8 Notification 2 Output (+) auxiliary power must
9 Notification 1 Output (-) 10 Notification 1 Output (+) 11 Normally Closed contact 2.5 A @ 250 VAC 12 Common 13 Normally Open contact 14 Input 2
16 Input 2 (+) 17 Input 1
19 Input 1 (+)
27.4 VDC 3.0 amps
27.4 VDC 3.0 amps
27.4 VDC 3.0 amps
27.4 VDC 3.0 amps
27.4 VDC 3.0 amps
or
2.5 A @ 30 VDC
9 - 30 VDC15 Input 2 (-)
9 - 30 VDC18 Input 1 (-)
is rated for 3 amps, the
the 4 outputs and the
not exceed 6 amps.
151341 3
HPF602ULADA Distributed Power Module Installation Manual

3.2 Signal Input Terminals

Terminals 14 through 19 are polarized signal input terminals. They provide the signaling connection from the main panel to the HPF602ULADA. See Figure 4-2 for more details.
The main panel supervises its notification appliance circuits used for communicating with the HPF602ULADA the same way it supervises ordinary notification appliance circuits. The signal inputs on the HPF602ULADA monitor the polarity of the voltage coming from the main panel’s notification appliance circuits to determine when to operate the notification appliance circuits on the HPF602ULADA. The HPF602ULADA emulates the trouble behavior of a normal notification appliance circuit by interrupting the EOL supervision current for internal or output trouble conditions on the HPF602ULADA.
Note that the HPF602ULADA will accurately sense the polarity of the main panel’s notification appliance circuits to drive the outputs whether or not the supervision connection is intact. The following situations will disconnect the EOL supervision at the signal inputs and indicate a trouble condition:
Low AC power
Low Battery condition
Earth ground fault to the system power or system ground
Auxiliary output power-limited condition
EOL supervision trouble or power-limited condition at an output Trouble conditions will not necessarily occur for both inputs when the trouble is specific to a
particular output. Only the signal input controlling the output circuit that is in trouble will indicate a trouble condition. Below are examples where both inputs do NOT indicate trouble for a trouble occurring at only one output circuit.
Example 1: If input 1 controls all four outputs, a fault on any output will cause input 1
to indicate trouble. The fault does not affect input 2.
Example 2: If input 1 controls outputs 1 and 2, and input 2 controls outputs 3 and 4, a
fault condition on output 3 or 4 will cause input 2 to indicate trouble. The fault does not affect input 1.
Note:Once the inputs are driven with forward polarity to activate the outputs, the main control panel will not be
able to sense trouble conditions through its notification appliance circuit connected to the HPF602ULADA input circuits. Use the HPF602ULADA trouble relay when it is necessary to monitor trouble conditions and active alarm conditions at the same time.
Section 6 explains the significance of each trouble condition in more detail.
4 151341
System Overview

3.3 Notification Appliance Circuit Terminals

T erminals 3 through 10 are the notification appliance circuit output terminals. Each of the four circuits are rated at 3 amps, although you can only draw a total of 6 amps from the HPF602ULADA. The HPF602ULADA outputs are short-circuit protected (power limited) according to UL 864 standards. Overcurrent indicators are yellow LEDs. The output voltage can vary depending on the load and input voltage.
The four power-limited NAC outputs can be configured as follows:
Four Class B circuits Faraday synchronized outputs
Two Class A circuits Gentex synchronized outputs
One Class A and two Class B circuits System Sensor synchronized outputs
Class B, ANSI temporal-coded circuits Wheelock synchronization outputs
AMSECO synchronized outputs
One or both HPF602ULADA signal inputs control the NAC outputs, depending on the specific configuration setup. Possible configurations for the HPF602ULADA are:
For Option: These Inputs: Control These Outputs: As:
1 Input 1 All outputs Class B circuits
2
3
4
5 Input 1 Outputs 1-2 and 3-4 Class A circuit pairs
6
7
8
9
10
11
12
13
Input 1 or Input 2 coded circuits Input 1 Outputs 1 and 2 Class B circuits Input 2 Outputs 3 and 4 Class B circuits Input 1 Output 1 Class B circuits Input 2 Outputs 2, 3, and 4 Class B circuits
Input 1 Outputs 1 and 2 Class B ANSI temporal-coded circuits Input 2 Outputs 3 and 4 Class B circuits Input 1 Outputs 1-2 Class A circuit pair Input 2 Outputs 3-4 Class A circuit pair Input 1 Outputs 1-2 Class A circuit pair Input 2 Outputs 3 and 4 Class B circuits Input 1 (Strobe Control) Input 2 (Audio Control) Faraday Sync. Output Input 1 (Strobe Control) Input 2 (Audio Control) Gentex Sync. Output Input 1 (Strobe Control) Input 2 (Audio Control) System Sensor Sync. Output Input 1 (Strobe Control) Input 2 (Audio Control) Wheelock Sync. Output Input 1 (Strobe Control) Input 2 (Audio Control) Amseco Sync. Output
Outputs 1, 2, 3, and 4
All outputs
All outputs
All outputs
All outputs
All outputs
Class B ANSI temporal-
Class A or Class B
Class A or Class B
Class A or Class B
Class A or Class B
Class A or Class B
You can select which input controls which output, and which inputs are Class A and Class B using the 7-position DIP switch on the printed circuit board. Section 4.8 for DIP switch settings.
151341 5
HPF602ULADA Distributed Power Module Installation Manual

Section 4 Installation

Before installing the HPF602ULADA, the AC input must first be wired into the building’s main electrical power through the TB1 terminals (see Figure 4-2). Shut off the electrical power to the HPF602ULADA, and then complete the general installation of the HPF602ULADA using the information in this section.

4.1 Mounting

Mount the HPF602ULADA in locations that meet the following temperature and humidity requirements. Do not expose the panel to conditions outside these ranges. For use in indoor, dry environments.
Temperature Humidity
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete, especially when moisture is expected, first attach a piece of 3/4-inch plywood to the concrete surface. Attach the HPF602ULADA to the plywood.
o
C-49o C (32o F-120o F)
0 10%-93% at 30o C (86o F) noncondensing

4.1.1 Preventing Water Damage

Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
6 151341
Installation
Note: The use of this knock out will reduce the number and/or size of batteries this cabinet can contain. Evaluation of space is important before using.

4.2 Wire Routing

To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated from high current output and power-limited wiring. Induced noise can interfere with telephone communication or even cause false alarms. Avoid pulling a single multiconductor cable for the entire system. Instead, separate high current input/output from low current. Separate power-limited from non-power-limited wiring. Non-power-limited wiring must be enclosed in conduit.
Wiring within the cabinet should be routed around the perimeter of the cabinet. It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the switching power supply circuit.
Figure 4-1 Sample Wire Routing
151341 7
HPF602ULADA Distributed Power Module Installation Manual

4.3 Current Requirements (Standby and Alarm)

4.3.1 Current Drawn From Host Panel

Table 4-1 shows the HPF602ULADA current draw requirements from the main control panel when the panel’s notification appliance circuit is in alarm. The current draw from the main panel when it is supervising the HPF602ULADA is the same current draw that would be present when the main panel supervises an ordinary notification appliance circuit.
Table 4-1: Alarm Current Drawn From Main Control Panel
Panel Voltage Current
Alarm Current (for typical voltages) drawn from main panel’s notification
appliance
circuits.

4.3.2 Current Drawn from Battery

12 VDC 6.5 mA 24 VDC One input circuit: 15 mA
Both input circuits: 30 mA
Batteries used with the HPF602ULADA must not exceed 35AH. (33AH max. for FM (Factory Mutual) Installations). Batteries larger than 7 AH will not fit into the HPF602ULADA cabinet and must be housed in the RBB Remote Battery Box. See Section
4.7 for battery installation. The following is the maximum current draw from the auxiliary power terminals for standby
calculations. These currents assume 24 or 60 hours of standby time, followed by 5 minutes of maximum alarm current.
195 mA for 24 Hour Standby Current
39 mA for 60 Hours of Auxiliary Standby Current The above numbers were calculated assuming the use of 7 AH batteries at 100% of rated
capacity. The total current of the HPF602ULADA, plus all items powered from it, must not exceed 6 A
when the panel is in alarm. Use Table 4-2 to ensure that the current does not exceed 6 A and, that the desired amount of standby is possible for the battery intended for use with the HPF602ULADA.
4.3.2.1 CAN/ULC-S527
Per CAN/ULC-S527, the maximum current draw from the auxiliary power terminals for standby calculations is 39 mA for 24 hours standby current. The current assumes 24 hours of standby time, followed by 30 minutes of maximum alarm current.
8 151341
Table 4-2: Battery Calculation Worksheet
Installation
Device
For each device use this formula: This column X This column = Current per number of devices.
HPF602ULADA Distributed Power Module
(Current draw from battery)
A
Auxiliary Devices Refer to device manual for current ratings.
B
Notification appliances Refer to device manual for current ratings.
C
Total current ratings of all devices in system (line A + line B + line C)
D
Total current ratings converted to amperes (line D x .001):
E
Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5). 24 Hrs. for NBC,
F
section 3.2.7.8 Multiply lines E and F. Total standby AH
G
Alarm sounding period in hours. In accordance with NBC and ULC.
H
(For example, 5 minutes = .0833 hours, or for ULC installations 30 minutes = 0.5 hours.) Multiply lines E and H. Total alarm AH
I
Add lines G and I. Total standby and alarm AH
J
Multiply line J by 1.20.
K
(20% extra insurance to meet desired performance) Total ampere-hours required
Number of
Devices
1
Current per Device
Standby: 75 mA 75 mA Alarm: 205 mA 205 mA
HPF602ULADA Current 75 mA 205 mA
Alarm/Standby mA mA mA Alarm/Standby mA mA mA Alarm/Standby mA mA mA Alarm/Standby mA mA mA
Auxiliary Device Current mA mA
Alarm: mA 0 mA mA Alarm: mA 0 mA mA Alarm: mA 0 mA mA Alarm: mA 0 mA mA
Notification Appliance Current
Standby
Current
0 mA mA
mA mA
AA
H
AH
AH
AH
Alarm
Current
H
AH
151341 9
HPF602ULADA Distributed Power Module Installation Manual

4.4 Connecting the HPF602ULADA to a FACP

Figure 4-2 shows the general layout of the HPF602ULADA PC board. This section also provides specific wiring details for accessories.
Figure 4-2 The Model HPF602ULADA PC Board Layout
Consult the installation manual for specific wiring information for the control panel being used.
10 151341
Installation
Must be connected to a power limited source

4.4.1 Common Trouble Relay

The HPF602ULADA has a Form C trouble relay built into Terminals 11-13. The relay provides a normally open and a normally closed contact, both of which are rated at 2.5A. The trouble relay will deactivate under any trouble condition.
A typical application of the trouble relay is to connect the HPF602ULADA normally closed (N.C.) contacts in series with the EOL supplied with the fire alarm control panel. This will cause a trouble on the fire alarm control panel when the HPF602ULADA opens its trouble contacts.
Note:The N.C. contact is the contact that is closed when the HPF602ULADA has power and there are no trouble
conditions.
Figure 4-3 Trouble Relay Connection Example
151341 11
HPF602ULADA Distributed Power Module Installation Manual

4.5 Notification Appliance Wiring

Note:Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device you have chosen
will work with this feature.
Important!
For all synchronization options, input 1 is the strobe input and input 2 is the audible input. The signals to input 1 and input 2 must be DC signals for the synchronization patterns to work properly. When it is desired to activate both strobes and audibles, input 1 and input 2 must be active. If it is desired to only activate strobes, then input 1 must be active and input 2 must be inactive. The audible can be deactivated and reactivated at any time by changing the signal at input 2 as long as input 1 remains active. If input 1 is not active, then input 2 is ignored.

4.5.1 Class A Supervised Wiring

Figure 4-4 shows how to wire for Class A input and output supervision. Use in/out wiring methods for proper supervision. (Refer to Appendix A for notification appliances compatible with the HPF602ULADA.)
Class A Output Notification Circuits
The configuration shown in Figure 4-4 shows two, 3 A devices wired as Class A. When using the outputs as Class A circuits, loop the wiring back to the corresponding circuit pair. For Class A wiring, no external EOL is necessary since it is built into the HPF602ULADA board.
Class A Supervised Input Circuits
The configuration shown in Figure 4-4 shows Class A supervised wiring from a fire alarm control panel to the HPF602ULADA board. Pay close attention to the polarities when wiring a panel to the HPF602ULADA and follow these requirements:
When wiring to Terminal 18 on the HPF602ULADA, you must use two separate wires. Do not loop a single wire or twist two conductors together.
Do not use notification appliances on Class A circuits connected to a HPF602ULADA for input. The HPF602ULADA will detect voltage across the input circuits, but is not
12 151341
designed to pass the added current load from notification appliances.
Installation
Figure 4-4 Class A Supervised Input/Output Connections

4.5.2 Class B Supervised Wiring

Figure 4-5 shows how to wire for Class B input and output supervision. Use in/out wiring methods for proper supervision (Refer to the Appendix for notification appliances approved for use with the HPF602ULADA.)
Class B Output Notification Circuits
Figure 4-5 shows four, 1.5 A devices wired as Class B. Place a 4.7k ohm EOL resistor (provided) at the end of each circuit to enable supervision
when using all outputs as Class B notification appliance circuits. The 4.7k EOLs must be wired to the terminals whether or not you are using all output terminals.
151341 13
HPF602ULADA Distributed Power Module Installation Manual
Class B Supervised Input Circuits
Figure 4-5 shows Class B supervised wiring from a fire alarm control panel to the HPF602ULADA.
Use an EOL resistor as shown to enable notification appliance circuit input supervision. Some panels use EOLs that have a different value from the 4.7k ohm EOL resistor used by the HPF602ULADA. In this case, the EOL must be UL listed for the fire alarm control panel (not the HPF602ULADA).
Figure 4-5 Class B Supervised Input/Output Connections

4.6 Ground Fault Detection Enable/Disable Jumper

In some cases the ground fault detection feature on the HPF602ULADA may interfere with the ground fault detection feature of the main control panel in the system. To disable the ground fault detection feature on the HPF602ULADA, place the jumper block on J1, across Pins 1 and 2 (see Figure 4-2).
14 151341
Installation
Model 6712
(Supervised)
Jumper
(P/N140694)

4.7 Battery Connection

Use two 12 VDC, 7 AH gel cell batteries inside the HPF602ULADA cabinet. For batteries larger than 7 AH (not to exceed 35 AH) use the RBB Remote Battery Box. It is recommended that you replace the batteries every five years. The following steps and diagram explain how to connect the batteries.
1. Connect the black wire to the negative (-) side of Battery #1.
2. Connect the jumper wire provided (PN 140694) from the positive (+) side of Battery #1 to the negative side of Battery #2.
3. Connect the red wire to the positive (+) side of Battery #2.
Figure 4-6 Battery Connection

4.8 DIP Switch Settings

A 7-position DIP switch on the HPF602ULADA board allows you to select the following:
How long the HPF602ULADA will wait before indicating a loss of AC.
Which input (Input 1 or Input 2) will control the NACs.
Which NACs to wire as Class A and Class B.
Auxiliary power state.
Which NACs to operate as steady, ANSI temporal, or sync. outputs
Refer to Figure 4-2 for the location of the DIP switch on the HPF602ULADA board.
151341 15
HPF602ULADA Distributed Power Module Installation Manual

4.8.1 Selecting the Standard Input/Output Configurations

Figure 4-7 and Figure 4-8 show the position of each switch for the non-synchronized input and output configurations. The position of Switches 4 and 5 does not affect the relationship of inputs to outputs.
Note:The HPF602ULADA checks switches 1, 2, 3, and 6 only when powering up the HPF602ULADA. If you
change these switch settings, you must remove both the AC power and the battery to make the HPF602ULADA recognize the new settings.
Figure 4-7 Setting DIP Switches 1-3
Figure 4-8 Setting DIP Switches 1-3 (Continued)
Note:For 100 mS input signal debounce with no synchronization DIP switches 6 and 7 must be turned On.
16 151341
Installation
4.8.1.1 Input/Output Configurations That Select ANSI
Temporal-Coded Outputs
The DIP switch settings marked with an asterisk (*) in Figure 4-7 and Figure 4-8 are designed to produce ANSI temporal-coded outputs from a constant input. The figures shown below compare the output patterns of configurations before and after the addition of this feature.
Standard HPF602ULADA Input to Output Relationship
Input/Output Relationship for ANSI
Temporal-coded Options
With this new feature, a steady signal can produce the pattern shown above for panels not previously able to do so.
Note:The HPF602ULADA can also produce temporal patterns if the inputs are non-ANSI temporal configura-
tions.
151341 17
HPF602ULADA Distributed Power Module Installation Manual

4.8.2 Selecting Synchronized Output Configurations

The following sections describe how to configure the HPF602ULADA as a synchronization power expander for Amseco, Faraday, Gentex, System Sensor, or Wheelock synchronized horn/strobe appliances.
Note:In order for the synchronization feature to operate properly, make sure you have set the DIP switches for
the proper manufacturer. See Sections 4.8.2.1, 4.8.2.2, or 4.8.2.3.
Important!
For all synchronization options, input 1 is the strobe input and input 2 is the audible input. The signals to input 1 and input 2 must be DC signals for the synchronization patterns to work properly. When it is desired to activate both strobes and audibles, input 1 and input 2 must be active. If it is desired to only activate strobes, then input 1 must be active and input 2 must be inactive. The audible can be deactivated and reactivated at any time by changing the signal at input 2 as long as input 1 remains active. If input 1 is not active, then input 2 is ignored.
4.8.2.1 Selecting Synchronized Faraday Configurations
To select the input/outputs for Faraday synchronized appliances, set the DIP switches as shown in Figure 4-9.
Figure 4-9 Faraday Synchronized Configurations
4.8.2.2 Selecting Synchronized Gentex Configurations
T o select the input/outputs for Gentex synchronized appliances, set the DIP switches as shown in Figure 4-10.
Figure 4-10 Gentex Synchronized Configurations
18 151341
Installation
4.8.2.3 Selecting Synchronized System Sensor Configurations
To select the input/outputs for System Sensor synchronized appliances, set the DIP switches as shown in Figure 4-11.
Figure 4-11 System Sensor Synchronized Configurations
4.8.2.4 Selecting Synchronized Wheelock Configurations
To select the input/outputs for Wheelock synchronized appliances, set the DIP switches as shown in Figure 4-12.
Figure 4-12 Wheelock Synchronized Configurations
4.8.2.5 Selecting Synchronized AMSECO Configurations
To select the input/outputs for AMSECO synchronized appliances, set the DIP switches as shown in Figure 4-13.
Figure 4-13 AMSECO Synchronized Configurations
151341 19
HPF602ULADA Distributed Power Module Installation Manual

4.8.3 Setting the Loss of AC Delay

Normal selection for reporting loss of AC is 3 hours. The ON position is for test purposes only and the normal position for Switch 4 is OFF. For
testing the Low AC reporting, you can temporarily turn Switch 4 ON without removing power.
Note:Remember to turn the switch OFF when testing is complete.
Figure 4-14 Setting DIP Switch 4

4.8.4 Setting the Auxiliary Output

Switch 5 on the DIP switch determines how the auxiliary power operates on the HPF602ULADA.
The HPF602ULADA checks Switch 5 only when powering up the HPF602ULADA. If you change this switch, you must remove both the AC power and the battery to force the HPF602ULADA to recognize the new switch setting.
Figure 4-15 Setting DIP Switch 5
20 151341
Sample Applications
HPF602ULADA
Local Fire Alarm
Control Panel
Local Fire Alarm
Control Panel
HPF602ULADA

Section 5 Sample Applications

The drawings in this section show various HPF602ULADA configurations, including “daisy-chaining”.

5.1 Notification Power Applications

Figure 5-1 Input 1 Activates All Four Outputs
Figure 5-2 Input 1 Activates NACs 1 and 2; Input 2 Activates NACs 3 and 4
151341 21
HPF602ULADA Distributed Power Module Installation Manual
HPF602ULADA
HPF602ULADA
Local Fire Alarm
Control Panel
HPF602ULADA
HPF602ULADA
HPF602ULADA
Local Fire Alarm
Control Panel
Note:When multiple power supplies are used with one control unit they will not sync with each other
Figure 5-3 One Control Activating Two HPF602ULADAs
22 151341
Figure 5-4 One Control Activating Three HPF602ULADAs in Series
Sample Applications
HPF602ULADA
HPF602ULADA
HPF602ULADA
Local Fire Alarm
Control Panel
Figure 5-5 Each Control NAC Activates Five Output NACs

5.2 Non-Resettable Power Application

The HPF602ULADA provides a dedicated 3 A auxiliary power output that you can select as non-resettable (output is always on). See Section 4.8.4 for setting the auxiliary power. If you need more than 3 A, wire the inputs as shown in Figure 5-6.
Figure 5-6 Auxiliary Output Wiring for Non-Resettable Power
151341 23
HPF602ULADA Distributed Power Module Installation Manual
HPF602ULADA
Fire Alarm Panel
ESL DHX 1224

5.3 Door Holder Application

In a typical door holder application, the door holder power must be interrupted to close all fire doors under the following conditions:
Any active alarm condition.
AC power failure (to conserve battery power).
T o close the fire doors in these situations, wire an N.C. programmable relay from the FACP in series with the auxiliary power to the door holders as shown in Figure 5-7.
The circuit shown in Figure 5-7 will provide up to 3 amps of door holder power. (See Section
5.2 if you need more than 3 amps of auxiliary power.) The power in this example is released
when AC power is off for 30 seconds or more, or when the relay from the fire alarm control panel becomes open. You would have to use the equivalent of a programmable relay from a fire alarm control panel that is programmed to open under alarm conditions. See Section 4.8.4 for selecting auxiliary power options.
Figure 5-7 Door Holder Wiring Example
24 151341
Troubleshooting

Section 6 Troubleshooting

Light-emitting diodes (LEDs) indicate fault conditions. This section describes the LED states.

6.1 LEDs

The eight LEDs indicate a fault in one of the circuits (either NACs 1 through 4, auxiliary power, earth fault, low AC, or battery). A fault in the LED's corresponding circuit will light the LED (labeled on the board). Their functions are as follows:
LED Color Description
OUT1 Yellow When ON, output circuit 1 is in trouble or in an overcurrent state. OUT2 Yellow When ON, output circuit 2 is in trouble or in an overcurrent state. OUT3 Yellow When ON, output circuit 3 is in trouble or in an overcurrent state. OUT4 Yellow When ON, output circuit 4 is in trouble or in an overcurrent state.
AUX Yellow When ON, the auxiliary power output is in an overcurrent state.
FLT Yellow When ON, an earth ground fault on the unit exists.
BATT Yellow When ON, a low battery condition exists.
AC Green When OFF , there is no AC power to the unit. Under normal conditions, this LED is ON
to indicate the presence of AC power.
See Figure 4-2 for locations of LEDs.
151341 25
HPF602ULADA Distributed Power Module Installation Manual

6.2 Trouble Conditions

Trouble Condition What Happens
Low AC (AC input voltage is low or off
for 6 hours or longer.)
Low Battery (Battery voltage is less than
21.4 VDC.)
Earth Ground Fault (The earth terminal is connected
to one of the positive or negative terminals on the output or auxiliary output circuits.)
Power Limit At AUX (Current draw at the auxiliary
power terminals is exceeding
3.0 amps.)
Power-limited OUTPUT (Current draw at an output
terminal is exceeding 3.0 amps.)
EOL supervision trouble (Equivalent resistance of the
EOL resistor is outside the range 2k - 10k.)
Input 1 and Input 2 supervision circuits open after a 6 hour delay. The green AC LED turns off as soon as low AC or loss of AC occurs (does not wait 6 hours). The trouble relay is de-energized after a 6 hour delay. The trouble restores within 1 minute of the AC voltage restoring to a normal level.
Input 1 and Input 2 supervision circuits open. The yellow “BATT” LED lights. The trouble relay is de-energized. The trouble restores when battery voltage is greater than 22.4 VDC.
Input 1 and Input 2 supervision circuits open. The yellow “FLT” LED lights. The trouble relay is de-energized. The trouble restores when the fault between the earth ground and one of the output circuit
terminals is removed.
Power disconnects at the AUX terminal. Input 1 and Input 2 supervision circuits open. The yellow “AUX” LED lights. The trouble relay is de-energized.
The trouble restores when the overcurrent condition no longer exists. When a circuit goes into a power limited state, it will reverse the polarity of the voltage at the terminals and verify the load. If it is more than 1k ohms, the power limit will self-restore.
This does not automatically occur for some devices typically connected to auxiliary power. Power limit conditions do not restore in reverse polarity monitoring if the devices are not polarized (for example, some door holder devices). To allow automatic restores for power-limited auxiliary circuits, it is recommended that all non-polarized devices be polarized using a diode in series with each device.
Power at the OUTPUT is disconnected. Input 1 and Input 2 supervision circuits open. The corresponding yellow LED lights. The trouble relay is de-energized.
The trouble restores when the overcurrent condition no longer exists.
Input 1 and Input 2 supervision circuits open. Corresponding yellow LED lights. The trouble relay is de-energized. Trouble restores if an EOL within (2k-10k) appears at the output terminals.
Note: While Input 1 & 2 are activated, Input 1 & 2 will not open to indicate a trouble or supervisory condition.
Once the circuit is deactivated it will open to indicate a trouble or supervisory condition.
26 151341
Troubleshooting

6.3 Earth Fault Resistance

Table 6-1 lists the earth fault resistance detection for each applicable terminal on the FACP.
Table 6-1: Earth Fault Resistance Values by Terminal
Function
Auxiliary Devices
Notification Appliance Circuit 4
Notification Appliance Circuit 3
Notification Appliance Circuit 2
Notification Appliance Circuit 1
Terminal
Number
1H5­2 H5+ 0 3H4­4 H4+ 0 5H3­6 H3+ 0 7H2­8 H2+ 0 9H1­10 H1+ 0
Terminal Label
AUX
OUT4
OUT3
OUT2
OUT1
Value
(in kohms)
0
0
0
0
0
151341 27
HPF602ULADA Distributed Power Module Installation Manual

6.4 Removing and Replacing the Control Panel

This section provides instruction on how to remove and replace the control panel if it is determined that the control panel needs to be repaired or replaced.

6.4.1 Removing the Control Panel

Follow these step to properly remove the control panel:
1. Remove the two heat sink screws. The heat sink screws are located on the top of the cabinet. See Figure 6-1.
Figure 6-1 Mounting Screw Locations
2. Remove the four chassis mounting screws. See Figure 6-1 for chassis screw locations.
3. Carefully remove the control panel.

6.4.2 Replacing the Control Panel

Follow these steps to replace the control panel:
Note:Use a grounding strap when working with static sensitive components.
1. Align the control panel with the chassis mounting stand-offs. See Figure 6-1.
2. Insert the four chassis mounting screws (see Figure 6-1). Do not over tighten the chassis mounting screws.
3. Insert the two heat sink screws (see Figure 6-1). Do not over tighten the heat sink screws.
Note:The heat sink screws must be installed for proper heat dispersion of the power module’s power supply.
28 151341

Appendix A UL Listed Notification Appliances

For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each circuit. All supervised notification appliances used with the HPF602ULADA must be polarized.
Note:Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen
will work with this feature. Synchronization is UL listed for multi-circuit operation.
A.1 Notification Appliances
Table A-1 below lists notification appliances compatible with the HPF602ULADA. Appliances which can be synchronized indicate the type of sync available in the columns marked Audio and/or Visual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
SH24W-153075 Horn/Strobe
AMSECO
SAD24-153075 Strobe SAD24-75110 Strobe SL24W-75110 Strobe SL24C-3075110 Strobe SLB24-75 Strobe RSD24-153075 Strobe RSD24-75110 Strobe SH24W-75110 Horn/Strobe SH24W-3075110 Horn/Strobe SHB24-75 Horn/Strobe SCM24W-153075 Chimes/Strobe SCM24W-75110 Chimes/Strobe SCM24C-3075110 Chimes/Strobe SCM24C-177 Chimes/Strobe H24W Horn H24R Horn
151341 29
HPF602ULADA Distributed Power Module Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
446 Vibrating Bell 476 Vibrating Bell 477 Single Stroke Bell 2700 -M. -R, -T, -Y, -Z Strobe 2701 Series Strobe 2705 Series Strobe 2820 Snyc T emporal Horn/Strobe 2821 Snyc T emporal Horn/Strobe 2824 Horn Strobe 5333 Multi-Tone Horn) 5336 Multi-Tone Horn/Strobe 5337 Multi-Tone Horn/Strobe
Faraday
5338 Multi-Tone Horn/Strobe 5343 Single Tone Horn/Strobe 5346 Electronic Horn with Strobe 5347 Electronic Horn with Strobe 5348 Single Tone Horn/Strobe 5373 8-Tone Horn/Strobe 6321 Sync Mini Horn/Strobe 6322 Mini Horn/Sync Strobe 6380 8-Tone Electronic Signal/Strobe 5376 8-Tone Horn/Strobe 5377 8-Tone Horn/Strobe 5378 8-Tone Horn/Strobe 5383 8-Tone Horn/Strobe with Sync Strobe 5386 8-Tone Horn/Strobe with Sync Strobe 5387 8-Tone Horn/Strobe with Sync Strobe 5388 8-Tone Horn/Strobe with Sync Strobe 5508 Single Gang Sync Strobe 5509 Strobe
30 151341
UL Listed Notification Appliances
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
5510 Strobe 5511 Strobe 5512 Strobe 5516 Strobe 5517 Strobe 5518 Strobe 5519 Strobe 5521 4” Square Sync Strobe 5522 4” Square Sync Strobe 6120 Horn 6140 Horn 6223 Horn
Faraday con’t
6226 Horn/Strobe 6227 Horn/Strobe 6228 Horn/Strobe 6243 Electron-Mechanical Horn 6244 Electron-Mechanical Horn 6245 Electron-Mechanical Horn 6246 Electron-Mechanical Horn/Strobe 6247 Electron-Mechanical Horn/Strobe 6248 Electron-Mechanical Horn/Strobe 6300 Mini-Horn 6301 Mini-Horn 6302 Mini-Horn 6310 Mini-Horn/Strobe 6311 Mini-Horn/Strobe 6312 Mini-Horn/Strobe 6314 Series -M, -R, -T, -Y, -Z Strobe 6320 Sync Mini Horn/Strobe
151341 31
HPF602ULADA Distributed Power Module Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
S2415-FC Strobe S241575-FC Strobe S2430-FC Strobe 130-3117C Mini Horn 130-3147C Mini Horn BLV-6 Vibrating Bell BLV-10 Vibrating Bell BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn
FCI
H12/24K-FC Horn HC12/24-FC Horn HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/Strobe P2415K-FC Horn/Strobe P241575-FC Horn/Strobe P241575W-FC Horn/Strobe P241575F-FC Horn/Strobe P241575K-FC Horn/Strobe P2430-FC Horn/Strobe
32 151341
UL Listed Notification Appliances
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
FCI
P2430W-FC Horn/Strobe P2430K-FC Horn/Strobe P2475-FC Horn/Strobe P2475W-FC Horn/Strobe P2475K-FC Horn/Strobe P24110-FC Horn/Strobe P24110W-FC Horn/Strobe P24110K-FC Horn/Strobe S2430W-FC Strobe S2430K-FC Strobe S2475-FC Strobe S2475W-FC Strobe S2475K-FC Strobe S24110-FC Strobe S24110W-FC Strobe S24110K-FC Strobe
Federal Signal
450 Horn VALS Horn/Strobe
151341 33
HPF602ULADA Distributed Power Module Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
GEC-24-15 Horn/Strobes GEC-24-30 Horn/Strobes GEC-24-60 Horn/Strobes GEC-24-75 Horn/Strobes GEC-24-177 Horn/Strobes GEC-24-110 Horn/Strobe GEC-24-15/75 Horn/Strobe GX91 MiniHorn Steady Tone GX93 MiniHorn Temporal Tone HG124 Horn HS24-15 Horn/Strobe HS24-30 Horn/Strobe
Gentex
HS24-60 Horn/Strobe HS24-75 Horn/Strobe HS24-110 Horn/Strobe HS24-1575 Horn/Strobe GCC24 Multi Candella Horn/Strobe Ceiling Mount GCCR24 Multi Candella Horn/Strobe Ceiling Mount GCS24 Multi Candella Strobe Ceiling Mount GCSR24 Multi Candella Strobe Ceiling Mount GECR-24 Multi Candella Horn/Strobe GES24-15 Strobes GES24-30 Strobes GES24-60 Strobes GES24-75 Strobes GES24-110 Strobes GES24-15/75 Strobes
34 151341
UL Listed Notification Appliances
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
GES24-177 Strobes GES3-24 Multi Candella Strobe GESR-24 Multi Candella Strobe GEH-24 Horn ST24-30 Strobe
Gentex con’t
ST24-60 Strobe ST24-75 Strobe ST24-110 Strobe ST24-1575 Strobe WGEC24-75W Weatherproof Horn/Strobe WGES24-75W Weatherproof Strobe WGMS-24-X Horn/Strobe
151341 35
HPF602ULADA Distributed Power Module Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
CHR Chime CHW Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe HR Horn HW Horn HRK Horn P2R 2-Wire Horn/Strobe P2R-P 2-Wire Horn/Strobe PC2R 2-Wire Horn/Strobe PC2R-P 2-Wire Horn/Strobe P2RH 2-Wire Horn/Strobe High Candela
System Sensor
P2RH-P 2-Wire Horn/Strobe High Candela PC2RH 2-Wire Horn/Strobe High Candela PC2RH-P 2-Wire Horn/Strobe High Candela P2W 2-Wire Horn/Strobe P2W-P 2-Wire Horn/Strobe PC2W 2-Wire Horn/S trobe PC2W-P 2-Wire Horn/Strobe P2WH 2-Wire Horn/Strobe High Candela P2WH-P 2-Wire Horn/Strobe High Candela PC2WH 2-Wire Horn/Strobe High Candela PC2WH-P 2-Wire Horn/Strobe High Candela P2RK 2-Wire Horn/Strobe PC2RK 2-Wire Horn/Strobe P2RHK 2-Wire Horn/Strobe High Candela PC2RHK 2-Wire Horn/Strobe High Candela P4R 4-Wire Horn/Strobe PC4R 4-Wire Horn/Strobe P4RH 4-Wire Horn/Strobe High Candela P4W 4-Wire Horn/Strobe
36 151341
UL Listed Notification Appliances
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
PC4W 4-Wire Horn/Strobe P4WH 4-Wire Horn/Strobe High Candela PC4WH 4-Wire Horn/Strobe High Candela P4RK 4-Wire Horn/Strobe PC4RK 4-Wire Horn/Strobe P4RHK 4-Wire Horn/Strobe High Candela PC4RHK 4-Wire Horn/Strobe High Candela PC4RH 4-Wire Horn/Strobe High Candela SR Strobe SR-P Strobe SCR Strobe SCR-P Strobe
System Sensor con’t
SRH Strobe High Candela SRH-P Strobe High Candela SCRH Strobe High Candela SCRH-P Strobe High Candela SW Strobe SW-P Strobe SCW Strobe SCW-P Strobe SWH Strobe High Candela SWH-P Strobe High Candela SCWH Strobe High Candela SCWH-P Strobe High Candela SRK Strobe SCRK Strobe SRHK Strobe High Candela SCRHK Strobe High Candela
151341 37
HPF602ULADA Distributed Power Module Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
AH-12 Horn AH-24 Horn AH-12WP Horn Weatherproof AH-24WP Horn Weatherproof AMT-241575W Multi-Tone Horn Strobe AMT-24MCW Mutli-Tone Horn Strobe AMT-241575W-NYC Multi-Tone Horn Strobe AMT-12/24 Multi-tone Horn AMT-12/24 NYC Multi-tone Horn AS-121575W Horn/Strobe NH-12/24 Horn AS-241575W Horn/Strobe
Wheelock
AS-24MCC Horn/Strobe AS-24MCCH Horn/Strobe AS-24MCW Horn/Strobe AS-24MCWH Horn/Strobe ASWP-2475W Horn/Strobe Weatherproof ASWP-2475C Horn/Strobe Weatherproof ASWP-24MCWH Horn/Strobe ASWP-24MCCH Horn/Strobe CH-70 Chime CH-90 Chime CH70-241575W Chime/Strobe CH70-24MCW Chime/Strobe CH70-24MCWH Chime/Strobe CH90-24MCC Chime/Strobe
38 151341
UL Listed Notification Appliances
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
CH90-24MCCH Chime/Strobe HS-24 Horn HS4-241575W Horn/Strobe HS4-24MCW Horn/Strobe HS4-24MCWH Horn/Strobe HS4-24MCC Horn/Strobe MIZ-24S Mini Horn Strobe MT-121575W MultitoneHorn Strobe MT-241575W Multitone Horn Strobe MT-24MCW Multitone Horn Strobe MTWP-2475W Multitone Horn Strobe MTWP-2475C Multitone Horn Strobe
Wheelock con’t
MTG-121575W Multitone Horn Strobe MTR-121575W Multitone Horn Strobe MTWPA-2475W Multitone Horn Strobe MTWPB-2475W Multitone Horn Strobe MTWPG-2475W Multitone Horn Strobe MTWPR-2475W Multitone Horn Strobe MTWPA-24MCCH Multitone Horn Strobe ZNH Horn NS-121575W Horn/Strobe NS-241575W Horn/Strobe NS-24MCW Horn/Strobe NS-24MCC Horn/Strobe NS-24MCCH Horn/Strobe ZNS-MCW Horn/Strobe ZNS-MCWH Horn/Strobe ZNS-24MCC Horn/Strobe ZNS-24MCCH Horn/Strobe
151341 39
HPF602ULADA Distributed Power Module Installation Manual
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
RSS-121575W Strobe RSS-241575W Strobe RSS-24MCC Strobe RSS-24MCCR Strobe RSS-24MCCH Strobe RSS-24MCCHR Strobe RSS-24MCW Strobe RSS-24MCWH Strobe RSSP-121575W Strobe RSSP-241575W Strobe RSSR-2415W Strobe RSSR-2415C Strobe
Wheelock con’t
RSSR-2475W Strobe RSSR-2475C Strobe RSSR-24110C Strobe RSSA-24110W Strobe RSSB-24110W Strobe RSSG-24110W Strobe RSSR-24110W Strobe RSSA-24MCC Multi-Cd Strobe RSSB-24MCC Multi-Cd Strobe RSSG-24MCC Multi-Cd Strobe RSSR-24MCC Multi-Cd Strobe RSSWPA-2475W Strobe Weatherproof RSSWPA-24MCCH Strobe Weatherproof RSSWPG-24MCCH Strobe Weatherproof RSSWPR-24MCCH Strobe Weatherproof RSSWP-2475W Strobe Weatherproof RSSWP-2475C Strobe Weatherproof
40 151341
UL Listed Notification Appliances
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
RSSWP-24MCWH Strobe Weatherproof ZRS-MCWH Strobe ZRS-24MCC Strobe ZRS-24MCCH Strobe MB-G6-24 Motor Bell MB-G10-24 Motor Bell MB-G6-12 Motor Bell MB-G10-12 Motor Bell MIZ-24-R Mini-Horn
Wheelock con’t
MT-12/24-R Multitone Horn MT4-12/24 Multitone Horn ZRS-MCW Strobe MTWPR-24MCCH Multitone Horn Strobe NH-12/24R Horn HSR Horn/Strobe HSW Horn/Strobe STR Strobe STW Strobe HNR Horn HNW Horn
151341 41
HPF602ULADA Distributed Power Module Installation Manual
42 151341
12 Clintonville Rd., Northford, CT 06472-1653 Phone: (203) 484-7161
Honeywell
Power Products
P/N 151341 Rev L1
Loading...