Make your TrueSTEAM installations accurate and efficient by addressing these commonly asked
questions:
Sizing for the Job
1. Selecting the appropriate humidifier for the job is critical:
The table below illustrates the square footage a TrueSTEAM humidifier can serve.
It is not recommended to install a 6 gallon device in a home larger than 2000 square feet.
* ARI Guideline F-2007 for maintaining 35% RH in a tight, residential four-person home with
8-ft. ceilings. Outdoor conditions = 20ºF and 70% RH.
Installation Check-out List
• Install the in-line water filter and back-flow prevention valve.
• Check that the main water supply line is open.
• Ensure there are no water leaks/drips at any of the water connections.
• Plug into a circuit with at least enough capacity to power the unit.
• Generate a call for humidity from the control and ensure TrueSTEAM fills and the Humidify
light turns on, indicating steam is being generated.
• Test the drain by pressing the EMPTY button until the Clean Tank light begins blinking,
indicating a drain cycle has begun.
NOTE: It may take approximately 10 minutes for the tank to fully flush and drain. TO BYPASS
AND DRAIN IMMEDIATELY, Press and hold the EMPTY button again while the Clean Tank light
is blinking. This will bypass the flush and immediately drain the tank. TO STOP draining, press
the Reset button.
• Mount the provided yellow tank service sticker on the duct/wall near the unit. Ensure the
drain hose is secured to prevent inadvertent disconnection. Check that the hose is plumbed
to a drain/condensate to prevent water spurting.
69-2036EFS—07
Installation Guide
InsTallaTIon ReCommendaTIons
Setting Homeowner Expectations for the TrueSTEAM Experience:
It may take up to a week of continuous operation to achieve the humidity set point, depending
on weather, size of home, furnishings in the home, insulation, etc.
If using a six (6) gallon unit, the most appropriate setpoint is 30-35% or until there is condensation on the windows, then lower the setpoint (if not in frost protection mode). If the home can’t
achieve the setpoint, the unit may be under-sized (if home is under 2000 sq ft, this can also be
due to insulation, windows, arid climate, etc.) or the outdoor temperature may be too low to
maintain adequate humidity levels. Honeywell recommends waiting for the temperature to moderate closer to 20°F (-6°C).
If this occurs and the selected humidity levels are not achieved, then a larger capacity model
may be needed.
For the first week of operation, it is normal to experience a slight plastic odor in the home,
depending on the amount of supplied ventilation. If the remote hose is used, there may be a
slight rubber odor. These odors will dissipate within days of installation.
If the homeowner sees that TrueSTEAM is not humidifying but there is a call for humidity, it is
likely the unit is operating in drain cycle mode. Ask the homeowner to check again in an hour if
they are concerned the device may not be operating.
If the Call Service light is blinking, instruct the homeowner to press and hold the Reset button to
clear the fault. If the fault doesn’t clear, unplug the power to TrueSTEAM and plug back in to the
electrical outlet. Wait 24 hours prior to calling a contractor. The call service light may be blinking
due to a low voltage condition in the area and will reset to operate correctly when full power is
restored.
There may be a slight increase in the homeowner’s energy consumption. However, when operating correctly, TrueSTEAM will make the home feel warmer, allowing the homeowner to lower the
temperature setting on the thermostat. Every degree lower on the thermostat can save up to 3%
on heating costs.
69-2036EFS—072
TrueSTEAM Humidification System
WhaT you WIll need To InsTall TRuesTeam
Tools/Hardware needed:
• Wire stripper/cutter
• Drill or duct-cutting tool
• 1-3/4-in. hole saw
• 1/8-in. drill bit
• Phillips and slotted (or Torx) screwdriver
• 18-gauge thermostat wire (5 or 2 conductor)
Material Provided:
• 1/4-in. copper or plastic water line
• 1/2-in. drain hose and clamps
• Mounting bracket and hardware
• In-line water filter* (50028044-001)
• Saddle valve
• Back-flow valve (50030142-001)
Options:
• Remote Installation Kits
– 10-foot hose and nozzle kit (50024917-001)
– 20-foot hose and nozzle kit (50024917-002)
• Remote mount duct board adapter kit
(32005530-001)
• Differential pressure switch (50027910-001)
* Warranty requires in-line water filter installation with regular service.
369-2036EFS—07
Installation Guide
safeTy PReCauTIons
CAUTION: Voltage Hazard.
Can cause electrical shock or equipment damage.
Disconnect HVAC equipment before beginning installation.
Safety Precautions
• Do not direct the steam nozzle at people.
• If used near a pool or spa, ensure the TrueSTEAM can not fall into the water or be splashed.
Also, ensure the TrueSTEAM is plugged into a GFI ground fault interrupt outlet.
• Water inside tank can be very hot. Follow installation instructions and service steps exactly
as given in the technical literature.
Warning: Electrocution, Heavy Equipment, and Chemical Hazard.
Can cause death, blindness, water damage to home and heating element failure.
• Do not cut into any air conditioning or electrical line
• Wear safety glasses when cutting or drilling.
• Mount the humidifier in a level position to avoid water damage or heating element failure.
• Reinforce duct as necessary to ensure stability.
The preferred installation location is on the warm or supply side of the furnace. If that location is
not possible, the steam nozzle should be inserted a minimum of 12 in. upstream of the furnace filter.
Depending on the location and the duct rigidity, additional duct reinforcement may be necessary.
Warning: Steam Condensation, Fire, and Freezing Water Hazard.
Can cause failure of fan or limit control or result in water damage to home.
• Do not install the humidifier where the ambient temperature is lower than 32°F (0°C) or higher
than 120°F (49°C).
• Do not install the humidifier through sidewalls of a return air duct made of wood (e.g., floor
joist).
• The mounting area must be strong enough to support the humidifier’s weight when it is full
of water (approximately 12 to 15 lbs.), and to hold the humidifier in a level position for safe,
reliable operation. Otherwise, additional duct or wall reinforcement will be necessary.
• If the ducting has exposed insulated materials on the interior, ensure the nozzle extends
beyond the insulation by clearing away excess insulation at the insertion point. You may wish
to replace a section of insulated duct (approximately 6 in. x 6 in.) with rigid, non-insulated
sheet metal to ensure effective installation.
• Mount the unit where it will have smooth air flow across the end of the steam nozzle.
• Allow at least 1 foot clearance to ventilation holes in humidifier’s cover. Do not cover these
holes. Covering them can increase the internal operating temperature of the humidifier and
shorten the humidifier’s life.
• Allow at least 4 inches of clearance between the steam nozzle insertion hole and the top of
the interior duct to avoid condensation forming. The mounting template is designed to allow
clearance if the top of the template is at or below the top surface of the interior duct.
• Do not mount directly to duct board. Remote mount nozzle attachment allowed only when
using with a duct board adapter kit (part #32005530-001).
• Do not install in completely enclosed spaces, such as a cabinet or unventilated closet.
Choose a location that is well ventilated.
69-2036EFS—07
TrueSTEAM Humidification System
M24744
M24745
M24746
M24894
If installing the humidifier directly to the supply duct, follow steps on pages 5–6 and 13–18.
If mounting remote from the duct, follow steps on pages 7–18.
duCT mounT InsTallaTIon
Choose a location that has access to a:
1
Draining water
may be hot.
Ensure drain outlet not exposed.
• Drain allowing a slope of 1/4 in.
per foot of drain hose.
• Cold water line.
• Electrical circuit rated to your
humidifier.
• Vertical surface with adequate
clearances.
Continuous
downslope
Required Minimum
Model
Circuit Capacity
HM5067 Amps
HM50910 Amps
HM51212 Amps
CAUTION
Hot water temperature above 120°F (49°C)
can cause burns from scalding.
2
Install duct nozzle.
Ensure o-ring gasket
is properly seated in
the groove.
Insert nozzle and twist clockwise to ensure tight seal of
nozzle to TrueSTEAM.
69-2036EFS—07
Installation Guide
M24749
M24750
M24748
SUPPLY
12 INCHES
duCT mounT InsTallaTIon
Position template sticker on supply duct. For tall coils that do not have this
3
clearance available, refer to remote mounting instructions.
Secure bracket to duct using #8
56
self-drilling sheet metal screws (4).
4
Drill 1-3/4-in. hole.
A) Slide foam gasket over nozzle and
insert the nozzle into duct hole
(pictured).
B) Push down to secure humidifier to
bracket arms. Ensure gasket forms
tight seal in duct hole.
Allow 3 in. clearance from nozzle
outlet to duct wall.
Proceed to page 13 for plumbing and wiring instructions.
69-2036EFS—076
B
A
Foam
gasket
M24896A
RemoTe mounT InsTallaTIon
Use for mounting to a location other than the supply duct.
TrueSTEAM Humidification System
Most operation problems are caused
by improper hose installation. Always
ensure an uphill flow when installing
the remote hose, and avoid kinks,
sharp turns, or low spots that could
restrict the flow of steam into the
injection nozzle or condensation back
into the humidifier.
If the remote hose cannot be installed
with an upward pitch of 2 in./ft., a
wetted drip tee must be installed.
Failure to do so can result in back
pressure on TrueSTEAM, which can
lead to duct nozzle water spitting or
leaking gasket. Remote hose must be
supported to prevent sagging or low
spots.
When remote mounting, also follow these critical
steps in sizing the proper TrueSTEAM:
If the steam distribution tube is going into an unconditioned air space (e.g., attic), insulate the tube to
ensure steam output efficiency:
• Honeywell recommends self-seal pipe insulation
for hot and cold water pipes. Insul-Tube 1-1/8 in. ID
x 1/2 in. wall 25/50 Factory Mutual 062411, flame
retardant added.
The 6-gallon model (HM506) can be remotely mounted up to:
• 5 feet without insulating the steam distribution tube
• 15 feet if insulating the steam distribution tube
The 9- and 12-gallon models (HM509 and HM512)
can be remotely mount up to 20 feet with or without
insulating the steam distribution tube.
Ensure at least 2 in. per foot slope if installing the
remote hose horizontally.
1
Choose a location for TrueSTEAM and the
remote duct nozzle (see remote installs on
pages 6–7).
It should have access for:
• Remote hose installation. Steam hose
must be installed with 2 in./ft. pitch on a
continuous uphill slope.
• Drain. Allow a continuous downslope to the
drain.
• Cold water line.
• Electrical circuit rated to your humidifier
(see circuit ratings on page 10).
Funnel or floor drain. Refer to governing
codes for drain pipe size and maximum
temperature requirements.
Maximum 3 ft.
2 in./ft. uphill
6 in.
8 in.
1/2 in.
minimum
diameter
Water in
elbow
769-2036EFS—07
Installation Guide
M24786
M24781
M24785
M24936
PRoPeR hose InsTalls
Furnace or Mechanical Room Remote
Note: If air handler location temperatures will drop
below freezing at any time, TrueSTEAM must be
mounted in a conditioned space, running a remote
hose to the duct.
Duct Mount Remote
CAUTION
Hot water temperature above 120°F (49°C)
can cause burns from scalding.
Living Area Remote Options
Garage Remote
Draining
water may
be hot.
Ensure
drain outlet not
exposed.
69-2036EFS—07
2 IN. PER FT
2 IN. PER FT
2 IN. PER FT
2 IN. PER FT
20 FT MAX
P - TRAP
DRAIN
WITH TRAP
5 FT MAX
3 FT MAXIMUM
DRAIN
P - TRAP
IF NO SLOPE
10 FT MAX
GENTLE BEND
OBSTRUCTION
SUPPORTED REMOTE HOSE
20 FT MAX
DRAIN
WETTED P - TRAP
NOTE: HEIGHT OF TRAP MUST BE GREATER
THAN THE DUCT STATIC PRESSURE
DRAIN
P - TRAP
IF NO SLOPE
TYPICAL INSTALLATION
WHEN TrueSTEAM IS ABOVE
REMOTE NOZZLE
KINKED
SAG
NO SLOPE
NO SLOPE
M24915A
UNDRAINED
ELBOW
TrueSTEAM Humidification System
PRoPeR hose InsTalls
NOTES:
• Slope hose up in direction of steam flow at 2 in. per foot;
• Maximum length of remote steam hose is 20 ft.
• Slope hose down in direction of steam flow at 3/4 in. per foot;
• Height of P-traps must be greater than the duct static pressure. (Typical
3 in. will suffice.) P-trap must also be wetted (see page 7).
• Minimize sharp bends and elbows.
• Insulating the remote hose in unconditioned spaces will sustain
efficiency better than not insulating the hose.
AVOID THESE INSTALLATION MISTAKES.
969-2036EFS—07
Installation Guide
M24744
M24745
M24764
M24765
M24894
RemoTe mounT InsTallaTIon
ModelMinimum Circuit Capacity
HM5067 Amps
HM50910 Amps
HM51212 Amps
Install hose adapter from Remote
2
Mount Kit.
Draining water
may be hot.
Ensure drain outlet not exposed.
Remote Mount Kit
(sold separately)
Ensure o-ring gasket is
properly seated in the
Continuous
groove.
downflow
CAUTION
Hot water temperature above 120°F (49°C)
can cause burns from scalding.
Hose Adapter
Hose Clamps
Duct Nozzle
Remote Hose
• 50024917-001 = Ten Foot Hose Kit
• 50024917-002 = Twenty Foot Hose Kit
69-2036EFS—070
Insert hose adapter and twist
clockwise to ensure tight seal
of nozzle to TrueSTEAM.
M24766
3
M24767A
M24768
TrueSTEAM Humidification System
RemoTe mounT InsTallaTIonRemoTe mounT InsTallaTIon
Position template sticker on remote location.
Note: TrueSTEAM will weigh 12–15 lbs. (+/- 2 lbs.) with
water, so if mounting onto drywall or plaster, position
one side over a wall stud.
4
Insert wall anchors (4) into pilot holes and secure
bracket to location.
5
Push down to secure TrueSTEAM to
bracket arms.
69-2036EFS—07
Installation Guide
M24770
M24771
RemoTe mounT InsTallaTIon
Cut a 1-3/4 in. diameter duct hole, install the provided
gasket, and slide the remote nozzle up into the duct.
6
7
Secure remote nozzle to duct using #8 self-drilling
sheet metal screws (4).
Run remote hose from
the humidifier to the duct
nozzle location. Up to 20
ft. of hose can be used.
Minimum 3 in. clearance
required from nozzle outlet to
duct wall.
8
9
If mounting remotely requires running
hose through structural barriers (ie.
wall or ceiling), cut at least a 1-3/4 in.
hole and slide hose through.
Seal off unconditioned space with a
grommet (not provided) or caulk.
Attach remote hose by sliding over the nozzle
and adapter. Secure both hose ends with
clamps (provided).
IMPORTANT:
Run hose continuously uphill. For horizontal runs,
ensure a slope of 2 in. uphill per foot. Secure hose
every horizontal foot using clamps (provided).
For long horizontal runs, support the hose by first
securing a length of 2 x 4 lumber, U-channel, or
angle iron with the appropriate slope. Then attach
the hose to the top of this support. If remote hose
requires downward pitch, refer to pages 5 and 7 for
instruction.
69-2036EFS—072
M24852
M24772
10
M27428
TrueSTEAM Humidification System
PlumbIng
A
Insert 1/4-in. water line into filter. Apply modest pressure to ensure a tight fit.
B
Insert 1/4-in. water line into back-flow valve. Apply modest pressure for a tight fit.
C
Connect 1/2-in. drain tube. Secure drain tube to barbed fitting with hose clamp.
D
Shut off the water supply. Secure 1/4-in. copper or plastic water feed tube.
DescriptionPart Number
In-Line Water Filter (included)
(required for warranty)
Back-flow valve (included)
(required)
To water supply
50028044-001
50030142-001
A
B
1/4-in. copper
or plastic
Enlarged view
Continuous
downslope
1/2-in.
drain tube
D
C
1/4-in. water line
Draining water may be
hot. Ensure drain outlet
not exposed. Ensure
drain or condensate
pump is rated for at
least 120°F water.
CAUTION
Hot water temperature above 120°F (49°C)
can cause burns from scalding.
Water line tapping options. See instructions provided with the option you choose.
Manual shutoff
valve (sold
separately)
To humidifier
T-fitting
Piercing pin
Water supply line
Saddle valve (provided)
To humidifier
Check all water line connections to ensure no leaks once TrueSTEAM is operational.
369-2036EFS—07
Installation Guide
M24754
M24895
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
M24893
WIRIng
CAUTION: Voltage Hazard.
Before wiring to HVAC terminals, disconnect HVAC
equipment power. Ensure humidifier is not plugged in.
Loosen captive cover
11
screw. Slide cover out from
front.
Low-Voltage Terminals
24V AC power for electronic humidistat.
HUM Low-voltage humidistat (or thermostat) terminals control
C, R Connects to HVAC system transformer terminals (or relay
RT Connects to thermostat R terminal, which is normally
GT, GT connects to thermostat G terminal. GF connects to
GF
EXT When a 24-vac fan board is not used to control blower
TabsNotch
Route wires through the raised harness tabs and out the notch at
the rear of the chassis. Ensure wires are secure and do not interfere with assembly of cover.
humidifier operation.
transformer fan control R and C) to ensure HVAC power
is present before humidifying. This can be disabled by
changing DIP switch 4 (see page 16).
switched to call for fan.
fan board G terminal. Thermostat G passes through the
normally-closed (NC) relay contacts to GF, allowing fan
activation. When TrueSTEAM is ready to provide humidity
to the home, it will take control of the fan by forcing power
from RT to GF (if not already activated).
(hydronic or cooling-only applications), this connection
with GF provides dry-contact closure for fan calls. EXT/
GF may be wired to a low-voltage relay control center to
provide line-voltage fan control.
69-2036EFS—07
HVAC
RECOMMENDED
AIR FLOW SWITCH (AFS)
MECHANICAL
HUMIDISTAT
HVAC
POWER
MASTER
THERMOSTAT
HUM
HUM
GYWR Rc
GYWRC
TrueSTEAM - INTERNAL
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
M24756
12
FAN
FURNACE BOARD
EQUIPMENT INTERFACE MODULE (EIM)
G
C
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
CONV. HP
1
2
3
C
R
RC
RH
W1
W2
W3
Y
Y2
G
O/B
AUX
AUX2
Y
Y2
G
H1
U
M2
D1
H
M2
V1
N
T2
HEAT 1 RELAY
HEAT 2 RELAY
HEAT 3 RELAY
COOL 1 RELAY
COOL 2 RELAY
FAN RELAY
VISIONPRO IAQ
D-1
R-2
C-3
M24758
RECOMMENDED AIR FLOW SWITCH (AFS)
TrueSTEAM - INTERNAL
HVAC
TrueIAQ
THERMOSTAT
HUM
HUM
R
C
GYWR Rc
GYWR C
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
RECOMMENDED
AIR FLOW
SWITCH (AFS)
M27409
HVAC
POWER
MASTER
TrueSTEAM - INTERNAL
TrueSTEAM Humidification System
WIRIng
Wire the TrueSTEAM according to the diagram that applies to your humidity control.
Follow this diagram if using a mechanical humidistat
such as H8908ASPST or other.
Factory
installed
jumper
If AFS is used, ensure DIP 5
is in ON position.
Follow this diagram to wire TrueIAQ for manual
operation.
A
Set TrueIAQ ISU parameter 10 to 1, and ISU 25 to 2.
For auto-operation: also wire W and G to thermostat
B
W and G.
B
A
Factory
installed
jumper
Follow this diagram if using VisionPRO IAQTM for independent fan control. TrueSTEAM will
independently activate furnace fan (humidity on demand).
Set VisionPRO IAQTM ISU
A
parameter 374 to 3.
If operating TrueSTEAM without
B
monitoring HVAC power or
AFS, C wiring hookup is
optional, but ensure DIP 4 is in
ON position.
If AFS is used, ensure DIP 5
is in ON position.
69-2036EFS—07
A
If AFS is used, ensure DIP 5 is in ON position.
B
Installation Guide
FAN
FURNACE BOARD
EQUIPMENT INTERFACE MODULE (EIM)
G
C
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
CONV. HP
1
2
3
C
R
RC
RH
W1
W2
W3
Y
Y2
G
O/B
AUX
AUX2
Y
Y2
G
H1
U
M2
D1
H
M2
V1
N
T2
HEAT 1 RELAY
HEAT 2 RELAY
HEAT 3 RELAY
COOL 1 RELAY
COOL 2 RELAY
FAN RELAY
HVAC
POWER
MASTER
VISIONPRO IAQ
D-1
R-2
C-3
M24761
RECOMMENDED
AIR FLOW SWITCH
(AFS)
TrueSTEAM - INTERNAL
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
HUMIDISTAT
HUM
HUM
HAC
HAC
MECHANICAL
HUMIDISTAT
HUM
HUM
HAC
HAC
RECOMMENDED
AIR FLOW SWITCH
(AFS)
TrueSTEAM - INTERNAL
HVAC
120 VAC
R8222
RED
BLACK
L1
L2
120
VAC
AT120
R C
M24760
HVAC POWER MASTER
WIRIng
Follow this diagram for a system with the VisionPRO IAQTM with operation dependent on HVAC power
(humidification and fan call by thermostat).
Set VisionPRO IAQTM ISU
B
parameter 374 to 1. This
allows the thermostat to call
B
for fan at the same time as it
calls for humidification.
If AFS is not used, set DIP 4
ON and wire HUM terminals
only.
If AFS is used, set DIP 5 ON
and DIP 4 OFF and wire R, C,
and Hum terminals.
Follow this diagram if using a blower fan dedicated to the TrueSTEAM (a fan separate from the HVAC
equipment, as in hydronic or cooling-only applications).
69-2036EFS—076
If AFS is used, ensure DIP 5
is in ON position.
Remove Factory installed
jumper (R/RT)
13
POWER
HUMIDIFYING
CLEAN TANK
CALL SERVICE
PRESS RESET
PRESS EMPTY
RESET
EMPTY
SEE LABEL BELOW
!
M24763
M24762
TrueSTEAM Humidification System
Slide the cover back into place and secure captive screw.
Turn on the water supply and plug in the humidifier.
The Press Reset light will blink when
14
power is applied.
Press/release the RESET button to
ready the TrueSTEAM. If not pushed,
TrueSTEAM will automatically move to
ready after five minutes.
WIRIngWIRIng
Turn the humidity control to the “Test” position. If the “Test” position is unavailable,
15
turn the control to a high setpoint (60% +). Be sure to turn this back down (or off) when
testing is complete. “Off” will turn TrueSTEAM off.
Confirm that the furnace blower turns on to circulate air. This will take about 10–15
16
minutes upon call for humidity.
Important for Remote Installation:
After TrueSTEAM has produced steam for 10–15 minutes, check the integrity of the
remote hose to ensure no sags have occurred. Add or adjust clamps if necessary to
ensure 2 in. per foot continuous slope.
769-2036EFS—07
Installation Guide
M24853
OFF
ON
OFF
ON
OFF
ON
DIP 1
DIP 2
DIP3
DIP 4
DIP 5
DIP6
DIP 1
DIP 2
DIP3
DIP 4
DIP 5
DIP6
DIP 1
DIP 2
DIP3
DIP 4
DIP 5
DIP6
DIP
3
DIP
3
D
IP
3
D
IP
6
D
IP
6
DIP
6
M28181
DIP 1
DIP 2
DIP3
DIP 4
DIP 5
DIP6
DIP 1
DIP 2
DIP3
DIP 4
DIP 5
DIP6
OFF
ON
OFF
ON
DIP 1
DIP 2
DIP3
DIP 4
DIP 5
DIP6
OFF
ON
DIP
3
D
IP
3
DIP
3
D
IP
6
DIP
6
D
IP
6
dIP sWITCh seleCTIon
Between the transformer and LED display on the circuit board are two sets of DIP switches. DIP
1 and 2 can be configured to adjust cleaning cycles. DIP 4 and 5 can simplify wiring. DIP 3 and 6
are not used at this time. Details below.
Run time (hrs)End-of-Season timer
(hrs)
10 hrs of humidifying before system
auto-flushes debris
48 hrs before system autodrains and remains empty
until next call for humidity.
from tank.
20 hrs of humidifying before system
auto-flushes debris
48 hrs before system autodrains and remains empty
until next call for humidity.
from tank.
30 hrs of humidifying before system
auto-flushes debris
48 hrs before system autodrains and remains empty
until next call for humidity.
from tank.
Clean tank indicator
1 year of total time (operational
and inactive) before the Press
Empty light will blink, indicating
it is time to manually clean the
water tank.
1 year of total time (operational
and inactive) before the Press
Empty light will blink, indicating
it is time to manually clean the
water tank.
1 year of total time (operational
and inactive) before the Press
Empty light will blink, indicating
it is time to manually clean the
water tank.
DIP 4 OFF, DIP 5 ON: If TrueSTEAM determines that no airflow*
is present two minutes after the blower fan call, it will shut down
steam output and activate a service light.
*Requires installation of air flow switch. See 'Wiring' section for details.
69-2036EFS—07
DIP 4 ON, DIP 5 either setting: TrueSTEAM will allow humidity
without HVAC power present and without airflow.
DIP 4 OFF, DIP 5 OFF: TrueSTEAM will not be allowed to humidify
without HVAC power being present.
TrueSTEAM Humidification System
M24901
TRoubleshooTIng
TrueSTEAM has internal system diagnostics that monitor system operation, maintenance schedules,
and faults. If a system fault is detected, the system will attempt to recover itself up to five times in a
24 hour period. If unable to recover in that time, the red Call Service LED light will activate.
If the TrueSTEAM Call Service light is red, a system fault has occurred from which the humidifier can not recover by itself. The table below shows the possible faults, along with steps to fix
TrueSTEAM.
If the red Call Service LED light is on, press/release the RESET button. The red Call Service LED
light will begin blinking in a series that indicates what fault occurred. Refer to the table below
for the fault signified by the number of blinks that occur. To clear the fault, press and hold the
RESET button for 5 seconds.
Press/hold the EMPTY button to clear the Service Timer light (i.e. the Press Empty button).
Press/release the EMPTY button to drain the tank.
No. of
Red
Light
Blinks
1Water/Heater temper-
2Water sensors failed. Yes, system will
3Failure to fill tank
Fault DescriptionAuto-
ature sensor failed.
B
A
with water.
Recoverable?
Yes, system will
return to “Ready”
if fault no longer
exists in 1 hour.
return to “Ready”
if fault no longer
exists in 1 hour.
Will attempt to
reset itself 5 times
in 24 hours.
Yes, system will
return to “Ready”
if fault no longer
exists in 1 hour.
Steps to Fix
To be Performed by Professional HVAC Technician Only
• Unplug TrueSTEAM and remove cover.
• Check water sensor connection to electronic board.
• Reattach cover and plug TrueSTEAM in.
• If fault reappears, follow the cleaning steps on pages 23–24.
• Reassemble tank and press the RESET button.
• If fault returns, replace with applicable wattage heating
element.
• Unplug TrueSTEAM and remove cover.
• Disconnect water level sensor wiring, remove screen and
lift snap-hinge clamp.
Remove water sensor assembly.
• Clean water sensor probes using warm soapy water so that
the metal is exposed.
• Reassemble the sensor assembly in the unit, reattach and
secure cover.
• Plug unit back in and press the RESET button.
• If fault reappears, replace sensor assembly.
• Ensure inlet water is on.
• Check for leaks around the tank seal and solenoid.
• Turn off water supply and replace in-line water filter.
• Press/hold RESET button until the red Call Service light
turns off.
• If tank still fails to fill, press the EMPTY button (if unit fails to
drain, unplug unit and make sure water in tank is cool).
• Follow tank cleaning instructions on page 21. Ensure you
have a firm grip of the tank prior to releasing the tank,
especially if water is present.
• Clear any excess debris from the tank’s bottom orifice to
the solenoid.
• Reassemble tank and plug unit back in. Press the RESET
button.
• If water still fails to flush into the tank, replace the solenoid
valve.
969-2036EFS—07
Installation Guide
TRoubleshooTIng
No. of
Red
Light
Blinks
4Heating element
5Input voltage insuf-
6Water overflow
7HVAC power not
Fault DescriptionAuto-
overheated.
ficient.
sensed.
present (monitor this
fault only when DIP 4
and 5 are OFF).
Steps to Fix
Recoverable?
No• Follow tank cleaning steps (pages 23–26).
Yes, system will
return to “Ready”
if fault no longer
exists in 1 hour.
Yes, system will
return to “Ready”
if fault no longer
exists in 1 hour.
Yes, system will
return to “Ready”
if fault no longer
exists in 1 hour.
To be Performed by Professional HVAC Technician Only
• Reassemble tank and press the RESET button.
• If fault returns, replace with applicable TrueSTEAM.
• Unplug and replug the unit in to see if the fault returns.
• If fault returns, unplug unit and remove cover.
• Ensure wiring connections are secure and attached.
• If fault returns, replace the TrueSTEAM with a new one (field
service is not recommended in the event line voltage is lost).
• Ensure drain hose is not kinked or submerged in water at
the drain. Check functionality of condensate pump if used.
• Check for water coming out of drain/overflow line. If
continuous water flow is present, follow the cleaning steps
on pages 23–26.
• Press EMPTY button to drain tank.
• Set humidistat RH setpoint to Test mode.
• If fault returns, unplug TrueSTEAM.
• Loosen cover screw and remove cover.
• Disconnect water level sensor wiring and lift snap-hinge clamp
to remove water sensor assembly. See image on page 17.
• Clean probes using warm soapy water so that the metal is
exposed.
• Reassemble the sensor assembly in the unit, reattach and
secure cover.
• Plug unit in, and press RESET button.
• If fault reappears, replace water sensor assembly and/or
solenoid valve.
• Unplug and replug the unit in to see if power returns.
• If not, ensure HVAC equipment has power. Check circuit
breaker and replace fuse if circuit is tripped.
• Unplug TrueSTEAM and remove cover.
• Ensure DIP 4 is ON and reattach cover.
• Plug unit in.
• If fault reappears, ensure the circuit being used has the
rating to support the unit. Unplug any additional equipment
plugged into this circuit. If fault disappears, the circuit
capacity is not properly sized to your unit.
• If fault returns, replace unit.
69-2036EFS—0720
TrueSTEAM Humidification System
TRoubleshooTIng
No. of
Red
Light
Blinks
8–11The backup weld
12Temperature of the
13Tank failed to drain.No• Water in tank may be hot (>140ºF [60ºC]).
14Heater failed to boil
15No Airflow.Yes• Ensure Differential Pressure Switch is installed and wired
Fault DescriptionAuto-
Recoverable?
No• Replace the unit.
monitor input is active
when the backup
heater relay is off.
Yes, system will
electronic circuit
board is too high.
water.
return to “Ready”
if fault no longer
exists in 1 hour.
Yes, system will
return to “Ready”
if fault no longer
exists in 1 hour.
Steps to Fix
To be Performed by Professional HVAC Technician Only
• Ensure ventilation holes in the cover are clear of
obstruction, and that 1 foot of clearance is maintained
around the cover’s vent holes.
• Ensure the TrueSTEAM is installed in a location with
conditioned air 32°F (0°C) to 104°F (40°C).
• Turn humidistat off and allow time for electronic board to cool.
• Turn humidistat on and press RESET button.
• Confirm humidity call starts by HUMIDIFYING light turning on.
• Allow unit to run and check for steam leaks around tank and
ventilation holes.
• If steam is present, replace TrueSTEAM.
• Press the EMPTY button.
• If unit fails to drain, wait for water in tank to cool. Ensure
tank water is cool before proceeding.
• Once cool, follow tank cleaning steps (pages 23–24).
• Reassemble tank and press the RESET button.
• If fault persists, replace the solenoid valve.
• Follow tank cleaning steps (pages 23–24).
• Reassemble tank and press the RESET button.
• If fault returns, replace the heating element with the
applicable wattage replacement part.
correctly. See the Wiring section for proper wiring.
• Ensure DIP switches are set correctly.
• If fault persists, replace AFS and/or unit.
269-2036EFS—07
Installation Guide
sPeCIfICaTIons
Capacity:
HM512: 12 gallons per day (gpd) (45 liters per day [lpd])
HM509: 9 gpd (34 lpd)
HM506: 6 gpd (23 lpd)
Humidified Area:
House
Description
LooseTwo2000 ft21300 ft21000 ft
Average One2500 ft21800 ft21500 ft
TightOne-half3000+ ft22500 ft22000 ft
• Auto flushing is configurable to 10, 20 or 30 hours of
operational time (heating element active).
• During auto flushing, cold water will enter the tank to
lower water temperature below 140ºF (60ºC) before
draining.
• During manual flush (performed by pressing the
EMPTY button) initial water temperature may be
above 140ºF (60ºC). Ensure drain outlet is not
exposed and use caution when pressing the EMPTY
button, and do NOT attempt to remove the tank with
water in it.
• Flush cycle takes approximately 15 minutes to
empty the tank completely. To override, press/hold
the EMPTY button while the “Clean Tank” light is
blinking.
• Drain Hose Operating Temperature Range: 34ºF–
212ºF (1.1ºC–100ºC)
Electrical Ratings and Tolerances
Input Ratings
• Power Supply: 120VAC +10/ -15%, 60Hz
- HM512: 1440W at 120VAC at full load
- HM509: 1200W at 120VAC at full load
- HM506: 840W at 120VAC at full load
• HM512: 12A, 120VAC
• HM509: 10A, 120VAC
• HM506: 7A, 120VAC
• 15A, 120VAC interlock switch
• Thermostat/HVAC power monitor (R to C): 10mA
resistive at 24VAC
• Field wiring terminals: 18–22 ga. solid
• HVAC power/airflow monitor: 10 mA resistive at 24
VAC
Output Ratings
• Relay output contacts:
- Fan: 1.5A full load, 7.5A locked rotor at 24VAC
- Heat and Backup: 15A resistive at 120VAC
• Fill Solenoid: 0.1A at 120VAC, 0.5 PF
• Drain Solenoid: 0.1A at 120VAC, 0.5PF
• Humidistat output contacts: 10mA resistive at 24VAC
• Humidistat power supply: 100mA at 24VAC
CAUTION
Hot water temperature above 140°F (60°C)
can cause burns from scalding.
Standards & Approval Body Requirements
Underwriters Laboratories: UL998, File no. E185662.
Federal Communications Commission: Class B compliance, File no. YU555.
Intended to be used in accordance with the National Electrical Code (NEC), ANSI/NFPA 70, and the rules of the
Canadian Electrical Code (CEC), Part 1, C22.1.
69-2036EFS—0722
TrueSTEAM Humidification System
EMPTY
M24774
CLEAN TANK
(BLINKING LIGHT)
M24775
M24776
CLEAN TANK
(ON SOLID)
CleanIng and seasonal oR VaCaTIon maInTenanCe
Maintenance is simple with TrueSTEAM—just remove the water tank for cleaning.
Warning: Scalding hazard.
Do not attempt to remove the humidifier from the mounting bracket during operation,
or when the humidifier’s water tank when full of water. Water heater could be hot when
tank is removed. Failure to comply could result in severe scalding or death.
Drain Operation
• Auto flushing is configurable to 10, 20 or 30 hours of operational time (heating element
active).
• During auto flushing, cold water will enter the tank to lower water temperature below 140°F
(60°C) before draining.
• During manual flush (performed by pressing the EMPTY button) initial water temperature may
be above 140°F (60°C). Ensure drain outlet is not exposed and use caution when pressing the
EMPTY button, and do NOT attempt to remove the tank with water in it.
To clean the TrueSTEAM:
1. Press and hold the EMPTY button for 3 seconds. Wait for the CLEAN TANK light to be
on solid (not blinking). The flush cycle takes approximately 15 minutes to empty the tank
completely. To override the flush cycle press/hold the EMPTY button a second time for 3
seconds. The tank will drain immediately.
Wait
Go to Step 2
2369-2036EFS—07
Installation Guide
M24777
M24778
M24779
M24856
M24857
CleanIng and seasonal oR VaCaTIon maInTenanCe
2. Turn the manual shut-off valve at the
bottom of the tank to the “Unlock”
position.
4. Firmly grip the tank bottom. Push down
the cover's safety button and pull the latch
forward to release the tank.
Note: Latch does not come off humidifier
with tank.
3. Grip the white water valve arm and slide it
back within the bracket to disengage from
the tank.
5. Use tap water to flush loose minerals from
the tank. Sediment screen at tank's bottom
is removable. For a more thorough cleaning,
soak tank in warm, soapy water, then rinse
clean. Tank is also dishwasher-safe.
6. Carefully rub minerals off of the heating
element, reservoir walls, and sensors. Scouring
pads suitable for non-stick pots or pans are
suitable for cleaning the TrueSTEAM reservoir
walls and components within the tank.
Sediment screen
69-2036EFS—072
TrueSTEAM Humidification System
M27410
M27411
7. Replace inline filter once per year. Turn water supply off before replacing.
Press down filter collar ring and pull
out 1/4 in. water line from each side.
Insert 1/4 in. lines into new filter. Apply
modest pressure to ensure a tight fit.
Once clean, reattach tank by securing the latch. Engage the water valve to the cam shaft, and
“Lock” the shut-off valve. The “Press Reset” light will blink at start-up. Push the RESET button
to ready the humidifier.
269-2036EFS—07
Installation Guide
CleanIng and seasonal oR VaCaTIon maInTenanCe
Automatic End of Season Shutdown
Your TrueSTEAM humidifier has the built-in intelligence to shut down when humidity is not needed for an extended period. After 48 hours of inactivity, TrueSTEAM will drain and remain empty
until humidity is needed again. This prevents water from stagnating within the tank. The tank will
refill with water upon next humidity call.
There are a few house-cleaning steps to follow to keep your TrueSTEAM operating at peak
efficiency:
1. Follow steps 1–6 in the Cleaning section on page 23 at least once per year, or when the
“Press Empty” light is blinking.
2. Clear ventilation holes in the humidifier’s cover.
3. Clear the water drain tube.
4. Make sure the water tank gasket seal is not cracked or split before reattaching the humidifier
water tank.
5. Check that the humidifier is still mounted level.
Extended Vacation
When you leave on extended vacations, it is recommended you turn off the humidifier’s water
supply and turn off the humidity control. When you return, turn on the humidifier water supply
and reset your humidity control to a comfortable position.
69-2036EFS—0726
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.