HMC 80/82
PRE-CONFIGURED KITS
PRODUCT DATA
FEATURES
• Direct control of mixing valve actuators for individual
room temperature control
• The HM80 is communicating with the Chronotherm
CM67RFMV, (CM67z) to keep the room temperature
constant, time program, holiday function
• Manual or automatic control
• Reduce installation time and costs
• Pump control, after running time adjustable 0..99 min.
• External Flow Sensor connectable NTC 20KΩ, 25°C
not linear (type T7414C1012)
• Maintenance run for pump and mixing valve
• Boiler feedback heat on demand with
CM67RFMV,CM67z
• Heating / Cooling operation
• RF communication check
GENERAL
The wireless Universal Mixing valve Controller is used for
heating/cooling zoning control. The HM80 controls the mixing
valve depending on the room temperature and room setpoint
by using fuzzy control logic to keep the room temperature
precisely constant. It can be done with and without the flow
sensor T7414C1012 (optional)
The pump can be controlled directly with the HM80 relay
output 230V~.
SPECIFICATIONS
ELECTRICAL
Electrical voltage supply : 230V ~ , 50Hz , max. 6A
Pump relay : 3A, cos φ 0,7, without potential
free relay contact
Mixing valve relay : 3A, cos φ 0,7, without potential
free relay contact
RF Communication
Frequency : 868,3 MHz Receiver
Receiver class : 2
RF communication range : 30m in a residential building
environment
RF communication : short, high rate transmission to
Technology minimize air time and avoid
collisions
ENVIRONMENTAL and STANDARDS
Storage temperature : -20 … +70 ºC
Operating temperature : 0 … +50 ºC
Dimensions (HxWxD) : 161,5 x121x 46 mm
Humidity : max. 5 … 90 %
Material : Socket: PA-GF 25-FR
Cover : PC-FR VO certificated
IP class : IP54
Options : Flow sensor NTC 20KΩ
connectable
Compatible products : CM67RFMV, CM67z
Approval : CE
EN0H0503GE51 R0905
HMC 80/82
KIT CONFIGURATION
Kit Components Pre-Configured
HMC80
HMC82
1x Universal Mixing Valve Controller HM80
1x Chronotherm CM67RFMV
4x Eurofix (strain relief)
1x Universal Mixing Valve Controller HM80
1x Chronotherm CM67RFMV
1x Flow sensor T7414C1012
4x Eurofix (strain relief)
Yes
Yes
APPLICATION EXAMPLES
Mixing Valve Application for UFH without boiler feedback
Mixing Valve Application for UFH without boiler feedback
Mixing Valve Application for UFH without boiler feedback
CM67RFMV with parameter
CM67RFMV with parameter
CM67RFMV with parameter
settings
settings
settings
Pump after running time 0…99 m in
Pump after running time 0…99 m in
Pump after running time 0…99 m in
Actuator running time 0…240 s
Actuator running time 0…240 s
Actuator running time 0…240 s
Min flow temperature setpoint 0…50°C
Min flow temperature setpoint 0…50°C
Min flow temperature setpoint 0…50°C
Max flow temperature setpoint 0…99°C
Max flow temperature setpoint 0…99°C
Max flow temperature setpoint 0…99°C
The HM80 controls the mixing valve depending on the room temperature
The HM80 controls the mixing valve depending on the room temperature
The HM80 controls the mixing valve depending on the room temperature
setpoint and communicates with the CM67RFMV. In addition the controller
setpoint and communicates with the CM67RFMV. In addition the controller
setpoint and communicates with the CM67RFMV. In addition the controller
has a relay output for pump control and connection for the flow sensor.
has a relay output for pump control and connection for the flow sensor.
has a relay output for pump control and connection for the flow sensor.
Without using the flow sensor the mixing valve position is adjusted in accordance with
Without using the flow sensor the mixing valve position is adjusted in accordance with
Without using the flow sensor the mixing valve position is adjusted in accordance with
the room setpoint temperature and the actual room temperature.
the room setpoint temperature and the actual room temperature.
the room setpoint temperature and the actual room temperature.
If the flow sensor is used the mixing valve position is adjusted in accordance with the
If the flow sensor is used the mixing valve position is adjusted in accordance with the
If the flow sensor is used the mixing valve position is adjusted in accordance with the
calculated flow temperature setpoint and the measured flow temperature. The flow
calculated flow temperature setpoint and the measured flow temperature. The flow
calculated flow temperature setpoint and the measured flow temperature. The flow
temperature setpoint is calculated from the room temperature setpoint and the actual
temperature setpoint is calculated from the room temperature setpoint and the actual
temperature setpoint is calculated from the room temperature setpoint and the actual
room temperature deviation.
room temperature deviation.
room temperature deviation.
CM67RFMV
CM67RFMV
CM67RFMV
Flow temperature sensor
Flow temperature sensor
Flow temperature sensor
Flow temperature sensor
T7414C1012 (optional)
T7414C1012 (optional)
T7414C1012 (optional)
T7414C1012 (optional)
HM80
HM80
HM80
HM80
Pump
Pump
Pump
Pump
M
M
M
M
Mixing Valve
Mixing Valve
Mixing Valve
Mixing Valve
Boiler
Boiler
Boiler
Boiler